Vous êtes sur la page 1sur 5

CHECK LIST FOR BTS SITES

1 (5)

SITE ENGINEERING

TELECOM IMPLEMENTATION INSPECTION REPORT


19/03/09
JAWALAPURI
SITE
NAME: ................................................Date
Of

DLS1262
SITE ID: ........................
Visit: .......................

R-909-910, Jwalapuri, Paschim Vihar, Delhi

SITE ADDRESS: ...........Document


number: .........................
Guard Name and contact No.
19/03/09
Date of submission of Report:.
Notation:
S.N
o.

Correctly installed / Acceptable

Not correct

Infrastructure

Check point

Radio Site

GBT

RTT

ID/OD/POLE/WALL

INDOOR

Shelter

Buildg. Height (Mtrs/floor) 13M/4

POLE

OUTDOOR

WALL

POLE

4
Equipment Room Floor

Chain Pulley required


4

Space For
Equipments
(Sharing sites)

Space available for BTS

Floor

Levelled
grounding

Door

Sealing

ID LADDER

ID LADDER INSTALLED

Lighting

No. of fittings 2 2
Sockets operational

Earthing system

No of Pits with Chamber prepared

Space Available for TRSM Rack

Antistatic Mat

Antistatic

Locking
NA
SPACE ON EXISTING LADDER

Operational

Earthpits are interconnected

DG,DG-N,Tower,Shelter are conneted to EP


Earthing Values EP1
Ohms
10

Earthing Bus
Bars

EP2

EGB under feeder entry


IGB under feeder entry
EMP BUS BAR

EP3

Connected to Body Earthpit

Connected to Eqpt Earthpit

CHECK LIST FOR BTS SITES

2 (5)

SITE ENGINEERING

11

PIU/ACDB

PIU/ACDB Installed

POWER TERMINATION AT PIU/ACDB

PIU/ACDB commissioned

12

Mains Incomer

Mains available

Energy Meter Installed

13

DC Power
Availability

DC Power Available

14

DG

DG installed

15

Air-conditioning

Installed

16

WFT

Size of opening made for WFT NA

MCB available for BTS& TRSM

DG Commissioned

Sealing around AC units

Openings are properly sealed


17

Tower

GBT

No of Platforms & height

18

Type

19

Cable ladder
(OD)

No of Openings made
1

RTT

ACs are comm.

Tower Height 12 M

Tower Painting

Tower Type

Vertical Cable tray installed

Horizontal Cable tray installed

Space available on Vertical/Horizontal tray

20

Cable Ladder
lengths

8
Length of Vertcal ladder(above HCT till antenna mount)
mtrs.

Length of HCT ladder 6

21

Lightening
Protection

Lightening Rod

22

Aviation Light

Installation

in mtrs.

LA connected to Earthpit

COMMISSIONED

in

CHECK LIST FOR BTS SITES

3 (5)

SITE ENGINEERING

23

Cable Inlet

24

Antenna Mount

For Power & Signal Cables

GSM antenna mount Installed

Antenna Mount for MW at nearend

Antenna Mount for MW at Far End

25

GSM antenna
Mount hts.(as
per TND)

Height of GSM antennas

20

20

20

26

GSM antenna
Mount hts.
(existing)

Height of GSM antennas 20

20

20

27

MW Antenna
Mount ht.

Height of MW antennas

23

Height of MW antennas

23

(as per TND)


28

MW Antenna
Mount ht.
(Existing)

29

GSM antenna
Azimuth(As per
TND)

120

240

30

GSM antenna
Azimuth
(existing)

120

240

31

MW Antenna
Azimuth(As per
TND)

112

32

MW Antenna
Azimuth
(Existing)

112

CHECK LIST FOR BTS SITES


SITE ENGINEERING

Problems / Comments (Refer to applicable activity Sl. No.)


Tower/DG/Shelter/Equipment Earthing not done, EGB/IGB not available.

_________________________________________________________________________________
HCT Grouting is not done.

_________________________________________________________________________________
DG/PIU/SMPS Cabling is not done, DG not commissioned.

_________________________________________________________________________________
Access ladder for shelter is required.

_________________________________________________________________________________

Site Engineer Name & Signature:


Ravi Gupta

Name:...

4 (5)

CHECK LIST FOR BTS SITES

5 (5)

SITE ENGINEERING
Pls sketch whole Site Plan along with shelter/cage plan (including HCT routing)