Vous êtes sur la page 1sur 42

Guidance Roofing

Flat Roof - Types


Introduction

A roof is defined in BS 6229 as a flat roof if it has a pitch of 10 degrees or less.

A flat roof must be strong, durable and stable throughout its lifetime. It must provide
adequate protection against the elements, keeping the buildings structure and
interior dry.

Flat roofs have a reputation of failing early but improvements in strength, flexibility,
ageing and weather resistance mean that, if built with care, using the correct
materials, todays high performance felts can have a life span of up to 20 years.

Roof Types
Flat roof constructions are generally classed as either Cold or Warm roofs depending on
the position of the thermal insulation.

The Cold Roof

Although not recommended today, and actually banned in Scotland, until recently
cold flat roofs were fairly common.

In a cold roof the thermal insulation is laid between the joists below the structural
deck.

As the insulation is not required to take any loads, quilts and other loose fill materials
can be used as well as rigid insulation.
Click Image for Low-Res Preview

Cold Flat Roof Detail, Felt Covering


2.49
Add To Basket
Includes DXF,
DWG and Jpeg

Because the structural elements of a cold roof are not protected by from the heat of
the sun by a layer of insulation they are liable to suffer the damaging effects of
thermal movement.

Ventilation is required above the insulation in a cold roof to prevent the build up of
moisture vapour in the roof void.

Foundations
Floors

Warm Deck Roof

In a warm deck roof the insulation is positioned above the structural deck and no
ventilation is required.

Throughout the course of the year the roof deck and all below it is kept at a
temperature close to that of the inside of the building, therefore the roof structure is
protected from extremes of hot and cold, lessening the potential for damage caused
by thermal movement.

Warm Flat Roof Detail, Felt Covering

A warm deck also provides added protection from the dangers of condensation as the
structure is kept warm, at a temperature above dewpoint, by the insulation above it.
Therefore water vapour which enters the roof structure from the room below will not
have a cold surface on which to condense. NHBC recommend that this type of roof be
considered as the standard form of construction.

Types of Warm deck roof


There are two forms of warm deck roof:

Sandwich

Inverted

Warm Deck: Sandwich Roof

The sandwich warm deck roof is the most common type of flat roof. The insulation is
placed below the waterproof covering and is either mechanically fixed or bitumen
bonded on to the top of the deck.

Inverted warm deck roof

The insulation boards in an inverted warm deck are laid over the structural deck and
the waterproof covering. The insulation is secured by a layer of ballast or paving
slabs to prevent wind uplift.

The waterproofing membrane has the added protection of the insulation from foot
traffic and degradation caused by exposure to solar radiation. However, it may be a
more difficult to locate defects in the membrane.

Proprietary systems are available now which combine the insulation and ballast
layers.

Flat Roof - Components


Components of a Flat Roof
A flat roof is a multi-layer construction typically comprising of the following elements:

Waterproof membrane with a protective covering - this should prevent water


reaching the roof structure and the room below.

Thermal insulation ensures thermal comfort is maintained inside the building and
often provides support for the waterproofing membrane (warm roof).

Roof deck - provides a base for the waterproof membrane or the insulation.

Vapour control layer - helps reduce the risk of condensation.

Load bearing supportive structure - transmits the weight of the roof and any loads
acting on it onto the loadbearing walls. In domestic buildings the structure is usually
in the form of timber joists although it may be concrete or even steel structures can
be used.

Ceiling - usually plasterboard.

Outlets and gutters.

The choice of materials for the different components will depend upon type of roof, whether
cold deck, warm deck or inverted (see below). Components must be compatible with each
other as some components, for example, may react badly when in contact with other
materials.

Roof Covering Waterproofing System


The covering for a flat roof will normally comprise of one or more layers of roofing sheet
material.
This material should be of adequate durability and remain weather tight, resisting the action
of rain, snow and ice, and preventing any water entering the building.
The designer will need to ensure the roof covering is robust enough to handle all the dead,
imposed and wind loads, and UV solar radiation.
There are various types of roof coverings including:

Builtup reinforced bitumen membrane (often named felt).

Mastic asphalt roofing.

Single-ply roofing systems.

Green roofs (intensive and extensive).

Metal sheet roofing, including zinc, copper and lead.

Priming decks and substrates


In order to achieve a good key, ensure a longer lasting watertight finish or to stabilise and
seal porous substrates, primers can be applied before applying the waterproofing covering.

Built up bituminous membranes (felt)

Built up bituminous membranes are probably the most economic and common form of roof
covering material for domestic flat roofs. They can be used on timber, metal and concrete
decks.

Todays high performance felts are reinforced with polyester or glass or a mixture of the two,
and are coated and impregnated with bitumen.
High performance felts are supplied in rolls and can be laid in two layers bonded together
with hot bitumen. The multiple layering reduces the risk of failure as any damage in one
layer will usually be covered by the next layer.
High performance felts are often referred to by the additive used in their manufacture:

AAP (atactic polypropoylene) normally used for torch-on technique.

SBS (stryrene butadiene- styrene) - normally used for pour-and-roll application.

Roofing felt should conform to the requirements of BS EN 13707:

Flexible sheets for waterproofing - reinforced bitumen sheets for roof waterproofing.

The most common tyoes of felts are described below:


Type 5

Class 5B or 5U felt can be used for the base or intermediate layer.

Class 5B can only be used for the top layer when provided with surface protection.

Class 5E can be used for the top layer and is already provided with a surface
protection in the form of mineral granules.

Type 3

Type 3 glass-fibre-based felts are less durable and are only suitable for intermediate
layers, but can be used as a base layer when partially bonded.

Type 3G is perforated and can be used as a venting base layer to give a partial bond.

Type 1 traditional organic woven rag based felts have been removed from the British
standards and should not be used.

Laying the felt


All felts should be laid in the following manner:

with staggered joints.

with side laps of 50mm minimum and end laps of 75mm minimum.

the sheets should be laid, starting from the bottom, laying progressively up the slope
of the roof so that water will not run into the joints of the laps.

a vapour control layer is required beneath the insulation.

Torch-on membranes

Torch-on bitumen felts are pre-coated with bitumen. The top layer is usually polyester based
and the underlay may be polyester reinforced or glass fibre based.
Application

Melt the bitumen by heating on the underside of the membrane from a gas torch.

Roll membrane out on to the substrate where it can form a bond.

The torch-on technique is very reliant on good workmanship and is unsuitable for laying on
to timber decks or flammable materials.

Traditional pour and roll method of bituminous flat roofing


The pour and roll method is the more traditional way of laying the roofing membrane.
Application

Heat the bitumen to over 200C.

Pour the heated bitumen onto the substrate in front of the felt.

Roll the felt onto the hot bitumen.

Full or partial bonding


The felt membrane can either be partially or fully bonded to the substrate. The pour and roll
and torch on technique will provide a full bond, this has the advantage of providing a high
level of resistance to wind uplift and ensuring no flow path for water is provided under the
membrane which could cause moisture to become trapped and blister the membrane.
However, a full bond will not accommodate thermal movement between the membrane and
the substrate which could possibly cause the membrane to split or crack.
Therefore, the first waterproofing layer is usually partially bonded. This can be achieved by
using one of the following methods:

Providing a perforated underfelt, for example Type 3G, laid loose over the decking or
over rigid insulation boards before applying the bitumen.

Pouring the hot bitumen in a series of strips, before rolling the felt into it.

Mechanically fixing the felt by nailing it to the substrate using 20mm galvanized clout
nails at approximately 150mm centres in both directions. This is the usual method of
fixing when laying the felt on to timber board substrates.

Subsequent layers of felt membrane should always be fully bonded.

Partial bonding will allow the waterproofing layer to be isolated from the substrate so that it
accommodates differential movement that might otherwise cause it to split.
However, the reduced contact between membrane and substrate in a partial bond will mean
there is a greater potential for wind uplift.
Click Image for Low-Res Preview

Warm Flat Roof Detail, Felt Covering


2.49
Add To Basket

Cold applied bitumen felt roofing


Cold applied membranes are a safer alternative to using hot bitumen and gas torches, but
are only really suitable for small jobs such as small repairs or shed roofs.
Cold applied bitumen membranes usually comprise of fibre or glass fibre and bitumen and
are bonded with a suitable cold adhesive of brushable consistency.
Membranes are applied in one, two or three layers on concrete, asphalt, metal and timber
decks, although the manufacturer's details should be checked to ensure compatibility.
Absorbent or dusty surfaces should first be primed with a suitable proprietary roof primer.
Application

The deck must be free from any dust, dirt, moisture etc and may need to be primed
with special primer.

The adhesive is applied evenly onto the roof surface.

The roofing felt is unrolled onto the adhesive.

All laps are sealed with the cold adhesive.

Pressure contact may be required to ensure full adhesion.

Laps should be a minimum of 75mm and sealed or heat welded.

Joints should be staggered.

Self Adhesive Membrane


Self-adhesive membranes are bituminous compounds with a polyester and/or fiberglass
reinforcement with the adhesive already on the underside of the membrane.
Normally laid in two layers, they can be applied without using hot gas torches and can be
laid with only basic skills.
Application

The deck must be free from any dust, dirt, moisture etc and may need to be primed
with special felt primer.

The backing paper should be pealed off and the membrane stuck to the prepared
deck.

Pressure contact is required to ensure full adhesion.

Laps should be a minimum of 75mm and sealed or heat welded.

Joints should be staggered.

Self adhesive membranes are ideal for the diy market for application on small roofs,
garages, sheds. Self adhesive membranes should not be laid in cold weather.

Single Ply Roofing


A single-ply roofing membrane is suitable for use on timber, metal and concrete decks;
although compatibly with other materials should always be checked with the with
manufacturer.
Single-ply membranes are mostly used on large commercial buildings. They can be laid in a
single sheet and allow more choice in roof design.

Todays single-ply membranes are strong, flexible and durable and have a typical life span of
about 20 years but are often known to last longer.
However, there are no national standards for single-ply membranes and installation should
be in strict accordance the manufacturer's details, the British Board of Agreement (BBA)
certificate or WIMLAS certificate.
Single-ply membranes are made from synthetic polymers or rubber often reinforced with
glass fibre or polyester. They can be categorised as either thermoplastic or elastomeric.
Click Image for Low-Res Preview

Warm Flat Roof Detail, Single-Ply Membrane

Thermoplastic
Thermoplastic membranes include PVC (polyvinyl chloride). These can soften when heated,
allowing them to be hot welded.
However, thermoplastic membranes can be susceptible to damage when in contact with
other chemicals including bitumen, therefore compatibitly with other materials should
always be checked.

Elastomeric

Elastomeric membranes include Butyl rubber and EPDM. Common in the UK, these
membranes are less sensitive to temperature than thermoplastic and provide good weather
resistance.
Installation
Single-ply membranes can be laid as one entire piece with the eaves and verge already
formed in the factory or in rolls which are laid in strips. The laps can then be joined by heat
welding or proprietary solvent to melt and fuse laps together or adhesive tapes, depending
on the type of membrane.
Single-ply sheets should always be laid starting from the lowest point of the roof so that
rainwater is shed over all lapped joints rather seeping between the sheets.
Insulation manufacturers often recommend an additional 12mm plywood to be provided
between the insulation and the membrane.
Fixing to the substrate
Single-ply membranes can be attached to the substrate using any of the following methods;

Mechanical fixing
This is the most common type of fixing.
The membrane is loosely laid and mechanically fixed through the insulation to the
substrate using proprietary metal or plastic screw fastenings.
Single-plys can also be mechanically fixed by heat or chemically welding special
membrane coated discs or strips to the deck.

Adhesive bonding
Adhesive bonding provides a full bond to the insulation or deck. The membrane is
rolled into a proprietary adhesive applied directly to the substrate. A few single-plys
come with the adhesive already bonded to the membrane.

Bitumen bonding
Some single-ply membranes are fully compatible with bitumen and can be rolled
directly into hot bitumen poured onto the substrate.

Loose laid and ballasted


This method of fixing is suitable for warm and inverted roofs.

In a warm roof design, the single-ply membrane is laid loose over the insulation. The
ballast, in the form of round washed stones, paving slabs or soil and planting (green
roof systems), is then laid over the membrane. The weight of the ballast holds the
membrane in place.
A polymeric layer should always be provided between the membrane and the ballast
to protect the membrane from abrasion.

Mastic Asphalt
A mastic asphalt roof gives a seamless covering and can be used on timber, metal and
concrete decks. It is not as common as built up felt for small domestic roofs, even though it
is known to be more durable and generally performs better as a waterproofing material.
Mastic asphalt is a mixture of asphalt, bitumen and aggregates. Asphalt occurs naturally in
asphalt lakes and rock but is more commonly obtained from the process of refining crude oil.
Modern mastic asphalt products incorporate polymer which enables an extremely durable
and flexible material to be produced.
Mastic asphalt should be laid to the recommendations of BS 8218 Code of Practice for mastic
asphalt roofing.

Mastic asphalt is delivered on to the site as solidified blocks and is re-melted before applying
to the deck. The number of coats should be appropriate to the waterproofing requirements
and anticipated traffic, but will usually be two coats a minimum 20mm thick over an
isolating membrane of type 4A black sheathing felt to BS747.
The sheathing felt should be laid loose with 50mm overlaps and will protect the mastic
asphalt covering from damage caused by thermal movement of the deck. Insulation
manufacturers often specify an additional 13mm fibreboard over the insulation.

The effects of solar radiation on the mastic asphalt can be reduced by rubbing sand into the
surface of the topcoat breaking up any build-up of bitumen.

Liquid Applied Coatings


Liquid applied systems are ideal for diy projects and carrying out repairs. They provide a
seamless finish with a full bond to substrate and are often a practical option for curved roofs.
Normally, bitumen-based liquid applied systems are emulsified flexible polyurethane
systems or synthetic rubber systems. Generic types are defined as ETAs.
Most liquid applied systems are cold-applied, although hot-applied systems are available.
Application

Apply a primer on a clean dry surface.

Brush, roll or spray the liquid applied membrane on to the substrate in three or four
layers.

Some form of reinforcement fabric(scrim) to deal with the tensile stresses, either
glass fibre or polyester fleece, should be laid loose before the second coat is applied
(some types are already fibre-filled and do not require additional reinforcement).

A high standard of workmanship is essential.


No standards exist for this type of system and the manufacturer's guidance should always
be followed. Compatibility with insulation, deck etc must be checked. Most types of liquidapplied membranes should not be applied below 5C.
However, liquid applied membranes do not offer the same durability as some other
coverings, with a life expectancy of only around 10 years.

Sheet Metal Roofing


Sheet metal materials commonly used for flat roof covering include aluminium, copper, lead,
stainless steel, terne coated stainless steel (TCSS) and zinc.
They are usually in the form of preformed panels with the sheet metal already bonded to a
plywood background. The sheets are laid over the supporting structure on a slip layer of
polythene to accommodate movement.
Copper is a particularly durable choice of metal but can be expensive. Lead is a more
common choice as it is less expensive and can still last 100 years or more.
Sheet membrane should not be laid in temperatures of 5C or below.
Lead

Lead is specified in codes from Code 3 to 8. The higher the code number, the thicker and
more durable the lead will be. Flat roofs will require a minimum of Code 6 lead. Expansion
joints known as rolls and drips must be formed in lead sheeting.

Service Perforations
Air leakage and water ingress should be prevented by sealing around pipes or ducts passing
through the roof, for example around soil and vent pipes or roof ventilators. The roofing
membrane should be taken up around the pipe or duct and provided with a cover flashing.
Any services through the vapour control layer must also be sealed.

Flat Roof - Surface Protection


Surface Protection
Most flat roofs will need some form of surface protection for the following reasons.

UV rays - The covering of a flat roof will spend many years exposed to ultra violet
light from the sun, this can lead to oxidisation of the roof surface causing the
plasticisers leak out and the surface to become brittle. This can significantly affect
the performance and durability of the roof.

Thermal movement - Heat from the sun can also cause solar radiation, where heat is
transmitted to the roof system causing continual expansion and contraction which
can be very damaging. This is a particular problem for built-up felt and asphalt roofs
as dark membranes absorb more heat.

Differential movement - The temperature difference between the roof covering and
the structure below, in a warm roof, may be high, leading to thermal stresses and
possible splitting of the membrane.

Fire protection - The Building Regulations Approved Document B4 sets out certain
specified performance levels of surface finishes on flat roof to control the spread of
flame.

Surface protection should be light in colour because it will provide good solar reflectiveness
and emit absorbed heat more efficiently.

Surface Protection Methods


The various methods of surface protection are detailed below.

Factory Applied Protection

Self finished mineral- surfaced felts are available which limit UV radiation, these
should be of Class 3E or 5E to BS747. Some of these felts also give an AA external
fire rating although AB is more common.

The felts are ready surfaced with a granular material of fine sand, green mineral
aggregate, small crushed slate flakes or granite. Membranes faced with metal
(aluminium, copper, stainless steel) are also available.

However some self finished felts have little reflective quality and do not provide
protection from the damaging effect of temperature rises in the membrane surface or
solar gain.

Single-Ply Membranes
These membranes are generally self finished with good reflectivity and resistance to UV
ageing and so do not usually require additional solar protection. However the fire rating of a
single ply membrane must be checked with the manufacture.

Solar Reflective Painted Finishes


Proprietary solar reflective paints can be painted on the surface of flat roof to provide solar
reflection. This helps protect the roof from the potentially damaging effect of the ultraviolet
solar radiation (compatibility with bitumen based materials should be checked).
However these paints are not very durable and reflectiveness deteriorates rapidly, therefore
repainting is required every 3 to 5 years. They also do not attain the AA fire rating required
for most flat roofs.

Solar Reflective Chippings

Solar protection is often achieved by the application of white reflective chippings,


usually limestone or light coloured spar, not less than 12.5mm. These are very
effective at providing protection from ultra-violet light and reducing the surface
temperature in hot weather. The density of the stones will also slow the rate of heat
gain and heat loss from the building.

The chippings can be laid loose or bonded in hot or cold bitumen compound to the
roof covering.

Chippings can be used provide a ballast layer to help hold down the roof surface in
exposed locations.

However, the chippings can move around or conceal defects in the roof and should
not be walked on as they may puncture the membrane.

Chippings should only be used on roofs at less than 10 as complete adhesion at


steeper pitched is not possible.

Foot Traffic
Where flat roofs are designed for regular access such as a terrace or balcony the surface
layer will need additional protection.
The form of protection will depend upon the anticipated usage and the appearance required,
but will usually be in the form of slabs or paving tiles, placed on raised supports to allow
rainwater to drain away.
The roof structure, the covering and insulation should be designed to support the dead
weight of the paving and live loads from foot traffic.

Cold Flat Roof Detail, Felt Covering


2.49
Add To Basket

Warm Flat Roof Detail, Felt Covering


2.49
Add To Basket

Flat Roof - Deck


Deck
A deck is the structural substrate of a flat roof and should be capable of supporting the
static and dynamic design loads as well as any loads occurring during construction from
machinery and plant.
The deck should be of adequate strength and stiffness to ensure structural integrity and
provide suitable support to the roof covering system, the VCL and insulation board (warm
roof) without deflection.
The deck must be dry, clean and primed as necessary before laying the waterproofing and
insulating system to ensure good adhesion.
The material used for the roof deck must be moisture resistant and will usually be plywood,
OSB or timber boards although concrete and woodwool slab or profiled metal can also be
used.

Ordinary chipboard is not recommended as it may absorb moisture when damp and lose its
structural integrity.

Timber Boarding
Softwood timber boarding is the traditional material for the deck.
The timber used for the deck should be:

of a naturally durable species or preservative-treated in accordance with BS EN 5991:2009

a minimum of 19mm thick.

double nailed at each joist.

laid with staggered joints.

laid with the edges of the board corresponding with joists or noggins.

Tongued and grooved boards are preferred over plain-edged to help minimise warping after
natural shrinkage, which may cause damage to the waterproof covering.

Plywood
Plywood for a roof deck should be of marine grade and suitable for external use to BS EN
636 or a bond Class 2 or better, complying with BS EN 314 (check).
Plywood boards used for the deck should be:

a minimum thickness of 18mm (these will be able to span up to 600mm).

double nailed at each joist.

laid with staggered joints.

laid with the edges of the board corresponding with joists or noggins.

provided with expansion gaps of 3mm should be provided between the boards.

Oriented Strand Board (OSB)


OSB is a type of wood panel comprising of timber strands and should be manufactured in
accordance with BS EN 300: Part 3: 1992.
OSB Boards used for the deck should be:

a minimum thickness of 18mm (these will be able to span up to 600mm).

double nailed at each joist.

laid with staggered joints.

laid with the edges of the board corresponding with joists or noggins.

provided with an expansion gap of 3mm between boards.

Concrete

A concrete deck is more common on blocks of flats and commercial buildings.

Concrete is a strong and steady deck material providing both the loadbearing
supportive structure and roof deck.

Concrete decks are either reinforced cast in situ (poured on site), or supplied as precast concrete units.

The surface of a concrete deck should be free from ridges and hollows. A screed of
sand and cement is usually provided over the surface to get a smooth base for the
insulating or waterproofing layer above and to create the desired fall. The fall can
also be produced by proprietary decking or insulation products which are produced
ready-cut to a suitable fall.

Concrete decks should only be covered by non-bonded or partially bonded roof


coverings.

Wood wool Slab

Woodwool slabs are a rigid timber and cement based panels, which can be reinforced
if long spans are required.

Woodwool slabs should be no less than 50mm thick and conform to BS EN 13168.

Profiled Metal Decking

This type of deck is usually formed in galvanised steel or aluminium.

The lightweight construction has the advantage of being able to cope with very long
spans, enabling large room spaces to be created and reducing the load on the
building's structure.

Profiled metal decking does not provide a continuous surface and therefore can only
be used when supporting a timber deck or rigid insulation which can then be covered
with a bitumous or polymeric membrane.

This type of decking is not suitable for cold roof design unless it is subsequently
overlaid with plywood or OSB.

Flat Roof - Insulation


Insulation

Insulation is required to minimise heat losses in the winter and control excessive solar gains
in the summer. This will help to conserve energy and ensure thermal comfort is maintained
within the building.
Insulation can also help to limit condensation and contribute to acoustic insulation
(depending on the type of insulation used).

U value of a flat roof

To comply with Part L of the building regulations 2010, all roofs to rooms (except
those in unheated buildings) should be thermally insulated to a maximum U-value of
of 0.18 W/mK.

A lower U-value indicates better insulation properties, hence U-value requirements


usually specify a maximum value.

U-values calculations take into account the thermal resistivity and thickness of the
insulation.

Thermal resistance is the rate of heat transmission through a unit area for each
degree of temperature difference from inside to outside the building.

When calculating the U-value of a flat roof, screeds, timber, air spaces, plasterboard
etc contribute to the thermal performance and should all be considered.

Insulation Materials
The choice of a insulation will be usually dictated by the roof design. Some of these are
fibrous materials which derive their performance from air trapped between fibres. Several
different insulation materials are available including:

Synthetic foam plastics

Natural materials (e.g. cork)

Inorganic materials (e.g. glass fibre. cellular)

Mineral wool

Loose fill

Quilt

Cellular glass CG. Cellular thermal insulation materials are composed of materials of
polymeric and mineral origin.

Polymeric materials

Polyurethane PUR

Polyisocyanurate PIR

Rigid urethane foam (PUR/PIR) RUF

Phenolic foam PF

Polystyrene - expanded EPS

Polystyrene - expanded - extruded XPS

About Materials

Some manufacturers of PVC waterproofing membranes recommend that a


separation/protection fleece is installed on top of the membrane before the insulation
board is laid in place.

Where a roof is to be finished in gravel, a water permeable filler fabric can be laid on
top to protect the membrane from any fines which may be washed down below the
insulation.

If the waterproofing is asphalt or BUR felt, depending on the size of the gravel being
used, it may not be necessary to use a filler fabric.

Rigid board cellular material which derives its performance from the thermal
resistance of gases trapped in the cell structure and from the thermal resistance of
the cell walls.

Insulation in a warm roof

The insulation for a warm roof will usually be boards of extruded polystyrene or rigid
compressed boards of glass fibre or rock fibre. These are can be supplied with rebated edges
which interlock reducing the risk of uplift.
The insulation material for a warm flat roof should:

be able to cope with extremes of temperature and UV light without deterioration in


thermal performance.

be able to resist pressure from any anticipated foot traffic.

be durable and suitable for external use.

be able to provide support for, or protection of, the weatherproofing membrane.

be able to resist moisture. This is particularly important for inverted roofs where the
insulation is directly exposed to the rain.

be capable of withstanding loads imposed on it during construction and future


maintenance.

An inverted warm roof must also:

be capable of receiving the extra load of the ballast.

An overlay between the membrane and the insulation will protect the insulation from heat
when laying hot bitumen and provide a slip layer to account for any thermal movement.

Tapered Insulation

Tapered insulation boards are designed and pre-formed to provide the appropriate drainage
falls.

Composite
Composite board can be found on both warm and inverted roof applications.
These often have a deck of plywood with a cellular insulation and metal foil vapour control
layer bonded to the underside and a top layer with an overlay factory-bonded to it.

Bonding

The insulation may be fully or partially bonded to the vapour control layer or laid
loose.

If the insulation has a sufficiently high vapour resistance, a separate vapour control
layer may not be required and the insulation can be bonded directly to the deck.
However, the insulation must be compatible with the bonding materials used.

Where insulation is mechanically fixed, the fixings must be of sufficient length to


ensure they can be secured through to the deck into the structure.

Avoiding Thermal Bridges


Thermal bridging occurs where the continuity of the insulation has been broken.
This can lead to condensation, mould growth or staining.
Cold bridging is likely to occur:

At Junctions with a wall.

Where pipes penetrate the roof.

Flat Roof - Drainage


Drainage
A correctly build flat roof will drain the rainwater quickly and effectively into the gutters
without allowing water to collect in depressions and pond on the surface of the roof leading
to the build-up of silt deposits on the roof and stresses in the membrane when the water
freezes (a small amount of ponding is evitable and it should not reduce the performance of
the roof covering).
Ponding will be reduced by ensuring the roof is provided with a decent fall allowing the
rainwater to be drained effectively towards the outlets and gutters at the edge of the roof.

Design Falls
When specifying a fall for a flat roof, the designer should take account of:

Any potential deflection of the structural members and decking under dead and
imposed loads (a particular problem with timber and metal deck roofs).

Possible inaccuracies in construction.

Type of weatherproofing material used.

Because the desired fall may be difficult to achieve in practice, the designer may need to
adopt a design fall considerably steeper (often twice) than the recommended finished fall.
The building regulations encourage a minimum fall of 1:40.

Minimum finished fall required according to BS6229 is 1:80.


Recommendations for specific materials are as follows:

Aluminium 1:60

Copper 1:60

Zinc 1:60

Lead sheet 1:80

Built-up bitumen sheet 1:80

Mastic asphalt 1:80

Single ply membranes 1:80

Liquid waterproofing systems (hot- or cold-applied) 1:80

Green roofs should have a fall of not less than 1:60 and be built in accordance with
manufacturers details and British Board of Agrment certification.

The desired fall may be created in one of the following ways:

Sloping decks
The fall of the roof may be created in the structure itself by laying the supporting
beams, or joists at a slope (giving a sloping soffit) or by installing tapered beams with
horizontal soffits.

Firrings
It is normal practice for the joists of a flat roof to be set level thus creating a perfectly
level ceiling. The required fall is then formed using strips of tapered shaped timbers
known as firrings fixed along the tops of the joists before the deck is laid. These
firings should be the same width and length of the joists. The firrings may also
provide the fall by each one decreasing in thickness along the slope of the roof.

The firrings can be fixed at right angles to the joists instead of along the length of the
joists, this will provide a better level of ventilation. However, when fixing in this
manner it is essential that the firrings are of suitable structural strength to span
between joists and should not be less than the following sizes.

Distance between Joists

Size of Firrings
Width of Firrings

Depth of Firrings

400 / 450 mm
600 mm

38 mm
38 mm

38 mm
50 mm

Pre-formed insulation boards


Proprietary preformed tapered insulation boards can provide drainage falls to a warm
decked roof (manufacturers recommend falls not less than 1:60). The boards should
be laid onto a vapour control layer and be covered with the waterproofing system.

Concrete and Screeds


Falls on a flat roof with a concrete deck are either provided within the structural
concrete itself or created within the screed which is laid over the concrete deck (as
for in-situ cast concrete slab).

A Selection of Detail Drawings by Categories. This is just a Small Sample from our Drawing
Library.
Foundations

Guttering

Gutters and downpipes should be adequately sized to deal with storm conditions in
accordance with BS EN 12056-3. Flat roofs should be designed to drain the roof to
one or two edges towards gutters and outlets.

There should be a smooth transition into the gutters which can often be lined using
the roofing membrane to achieve a completely uniform finish (check the
manufacturer's details).

Internal gutters can be used but conventional eaves gutters are preferable.

If unavoidable, internal outlets should be fitted with leaf and gravel guards.

Welted drips should extend to the middle of the rainwater gutter, and there should be
a minimum of 50mm turndown.

To ensure the rainwater is directed towards the gutters, the sides of the roof surface
(apart from the gutter edge) require a minimum of 50mm upstand verge provided
using triangular pieces of timber called tilt fillets nailed to the edges of the decking,
not to the wall.

All gutters and downpipes should be accessible for maintenance.

Weathering Details

Upstands

At the point where the roof deck meets the external wall or at parapets, careful
detailing will be required to prevent water ingress.

To avoid a sharp bend where the membrane is folded up the wall, which could cause
a split, a small strip of timber angle fillet a minimum 75mm x 75mm is fitted under
the felt and fixed firmly to the deck.

The waterproofing membrane must be taken up the wall at least 150mm (providing
an upstand) above the roofing surface.

Flashing

The membrane upstand should be protected by a cover flashing to give a good


watertight joint.

Lead should be cut into the horizontal mortar joint and overlap the top edge of
roofing material not less than 50mm, finishing no closer than 75mm above the roof
surface.

Cavity Tray

If the wall is a cavity wall, a cavity tray must be fitted, stepping downwards at least
150mm and weep holes should be provided.

Flat Roof - Structure


Loading

Flat roofs shall be designed to carry all imposed and dead loads acting on the structure of
the roof. These may include:

Dead loads- from the self weight of the roof construction.

Environmental loads - such as snow, water and wind loads should be calculated in
accordance with BS EN 1991.

Plant and equipment placed on it during its construction.

Traffic loads from roof maintenance equipment and personnel.

Roof terraces and gardens must be able to carry the additional loads expected from foot
traffic, planting and furniture etc.

Uplift
Flat roofs should be constructed to provide protection from wind uplift this can be achieved
by either

being sufficient weight to prevent lifting or

by fixing the joists to the wall plates and securing the wall plate with vertical holding
down straps, at least 1m long and 30mm x 2.5mm in cross section at 2.0m centres.
Wall plates are to be fixed to masonery using hardened nails 4mm in diameter x
75mm long or 50mm long wood screws if fixed into timber.

The roof covering membrane may also require additional fixing using mechanical fasteners
to prevent uplift high wind load areas.

Timber Roof joists


All roof timbers including joists, wall plates, blocking, strutting, battens, firings and noggings
must be to be preservative treated unless the timber used is naturally durable.

Sizing Joists

The joists should be sized using either the TRADA span tables or BS EN 1995.

The sizing and spacing will depend upon the loads imposed on them and the required
span.

Wherever possible joists should span the shortest distance.

Common joists sizes are 200 x 50mm, 175 x 50mm, and 150 x 50mm.

The joists will normally be placed at 400mm centres but no more than 600mm
centres.

Packing

Hard packing, for example tiles or slates bedded in mortar, can be use to ensure the
joists are level.

Loose or soft packing including timber should not be used.

Fixing Joists

The joists can be built into the wall or hung from joist hangers.

The joist hangers must be the correct size for the joists and conform to BS EN 845.

The joists should be placed on and fixed to timber a wall plate which is bedded in
mortar on top of the inner skin and strapped down using galvanised holding-down
straps.

Fixing joists to an existing wall

Where a new flat roof abuts an existing external wall, the joists can be hung on metal
joist hangers which are fixed to a horizontal timber plate wall bolted to the wall.

A cavity closer should be provided to the top of the walls to prevent fire spread and
to stop damp air entering the roof space.

Lateral Restraint
Lateral restraint should be provided to walls by:

ensuring concrete elements and timber joists where they are built in have a minimum
bearing of 90mm.

proving restraint straps at 2m centres where joists run parallel to walls.

Strutting
Strutting is required in order to prevent twisting of the joists at the following points:

one row when the span of the joists exceeds 2.5m.

two rows or more when the span exceeds 4.5m.

Strutting should be either:

herringbone type (timber 38mm x 38mm).

solid blocking (38mm thick timber x depth of joist).

proprietary steel strutting.

or

Any strutting provided should not obstruct the cross ventilation. required to cold deck roofs.

Flat Roof - Condensation


Introduction
Condensation within a flat roof mainly occurs during cold weather when moisture vapour in
the air which has been generated within the heated building rises from the room below into
the cold roof void above the ceiling.
When the temperature of the vapour falls to or below its dew point the water vapour
condenses on cold surfaces.
The warmer than air the more water vapour it can contain and the higher the moisture
content in the air (relative humidity; RH) the lower the dew point temperature will be.
Condensation is a particular problem in roofs above rooms which generate a lot of moisture
such as kitchens and bathrooms.
A flat roof should be designed to minimise condensation and a condensation risk analysis
should be undertaken taking into account positioning of insulating materials, vapour control
layers, ventilation, thermal insulation and the choice of materials. This can be calculated
using computer programmes.

Surface Condensation
Another type of condensation is surface condensation which is visible on surfaces within the
building and occurs when the temperature of the surface is at or below the dew point of the
moist air.
This type of condensation is often identifiable by black mould on the walls, windows, ceilings
etc.

Interstitial Condensation
Condensation which occurs within the roof structure is called interstitial condensation. It is
particularly dangerous because it can cause unseen decay in roof timbers and fixings.

Condensation in a cold roof

Interstitial condensation is a particular problem in cold deck roofs where the insulation is
placed in-between the joists in the void above the ceiling.
The position of the insulation means that the roof deck and most of its structure has no
protection from low temperatures during the winter.
These elements then become much colder than the interior of building, and moisture vapour
which has made its way up from the room below is then liable to condense on the timber
structure possibly leading to decay.
Cold deck roofs are not recommended for new work, and actually banned in Scotland.

Cross-Ventilation
To help disperse the moisture vapour, the building regulations require cross ventilation to be
provided in the form of a 50mm air gap between the deck and the insulation and continuous
gap of about 25mm at the eaves.
This can be difficult to achieve where roofs abut external walls and propriety mushroom
vents to provided the equivalent 25mm continuous ventilation are available.

Vapour control layer for a cold roof


However the cross ventilation does not completely remove the moisture vapour in the
ceiling void and a vapour control layer sealed at joints and penetrations is required under
the insulation and over the plasterboard to provide a barrier against moisture vapour rising
up from the room below.
Alternatively metalized polyester lined plasterboard can be used.

Vapour control layer for a warm roof


A vapour layer should be positioned under the insulation or, in some situations, immediately
below the roof covering to minimise water vapour condensing beneath the membrane.
Vapour control layer may be formed using any of the following:

A polythene sheet membrane loose laid and restrained by mechanical fasteners or


nailed to the deck (timber decks) all laps should be sealed with an appropriate
adhesive.

A reinforced bitumen sheet. - one layer of BS 747 Type 5U felt, fully bonded or
mechanically nailed to the deck.

Two layers of Type 5U felt fully bonded in hot bitumen. check - all laps must be sealed
with bitumen.

For single-ply membranes, the VCL should be either polythene or reinforced


aluminium foil.

Designers often specify readymade composite decking that combines together plywood,
insulation, vapour control layer and felt covering into one product.

Flat Roof - Green Roofs


Green Roofs
Green roofs offer a sustainable and ecologically friendly solution, whereby plants and
vegetation can live on the deck of the roof.
The plants on a green roof contribute to improving air quality by producing oxygen and
absorbing air pollutants, dust and CO2.
The thermal mass of a green roof provides a good level of thermal performance providing
passive heat storage, as well as significantly reduce cooling requirements in the summer.
Green roofs contribute to suds (sustainable urban drainage).
Rainwater is stored in the substrate and vegetation reducing the volume of rainwater runoff
from the roof which provides a more natural drainage process for storm water than a
traditional flat roof.
There are two main types of green roof:

Extensive
Supplied as a complete system this type of roof can be built using a only 50mm soil
base and lightweight construction.
However vegetation for this type of roof is limited to sedum, grasses, and mosses
contained within a sedum blanket.
This type of green roof requires minimal maintenance is required, although an
irrigation system may be required for use in dry weather feeding with a slow release
fertilizer a biodiverse roof is the soil seeds naturally and no watering is required.

Intensive (roof garden)


Intensive roofs may contain a variety of plants including shrubs and trees, as well as
garden furniture and even small ponds.
Intensive roofs can only used on roof with a maximum pitch of 20o.
They require a soil base at least 150mm deep and a substantial steel or concrete
deck is needed to support the weight of the soil and plants.

Regular intensive maintenance is required for this type of roof.

Construction
The majority of green roofs both intensive and extensive are build-from the following
elements:

Vapour control layer - placed above the roof structure.

Rigid slab insulation must be strong enough to withstand the additional loads.
Where the insulation is above the weatherproofing, only extruded polystryrene (XPS)
should be used.

Waterproof root barrier - for an intensive roof this should be reinforced bitumen
membrane (RBM) or mastic asphalt.
This will prevent roots penetrating the roof membrane. Suitable materials include,
rubber mats, bitumen, slate-surfaced layers or polyethylene.

Drainage layer- controls the rate of rainwater runoff.

Filter layer - prevents the soils etc from blocking the drainage layer or causing
damage includes foams, mineral wool, plastic sheets and granular drainage.

Growing medium (soil) - the depth of the growing layer will depend on the type of
roof. For an extensive roof the growing medium could be just a 20mm geotexile mats.
However soil 400mm deep is typical for an intensive roof.

Vegetation this is the planted layer which could be sedum, mosses and grasses for
an extensive roof or shrubs and trees for an intensive roof.

Green roof systems should be installed by a specialist installer to drainage falls of 1:60 min.

Pitched Roofs - Overview


Introduction
The function of a roof is to protect the building below from the weather. In order to
satisfactorily fulfil this function over a period of years it must be strong, stable and durable.
In addition, roofs must provide good thermal insulation and prevent the spread of fire from
adjacent or adjoining properties.

Click Image for Low-Res Preview

Pitched Roof Detail, Ceiling-Level Insulation

The majority of houses in this country are constructed with pitched roofs.

The angle of the pitch may be dictated by aesthetic or structural factors.

It may also be influenced by the nature of the roof covering.

Modern tiles permit shallow pitch but some of the older traditional coverings, such as
hand made clay tiles, require quite steep slopes to ensure rain does not penetrate
the roof covering.

Shallow pitches are generally cheaper to construct with savings in both timber and
tiling.

In traditional pitched roofs, the rafters are supported by a wall plate at the bottom
and a ridge board at the top.

Intermediate support is supplied by a horizontal purlin.

Most modern roofs for new houses are built from prefabricated components erected
on site.

Lean-to Roofs
The simplest of pitched roofs is the Lean-to roof, commonly found forming the rear
extensions to terraced housing.

The sloping timbers are known as rafters and are supported at the top by building
them into the solid wall (not recommended nowadays) and at the bottom by securing
to a wall plate.

The wall plate is a strip of timber which is bedded in mortar on top of the wall, and
which evenly distributes the load from the roof and provides a good fixing for the
rafters.

Note: Mortar cannot actually bond the timber to the wall.

The wall plate should be 100mm x 75mm 0r 100mm x 50mm.

Ceiling joists are often built into the wall or supported on a wall plate bedded within
the wall (not recommended).

The rafters are skew nailed to the plate

The depth of the rafter depends on its span and loading, and the width is primarily to
prevent twisting and to provide a sufficiently wide surface on which to nail the
battens supporting the tiles

It is good practice to notch the bottom of the rafter where it sits on the plate as this
gives a good bearing and aids alignment of the rafters.

The rafters are usually spaced at 400mm centres.

In most houses, the guttering is supported by the facia board. This is fixed to the feet
of the rafters and it can be flush against the wall or it can form an overhang.

Lean-to roofs can achieve only modest spans.

Drainage - Foul Water


Foul Water Drainage
Foul water comprises of black soil water from toilets and grey waste water from baths,
basins, sinks, washing machines etc.
A foul water drainage system carries foul water from the building to an underground sewer
pipe, a cesspool, a septic tank or a wastewater treatment system. (Public sewers are not

considered in this guidance and consultation with the Local water authority should be sought
when building near or over a public sewer see below.)
The Building Regulations 2010 require that the foul water should be discharged in order of
priority, therefore where it is reasonably practicable to do so, a connection should be made:
Click Image for Low-Res Preview

Drainage Pipe Through Wall Lintel

1) to a public sewer.

2) to a private sewer communicating with a public sewer.

3) to a septic tank or other wastewater treatment plant.

4) to a cesspool.

The first solution on the list should preferably be adopted, where this is not possible move
down the list to the next.

Combined and Separate systems of drainage


Underground drainage systems can be divided into two types :

1) Combined system - In a combined system the foul water and the rainwater are
carried in the same underground pipes. The advantages of this system are firstly that
the rainwater helps to clean the pipework minimising blockages, and secondly less
pipe work is required, although the pipe sizes may need to be increased.

2) Separate system - In a separate drainage system separate sewer pipes are


provided for the foul water and the rainwater.

The water authorities discourage combined systems because:

1) They can cause an overload of the drainage system.

2) They produce an increased amount of water to treat. New developments are often
required to provide a separate system of drainage up to the point of connection with
a combined sewer.

Pipe materials
In the past, drainage pipes have been made from a variety materials, including pitch fibre,
vitrified clay, uPVC, concrete, glassfibre reinforced plastics (GRP), iron and asbestos cement.
Not all of the materials used have performed well, for example, pitch fibre has a tendency to
collapse under heavy clay soils and expensive repair work may be required.
Today, most new domestic drainage is constructed using plastic (flexible) pipes or clay (rigid)
pipes, usually 100mm and 110mm in diameter, or 150mm and 225mm in diameter for public
sewer pipes.

Types of pipes

Socketed clayware.

Plain-end clay c/w coupling.

Plastic 100/150mm.
Click Image for Low-Res Preview

Drainage Pipe Through Wall

Clay
Clay drainage pipes date back to the Victorian times, their inherent strength means they are
more durable and less likely to deform under loads than plastic. They are also:

Highly frost resistant.

Rodent resistant.

Able to be laid directly into a well trimmed trench (Class D bedding).

Clay pipe manufacturers promote their environmental advantages claiming clay uses less
energy in production as well as requiring less aggregates for bedding and backfilling.

Plastic

Typically golden brown in colour, 110mm plastic pipes are the most common material used
for underground drainage today.
The advantage of plastic pipework is that it is:

Relatively cheap compared to clay.

Frost resistant.

Simple to cut to size with a hacksaw and lightweight, making the pipes easy to
handle and work with.

Flexible and can remain watertight and resist fracture when subject to small amounts
of movement.

However, excessive pressure from loads or ground movement may cause plastic pipes to
deform. Therefore they must be surrounded by a good bedding material such pea-shingle to
provide support and prevent the pipe from cracking.
http://www.buildingregs4plans.co.uk/guidance_flat_roof_types.php

Vous aimerez peut-être aussi