http://electrical-engineering-portal.com/calculation-of-motor-starting-time...
Ca = CM CL
and shall be well calibrated to prevent it from being either too low, so as starting is
not too long and heavy which causes risks of temperature rise for the motor
or from being too high on the joints or on the operating machines.
8/4/2015 1:39 PM
2 of 6
http://electrical-engineering-portal.com/calculation-of-motor-starting-time...
A generic curve of the above mentioned quantities is shown in the Figure 1 below.
The concept of motor starting time ta can be associated to this concept of properly
calibrated starting and can be evaluated making reference to concepts linked to the
motion dynamics, but also by introducing simplifying hypotheses which allows, however,
an evaluation with a good approximation.
8/4/2015 1:39 PM
3 of 6
http://electrical-engineering-portal.com/calculation-of-motor-starting-time...
Load Coefficient
KL
Lift
Fans
Piston Pumps
Flywheel
0.33
0.5
The starting time allows to define whether a normal or a heavy duty start must
8/4/2015 1:39 PM
4 of 6
http://electrical-engineering-portal.com/calculation-of-motor-starting-time...
be realized and to choose correctly the protection and switching devices. The
above mentioned parameters relevant to the motor are given by the
manufacturer of the motor.
As an example, Table 2 below shows the values that these parameters can take for
three-phase asynchronous motors of common use and typically present on the market.
Obviously the parameters relevant to the load characterize each single application and
must be known by the designer.
Table 2 Typical values of some electrical and mechanical parameters of a three-phase
asynchronous motor
8/4/2015 1:39 PM
5 of 6
http://electrical-engineering-portal.com/calculation-of-motor-starting-time...
160 kW
Frequency
50 Hz
Rated speed
1500 rpm
1487 rpm
JM = 2.9 Kgm2
JL = 60 Kgm2
Load torque
CL = 1600 Nm
CN = 1028 Nm
Inrush torque
Max. torque
Load
with constant torque
KL = 1
For both typologies of load, the esteemed motor starting time results to comply
with the instruction given by the manufacturer regarding the maximum time
admitted for DOL starting. This indication can be also taken as a cue for a
correct evaluation of the thermal protection device to be chosen.
8/4/2015 1:39 PM
6 of 6
http://electrical-engineering-portal.com/calculation-of-motor-starting-time...
Recommended EE articles //
Share with engineers //
About Author //
Edvard Csanyi
Edvard - Electrical engineer, programmer and founder of EEP.
Highly specialized for design of LV high power busbar trunking
(<6300A) in power substations, buildings and industry fascilities.
Designing of LV/MV switchgears.Professional in AutoCAD
programming and web-design.Present on Google+
2015 EEP - Electrical Engineering Portal. All Rights Reserved | Privacy Policy | 17 queries in 0.124 seconds.
Powered by CsanyiGroup
8/4/2015 1:39 PM