Advantages of DOL
DOL starting is the simplest, cheapest and most common starting method.
Furthermore it actually gives the lowest temperature rise within the motor during start up
of all the starting methods.
Power plants may have varying rules and regulations in different countries. For example:
Three-phase motors with locked-rotor currents above 60 A must not use direct-on-line
starting in Denmark. In such cases, it will obviously be necessary to select another
starting method.
8/4/2015 1:30 PM
3 of 8
http://electrical-engineering-portal.com/comparision-of-direct-on-line-do...
Motors that start and stop frequently often have some kind of control system, which
consist of a contactor and overload protection such as a thermal relay.
Go back to Methods
Drawbacks of DOL
Small motors which do not start and stop frequently need only very simple starting
equipment, often in the form of a hand-operated motor protection circuit breaker.
Full voltage is switched directly onto the motor terminals. For small motors, the starting
torque will be 150% to 300% of the full-load value, while the starting current will be 300%
to 800% of the full-load current or even higher.
Go back to Methods
Star-delta starting
The objective of this starting method, which is used with three-phase induction motors, is
to reduce the starting current.
In starting position, current supply to the stator windings is connected in star (Y) for
starting. In the running position, current supply is reconnected to the windings in delta
8/4/2015 1:30 PM
4 of 8
http://electrical-engineering-portal.com/comparision-of-direct-on-line-do...
Go back to Methods
Advantages of Y-
particularly suited for high inertias, where the load are initiated after full load speed.
Go back to Methods
Drawbacks of of Y-
But they also reduce the starting torque to about 33%. The motor is started in
8/4/2015 1:30 PM
5 of 8
http://electrical-engineering-portal.com/comparision-of-direct-on-line-do...
If the changeover from star to delta takes place at too low a speed, this can
cause a current surge which rises almost as high as the corresponding DOL
value. During the even small period of switch over from start to delta
connection the motor looses speed very rapidly, which also calls for higher
current pulse after connection to delta.
The two illustrations to the right show two features which should be taken into
consideration when using star-delta starting. The starter first connects the motor in star
(contactor K1 and K3). After a time period which depends on individual needs it
connects the motor in delta contactor K3 open and contactor K2 close.
8/4/2015 1:30 PM
6 of 8
http://electrical-engineering-portal.com/comparision-of-direct-on-line-do...
Starting torque and current are considerably lower at star-delta starting than at directon-line starting: one third of the equivalent DOL value.
Mismatching of motor torque speed curve and load torque speed curve. In the example
shown here, the motor would slowly accelerate up to approximately 50 per cent rated
speed.
Go back to Methods
The star-delta starting method features a lower locked-rotor current, but peaks during
the starting process as the changeover from star to delta is made.
When starting in star (t = 0.3 s), the current is reduced.
8/4/2015 1:30 PM
7 of 8
http://electrical-engineering-portal.com/comparision-of-direct-on-line-do...
However, when switching over from star to delta (at t = 1 .7 s), the current pulse
reaches the same level as the locked-rotor current seen with direct-on-line starting. The
current pulse can even get higher, because the motor during the switching period is
un-powered which means it reduce speed before the full voltage (delta voltage) are
supplied.
Go back to Methods
Reference // The Motor Book Grundfos (Download)