PREPARED BY
GOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
gk_aptransco@yahoo.co.in,
Mobile:9440336984
BASICS
OF
ONE AND HALF
CIRCUIT BREAKER
SCHEME
PREPARED BY
GOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
BUS-1
BUS-2
BUS-2
BUS-1
BUS-2
BUS-2
1-52 CB
BUS-1
BUS-2
1-52 CB
3-52 CB
2-52 CB
2-52 CB
3-52 CB
BUS-2
1-52 CB
LINE-1
BUS-1
BUS-2
1-52 CB
3-52 CB
2-52 CB
LINE-2
2-52 CB
3-52 CB
LINE-1
BUS-2
LINE-2
LINE-1
BUS-1
BUS-2
1-52 CB
3-52 CB
2-52 CB
LINE-2
2-52 CB
3-52 CB
LINE-1
BUS-2
LINE-2
1-52 CB
LINE-1
BUS-1
BUS-2
1-52 CB
3-52 CB
2-52 CB
LINE-2
2-52 CB
3-52 CB
LINE-1
BUS-2
LINE-2
10. FOR ANY PROBLEM IN LINE-1 OR LINE-2 ALONG WITH MAIN BREAKER
THE MIDDLE BREAKER OR SAY TIE BREAKER (2-52 CB) MUST TRIP.
1-52 CB
LINE-1
BUS-1
BUS-2
1-52 CB
3-52 CB
2-52 CB
LINE-2
2-52 CB
3-52 CB
LINE-1
BUS-2
LINE-2
LINE-1
BUS-1
BUS-2
1-52 CB
3-52 CB
2-52 CB
LINE-2
2-52 CB
3-52 CB
LINE-1
BUS-2
LINE-2
1-52 CB
LINE-1
2-52 CB
LINE-2
14. THE BAY BETWEEN BUS-1 & LINE-1 IS CALLED MAIN BAY FOR FEEDER-1.
BUS-1
BUS-1
BUS-2
1-52 CB
3-52 CB
2-52 CB
3-52 CB
LINE-1
BUS-2
LINE-2
LINE-1
2-52 CB
LINE-2
15. THE BAY BETWEEN LINE-1 & LINE-2 IS CALLED TIE BAY FOR FEEDER-1 & 2.
BUS-1
1-52 CB
BUS-1
BUS-2
1-52 CB
3-52 CB
2-52 CB
3-52 CB
LINE-1
BUS-2
LINE-2
LINE-2
3-52 CB
BUS-2
BUS-1
BUS-2
1-52 CB
3-52 CB
2-52 CB
LINE-1
LINE-2
2-52 CB
16. THE BAY BETWEEN BUS-2 & LINE-2 IS CALLED MAIN BAY FOR FEEDER-2.
LINE-1
1-52 CB
BUS-1
LINE-2
3-52 CB
BUS-2
BUS-1
BUS-2
1-52 CB
3-52 CB
2-52 CB
LINE-1
LINE-2
2-52 CB
LINE-1
1-52 CB
BUS-1
3-52 CB
BUS-2
BUS-2
1-52 CB
3-52 CB
2-52 CB
LINE-1
LINE-2
LINE-2
BUS-1
2-52 CB
LINE-1
1-52 CB
BUS-1
SUBSTATION DESIGN/LAYOUT
DIA5
BAY17
BAY18
BAY15
BAY16
DIA6
BAY14
BAY11
BAY8
BAY9
BAY5
FEEDER11
BAY13
DIA4
BAY10
DIA3
BAY6
BAY2
BAY3
FEEDER9
FEEDER7
BAY12
DIA2
BAY1
BUS-1 DIA1
FEEDER5
BAY7
FEEDER3
BAY4
FEEDER1
(I-CONFIGUARATION)
BUS-2
FEEDER2
FEEDER4
FEEDER6
FEEDER8
FEEDER10
FEEDER12
SUBSTATION DESIGN/LAYOUT
(D-CONFIGUARATION)
FEEDER5
FEEDER10
BAY14
BAY13
BAY7
DIA1
FEEDER9
BAY8
BAY3
BAY1
BAY2
FEEDER6
DIA3
BAY15
FEEDER2
BAY9
FEEDER1
DIA5
BUS-1
BAY5
FEEDER3
BAY11
FEEDER4
FEEDER7
FEEDER8
DIA6
BAY18
BAY16
DIA4
BAY12
BAY10
DIA2
BAY6
BAY4
BUS-2
BAY17
FEEDER11
FEEDER12
SUBSTATION DESIGN/LAYOUT
(DOUBLE BUS & DOUBLE BREAKER SYSTEM)
FEEDER1
FEEDER3
FEEDER1
FEEDER3
BAY6
BAY5
BAY2
BAY1
BAY7
BAY5
BAY3
BAY1
BUS-1
BUS-1
BAY8
BAY7
BAY4
BAY3
BAY8
BAY6
BAY4
BAY2
BUS-2
BUS-2
FEEDER2
FEEDER4
FEEDER2
FEEDER4
FEEDER 8
FEEDER 1
1-52 CB
FEEDER 2
2-52 CB
3-52 CB
8-52 CB
FEEDER 7
MESH / RING
LAYOUT
4-52 CB
7-52 CB
5-52 CB
6-52 CB
FEEDER 6
FEEDER 3
FEEDER 5
FEEDER 4
SUBSTATION DESIGN/LAYOUT
(DOUBLE MAIN BUS & TRANSFER BUS SYSTEM)
T/F-1
T/F-2
BUS-2
BAY3
BAY1
BAY2
FEEDER1 FEEDER2
BAY4
TRANSFER BUS
BAY5
TRANSFER BUS
COUPLER
BUS COUPLER
BUS-1
BAY6
BAY7
BAY8
FEEDER3 FEEDER4
FOR ECONOMICAL& RELIABULITY PURPOSE THIS SYSTEM ADOPTED IN 400 & 220 KV SYSTEM
SUBSTATION DESIGN/LAYOUT
(DOUBLE MAIN BUS & CB BYPASS ISO SYSTEM)
T/F-1
BAY1
BAY2
T/F-2
BAY6
BAY4
BUS COUPLER
BUS-1
BAY7
BUS-2
BAY3
FEEDER1
FEEDER2
BAY5
FEEDER3
FEEDER4
SUBSTATION DESIGN/LAYOUT
(SINGLE BUS & TRANSFER BUS SYSTEM)
T/F-2
T/F-1
TRANSFER BUS
BUS-1
BAY1
FEEDER1
BAY2
FEEDER2
BAY3
BAY4
BAY5
BAY6
FEEDER3
BAY7
FEEDER4
FOR ECONOMICAL& RELIABULITY PURPOSE THIS SYSTEM ADOPTED IN 220 & 132 KV SYSTEM
CT METHODS
IN
ONE AND HALF
CIRCUIT BREAKER
SCHEME
PREPARED BY
GOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
CB
LINE
CB
LINE
CB
LINE
CB
CB
4 CT METHOD
CB
CB
CB
AT/F
AT/F
CB
CB
6 CT METHOD
CB
LINE
CB
5 CT METHOD
LINE
LINE
CB
3 CT METHOD
CB
CB
6 CT METHOD
CB
CB
6 CT METHOD
CB
AT/F
AT/F
AT/F
AT/F
BUS-2
1-89
3-89
1-52CB
1-CT
3-52CB
P2
P2
3P1
3-CT
3
P1
1-89A
3-89A
3
3
2-CT
2-89A 2-52CB
1-89L
P1
P2
2-89B
3-89T
LINE 1
T/F-1
BUS-2
1-89
3-89
1-52CB
1-CT
3-52CB
P2
P2
3P1
3-CT
3
P1
1-89A
3-89A
P2
2-89A
1-89L
P1
2-BCT
2-ACT
P1
2-52CB
P2
2-89B
3-89T
LINE 1
T/F-1
BUS-2
1-89
3-89
1-52CB
1-CT
3-52CB
P2
P2
3P1
3 3-CT
P1
1-89A
3-89A
2-CT
2-89A
P1
2-52CB
P2
2-89B
1-89L
1L-CT
3-89T
P2
3P1
P2
3T-CT
3
P1
LINE 1
T/F-1
BUS-1
BUS-2
1-89
P2
P1
3-89
3 1A-CT
3A-CT
1-52CB
3 P1
3-52CB
P2
1B-CT
3
P1
3B-CT
1-89A
P2
P1
3-89A
2-89A
P2
P1
2B-CT
2A-CT
1-89L
P2
P1
2-52CB
P2
2-89B
3-89T
T/F-1
LINE 1
BUS-2
1-89
3-89
1-52CB
3-52CB
P2
1-CT
3
P1
3-CT
1-89A
P2
P1
2B-CT
2-89A
P1
2-52CB
P2
2-89B
1-89L
1L-CT
3
P1
LINE 1
P1
3-89A
2A-CT
P2
P2
3-89T
3T-CT
P2
3 P1
T/F-1
BUS-1
BUS-2
1-89
P2
P2
3 1-CT
1-52CB
3-52CB
1-89A
3-89A
2-89A
P2
P1
2B-CT
2A-CT
P1
2-52CB
P2
2-89B
1-89L
1L-CT
3
P1
LINE 1
3 3-CT
P1
P1
P2
3-89
3-89T
3T-CT
P2
3 P1
T/F-1
DS : DISCONNECTOR SWITCH, GS: GROUNDING SWITCH, CT: CURRENT TRANSFORMER, VD: VOLTAGE DIVIDER
1-1/2 CB SYSTEM
(SIEMENS VATECH)
VD
VD
CT
DS
CT
CB
CT
DS
DS
CT
CB
GS
GS
GS
GS
VD
GS
GS
GS
GS
VD
CT
DS
DS
CT
CB
DS
CORE WISE
APLICATION OF
CTs IN
ONE AND HALF
CIRCUIT BREAKER
SCHEME
PREPARED BY
GOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
CURRENT TRANSFORMER
CONNECTIONS IN 3CT METHOD
1 CT
2 CT
3 CT
BUSBAR-1
2CTs SECONDARIES ARE CONNECTED IN PARALLEL AND
CORE 1
( PS)
CORE 2
( PS)
CORE 3
( 0.5 / 0.2)
CORE 4
(0.5 / 0.2)
CORE 5
( PS)
CORE 6
( PS)
PROTECTION
BUSBAR-1 CHECKUP
PROTECTION (SPARE)
SPARE
SPARE
BUSBAR-2 CHECKUP
PROTECTION (SPARE)
BUSBAR-2
PROTECTION
CURRENT TRANSFORMER
CONNECTIONS IN 3CT METHOD
1 CT
2 CT
3 CT
BUSBAR-1
2CTs SECONDARIES ARE CONNECTED IN PARALLEL AND
CORE 1
( PS)
CORE 2
( PS)
CORE 3
(0.5 / 0.2)
CORE 4
( PS)
CORE 5
( PS)
BUSHING CT
METERING
CORE (0.5 / 0.2)
PROTECTION
BUSBAR-1 CHECKUP
PROTECTION (SPARE)
SPARE
BUSBAR-2 CHECKUP
PROTECTION (SPARE)
BUSBAR-2
PROTECTION
NORMALLY THIS SYTEM ADOPTS, WHEN ONE SIDE LINE, OTHER SIDE AUTO
TRANSFORMER / BUS REACTOR IS PROVIDED IN A DIA OF ONE AND HALF BREAKER
SYSTEM, IF BUSHING CT METERING CORE IS AVAILABLE, THEN IT IS USED FOR
METERING & ENERGY METER FOR AT/F OR BUS REACTOR.
CURRENT TRANSFORMER
CONNECTIONS IN 4CT METHOD
CORE-1
(PS)
CORE-2
(PS)
CORE-3
(0.5/0.2)
CORE-4
(PS)
CORE-5
(PS)
1- CT
2-BCT
2-ACT
3-CT
CT SECONDARY
CORE IS
CONNECTED TO
BUSBAR-1
PROTECTION
SPARE
SPARE
CT SECONDARY
CORE IS
CONNECTED TO
BUSBAR-2
PROTECTION
BUSBAR-1
CHECKUP
PROTECTION
(SPARE)
SPARE
SPARE
BUSBAR-2
CHECKUP
PROTECTION
(SPARE)
CURRENT TRANSFORMER
CONNECTIONS IN 5CT METHOD
1-CT
1-LCT
2-CT
3-TCT
3-CT
BUSBAR-1
PROTECTION
TEED PROT-1
(BAY 1&2)
TEED PROT-1
(BAY 2&3)
TEED PROT-1
(BAY 2&3)
BUSBAR-2
PROTECTION
BUSBAR-1
CHECKUP
PROTECTION
(SPARE)
TEED PROT-2
(BAY 1&2)
TEED PROT-2
(BAY 2&3)
TEED PROT-2
(BAY 2&3)
BUSBAR-2
CHECKUP
PROTECTION
(SPARE)
CORE-3
(0.5/0.2)
SPARE
METERING &
ENERGY
METER
SPARE
METERING &
ENERGY
METER
SPARE
CORE-4
(PS)
TEED PROT-2
(BAY 1&2)
AFTER
LBB/BFR
(1-52)
MAIN-2
PROTECTION
TEED PROT-2
(BAY 1&2)
AFTER
LBB/BFR
(2-52)
BACKUP
PROTECTION
TEED PROT-2
(BAY 2&3)
AFTER
LBB/BFR
(3-52)
CORE-5
(PS)
TEED PROT-1
(BAY 1&2)
MAIN-1
PROTECTION
TEED PROT-1
(BAY 1&2)
MAIN
PROTECTION
TEED PROT-1
(BAY 2&3)
CORE-1
(PS)
CORE-2
(PS)
Paralleling of 2Nos CTs to the Main-1/Main-2/Backup line protection is not required. This gives better
transient response. Separate STUB protection can be connected (Nothing BUT TEED Protection).
CURRENT TRANSFORMER
CONNECTIONS IN 6CT METHOD
(GIS or AIS with DEAD TANK CBs)
1B-CT
CORE-1
(PS)
CORE-2
(PS)
CORE-3
(0.5/0.2)
BUSBAR-1
PROTECTION
BUSBAR-1
CHECKUP
PROTECTION
(SPARE)
SPARE
1A-CT
2B-CT
2A-CT
3A-CT
2CTs SECONDARIES
ARE CONNECTED
IN PARALLEL AND
CONNECTED TO
MAIN-1 PROTECTION
2CTs SECONDARIES
ARE CONNECTED
IN PARALLEL AND
CONNECTED TO
MAIN-1 PROTECTION
2CTs SECONDARIES
ARE CONNECTED IN
PARALLEL AND
CONNECTED TO
MAIN-2 PROTECTION
AFTER LBB/BFR
2CTs SECONDARIES
ARE CONNECTED IN
PARALLEL AND
CONNECTED TO
BACKUP PROTECTION
AFTER LBB/BFR
2CTs SECONDARIES
ARE CONNECTED IN
PARALLEL AND
CONNECTED TO
PANEL METERS &
ENERGY METER
2CTs SECONDARIES
ARE CONNECTED IN
PARALLEL AND
CONNECTED TO
PANEL METERS &
ENERGY METER
3B-CT
BUSBAR-2
PROTECTION
BUSBAR-2
CHECKUP
PROTECTION
(SPARE)
SPARE
CURRENT TRANSFORMER
CONNECTIONS IN 6CT METHOD
1-CT
1L-CT
2A-CT
2B-CT
3T-CT
3-CT
CORE-1
(PS)
CORE-2
(PS)
BUSBAR-1
PROTECTION
TEED PROT-1
(BAY 1&2)
SPARE
SPARE
TEED PROT-1
(BAY 2&3)
BUSBAR-2
PROTECTION
BUSBAR-1
CHECKUP
TEED PROT-2
(BAY 1&2)
SPARE
SPARE
TEED PROT-2
(BAY 2&3)
BUSBAR-2
CHECKUP
CORE-3
(0.5/0.2)
SPARE
METERING &
ENERGY
METER
SPARE
SPARE
METERING &
ENERGY
METER
SPARE
CORE-4
(PS)
TEED PROT-2
(BAY 1&2)
MAIN-2
PROTECTION
TEED PROT-2
(BAY 2&3)
TEED PROT-2
(BAY 1&2)
BACKUP
PROTECTION
TEED PROT-2
(BAY 2&3)
CORE-5
(PS)
TEED PROT-1
(BAY 1&2)
PROTECTION
(SPARE)
PROTECTION
(SPARE)
AFTER LBB/BFR
(1-52)
AFTER LBB/BFR
(2-52)
MAIN-1
PROTECTION
TEED PROT-1
(BAY 2&3)
TEED PROT-1
(BAY 1&2)
AFTER LBB/BFR
(3-52)
MAIN
PROTECTION
TEED PROT-1
(BAY 2&3)
CT CORES
CONEECTION
DIAGRAMS IN
ONE AND HALF
CIRCUIT BREAKER
SCHEME
PREPARED BY
GOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
3
3
3
2
BB-EVT
/ CVT
1-52CB
P1
3
3
3
CORES
3
4
MAIN-1 PROTECTION
MAIN-2/BACKUP PROTECTION
BUS
METERING
1-89
P2
1-CVT
CVT
VBB1
21M1
VBB1
VL1
25
VL1 / VL2
OR VBB2
BF
87L
21M2
VL1
CVT
VL1
FEEDER1 / LINE1
79
VL1 / VBB1
VL2 / VBB2
25
BF
FEEDER2 / LINE2
CVT VL2
MAIN-1
BF
VL2 / VL1
OR VBB1
CVT
VBB2
VBB2
79
MAIN-2
PROTECTION OF LINE2
(OR TRANSFORMER, IF APPLICABLE)
25
BUSBAR-2
87BB2
CVT
VBB1
21M1
VBB1
VL1
25
VL1 / VL2
OR VBB2
BF
87L
21M2
VL1
CVT
VL1
FEEDER1 / LINE1
79
VL1 / VBB1
VL2 / VBB2
25
BF
FEEDER2 / LINE2
CVT VL2
MAIN-1
BF
VL2 / VL1
OR VBB1
CVT
VBB2
VBB2
79
MAIN-2
PROTECTION OF LINE2
(OR TRANSFORMER, IF APPLICABLE)
25
BUSBAR-2
87BB2
21M1
VBB1
BF
79
VBB1
VL1
25
87L
VL1 / VL2
OR VBB2
21M2
VL1
CVT
VL1
FEEDER1 / LINE1
79
VL1 / VBB1
VL2 / VBB2
25
BF
FEEDER2 / LINE2
CVT VL2
MAIN-1
VL2 / VL1
OR VBB1
CVT
VBB2
VBB2
BF
79
MAIN-2
PROTECTION OF LINE2
(OR TRANSFORMER, IF APPLICABLE)
25
BUSBAR-2
87BB2
CVT
VBB1
21M1
VBB1
VL1
87 TD1 HZ
25
VL1 / VL2
OR VBB2
BF
87L
87 TD2 LZ
21M2
VL1
CVT
VL1
FEEDER1 / LINE1
79
VL1 / VBB1
VL2 / VBB2
25
BF
FEEDER2 / LINE2
.
BF
VL2 / VL1
OR VBB1
CVT
VBB2
VBB2
CVT VL2
MAIN-1
87 TD2 LZ
PROTECTION OF LINE2
(OR TRANSFORMER, IF APPLICABLE)
MAIN-2
79
87 TD1 HZ
25
BUSBAR-2
87BB2
CVT
VBB1
21M1
VBB1
VL1
87 TD1 HZ
25
VL1 / VL2
OR VBB2
BF
87L
87 TD2 LZ
21M2
VL1
CVT
VL1
FEEDER1 / LINE1
79
VL1 / VBB1
VL2 / VBB2
25
BF
FEEDER2 / LINE2
.
BF
VL2 / VL1
OR VBB1
CVT
VBB2
VBB2
CVT VL2
MAIN-1
87 TD2 LZ
PROTECTION OF LINE2
(OR TRANSFORMER, IF APPLICABLE)
MAIN-2
79
87 TD1 HZ
25
BUSBAR-2
87BB2
VL1
87 TD1 HZ
CVT
VBB1
BF
87 TD2 LZ
79
VBB1
87L
21M2
VL1
CVT
VL1
25
VL1 / VL2
OR VBB2
FEEDER1 / LINE1
79
VL1 / VBB1
VL2 / VBB2
VL2 / VL1
OR VBB1
VBB2
25
BF
FEEDER2 / LINE2
79
CVT VL2
25
MAIN-1
87 TD2 LZ
PROTECTION OF LINE2
(OR TRANSFORMER, IF APPLICABLE)
MAIN-2
BF
VBB2
CVT
87 TD1 HZ
BUSBAR-2
87BB2
3 CT
METHOD
4 CT
METHOD
6 CT (S)
METHOD
5 CT
METHOD
6 CT (T1)
METHOD
6 CT (T2)
METHOD
BUSBAR &
BUSBAR
CHECKUP
PROTECTION
1 CT
1 CT
1B CT
1 CT
1 CT
1 CT
MAIN-1
MAIN-2
PROTECTION
&
METERING
ADDITIONAL
PROTECTION
AVAILABLE
BLIND
ZONE
ADVANTAGES
&
3 CT
3 CT
3B CT
3 CT
3 CT
3 CT
1 - CT & 2 - CT
1 CT & 2 B - CT
1 A CT & 2 B CT
1 L - CT
1 L - CT
1 L - CT
3 - CT & 2 A - CT
3 A - CT & 2 A - CT
3 L - CT
3 L CT
A FAULT BETWEEN CIRCUIT BREAKERS AND CT (END FAULT) MAY THEN STILL BE FED FROM ONE SIDE
EVEN WHEN THE BREAKER HAS BEEN OPENED. CONSEQUENTLY, FINAL FAULT CLEARING BY CASCADED
TRIPPING HAS TO BE ACCEPTED IN THIS CASE. THIS SITUATION LBB/BFR OPERATES AND TIME TAKEN TO
CLEAR FAULT IS ABOUT 300 mSECs. THIS IS BLIND ZONE AREA.
MINIMUM CT
METHOD. REDUCING
THE COST OF CTs
WHEN THE FAULT IS TAKEN PLACE BETWEEN THE MAIN CB, TIE CB &
LINE ISOLATOR DURING SERVICE ONLY, TEED PROTECTION IN
ADDITION TO DISTANCE SCHEME SHOULD TAKE CARE.
PRIMARY CONNECTIONS : P1 P2
CURRENT RATING : 2000 AMPS
500/ 1A
1S1 1S3
1S1 1S2
1S2 1S3
__
PS
BUSBAR
CHECKUP 2S1 2S3
PROTECTION
2S1 2S2
2S2 2S3
__
METERING
3S1 3S3
3S4 3S2
3S1 3S2
3S4 3S3
CORE-4
MAIN-2
4S1 4S3 4S1 4S2
4S1 4S4
PROTECTION
4S4 4S2 4S4 4S3
5S1 5S2
5S4 5S3
5S1 5S3
5S4 5S2
2S12
2S 3
2S
4S1
4S2
4S3
4S4
MAIN-1
5S1 5S4
PROTECTION
PS
1
5S S2
5 S3
5 S4
5
1
1S S1
1S 2
3
3S1
3S2
3S3
3S4
CORE-5
PS
3S1 3S4
3
3
2S1
2S2
2S3
CORE-2
1S1
1S2
1S3
5S1
5S2
5S3
5S4
4S1
4S2
4S3
4S4
BUSBAR
PROTECTION
3S1
3S2
3S3
3S4
PS
CORE-1
1000/ 1A
2000/ 1A
PURPOSE
CLASS
P1 P2
3
3
CORES
SECONDARY CONNECTIONS
CURRENT RATING : 1A
P2
HAIR
PIN /
U SHAPE
DESIGN
EYE BOLT
DESIGN
MAIN-1, MAIN-2
PROTECTION &
METERING
FOR LINE
ADOPTED IN
ONE AND HALF
CIRCUIT BREAKER
SCHEME
PREPARED BY
GOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
Sr.No
1.
2.
3.
4.
VOLTAGE
11 KV LINES
33 KV LINES
66 KV LINES
132 KV LINES
MAIN- 1 PROTECTION
5.
220 KV LINES NUMERICAL DISTANCE SCHEME (21P + 21N) NUMERICAL DISTANCE SCHEME (21P+ 21N)
6.
7.
IF MAIN-1 & MAIN-2 ARE NUMERICAL RELAYS, BOTH SHOULD BE SEPARATE MEASURING PRINCIPLES (CHARECTERESTICS), MODELS
AND ALGORITHAMS (SHOULD NOT BE DUPLICATED) AND ALL FEATURES SHOULD BE AVAILABLE IN BOTH SCHEMES AND BOTH RELAYS
SHOULD BE 100% REDENDENCY IN ALL ASPECTS ( COMPLEMENTARY TO EACH OTHER ) . DISSIMILAR CARRIER SCHEMES ARE TO BE
SELECTED ( POTT & PUTT or BLOCK & UNBLOCK). OTHER WISE MAIN-2 MAY BE DIFFERENT MAKE OR PHASE COMPARISION
PROTECTION/LINE DIFFERENTIAL PROTECTION WITH BACKUP DISTANCE PROTECTION IS TO BE ADOPTED. BOTH M1 & M2 SHOULD
CONTAIN DIRECTIONAL EARTH FAULT PROTECTION (67N) WITH DIRECTIONAL COMPARISION PICKUP SCHEME AS INBUILT FUNCTION.
ZONE-1: 80% OF MAIN LINE
ZONE-2: 100% OF MAIN LINE + 50% OF SHORTEST LINE AT OTHER END
ZONE-3: 100% OF MAIN LINE + 100% OF SHORTEST LINE AT OTHER END
ZONE-4: 100% OF MAIN LINE + (100% OF SHORTEST LINE + 20% OF LONGEST LINE) AT
OTHER END.
CT MB
IR5 / A511
IY5 / A531
IB5 / A551
1-CT
CTR: 2000-1000-500/1A
3 3 3
CORE-5
(4CT METHOD)
5S4
5S4
5S4
5S2
5S2
5S2
IN5 / A571
REL 521
ACTIVE START
TRIP
1-CVT
CLASS: PS
3 CT METHOD : 1-CT & 2-CT
4 CT METHOD : 1-CT & 2-BCT
6 CT METHOD : 1-ACT & 2-BCT
DISPLAY
C
CT MB
2-BCT
CTR: 2000-1000-500/1A
5S2
5S2
5S2
5S4
5S4
5S4
3 3 3
CORE-5
CLASS: PS
P2 P2 P2
VR11 / E111
VY11 / E131
VB11 / E151
VN11 / E171
CORE 1
200VA
CLASS: 3P
CT MB
IR5 / A511
IY5 / A531
IB5 / A551
1-CT
CTR: 2000-1000-500/1A
3 3 3
CORE-5
5S4
5S4
5S4
5S2
5S2
5S2
IN5 / A571
CLASS: PS
ESC
CT MB
2-BCT
CTR: 2000-1000-500/1A
ENABLED
TRIP
IN5 / A571
5S2
5S2
5S2
5S4
5S4
5S4
3 3 3
CORE-5
IA =250.10 A
IB =250.10 A
IC =250.10 A
VAB =400.0 KV
VBC =400.0 KV
VCA =400.0 KV
CLASS: PS
IB5 / A551
IY5 / A531
IR5 / A511
P2 P2 P2
INST
TIME
COMM
SOTF
ZONE1
ZONE2
ZONE3
ZONE4
SEL
ENT
TARGET
RESET
PH-A
PH-B
PH-C
GND
50
51
79 RESET
79 LOCKOUT
SEL- 421
PROTECTION
AUTOMATION
CONTROL
VR11 / E111
VY11 / E131
VB11 / E151
VN11 / E171
1-CVT
CORE 1
200VA
CLASS: 3P
P2 P2 P2
IR5 / A511
IY5 / A531
IB5 / A551
1-LCT
CTR: 2000-1000-500/1A
3 3 3
CORE-5
CT MB
5S4
5S4
5S4
5S2
5S2
5S2
IN5 / A571
REL 521
ACTIVE START
TRIP
VR11 / E111
VY11 / E131
VB11 / E151
VN11 / E171
1-CVT
CLASS: PS
DISPLAY
C
E
CORE 1
200VA
CLASS: 3P
50Z
CT MB
1-CT
RAICA
CORE-4
LBB / BFR
3 3 3
CTR: 2000-1000-500/1A
4S4
4S4
4S4
4S2
4S2
4S2
IR4 / C411
IY4 / C431
IB4 / C451
IN4 / C471
REL 316
ACTIVE START
TRIP
1-CVT
CLASS: PS
3 CT METHOD : 1-CT & 2-CT
4 CT METHOD : 1-CT & 2-BCT
6 CT METHOD : 1-ACT & 2-BCT
DISPLAY
C
E
CT MB
2-BCT
CTR: 2000-1000-500/1A
4S2
4S2
4S2
4S4
4S4
4S4
3 3 3
CORE-4
RAICA
CLASS: PS
LBB / BFR
P2 P2 P2
50ZT
VR21 / E211
VY21 / E231
VB21 / E251
VN21 / E271
CORE 2
200VA
CLASS: 3P
CT MB
IR4 / C411
IY4 / C431
IB4 / C451
1-CT
CTR: 2000-1000-500/1A
3 3 3
CORE-4
4S4
4S4
4S4
4S2
4S2
4S2
IN4 / C471
CLASS: PS
CT MB
2-BCT
CTR: 2000-1000-500/1A
4S2
4S2
4S2
4S4
4S4
4S4
3 3 3
CORE-4
IN4 / C471
CLASS: PS
P2 P2 P2
IB4 / C451
IY4 / C431
IR4 / C411
VR21 / E211
VY21 / E231
VB21 / E251
VN21 / E271
1-CVT
CORE 2
200VA
CLASS: 3P
BUS-1 PT
BUS-2 PT
59
50 BF-1 50 BF-2
25-2
3
LINE CVT
3
2-52 CB
1-52 CB
(NEW APPLICATION) (ONE & HALF BREAKER SYSTEM or RING BUS SYSTEM)
LINE
27
P2 P2 P2
IR4 / C411
IY4 / C431
IB4 / C451
1-LCT
CTR: 2000-1000-500/1A
3 3 3
CORE-4
CT MB
4S4
4S4
4S4
4S2
4S2
4S2
IN4 / C471
REL 316
ACTIVE START
TRIP
VR21 / E211
VY21 / E231
VB21 / E251
VN21 / E271
1-CVT
CLASS: PS
DISPLAY
C
E
CORE 2
200VA
CLASS: 3P
CT MB
IR3 / D311
IY3 / D331
IB3 / D351
1-CT
CTR: 2000-1000-500/1A
3 3 3
CORE-3
3S4
3S4
3S4
3S2
3S2
3S2
IN3 / D371
CLASS: 0.5
CT MB
2-BCT
CTR: 2000-1000-500/1A
3S2
3S2
3S2
3S4
3S4
3S4
3 3 3
CORE-3
CLASS: 0.5
VR31 / E311
VY31 / E331
VB31 / E351
VN31 / E371
1-CVT
CORE 3
100VA
P2 P2 P2
CLASS: 0.5/0.2
IR3 / D311
IY3 / D331
IB3 / D351
1-LCT
CTR: 2000-1000-500/1A
3 3 3
CORE-3
CT MB
3S4
3S4
3S4
3S2
3S2
3S2
CLASS: 0.5/0.2
IN3 / D371
VR31 / E311
VY31 / E331
VB31 / E351
VN31 / E371
1-CVT
CORE 3
100VA
CLASS: 0.5/0.2
REMOTE BACK-UP
LOCAL BACK-UP
LOCAL BACK-UP PROTECTION CAN BE DEVIDED INTO TWO
CATAGORIES.
RELAY BACK-UP
BREAKER BACK-UP
RELAY BACK-UP
z
BREAKER BACK-UP
BECAUSE OF THE HIGH COST OF HIGH VOLTAGE CIRCUIT
BREAKERS, IT IS NOT FEASIBLE TO DUPLICATE THEM.
IN CASE OF A BREAKER FAILURE THE OTHER CIRCUIT BREAKERS
CONNECTED TO THE SAME BUS AS THE FAULTED BREAKER MUST THERE
FORE BE TRIPPED.
YES
TRIP
MAIN
BREAKER
FAULT
CLEARED
NO
RETRIP
YES
INITIATE
BFR
YES
RESET
BREAKER
FAILURE
SCHEME
WAIT FOR
FAULT
CLEARENCE
AND
TRIP
BACK-UP/
Adjacent
BREAKERS
NORMAL
CLEARING
PROTECTIVE RELAY
FOR EX: DISTANCE RELAY
BREAKER
INTURUPTING TIME
~30ms
~60ms
MARGIN
<12ms
INOPERATIVE
BREAKER
TRIPPING
RELAY
TIME
BACK-UP BREAKER
INTERUPTING TIME
MARGIN
LBB/BFR LOGIC
CURRENT INPUTS
PHASE L1
A/D
CONVERTER PHASE CURRENT SET POINT
I > ISET
PHASE L2/E
PHASE L3
I > ISET
|||
&
LED
(PHASE START)
ALARM RELAY
(PHASE START)
>1
&
ALARM RELAY
(EARTH START)
LED
(EARTH START)
BINARY INPUT
CIRCUIT BREAKER FAILURE INITIATE
TIMING/OUTPUT
STAGE
TRIP T1
RELAY
TIME STAGE T1
&
ALARM T1
RELAY
&
TIME STAGE T2
SWITCHED OFF
>1
TIME STAGE T2
O&
0
LED
TRIP T2
RELAY
LED
LED
CB FAILURE
INITIATE
LBB/BFR PROTECTION
LINE1
BUS-1
AT/F-1
1-52CB
50Z
2-52CB
50ZT
3-52CB
50Z
BUS-2
50Z
1-52CB
TC-1
BUS-1
ABB
REL316
MAIN-2
86-B
86-B
86-A
ABB
REL521
MAIN-1
TC-2
2-52CB
TC-2
TC-1
3-52CB
BUS-2
86-A
ABB
REL521
MAIN-1
86-B
ABB
REL316
MAIN-2
ABB
RET316
MAIN-2
50ZT
DIRECT TRIP 1&2
VIA CARRIER
TO OTHER END
INTER TRIP TO
LVCB & TBCCB
2-52CB
1-52CB
TC-1
BUS-1
3-52CB
TC-2
BUS-2
ABB
RET316
MAIN-2
86-A
86-B
86-B
86-A
ABB
RET521
MAIN-1
50Z
INTER TRIP TO
LV CB & TBC CB
BUSBAR-2
PROTECTION OPTD
AND BUSBAR-2
ISOLATED
2-52CB
1-52CB
TC-1
BUS-1
3-52CB
TC-2
TC-2
TC-1
BUS-2
BASIC THEORY
KIRCHOFFs CURRENT LAW STATES THAT THE SUM OF THE CURRENTS ENTERING A
GIVEN NODE MUST BE EQUAL TO THE CURRENTS LEAVING AT THAT NODE.
ADVANTAGES
EXTERNAL FAULT
INTERNAL FAULT
IF
I1
I1
I2
I3
I2
I3
I4
I5
I4
I5
I6
I6
IF
IF= I1+I2+I3+I4+I5+I6
UU
UU
UU
UU
UU
UU
UU
UU
UU
UU
UU
UU
87BBM
96 BBC : BUSBAR
CHECK TRIPPING RELAY
52 CIRCUIT
BREAKER
TRIP COIL
- VE
A varistor is normally applied across the
relay input terminals to limit the voltage
to a value safely below the insulation
voltage of the secondary circuits
+ VE
96 BBM : BUSBAR
MAIN TRIPPING RELAY
UU
UU
OVER CURRENT
COIL
UU
.
Is
Id
OVER CURRENT
STARTER RELAYS
RESTRAINT
COIL
UU
UU
52 CIRCUIT
BREAKER
TRIP COIL
UU
OPERATING
COIL
96 BUS BAR
TRIPPING
RELAY
-VE
PRINCIPLE
CTs
IT REQUIRES ALL IDENTICAL CT RATIOs & TURNS RATIO. LOW IT CAN WORK WITH CTs OF UNEQUAL RATIOS ALSO. FREE OF
RESISTANCE OF SECONDARY WINDING. Class X for all CT Cores.
ANY NEED OF MATCHED CT CHARACTERESTIC OR RATIOs LOW
MINIMUM KNEE POINT VOLTAGE OF 300-500V.
LEAKAGE REACTANCE OR RESISTANCE. OTHER PROTECTIVE
LOW MAGNETISING CURRENT(FEW MILLIAMPS).
RELAYS CAN BE INCLUDED IN THE SAME CIRCUIT.
BURDEN
IMPOSES COMPARATIVELY HIGH BURDEN ON CTs. AUXILIARY CTs IMPOSES LESS BURDEN ON CTs. AUXILIARY CTs HAVE NO
REDUCE THE PERFORMANCE OF THE SCHEME
EFFECT ON PERFORMANCE OF SCHEME.
CT SATURATION
OPERATION OF SCHEME EVEN WHEN CTs GET SATURATED DURING OPERATION OF SCHEME EVEN WHEN CTs GET SATURATED
INTERNAL FAULTS.
DURING INTERNAL FAULTS. INSENSITIVE TO CT SATURATION.
UTILISATION
IT IS GOOD SOLUTION FOR SINGLE BUSBAR ARRANGEMENTS, ONE & MOST SUITABLE FOR DOUBLE AND MULTIPLE BUSBAR SYSTEMS
HALF BREAKER SYSTEMS OR RING BUSBAR SYSTEMS.
( WITH OR WITHOUT TRANSFER BUS).
OPERATING TIME
STABILITY
PERFORMANCE
HIGHLY SENSITIVE FOR INTERNAL FAULTS AND COMPLETELY STABLE HIGHLY SENSITIVE FOR INTERNAL FAULTS AND COMPLETELY
FOR EXTERNAL FAULTS.
STABLE FOR EXTERNAL FAULTS.
ADDITIONAL
PROTECTION
THIS RELAY REQUIRES CHECK ZONE FEATURE. THE TRIP COMMAND IS THIS RELAY HAS IN BUILT CHECK ZONE FEATURE (NO SEPARATE
ONLY GIVEN WHEN BOTH A DISCRIMINATING & CHECK ZONE SYSTEM CHECKZONE FEATURE) i.e OVER CURRENT STARTING RELAY
OPERATES.
PROVIDED.
DETAILS
CT MB
1-CT
CTR: 2000-1000/1A
3 3 3
CORE-1
REB 521
IN1 / B171
1S3
1S3
1S3
1S1
1S1
1S1
ACTIVE START
TRIP
IB1 / B151
CLASS: PS
IY1 / B131
IR1 / B111
BUS BAR
PROTECTION
FOR
BUS-1
DISPLAY
C
E
CT MB
IR1 / B111
IY1 / B131
3-CT
CTR: 2000-1000/1A
ACTIVE START
TRIP
IB1 / B151
1S1
1S1
1S1
1S3
1S3
1S3
3 3 3
CORE-1
RED 521
IN1 / B171
CLASS: PS
P2 P2 P2
BUS BAR
PROTECTION
FOR
BUS-2
DISPLAY
C
E
BUS-2
87 BB2
BUS BAR-2 PROTECTION
UU
10-CT
UU
13-CT
UU
16-CT
UU
UU
12-CT
UU
15-CT
UU
18-CT
UU
12-52
15-52
18-52
21-52
20-52
17-52
14-52
11-52
19-CT
7-CT
9-CT
19-52
16-52
13-52
10-52
7-52
4-52
1-52
87 BB1
21-CT
UU
UU
9-52
8-52
4-CT
UU
1-CT
UU
6-CT
5-52
2-52
UU
3-CT
UU
6-52
3-52
BUS-1
1-52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
4-52 CB PANEL
REB 521
HIGH SPEED
TRIP RELAY
FOR
4-52 CB
ACTIVE
START
TRIP
7-52 CB PANEL
HIGH SPEED
TRIP RELAY
FOR
7-52 CB
DISPLAY
HIGH SPEED
TRIP RELAY
FOR
10-52 CB
10-52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
HIGH SPEED
TRIP RELAY
FOR
13-52 CB
13-52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
16-52 CB PANEL
HIGH SPEED
TRIP RELAY
FOR
16-52 CB
+VE
BUSBAR PANEL
1-52 CB PANEL
TO CLOSE CKT INTERLOCK
TO BLOCK A/R
TO TRIP COIL-1
TO TRIP COIL-2
DIRECT TRIP SEND CH-1
DIRECT TRIP SEND CH-2
TO DISTURBENCE RECORDER
4-52 CB PANEL
TO CLOSE CKT INTERLOCK
TO BLOCK A/R
TO TRIP COIL-1
TO TRIP COIL-2
DIRECT TRIP SEND CH-1
DIRECT TRIP SEND CH-2
TO DISTURBENCE RECORDER
7-52 CB PANEL
TO CLOSE CKT INTERLOCK
TO BLOCK A/R
TO TRIP COIL-1
TO TRIP COIL-2
DIRECT TRIP SEND CH-1
DIRECT TRIP SEND CH-2
TO DISTURBENCE RECORDER
10-52CB PANEL
TO CLOSE CKT INTERLOCK
TO BLOCK A/R
TO TRIP COIL-1
TO TRIP COIL-2
DIRECT TRIP SEND CH-1
DIRECT TRIP SEND CH-2
TO DISTURBENCE RECORDER
13-52 CB PANEL
TO CLOSE CKT INTERLOCK
TO BLOCK A/R
TO TRIP COIL-1
TO TRIP COIL-2
DIRECT TRIP SEND CH-1
DIRECT TRIP SEND CH-2
TO DISTURBENCE RECORDER
16-52 CB PANEL
TO CLOSE CKT INTERLOCK
TO BLOCK A/R
TO TRIP COIL-1
TO TRIP COIL-2
DIRECT TRIP SEND CH-1
DIRECT TRIP SEND CH-2
TO DISTURBENCE RECORDER
3-52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
6-52 CB PANEL
REB 670
HIGH SPEED
TRIP RELAY
FOR
6-52 CB
ACTIVE
START
TRIP
9-52 CB PANEL
HIGH SPEED
TRIP RELAY
FOR
9-52 CB
DISPLAY
HIGH SPEED
TRIP RELAY
FOR
12-52 CB
12-52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
HIGH SPEED
TRIP RELAY
FOR
15-52 CB
15-52 CB PANEL
TRIP FROM 50 LBB
TO START 50 LBB
18-52 CB PANEL
HIGH SPEED
TRIP RELAY
FOR
18-52 CB
+VE
BUSBAR PANEL
3-52 CB PANEL
TO CLOSE CKT INTERLOCK
TO BLOCK A/R
TO TRIP COIL-1
TO TRIP COIL-2
DIRECT TRIP SEND CH-1
DIRECT TRIP SEND CH-2
TO DISTURBENCE RECORDER
6-52 CB PANEL
TO CLOSE CKT INTERLOCK
TO BLOCK A/R
TO TRIP COIL-1
TO TRIP COIL-2
DIRECT TRIP SEND CH-1
DIRECT TRIP SEND CH-2
TO DISTURBENCE RECORDER
9-52 CB PANEL
TO CLOSE CKT INTERLOCK
TO BLOCK A/R
TO TRIP COIL-1
TO TRIP COIL-2
DIRECT TRIP SEND CH-1
DIRECT TRIP SEND CH-2
TO DISTURBENCE RECORDER
12-52CB PANEL
TO CLOSE CKT INTERLOCK
TO BLOCK A/R
TO TRIP COIL-1
TO TRIP COIL-2
DIRECT TRIP SEND CH-1
DIRECT TRIP SEND CH-2
TO DISTURBENCE RECORDER
15-52 CB PANEL
TO CLOSE CKT INTERLOCK
TO BLOCK A/R
TO TRIP COIL-1
TO TRIP COIL-2
DIRECT TRIP SEND CH-1
DIRECT TRIP SEND CH-2
TO DISTURBENCE RECORDER
18-52 CB PANEL
TO CLOSE CKT INTERLOCK
TO BLOCK A/R
TO TRIP COIL-1
TO TRIP COIL-2
DIRECT TRIP SEND CH-1
DIRECT TRIP SEND CH-2
TO DISTURBENCE RECORDER
(7 SS 52) SIEMENS
OR
OR
OR
OR
14-52
15-52
13-52
11-52
10-52
BUS-2
12-52
7-52
8-52
9-52
5-52
6-52
4-52
2-52
3-52
1-52
BUS-1
ABB
SIEMENS
AREVA
BUSBAR
PROTECTION
CENTRAL UNIT
BAY UNIT
ABB Network Partner AG
REL531
1
2
3
4
5
6
7
8
LINE
PROTECTION
MAIN -1
ABB Network Partner AG
MAIN -2
REL531
1
2
3
4
5
6
7
8
TRANSFORMER
PROTECTION
MAIN
1.
2.
DESCRIPTION
REC 316*4
9
10
11
12
13
14
15
16
3.
4.
MAIN -1
MAIN -2
MAIN -1
MAIN -2
MAIN
B/U
MAIN
B/U
REC 316*4
9
10
11
12
13
14
15
16
B/U
IN THIS NO SEPARATE CORE IS REQUIRED FOR EITHER BUSBAR PROTECTION OR LBB / BFR.
CENTRALISED BUSBAR IS CONNECTED FROM BAY UNIT OR LBB OR BFR THROUGH FIBRE OPTIC.
BAY UNIT / BFR / LBB IS CONNECTED FROM MAIN-1 & MAIN-2 OF LINE PROTECTION OR MAIN & BACKUP
PROTECTION OF TRANSFORMER THROUGH FIBRE OPTIC FOR REDUNDANCY TO BAY UNIT.
THE CURRENT DATA IS TRANSFERED TO BAY UNIT TO BUSBAR CENTRAL UNIT FROM LINE / TRANSFORMER
PROTECTIONS FOR NUMIRICAL ALGORITHAM OF LBB & BUSBAR CENTRAL UNIT AND IT WILL OPERATE FOR
INTERNAL FAULTS AND DOES NOT OPERATE FOR THROUGH / EXTERNAL FAULTS.
MISCELENEOUS
RELAYS & PROTECTIONS
ADOPTED FOR LINE IN
ONE AND HALF
CIRCUIT BREAKER
SCHEME
(STUB, TEED AND AUTO RECLOSURE
FUNCTIONS)
PREPARED BY
GOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
LINE-1
STUB-1&2
(BAY 1&2)
1-89L
REL 521
REL 316
DISTANCE / ATF
RELAYS
CONVERTED
TO STUB/BUS
OVER LOAD
RELAYS WHEN
LINE ISOLATOR
OPENS
2-52CB
1-52CB
BUS-1
STUB-3&2
(BAY 3&2)
3-89T
BUS-2
AT/F-1
RET 521
RET 316
WHEN A LINE IS SUPPLIED VIA TWO CIRCUIT BREAKERS IN A ONE & HALF CIRCUIT
BREAKER ARRANGEMENT, THE LINE PROTECTION INCLUDES THE AREA BETWEEN THE TWO
CTs. HOWEVER, WHEN THE LINE ISOLATOR IS OPEN THE LINE CVTs FOR THE DISTANCE
PROTECTION ARE CONNECTED TO THE LINE AND CANNOT PROVIDE THE CORRECT
VOLTAGE FOR THE STUB END.(i.e THE AREA BETWEEN THE LINE ISOLATOR AND CTs)
(STUB = DEAD END)
TO PROVIDE PROTECTION FOR A FAULT IN THIS AREA, REL 521/ REL 316 IS
PROVIDED WITH A STUB PROTECTION WHICH GIVES AN BUS OVER CURRENT TRIP IF THE
LINE ISOLATOR IS OPEN AND THE CURRENT EXCEEDS THE SET VALUE IN ANY PHASE.
2-52CB
TEED-1&2
(BAY 1&2)
1-52CB
BUS-1
3-52CB
BUS-2
TEED-1&2
(BAY 2&3)
LINE-1
AT/F-1
TEED PROTECTION IS BASED ON KIRCHOFFS CURRENT LAW. THREE SETS OF CTS
ARE CONNECTED IN STAR FASHION. SOME OF THE CURRENTS MUST BE ZERO. IF ANY
UNBALANCE CURRENTS ARE NOTICED THEN IMMEDIATELY TEED PROTECTION
OPERATES. IF TEED PROTECTION BAY 1&2 OPERATED THEN IT TRIPS 1-52CB & 2-52CB.
SIMILARLY IF TEED PROTECTION BAY 2&3 OPERATED THEN IT TRIPS 2-52CB & 3-52CB.
TEED-1
PROTECTION
TEED-2
PROTECTION
TEED-1 PROTECTION
P2 P2 P2
1-CT
CTR: 2000-1000-500/1A
IR5
IY5
IB5
3 3 3
CORE-5
{BAY1&2}(5CT METHOD)
5S4
5S4
5S4
5S2
5S2
5S2
CLASS: PS
IN5
RADHA
P1 P1 P1
P2 P2 P2
IR5
IY5
IB5
2-CT
CTR: 2000-1000-500/1A
3 3 3
CORE-5
5S4
5S4
5S4
5S2
5S2
5S2
CLASS: PS
IN5
ACTIVE START
TRIP
DISPLAY
C
P1 P1 P1
P2 P2 P2
1-LCT
CTR: 2000-1000/1A
CLASS: PS
IN1
1S3
1S3
1S3
1S2
1S2
1S2
3 3 3
CORE-1
IB1
IY1
IR1
P1 P1 P1
IT WORKS ON CIRCULATING
CURRENT PRINCIPLE AND
IT IS HIGH IMPEDENCE
DIFFERENTIAL RELAY.
TEED-1 PROTECTION FOR
BAY 2&3 IS ALSO SAME AS
ABOVE AND THE
FOLLOWING CTs & CORES
ARE USED
3-CT(CORE-5), 2-CT(CORE-1)
& 3-TCT(CORE-1) ARE
STARRED AND CONNECTED
TO TEED-1 PROTECTION
TEED-2 PROTECTION
1-CT
CTR: 2000-1000-500/1A
3 3 3
CORE-4
4S4
4S4
4S4
4S2
4S2
4S2
CLASS: PS
{BAY1&2}(5CT METHOD)
CT MB
RAICA
LBB/BFR
CT MB
RAICA
LBB/BFR
P2 P2 P2
RADSB
ACTIVE
START
P2 P2 P2
4S4
4S4
4S4
4S2
4S2
4S2
3 3 3
TRIP
2-CT
CORE-4
DISPLAY
CTR: 2000-1000-500/1A
CLASS: PS
P2 P2 P2 CT MB
1-LCT
CTR: 2000-1000/1A
CLASS: PS
C
2S3
2S3
2S3
2S2
2S2
2S2
3 3 3
CORE-2
TRIP COIL-1
1-52CB
TRIP COIL-2
BUS-1
86-B
ABB
REL521
MTR/
MAIN-1
HSTR
OR
ABB
(BAY
1&2)
REL521
STUB-1
(BAY 1&2)
(BAY 1&2)
ABB
RADSB
TEED-2
OR
ABB
REL316
STUB-2
ABB
RADHA
TEED-1
86-A
MTR/
HSTR
TRIP COIL-1
2-52CB
TRIP COIL-2
86-B
MTR/
HSTR
OR
ABB
RET521
STUB-1
(BAY 2&3)
(BAY 2&3)
ABB
RADSB
TEED-2
OR
ABB
RET316
STUB-2
86-A
MTR/
HSTR
TRIP COIL-1
3-52CB
TRIP COIL-2
BUS-2
86-B
MTR/
HSTR
AUTO-RECLOSURE FOR
ONE & HALF BREAKER SCHEME
TRIP COMMANDS
AUTO RECLOSURE
COMMANDS
79 (A/R)+
25(SYNC)
RAAAM
RASC
79 (A/R)+
25(SYNC)
RAAAM
RASC
79 (A/R)+
25(SYNC)
RAAAM
RASC
1-52CB
2-52CB
3-52CB
LINE-1
1
2
3
4
5
6
7
8
C
E
21 MAIN-1
REL 521
REL531
REL531
21 MAIN-2
REL 316
REC 316*4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
LINE-2
C
21 MAIN-1
REL 521
REC 316*4
9
10
11
12
13
14
15
16
C
E
21 MAIN-2
REL 316
RESETS
TRANSIENT FAULT
PROTECTION
OPERATING
TIME
CIRCUIT
BREAKER
OPENING
TIME
CLOSING
TIME
ARCING
TIME
OPERATING TIME
OPERATES
RESETS
PROTECTION
PERMANENT FAULT
OPERATES
RESETS
RECLOSE
ON TO FAULT
OPERATING
TIME
CIRCUIT
BREAKER
DEAD TIME
OPENING
TIME
CLOSING
TIME
ARCING
TIME
OPERATING TIME
DEAD TIME
ARC
CONTACTS
CONTACTS
SEPARATE EXTINGUISHED FULLY OPEN
TRIP COIL
ENERGISED
AUTO RECLOSE
RELAY
DEAD TIME
TIME
CARRIER
INTERTRIPPING
SCHEMES
ADOPTED IN
ONE AND HALF
CIRCUIT BREAKER
SCHEME
PREPARED BY
GOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
BLOCKING SCHEME
Blocking commands are initiated by a protection element that
detects faults external to the protected zone. Detection of an
external fault at the local end of a protected circuit results in a
blocking signal being transmitted to the remote end. At the remote
end, receipt of the blocking signal prevents the remote end
protection operating if it had detected the external fault. Loss of the
communications channel is less serious for this scheme than in
others as loss of the channel does not result in a failure to trip when
required. However, the risk of a spurious trip is higher.
UNDER
REACHING
SENDING
OVER
REACHING
SENDING
PERMISSIVE
CRITERIA
RECEIVING
GENERAL
REQUIREMENTS
UNDER IMPEDENCE
UNDER VOLTAGE
OVER CURRENT
DISTANE &
DIRECTION
SECURE &
FAST
PERMISSIVE
UNDER
REACH
(PUTT)
ZONE-1
- - -
PERMISSIVE
OVER
REACH
(POTT)
- - -
ZONE-2
DIRECT
TRIP
ZONE-1
- - -
DISTANCE &
DIRECTION
DEPENDABLE
ACCELERA
TED UNDER
REACH
ZONE-1
- - -
ZONE-2
SECURE &
FAST
BLOCKING
OVER
REACH
- - -
REVERSE
LOCKING
DISTANCE &
DIRECTION
SECURE &
FAST
SECURE &
FAST &
DEPENDABLE
Signal
Transmission
System
PUTT
POTT
1. Excellent
coverage On short
lines in the
Presence of fault
resistance.
2. Suitable for the
Protection of multiterminal lines with
intermediate infeed.
BLOCKING
UNBLOCKING
Reliable
communication
channel
(only
required during
external faults)
1. Power line carrier
With
amplitude
Modulation (ON/OFF).
The same frequency
may be used on all
terminals)
All line types
Preferred practice
in the USA.
Dedicated channel
With
continuous
signal Transfer
1. Power line carrier
With frequency shift
keying. Continuous
Signal transmission
must be permitted.
Same as POTT
Criterion
Speed of operation
Blocking scheme
Not as Fast
As fast
Yes
Yes
Loss of communications
Poor
good
Weak In feed/Open CB
PUTT
POTT
ADVANTAGES
1. Simple technique
2. No coordination
Of zones and times
With the opposite
End required.
3.The combination
Of different relay
Types therefore
presents no
Problems.
Same as POTT
DRAWBACKS
1. Overlapping of the
zone 1 reaches must be
ensured. On parallel
lines, teed feeders and
tapped lines, the
influence of zero
sequence coupling and
intermediate In feeds
must be carefully
considered to make sure
a minimum overlapping
of the zone 1 reach is
always present.
2. Not suitable for weak
In feed terminals
Same as POTT
Same as
1. Slow tripping all POTT
Tele-protection trips
must be delayed to
wait for the eventual
blocking signal.
2. Continuous
channel
Monitoring is not
Possible.
BLOCKING
UNBLOCKING
Same as POTT
but:
1. If no signal is
Received (no
block and no
unblock) then
tripping by the
overreach zone
is released
after 20 ms
Short Line
Weak Infeed
Amplitude
Modulated
Power Line
Carrier
Frequency or
Phase
Modulated
Power Line
Carrier
Communication
independent
of Power Line
PUTT
Not Suitable as the
Zone1 Operation is
essential and Zone1
setting in X and R
direction must be
small on Short Lines.
POTT
BLOCKING
UNBLOCKING
Suitable Same as
POTT.
Suitable as
Reverse Reach
Setting is
independent of
Line Length.
Suitable as the
Signal is only sent
when the Line is
not Faulted.
Suitable as the
Signal can be
Transmitted through
the Fault Location.
Suitable same as
PUTT.
Suitable as the
Signal can be
Transmitted under
all Conditions.
Suitable Same as
PUTT.
Suitable.
Suitable.
Suitable.
Suitable.
Partially Suitable
Suitable Same as
as the Reverse Fault POTT.
is also Detected at
the Weak In-feed
end but no trip at
Weak In-feed end.
NSD 50/
NSD 70
ACTIVE
START
TRIP
ALARM-1
250V DC
2+
5C
R
6+
ALARM-2
250V DC
DISPLAY
C
1-
C
S
910+
C
R
1314+
TX
TRIP
A(C)
RX
TRIP
A(C)
C
S
2+
5-
C
R
TX
TRIP
B(D)
RX
TRIP
B(D)
1-
6+
C
S
910+
C
R
1314+
TX
TRIP
C(A)
RX
TRIP
C(A)
TX
TRIP
D(B)
RX
TRIP
D(B)
GA4D TB:V9LC
NSD 50
CARRIER RECEIVE
G4AC V9LC 5
ABB
REL521
CR
-VE
CS
G4AC V9LC 2
CARRIER SEND
G4AA V9LB 5
G4AA V9LB 6
PANEL-1
NSD 50
ABB
IN OUT
ALARM
+VE
-VE
G4AC V9LC 10
G4AC V9LC 13
G4AC V9LC 14
ABB
G4AC V9LC 9
PANEL-2
NSD 50
CARRIER RECEIVE
G4AC V9LC 5
ABB
REL316
CR
-VE
CS
G4AC V9LC 2
CARRIER SEND
G4AA V9LB 5
G4AA V9LB 6
PANEL-2
NSD 50
ABB
IN OUT
ALARM
+VE
-VE
G4AC V9LC 10
G4AC V9LC 13
G4AC V9LC 14
ABB
G4AC V9LC 9
PANEL-1
PANEL-1
ABB
NSD 50
DC +VE
FROM PANEL
CONTROL PANEL
T NC
MAIN CB(1-52CB)
T NC
TIE CB(2-52CB)
G4AD V9LC 2
G4AD V9LC 1
DC VE FROM PANEL
CONDITIONS FOR DIRECT TRIP
1.
TIE CB OPEN CONDITION + MAIN CB REMOTE HAND TRIP GIVEN.
2.
MAIN CB OPEN CONDITION + TIE CB REMOTE HAND TRIP GIVEN.
3.
TIE CB OPEN CONDITION + 96 BUSBAR-1 OPERATED.
4.
MAIN CB OPEN CONDITION + 96 BUSBAR-2 OPERATED (FOR HALF DIA ONLY).
5.
MAIN CB 50 LBB/BFR OPERATED.
6.
TIE CB 50 LBB/BFR OPERATED.
7.
59L1 OVER VOLTAGE STAGE-1 OPERATED.
8.
59L2 OVER VOLTAGE STAGE-2 OPERATED.
9.
87 HZ TEED-1 PROTECTION OPERATED
10. 87 LZ TEED-2 PROTECTION OPERATED.
PANEL-2
ABB
NSD 50
DC +VE
FROM PANEL
CONTROL PANEL
T NC
MAIN CB(1-52CB)
T NC
TIE CB(2-52CB)
G4AD V9LC 2
G4AD V9LC 1
DC VE FROM PANEL
CONDITIONS FOR DIRECT TRIP
1.
TIE CB OPEN CONDITION + MAIN CB REMOTE HAND TRIP GIVEN.
2.
MAIN CB OPEN CONDITION + TIE CB REMOTE HAND TRIP GIVEN.
3.
TIE CB OPEN CONDITION + 96 BUSBAR-1 OPERATED.
4.
MAIN CB OPEN CONDITION + 96 BUSBAR-2 OPERATED (FOR HALF DIA ONLY).
5.
MAIN CB 50 LBB/BFR OPERATED.
6.
TIE CB 50 LBB/BFR OPERATED.
7.
59L1 OVER VOLTAGE STAGE-1 OPERATED.
8.
59L2 OVER VOLTAGE STAGE-2 OPERATED.
9.
87 HZ TEED-1 PROTECTION OPERATED
10. 87 LZ TEED-2 PROTECTION OPERATED.
ABB
NSD 50
DC +VE
G4AD V9LC 6
G4AD V9LC 5
PANEL-2
DIRECT TRIP-1
CARRIER RECEIVE
RELAY
+VE
-VE
ABB
NSD 50
DC +VE
G4AD V9LC 6
G4AD V9LC 5
DIRECT TRIP-2
CARRIER RECEIVE
RELAY
REL531
REL531
REL 521
MAIN-1
PROTECTION
C
ELECTRICAL CONNECTION
NSD 50
PANEL
NSD 50
PANEL
PLCC
PANEL
PLCC
PANEL
NSD 50
PANEL
NSD 50
PANEL
ELECTRICAL CONNECTION
ABB Network Partner AG
2
3
4
5
6
10
11
12
13
14
7
8
15
16
REC 316*4
REL 316
MAIN-2
PROTECTION
2
3
4
5
6
10
11
12
13
14
7
8
15
16
REC 316*4
REL531
REL531
REL 521
MAIN-1
PROTECTION
C
ELECTRICAL CONNECTION
TUNOS
TUNOS
FOX-U
FOX-515
FOX-U
FOX-515
GECOD/ SIFOX
NSD 70
PANEL
NSD 70
PANEL
GECOD/ SIFOX
NSD 70
PANEL
NSD 70
PANEL
ELECTRICAL CONNECTION
ABB Network Partner AG
2
3
4
5
6
10
11
12
13
14
7
8
15
16
REC 316*4
REL 316
MAIN-2
PROTECTION
2
3
4
5
6
10
11
12
13
14
7
8
15
16
REC 316*4
REL531
REL531
REL 521
MAIN-1
PROTECTION
2
3
4
5
6
10
11
12
13
14
7
8
15
16
FOX-U
FOX-515
REC 316*4
REL 316
MAIN-2
PROTECTION
2
3
4
5
6
10
11
12
13
14
7
8
15
16
OTERM
TUNOS
TUNOS
OTERM
FOX-U
FOX-515
REC 316*4
PREPARED BY
GOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
2.
3.
5. BACK UP PROTECTION
A VARIETY OF RELAYS ARE AVAILABLE.
A. OVER CURRENT & EARTH FAULT PROTECTION. ( 50, 50N, 51, 51N, 67, 67N - ANY COMBINATION OF THESE)
B. UNDER IMPEDENCE / DISTANCE ( Z<)(21T).
C. NEUTRAL DISPLACEMENT PROTECTION (Un>).
HV
VOLTAGE
HV CURRENT
LV VOLTAGE
LV
CURRENT
315 MVA
500 MVA
630 MVA
400 KV
400 KV
400 KV
454.68 A
721.71 A
909.35 A
220 KV
220 KV
220 KV
0826.68 A
1312.20 A
1653.37 A
CAPACITY
132KV/11KV
16 MVA
31.5 MVA
50 MVA
80 MVA
31.5 MVA
50 MVA
220KV/33KV
100 MVA
160 MVA
220KV/132KV
315 MVA
500 MVA
630 MVA
400KV/220KV
630 MVA
750 MVA
1000MVA
1500MVA
MAIN
PROTECTION
132KV/33KV
765KV/400KV
7.5 MVA
16 MVA
25 MVA
31.5 MVA
VOLTAGE
RATIO
BACK UP
PROTECTION
HV
LV
3 OL +
1 DIR EL
3 OL +
1 EL
3 OL +
1 DIR EL
3 OL +
1 EL
3 OL +
1 DIR EL
3 OL +
1 DIR EL
3 OL +
1 EL
3 OL +
1 DIR EL
3 DIR OL
(HIGHSET) +
1 DIR EL
(HIGHSET)
3 DIR OL
(HIGHSET) +
1 DIR EL
(HIGHSET)
ADDITIONAL
PROTECTION
SPECIAL
PROTECTION
BUCHHOLZ,
OLTC OSR
OIL TEMP
WDNG TEMP
NIL
BUCHHOLZ
OVER FLUX
OLTC OSR
PRV/PRD
REF RELAY,
OIL TEMP
OVER LOAD
WDNG TEMP ALARM RELAY
T/F NEUTRAL
CURRENT RELAY
+ HIGH
IMPEDENCE
DIIFERENTIAL
RELAY
3-CT
5S4
5S4
5S4
5S3
5S3
5S3
CLASS: PS
TRIP
5S1
5S1
5S3
5S3
5S3
CORE-5
DISPLAY
CTR: 1200-800/1A
CLASS: PS
CT MB
5S3
5S3
5S3
5S4
5S4
5S4
3 3 3
CTR: 2000-1000-500/1A
START
3 3 3
5S1
P2 P2 P2
LV-CT
2-ACT
CORE-5
RET 521/
RET 316
RADSB
ACTIVE
CLASS: PS
P2 P2 P2
AUX.CT Y/
0.91 / 0.577A
CTR: 2000-1000-500/1A
3 3 3
CORE-5
CT MB
AUX.CT Y/
0.689 / 0.577A
AUX.CT Y/
0.91 / 0.577A
P2 P2 P2
IN CASE OF 1&1/2 CB
SYSTEM, THE DIFFERENTIAL
PROTECTION CTs
ASSOCIATED WITH MAIN &
TIE CBs SHOULD BE
CONNECTED TO SEPARATE
BIAS WINDINGS AND THESE
SHOULD NOT BE PARALLED
IN ORDER TO AVOID FALSE
OPERATION DUE TO
DISSIMILAR CT TRANSIENT
RESPONSE.
3-TCT
CTR: 2000-1000-500/1A
CLASS: PS
3 3 3
CORE-5
5S4
5S4
5S4
5S3
5S3
5S3
CT MB
AUX.CT Y/
0.91 / 0.577A
P2 P2 P2
RET 521/
RET 316
RADSB
ACTIVE
START
TRIP
AUX.CT Y/
0.689 / 0.577A
CT MB
3 3 3
5S1
5S1
5S1
5S3
5S3
5S3
P2 P2 P2
LV-CT
CORE-5
DISPLAY
CTR: 1200-800/1A
CLASS: PS
NORMALLY LOW
IMPEDENCE BIASED
DIFFERENTIAL RELAY
IS USED FOR
TRANSFORMER
DIFFERENTIAL
PROTECTION
CT MB
IR4 / C411
IY4 / C431
RAICA IB4 / C451
LBB / BFR
IN4 / C471
50Z
3-CT
CTR: 2000-1000-500/1A
3 3 3
CORE-4
4S4
4S4
4S4
4S3
4S3
4S3
CLASS: PS
START
C
4S3
4S3
4S4
4S4
4S4
CLASS: PS
P2 P2 P2
IB4 / C451
IY4 / C431
IR4 / C411
VB11 / E151
VN11 / E171
3 3 3
E172
E174
CT MB
4S3
VY11 / E131
TRIP
DISPLAY
3 3 3
CTR: 2000-1000-500/1A
RAPDK
DIR O/L & E/F
REL 505
ACTIVE
2-ACT
CORE-4
VR11 / E111
3 3
CVT
SELECTION
BUS-1 CVT /
BUS-2 CVT /
LINE CVT
CORE-1
VA : 200
CLASS: 3P
P2 P2 P2
IR4 / C411
IY4 / C431
IB4 / C451
3-TCT
CTR: 2000-1000-500/1A
CLASS: PS
3 3 3
CORE-4
CT MB
4S4
4S3
4S4
4S4
4S3
4S3
RAPDK
DIR O/L & E/F
REL 505
ACTIVE
START
VY11 / E131
VB11 / E151
VN11 / E171
TRIP
3 3 3
E172
E174
IN4 / C471
DISPLAY
C
3 3
CVT
SELECTION
BUS-1 CVT /
BUS-2 CVT /
LINE CVT
CORE-1
VA : 200
CLASS: 3P
3 3 3
CORE-4
4S2
4S2
4S2
4S1
4S1
4S1
CLASS: PS
P2 P2 P2
CT MB
IR4 / C411
IY4 / C431
RAICA IB4 / C451
LBB / BFR
IN4 / C471
50Z
VR11 / E111
RAPDK
DIR O/L & E/F
REL 505
ACTIVE
START
VY11 / E131
VB11 / E151
VN11 / E171
TRIP
3 3 3
E172
E174
DISPLAY
3 3
VOLTAGE
SELECTION
BUS-1 PT /
BUS-2 PT
CORE-1
VA : 200
CLASS: 3P
MISCELLENEOUS
RELAYS & PROTECTIONS
ADOPTED FOR
AUTO TRANSFORMER IN
ONE AND HALF
CIRCUIT BREAKER
SCHEME
(OVER FLUX & REF FUNCTIONS)
PREPARED BY
CVT SELECTION
BUS-1 CVT /
BUS-2 CVT /
LINE CVT
CORE-1
VA : 200
CLASS: 3P
RATUB
BUS-1 PT /
V/F RELAY
HV
CORE-1
RATUB
V/F RELAY
LV
BUS-2 PT
VA : 200
CLASS: 3P
S2
S2
S1
S1
S1
3 3 3
BUSHING CT
S2
RADHD
ACTIVE START
TRIP
CTR: 1000/1A
CLASS: PS
P1 P1 P1
P1 P1 P1
NEUTRAL
CORE-1
S1
S1
S1
S2
S2
S2
3 3 3
BUSHING CT
CTR: 1000/ 1A
CLASS: PS
P2 P2 P2
P1 P1 P1
220KV LV
CORE-1
CTR: 1000/1A
S1
S1
S1
S2
S2
S2
3 3 3
BUSHING CT
DISPLAY
CLASS: PS
P2 P2 P2
400KV HV
CORE-1
S2
S2
S1
S1
S1
3 3 3
BUSHING CT
S2
RADHA
ACTIVE START
TRIP
CTR: 1000/1A
CLASS: PS
P1 P1 P1
P1 P1 P1
NEUTRAL
CORE-1
S1
S1
S1
S2
S2
S2
3 3 3
BUSHING CT
CTR: 1000/ 1A
CLASS: PS
P2 P2 P2
P1 P1 P1
220KV LV
CORE-1
CTR: 1000/1A
S1
S1
S1
S2
S2
S2
3 3 3
BUSHING CT
DISPLAY
CLASS: PS
P2 P2 P2
LINE1
1-52CB
2-52CB
3-52CB
BUS-2
AT/F-1
FEEDER HAVING LINE CVTs &BUSES ARE HAVING BUS CVTs BUT AT/Fs ARE
NOT HAVING CVTs. FOR TRANSFORMER PANEL, PT SUPPLY IS SELECTED AS
PER SELECTION DESCRIBED BELOW FOR METERING AND PROTECTION,
WHICH IS FIRST SELECTED .
BUS-1
CVT
BUS-2
CVT
LINE
CVT
If AT/F is feeding from Bus-1 and 1-52CB & 2-52CB is closed. Then
Bus-1 CVT is selected and this supply is extended to Control &
Relay Panels for Auto Transformer.
If AT/F is feeding from Bus-2 and 3-52 CB is closed & 2-52CB is
open. Then Bus-2 CVT is selected and this supply is extended to
Control & Relay Panels for Auto Transformer.
If AT/F is feeding from Direct Line and 2-52CB is closed & 1-52 CB
& 3-52 CB is open and 389T ISO is Closed . Then line CVT is
selected and this supply is extended to Control & Relay Panels for
Auto Transformer.
PREPARED BY
GOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
1. TYPES OF REACTORS :
A. BASED ON REACTOR CONNECTION
i. SHUNT REACTOR.
ii. SERIES REACTOR.
B. BASED ON REACTOR LOCATION
i. BUS REACTOR
ii. LINE REACTOR
C. BASED ON CONTROL
i. 3-PH OIL IMMERSED REACTOR WITH GAPPED IRON CORE.
ii. THYRISTOR CONTROLLED REACTOR (STATIC VAR COMPENSATOR)
(APTRANSCO UTILISING SHUNT REACTORS FOR BUS & LINE IN 400KV NETWORK)
2. NEED OF SHUNT REACTOR:
A. LINE REACTOR
SHUNT REACTORS ARE USED IN ORDER TO COMPENSATE FOR THE CAPACITIVE SHUNT
REACTANCE OF TRANSMISSION LINES. THE REACTOR IS CONNECTED PARALLEL TO THE LINE. THE
LOCATION OF REACTOR IS OUT GOING SIDE OF LINE i.e AFTER CIRCUIT BREAKER. LENGTH OF LINE
IS MORE THERE MAY BE VOLTAGE IS RAISING DUE TO FARANTI EFFECT(CAPACITANCE) DURING
CHARGING. IN CASE OF ZONE-2 (OPEN JUMPER) FAULT, THE FAULT CLEARED BY REMOTE END IS
FAST, BUT THIS END IT WILL TAKE TIME DELAY DUE TO ZONE-2. DURING THIS TIME, VOLTAGE MAY
RAISING. SO, LINE REACTOR IS USED FOR CONTROLLING THE SWITCHING OVER VOLTAGES AND
SAFEGUARD THE OPERATING EQUIPMENT. NORMALLY IT IS ALWAYS IN SERVICE. NORMALLY BOTH
ENDS LINE REACTORS ARE PROVIDED. THE ELECTRICAL INTERLOCK IS PROVIDED THAT IF
REACTOR ISOLATOR CLOSSED POSITION ONLY WILL GIVE PERMIT TO CLOSE THE LINE ISOLATOR.
SIMILARLY FOR OPENING REACTOR ISOLATOR THE LINE ISOLATOR SHOULD BE IN OPEN POSITION.
NEUTRAL REACTOR CONNECTED BETWEEN THE STAR POINT OF EHV SHUNT REACTOR AND THE
GROUND, LIMITS THE SECONDARY ARC CURRENT TO A LOW VALUE OF AROUND 10 AMPS
TYPICALLY FOR 400KV SYSTEM TO ENSURE COMPLETE DE-IONISATION OF ARC PATH WHEN EHV
SYSTEM DEVELOPS A SINGLE LINE TO GROUND FAULT. ARC EXTINCTION DURING LINE SINGLEPHASE AUTORECLOSE DEAD TIME IS ASSISTED BY THIS NEUTRAL REACTOR.
3.
4.
B. BUS REACTOR
THE REACTOR IS CONNECTED PARALLEL TO THE BUS i.e LIKE A FEEDER/LINE.
DURING LIGHTLY LOADED CONDITIONS THERE MAY BE POSSIBULITY OF RAISING
BUS VOLTAGES. FOR SAFEGUARD THE OPERATING EQUIPMENT BUS REACTORS
ARE UTILISING. NORMALLY IT IS NOT IN SERVICE. WHENEVER THE VOLTAGE
RAISES TO 4%TO 5% MORE THAN THE RATED VOLTAGE THIS MAY BE KEPT IN
SERVICE AND 2% TO 3% LESS THAN THE RATED VOLTAGE THIS MAY BE KEPT OUT
OF SERVICE.
SELECTION OF REACTOR
A. LINE REACTOR
NORMALLY LINE REACTORS ARE PROVIDED IF THE LINE IS MORE OR EQUAL TO
250KM. IN APTRANSCO NETWORK MAXIMUM LENTH OF LINE IS 350KM. AS PER
SYSTEM STUDIES RECOMANDATIONS IF LINE LENGTH IS 250KM TO 300KM 50MVAR
REACTOR IS TO BE USED. IF MORE THAN 300KM 63MVAR REACTOR IS TO BE
USED.
B. BUS REACTOR
NORMALLY BUS REACTORS ARE PROVIDED IF THE SUBSTATION BUS VOLTAGE IS
RAISING 5% MORE THAN THE RATED VOLTAGE DURING LIGHTLY LOADED
CONDITION. BASED ON THE SYSTEM STUDIES RECOMANDATIONS BUS REACTORS
ARE TO BE PROVIDED. CALCULATIONS ARE REQUIRED FOR PROVIDING BUS
REACTOR. IN THIS THERE IS NO STANDARDISATION.
LOCATION OF REACTORS WITH CAPACITY IN APTRANSCO
A. LINE REACTOR
1. 400KV KALAPAKA-KHAMMAM 1 AT BOTH ENDS 63MVAR
2. 400KV KALAPAKA-KHAMMAM 2 AT BOTH ENDS 63MVAR
B. BUS REACTOR
1. 400KV KALAPAKA SS 2 X 50 MVAR
2. 400KV NUNNA SS(PGCIL BAYS) 1 x 63 MVAR
5.
6.
7.
8.
9.
BUS-2
1-89
IL
INTER LOCK FACILITY:
WHEN 1-89R CLOSES ONLY
PERMIT TO CLOSE 1-89L AND
1-89L OPENS ONLY
PERMIT TO OPEN 1-89R.
3-89
1-52CB
1-CT
3-52CB
P2
P2
3P1
3-CT
3
P1
1-89A
UUU
1-89L
2-89A
P1
P2
2-BCT
P1
2-52CB
P2
2-89B
3-89R
UUUU
1-PH NEUTRAL
GROUNDING REACTOR
IL
UUU
LINE
SHUNT
REACTOR
P1 3
1-RCT
2-ACT
1-89R
P2
3-89A
LINE 1
BUS
SHUNT
REACTOR
BUS-2
1-89
IL
INTER LOCK FACILITY:
WHEN 1-89R CLOSES ONLY
PERMIT TO CLOSE 1-89L AND
1-89L OPENS ONLY
PERMIT TO OPEN 1-89R.
3-89
1-52CB
1-CT
3-52CB
P2
P2
3P1
3 3-CT
P1
1-89A
2-89A
IL
2-52CB
P2
2-89B
3-89R
P2
1-89L
1-LCT
P1
P2
3P1
LINE 1
P1
3 3-RCT
UUUU
UUU
UUU
1-PH NEUTRAL
GROUNDING
REACTOR
P2
LINE
SHUNT
REACTOR
2-CT
1-89R
1-RCT
P1 3
3-89A
BUS
SHUNT
REACTOR
3,4,6S - CT METHOD
5,6T1,6T2 - CT METHOD
LINE PROTECTION
IN THIS REACTOR CT CURRENT IS OPPOSES THE
MAIN&TIE CT CURRENT. VECTOR SUM OF CTs i.e.
MAIN, TIE & REACTOR IS LINE CURRENT.
MAIN-1 PROTECTION,
MAIN-2 PROTECTION,
METERING,
BUSBAR & BUSBAR
CHECKUP PROTECTION
AS USUAL IN
5CT METHOD,
6CT(T1) METHOD,
6CT(T2) METHOD
BACK UP PROTECTION(21R)
( SINGLE STEP REACTOR
IMPEDENCE PROTECTION )
METERING
4 CT METHOD
5 CT METHOD
HV BUSHING CT CORE-1&
NEUTRAL BUSHING CT CORE-3 OF
BUS SHUNT REACTOR IS
CONNECTED TO 3-PH HIGH
IMPEDENCE DIFFERENTIAL RLY.
SPECIAL PROTECTION
LINE SHUNT REACTOR
STUB PROTECTION
CVT SELECTION
5 CT METHOD
5 CT METHOD
REACTOR HIGH
IMPEDENCE
DIFFERENTIAL RELAY
REACTOR HIGH
IMPEDENCE
DIFFERENTIAL RELAY
REACTOR HIGH
IMPEDENCE
DIFFERENTIAL RELAY
CORE-2(PS)
RESTRICTED EARTH
FAULT PROTECTION
CORE-3*(PS)
SPARE
REACTOR HIGH
IMPEDENCE
DIFFERENTIAL RELAY
RESTRICTED EARTH
FAULT PROTECTION
SPARE
RESTRICTED EARTH
FAULT PROTECTION
RESTRICTED EARTH
FAULT PROTECTION
TEED PROTECTION
SPARE
METERING
METERING
METERING
METERING
CORE-2(PS)
SPARE
SPARE
CORE-3(PS)
REACTOR HIGH
IMPEDENCE
DIFFERENTIAL RELAY
REACTOR HIGH
IMPEDENCE
DIFFERENTIAL RELAY
(0.2/0.5)
SPARE
SPARE
RESTRICTED EARTH
FAULT PROTECTION
RESTRICTED EARTH
FAULT PROTECTION
RESTRICTED EARTH
FAULT PROTECTION
REACTOR HIGH
IMPEDENCE
DIFFERENTIAL RELAY
RESTRICTED EARTH
FAULT PROTECTION
REACTOR HIGH
IMPEDENCE
DIFFERENTIAL RELAY
(4CT METHOD)
1-RCT
NEUTRAL BUSHING
(STAR PONT SIDE)
CTs
CORES
3 2 1
200/ 1A
P1
3
3
3
LINESHUNT
REACTOR
UUU
P2
.
.
CORE 1.1
.
P2
CORES
4 3 2
.
.
.
.
LINE
METERING
MAIN-2 PROTECTION
MAIN-1 PROTECTION
1-CT
1-PH NEUTRAL
GROUNDING REACTOR
UUU
P2
.
CORE 1.2
.
P1
200/ 1A
P2
1-CT
2B-CT
LINE
1-CT
2B-CT
LINE
2B-CT
P1
200/ 1A
2000-1000-500/1
2000-1000-500/1
2000-1000-500/1
2000-1000-500/1
2000-1000-500/1
1-89R
3
3
3
3
3
3
3
3
HV BUSHING
(400KV SIDE) CTs
CORES
3 2 1
P1
200/ 1A
CORE-1:
CORE-2:
CORE-3:
CORE-4:
CORE-5:
SELECTED
BUS-1/ BUS-2/ LINE
CVT VOLTAGE
REACTOR METERING
(5CT METHOD)
1-RCT
NEUTRAL BUSHING
(STAR PONT SIDE)
CTs
2000-1000-500/1
2000-1000-500/1
2000-1000-500/1
2000-1000-500/1
2000-1000-500/1
1-89R
P2
1-LCT CORE-1
P1
CORES
3 2 1
200/ 1A
3
3
3
LINESHUNT
REACTOR
P1
UUU
P2
CORES
4 3 2
3
3
3
3
3
3
3
3
HV BUSHING
(400KV SIDE) CTs
CORES
3 2 1
P1
200/ 1A
CORE-1:
CORE-2:
CORE-3:
CORE-4:
CORE-5:
2-CT CORE-5
.
.
CORE 1.1
.
P2
SELECTED
BUS-1/ BUS-2/ LINE
CVT VOLTAGE
UUU
P2
1-PH NEUTRAL
GROUNDING REACTOR
.
CORE 1.2
.
P1
200/ 1A
P2
2-CT
CORE-4
1-LCT
CORE-2
P1
200/ 1A
1-CT
CORE-4
REACTOR METERING
2-52CB
4 3 2
CORES
2A-CT
.
3 2 1
CORES
. UUU
P1
3
3
3
3
3
3
P2
3-89R
2-89B
P1
P1
3-89A
P2
3-CT
5 4 3
CORES
3
3
3
3
3
3
3
3
REACTOR METERING
P2
3
3
SELECTED
BUS-1/ BUS-2
CVT VOLTAGE
3-52CB
P2 3
2 1
CORES
200/ 1A
P1
HV BUSHING CTs
(400KV SIDE)
3-89
BUS-2
(4CT METHOD)
1
2
3
3
3
.
2-52CB P1
2-CT
P2
3-89A
P2 3
2 1
CORES
P1
HV BUSHING CTs
(400KV SIDE)
2-89B
3
3
3
3
3
P2
3R-CT
P1
P1
3-89R
CORES
2 3 4
3 2 1
CORES
. UUU
3
3
3
P2
3
3
3
3-CT
4 3 2
CORES
P2
P1
3-52CB
CORES
3 4 5
3-89
3
3
3
3
3
REACTOR METERING
(5CT METHOD)
3
3
SELECTED
BUS-1/ BUS-2
CVT VOLTAGE
ABB
NSD 50
LINE PROTECTION
COUPLER PANEL-1
DC +VE
FROM PANEL
RADHD
REACTORS INTERNAL FAULTS
G4AD V9LC 2
GROUP-1/A TRIPPINGS
G4AD V9LC 1
87R REACTOR DIFFERENTIAL RELAY
RADHA
21R REACTOR IMPEDENCE RELAY
RAKZB
ABB
NSD 50
DC VE FROM PANEL
LINE PROTECTION
COUPLER PANEL-2
DC +VE
FROM PANEL
RADHD
REACTORS INTERNAL FAULTS
G4AD V9LC 2
GROUP-2/B TRIPPINGS
G4AD V9LC 1
DC VE FROM PANEL
ADDITIONAL AND
SPECIAL FUNCTIONS
ADOPTED IN
ONE AND HALF
CIRCUIT BREAKER
SCHEME
(EVENT LOGGER & DISTURBANCE
RECORDER)
PREPARED BY
GOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
DISTURBANCE RECORDER
R PH VOLTAGE
Y PH VOLTAGE
B PH VOLTAGE
OPEN DELTA VOLTAGE
R PH CURRENT
Y PH CURRENT
B PH CURRENT
STAR/NEUTRAL CURRENT
MAIN CB R PH OPEN
MAIN CB Y PH OPEN
MAIN CB B PH OPEN
TIE CB R PH OPEN
TIE CB Y PH OPEN
TIE CB B PH OPEN
MAIN/TIE CB LBB OPTD
DIRECT TRIP CH-1/2 OPTD
BUSBAR PROT OPTD
MAIN-1 PROT OPTD
MAIN-2 PROT OPTD
OVER VOLTAGE STAGE-1/2 OPTD
STUB PROT-1/2 OPTD
MAIN-1 PROT CARRIER RECEIVE
MAIN-2 PROT CARRIER RECEIVE
DF/DT OPTD
EVENT NO
NAME OF FEEDER
DATE & TIME
400 KV TRANSFORMER
ANALOG CHANNELS
ANALOG CHANNELS
DIGITAL CHANNELS
1.
2.
3.
4.
5.
6.
7.
8.
1. HV
2. HV
3. HV
4. HV
5. LV
6. LV
7. LV
8. LV
9. HV
10. HV
11. HV
12. HV
13. LV
14. LV
15. LV
16. LV
R-PH VOLTAGE
Y-PH VOLTAGE
B-PH VOLTAGE
OPEN DELTA VOLTAGE
R-PH CURRENT
Y-PH CURRENT
B-PH CURRENT
NEUTRAL/STAR CURRENT
DIGITAL CHANNELS
1. HV MAIN CB R-PH OPEN
2. HV MAIN CB Y-PH OPEN
3. HV MAIN CB B-PH OPEN
4. HV TIE CB R-PH OPEN
5. HV TIE CB Y-PH OPEN
6. HV TIE CB B-PH OPEN
7. 21 MAIN1 REL 521 OPERATED
8. 21 MAIN2 REL 316 OPERATED
9. 87 BUSBAR RELAY OPERATED
10. MAIN CB A/R OPERATED
11. TIE CB A/R OPERATED
12. PSB OPERATED
13. SOTF OPERATED
14. 27 O/V STG-1/2 OPERATED
15. 51 STUB-1/2 OPERATED
16. 87HZ / LZ TEED-1/2 OPERATED
17. MAIN CB LBB OPERATED
18. TIE CB LBB OPERATED
19. DIRECT TRIP CH-1/2 TRIP
20. 21M1 / 21M2 CARRIER RECEIVE
21. 86 GR-A/B RELAY OPERATED
22. 67N DEF/TEF RLY OPERATED
23. DF/DT RELAY OPERATED
R-PH VOLTAGE
Y-PH VOLTAGE
B-PH VOLTAGE
OPEN DELTA VOLTAGE
R-PH VOLTAGE
Y-PH VOLTAGE
B-PH VOLTAGE
OPEN DELTA VOLTAGE
R-PH CURRENT
Y-PH CURRENT
B-PH CURRENT
NEUTRAL/STAR CURRENT
R-PH CURRENT
Y-PH CURRENT
B-PH CURRENT
NEUTRAL/STAR CURRENT
CONFIGUARATION
OF CONTROL &
RELAY PANELS IN
ONE AND HALF
CIRCUIT BREAKER
SCHEME
PREPARED BY
GOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
CB RELAY PANEL
1. AMMETERS IN 3Phs
2. VOLTMETER WITH SEL. SWITCH
3. WATTMETER
4. VAR METER
5. 20W ANNUCIATION FACIA
6. CB CONTROL (TNC) SWITCH
7. ISO CONTROL (TNC) SWITCH
8. SEMAPHORE FOR EARTH SWITCH
9. INDICATING LAMPS FOR CB G&R
10. INDICATING LAMPS FOR ISO
11. INDICATING LAMPS FOR DC
12. INDICATING LAMPS FOR ISO I/L
13. PUSH BUTTON FOR ANNUNCIATION
14. SYNCHRONISING SOCKET FOR CB
15. SYNCHRONISING SEL.SWITCH
16. PROTECTION TRANSFER
17. MIMIC TO REPRESENT SLD
18. CUTOUT FOR RWTI WITH SEL .SWI.
19. PANEL INDICATING LABEL
MV PROTECTION PANEL
MV CB RELAY PANEL
MV PROTECTION PANEL
HV PROTECTION PANEL
HV CB RELAY PANEL
MV PROTECTION PANEL
HV PROTECTION PANEL
HV CB RELAY PANEL
TRIP LOGICS
OF
ONE AND HALF
CIRCUIT BREAKER
SCHEME
PREPARED BY
GOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
LINE PROTECTION
TRANSFORMER PROTECTION
REACTOR PROTECTION
GROUP-A
GROUP-A
GROUP-A
MAIN-1 PROTECTION
M1 BUILT IN FUNCTIONS
TEED-1 PROTECTION
OVER VOLTAGE STAGE-1 PROT
DIRECT TRIP CHANNEL-1 RECEIVED
GROUP-B
MAIN-2 PROTCTION
M2 BUILT IN FUNCTIONS
TEED-2 PROTECTION
OVER VOLTAGE STAGE-2 PROT
LBB/BFR RELAY
DIRECT TRIP CHANNEL-2 RECEIVED
GROUP-B
T/F REF / HIGH Z DIFF RELAY
BUCHHOLZ TRIP
T/F LV BACKUP RELAY
T/F NEUTRAL CURRENT / 51 O/C RLY
T/F LV OVERFLUX RELAY
OVER LOAD PROT (ALARM ONLY)
OLTC BUCHHOLZ TRIP
WINDING TEMP HIGH TRIP
LOW/ HIGH OIL LEVEL TRIP
GROUP-B
REACTOR REF RELAY
BUCHHOLZ TRIP
WINDING TEMP HIGH TRIP
LOW/ HIGH OIL LEVEL TRIP
FIRE PROTECTION TRIP
SOTF, PSB
INITIATE ALARM
1-PH
21 M2
MAIN-2 PROTECTION
1-PH
OUTPUT
GROUP
21 M1
SYMBOL
MAIN-1 PROTECTION
PROTECTION
RELAY
OVER VOLTAGE
STAGE-1 & STAGE-2
(BUILT IN 21 M1)
59 L1 & L2
3-PH
OVER VOLTAGE
STAGE-1 & STAGE-2
(BUILT IN 21 M2)
59 L1 & L2
3-PH
3-PH
3-PH
TEED PROT-1
87T HZ
3-PH
TEED PROT-2
87T LZ
3-PH
3-PH
3-PH
3-PH
3-PH
X
X
X
X
X
X
X
X
X
X
X
X
INITIATE ALARM
25 SYNC
A&B
3-PH
186
1-PH
86 GR A
3-PH
286
1-PH
86 GR B
3-PH
96 BB
3-PH
27 UV
OUTPUT
A&B
GROUP
79 A/R
SYMBOL
PROTECTION
RELAY
CLOSE MAIN CB
PROTECTION
RELAY
SYMBOL
GROUP
OUTPUT
X
X
INITIATE ALARM
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
HV BACKUP PROTECTION
67 ABCN
3-PH
99T HV
3-PH
51 O/L
3-PH
86 GR-A/B
A/B
3-PH
REF PROTECTION
64T(HZ)
3-PH
TEED PROT-1 / 2
87T HZ/LZ
A/B
3-PH
STUB PROT
50 STUB
3-PH
86 GR-A/B
A/B
3-PH
X
X
X
X
X
X
X
X
3-PH
INITIATE ALARM
OUTPUT
87T(LZ)
GROUP
DIFFERENTIAL RELAY
PROTECTION
RELAY
SYMBOL
50Z
3-PH
50ZT
3-PH
50Z
3-PH
87 BB
96
3-PH
87 BB
96
3-PH
LV BACKUP PROTECTION
67 ABCN
3-PH
99T LV
3-PH
151N
3-PH
86 GR-A/B
A/B
3-PH
X
X
ABB
REL521
MAIN-1
TRIP COIL-1
1-52CB
TRIP COIL-2
86-A
MTR/
HSTR
ABB
RET521
MAIN-1
TRIP COIL-1
2-52CB
TRIP COIL-1
3-52CB
TRIP COIL-2
TRIP COIL-2
BUS-2
BUS-1
86-B
ABB
REL521
MTR/
MAIN-1
HSTR
ABB
REL316
MAIN-2
86-A
MTR/
HSTR
86-B
MTR/
HSTR
ABB
RET316
MAIN-2
86-B
MTR/
HSTR
MAIN-1/ MAIN-2
ZONE-1 & SINGLE PHASE FAULT
REL 521
ACTIVE
START
TRIP
INITIATE MAIN CB GR-A 1-PH TRIP UNIT ( INTURN IT WILL TRIP 1-POLE )
INITIATE TIE CB GR-A 1-PH TRIP UNIT ( INTURN IT WILL TRIP 1-POLE )
START MAIN CB AUTO RECLOSURE
START TIE CB AUTO RECLOSURE
DISPLAY
REL 316
ACTIVE
START
TRIP
CARRIER SEND
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
TO DISTURBANCE RECORDER
TO EVENT RECORDER ( SOE/ SCADA )
TO LBB/BFR INITIATION
INITIATE MAIN CB GR-B 1-PH TRIP UNIT ( INTURN IT WILL TRIP 1-POLE )
INITIATE TIE CB GR-B 1-PH TRIP UNIT ( INTURN IT WILL TRIP 1-POLE )
START MAIN CB AUTO RECLOSURE
START TIE CB AUTO RECLOSURE
DISPLAY
CARRIER SEND
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
TO DISTURBANCE RECORDER
TO LBB/BFR INITIATION
AUTO RECLOSURE
1.
2.
3.
7.
8.
9.
CB CLOSE CONDITION.
TIME LAPSED MORE THAN RECLAIM TIME.
OPERATING PRESSURE OF CB SUITABLE FOR AUTORECLOSURE
OPERATION.
DC SUPPLY TO AUTORECLOSURE SHOULD BE AVAILABLE.
PREPARE 3-PH TRIP RELAY SHOULD BE RELEASED CONDITION.
NO BLOCKING SIGNAL TO AUTORECLOSURE RELAY.
POLE DISTURBANCE RELAY TIME SHOULD BE MORE THAN
TWICE OF DEAD TIME OF AUTO RECLOSURE.
CARRIER FAIL SIGNAL SHOULD NOT COME AT BOTH ENDS.
CARRIER SWITCH SHOULD BE IN SERVICE CONDITION.
SINGLE PHASE & ZONE-1 FAULT ONLY.
1.
2.
3.
4.
4.
5.
6.
7.
5.
6.
MAIN-1/ MAIN-2
ZONE-1 & TWO / THREE PHASE FAULT
REL 521
ACTIVE
START
TRIP
INITIATE MAIN CB GR-A 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB GR-A 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
DISPLAY
REL 316
ACTIVE
START
TRIP
CARRIER SEND
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION COME)
TO DISTURBANCE RECORDER
TO EVENT RECORDER ( SOE/ SCADA )
TO LBB/BFR INITIATION
INITIATE MAIN CB GR-B 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB GR-B 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
DISPLAY
CARRIER SEND
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
TO DISTURBANCE RECORDER
TO LBB/BFR INITIATION
MAIN-1/ MAIN-2
ZONE-2 & 1 / 2 / 3 PHASE FAULT
REL 521
CARRIER SIGNAL
ACTIVE START
RECEIVED
& ZONE-2 STARTER
IS PICKUP CONDITION
TRIP
REL 316
ACTIVE
START
INITIATE TIE CB GR-A 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
DISPLAY
CARRIER SIGNAL
RECEIVED
& ZONE-2 STARTER
IS PICKUP CONDITION
INITIATE MAIN CB GR-A 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
TRIP
TO LBB/BFR INITIATION
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION CAME)
TO DISTURBANCE RECORDER
TO EVENT RECORDER ( SOE/ SCADA )
INITIATE MAIN CB GR-B 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB GR-B 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
DISPLAY
TO DISTURBANCE RECORDER
TO LBB/BFR INITIATION
MAIN-1/ MAIN-2
ZONE- 3/4/5 & 1 / 2 / 3 PHASE FAULT
REL 521
ACTIVE
START
TRIP
INITIATE MAIN CB GR-A 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB GR-A 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
DISPLAY
REL 316
ACTIVE
START
TRIP
TO LBB/BFR INITIATION
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
INITIATE ALARM (ANNUNCIATION CAME)
TO DISTURBANCE RECORDER
TO EVENT RECORDER ( SOE/ SCADA )
INITIATE MAIN CB GR-B 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB GR-B 1-PH TRIP UNITS ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
DISPLAY
TO LBB/BFR INITIATION
INITIATE FLAG RELAY (INTURN FLAG RELAY OPERATES)
TO DISTURBANCE RECORDER
MAIN CB
186 R
CO
CO
REL 521
TO TRIP COIL-1
TO TRIP COIL-2
ACTIVE
START
TO TRIP COIL-1
TO TRIP COIL-2
TRIP
186 Y
186 Y
DISPLAY
TO TRIP COIL-1
TO TRIP COIL-2
TO TRIP COIL-1
TO TRIP COIL-2
186 B
186 B
TO TRIP COIL-1
TO TRIP COIL-2
286 R
CO
TO TRIP COIL-1
TO TRIP COIL-2
CO
286 R
REL 316
TO TRIP COIL-1
TO TRIP COIL-2
ACTIVE
START
TO TRIP COIL-1
TO TRIP COIL-2
TRIP
286 Y
286 Y
DISPLAY
TO TRIP COIL-1
TO TRIP COIL-2
286 B
TO TRIP COIL-1
TO TRIP COIL-2
186 R
TO TRIP COIL-1
TO TRIP COIL-2
286 B
TO TRIP COIL-1
TO TRIP COIL-2
MAIN LBB
INITIATION
1-PH TRIP RELAYS OF
MAIN-1 PROTECTION
RAICA
ACTIVE
START
TRIP
DISPLAY
96 BB
BUSBAR RELAY
86-GR-B
MASTER TRIP RELAY
TIE LBB
INITIATION
86-GR-A
MASTER TRIP RELAY
86-GR-B
MASTER TRIP RELAY
86-GR-A
MASTER TRIP RELAY
INITIATE TIE CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
RAICA
ACTIVE
START
TRIP
DISPLAY
REB 521
ACTIVE
START
TRIP
DISPLAY
TO LBB/BFR INITIATION
FROM LBB/BFR TO BUS BAR TRIPPING
INITIATE ALL CBs TRIP UNITS CONNECTED TO THIS BUS AND OPERATE.
RED 521
ACTIVE
START
TRIP
DISPLAY
TO LBB/BFR INITIATION
FROM LBB/BFR TO BUS BAR TRIPPING
STUB PROTECTION
REL 521
ACTIVE
LINE /AT/F
ISOLATOR
OPENS
START
TRIP
INITIATE TIE CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
DISPLAY
REL 316
ACTIVE
LINE /AT/F
ISOLATOR
OPENS
INITIATE MAIN CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
START
TRIP
INITIATE MAIN CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
DISPLAY
TO DISTURBANCE RECORDER
TEED PROTECTION
RADHA
ACTIVE
START
TRIP
INITIATE MAIN CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
DISPLAY
RADSB
ACTIVE
START
TRIP
INITIATE MAIN CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
DISPLAY
TO DISTURBANCE RECORDER
MAIN-1/ MAIN-2
OVER VOLTAGE STAGE-1
110% OF V
4 SECS FOR
FEEDER-1
5 SECS FOR
FEEDER-2
REL 521
ACTIVE
START
TRIP
INITIATE MAIN CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB & TIE CB AUTO RECLOSURE
DIRECT TRANSFER TRIP-1 CARRIER SEND TO OTHER END
DISPLAY
REL 316
110% OF V
ACTIVE START
4 SECS FOR
FEEDER-1
5 SECS FOR
FEEDER-2
TRIP
INITIATE MAIN CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB 86-GR-a 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB & TIE CB AUTO RECLOSURE
DIRECT TRANSFER TRIP-1 CARRIER SEND TO OTHER END
DISPLAY
TO DISTURBANCE RECORDER
START
TRIP
INITIATE MAIN CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB & TIE CB AUTO RECLOSURE
DIRECT TRANSFER TRIP-1 CARRIER SEND TO OTHER END
120% OF V
20m SECS
DISPLAY
1O% OF V
START
TRIP
DISPLAY
PERMISSIVE TRIPPING
CHANNEL-1
SEND
MAIN-1 PROTECTION :
IT SENDS SIGNAL PARALLEL VIA
PLCC PROTECTION COUPLER PANEL-1 AS A MAIN CHANNEL &
PLCC PROTECTION COUPLER PANEL-2 AS A ALTERNATE
CHANNEL..
CHANNEL-2
SEND
DIRECT TRIPPING
HERE CHANNEL-1 & CHANNEL-2 SIGNALS ARE MAIN & ALTERNATE CHANNEL
1. TIE CB OPEN CONDITION + MAIN CB REMOTE HAND TRIP GIVEN.
2. MAIN CB OPEN CONDITION + TIE CB REMOTE HAND TRIP GIVEN.
3. TIE CB OPEN CONDITION + 87 BUSBAR-1 OPERATED.
4. MAIN CB OPEN CONDITION + 87 BUSBAR-2 OPERATED
(FOR HALF DIA ONLY).
MAIN-2 PROTECTION :
5. MAIN CB 50 LBB/BFR OPERATED.
6. TIE CB 50 LBB/BFR OPERATED.
IT SENDS SIGNAL PARALLEL VIA
PLCC PROTECTION COUPLER PANEL-2 AS A MAIN CHANNEL &
7. 59L1 OVER VOLTAGE STAGE-1 OPERATED.
PLCC PROTECTION COUPLER PANEL-1 AS A ALTERNATE 8. 59L2 OVER VOLTAGE STAGE-2 OPERATED.
9. 87 TEED-1 PROTECTION OPERATED
CHANNEL.
10. 87 TEED-2 PROTECTION OPERATED
CHANNEL-1
RECEIVE
MAIN-1 PROTECTION :
1. TO 86-A MASTER TRIP RELAY (HIGH SPEED TRIP RELAY) FOR MAIN CB.
IT RECEIVES SIGNAL PARALLEL VIA
2. TO 86-A MASTER TRIP RELAY (HIGH SPEED TRIP RELAY) FOR TIE CB.
PLCC PROTECTION COUPLER PANEL-1 AS A MAIN CHANNEL &
PLCC PROTECTION COUPLER PANEL-2 AS A ALTERNATE
CHANNEL.
CHANNEL-2
RECEIVE
MAIN-2 PROTECTION :
1. TO 86-B MASTER TRIP RELAY (HIGH SPEED TRIP RELAY) FOR MAIN CB.
IT RECEIVES SIGNAL PARALLEL VIA
PLCC PROTECTION COUPLER PANEL-2 AS A MAIN CHANNEL &
2. TO 86-B MASTER TRIP RELAY (HIGH SPEED TRIP RELAY) FOR TIE CB.
PLCC PROTECTION COUPLER PANEL-1 AS A ALTERNATE
CHANNEL.
21 M1 REL 521
ABB Network Partner AG
REL531
DIRECT TRIP
SEND CH-1
MAIN CB 86-A
TIE CB 86-A
21 M2
REL 316
ABB Network Partner AG
2
3
4
5
6
10
11
12
13
14
7
8
15
16
CARRIER
PROTECTION
PANEL-1
CARRIER
PROTECTION
PANEL-1
PT SEND
PT SEND
PT RECEIVE
PT RECEIVE
PT SEND
PT SEND
PT RECEIVE
PT RECEIVE
DT SEND
DT SEND
DT RECEIVE
DT RECEIVE
ONE END
CARRIER
PROTECTION
PANEL-2
REC 316*4
OTHER END
CARRIER
PROTECTION
PANEL-2
PT SEND
PT SEND
PT RECEIVE
PT RECEIVE
REL531
DIRECT TRIP
SEND CH-1
MAIN CB 86-A
TIE CB 86-A
21 M2
REL 316
ABB Network Partner AG
2
3
4
5
6
10
11
12
13
14
7
8
15
16
REC 316*4
PT SEND
PT SEND
DIRECT TRIP
SEND CH-2
PT RECEIVE
PT RECEIVE
DT SEND
DT SEND
MAIN CB 86-B
DT RECEIVE
DT RECEIVE
TIE CB 86-B
21 M1 REL 521
DIRECT TRIP
SEND CH-2
MAIN CB 86-B
TIE CB 86-B
DIRECT TRIP
CHANNEL-1
RECEIVED
START
TRIP
INITIATE TIE CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
DISPLAY
85 LO X2
ACTIVE
DIRECT TRIP
CHANNEL-2
RECEIVED.
INITIATE MAIN CB 86-GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
START
TRIP
INITIATE MAIN CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE TIE CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
BLOCK MAIN CB AUTO RECLOSURE
BLOCK TIE CB AUTO RECLOSURE
DISPLAY
TO DISTURBANCE RECORDER
86-GA
MASTER
TRIP /
HIGH
SPEED
TRIP
RELAY
86-GB
MASTER
TRIP /
HIGH
SPEED
TRIP
RELAY
86-GB
MASTER
TRIP /
HIGH
SPEED
TRIP
RELAY
TRIP COIL -2
MAIN CB
TIE CB
TRIP COIL-2
86-GA
MASTER
TRIP /
HIGH
SPEED
TRIP
RELAY
TRIP COIL-1
TRIP COIL -1
86-GA
MASTER
TRIP /
HIGH
SPEED
TRIP
RELAY
86-GB
MASTER
TRIP /
HIGH
SPEED
TRIP
RELAY
TRANSFORMER PROTECTION
(DIFFERENCIAL & REF / 3-PH HZ DIFF PROTECTION)
RADSB
87 T
(LZ)
ACTIVE
START
TRIP
INITIATE 400KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 400KV TIE CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
DISPLAY
64 REF
OR
87 T
(HZ)
RADHD
ACTIVE
START
TRIP
INITIATE 400KV MAIN CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 400KV TIE CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV MAIN CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
DISPLAY
TRANSFORMER PROTECTION
( BACKUP DIRECTIONAL O/L & E/F PROTECTION FOR HV & LV)
RAPDK
67 HV
ABCN
ACTIVE
START
TRIP
INITIATE 400KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 400KV TIE CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
DISPLAY
RAPDK
67 LV
ABCN
ACTIVE
START
TRIP
INITIATE 400KV MAIN CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 400KV TIE CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV MAIN CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
DISPLAY
TRANSFORMER PROTECTION
( OVER FLUX PROTECTION FOR HV & LV)
INITIATE 400KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
RALK
99T HV
ACTIVE
START
INITIATE 400KV TIE CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
TRIP
INITIATE 220KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
DISPLAY
RATUB
99T LV
ACTIVE
START
TRIP
INITIATE 400KV MAIN CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 400KV TIE CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV MAIN CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
DISPLAY
ABB
O/V 1
O/V 2
86-A
MTR/
HSTR
ABB
RALK
O/F- HV
(BAY 2&3 / HV)
(BAY 1&2)
TRIP COIL-1
1-52CB
TRIP COIL-2
BUS-1
86-B
ABB
REL521
MTR/
MAIN-1
HSTR
TRIP COIL-1
2-52CB
TRIP COIL-1
TRIP COIL-2
TRIP COIL-2
BUS-2
3-52CB
(BAY 1&2)
ABB
O/V 1
O/V 2
86-A
MTR/
HSTR
86-B
MTR/
HSTR
86-B
MTR/
HSTR
TRIP COIL-2
86-B
MTR/
HSTR
LV - CB
(BAY LV)
ABB
RATUB
O/F- LV
TRIP COIL-1
86-A
MTR/
HSTR
TRANSFORMER PROTECTION
RXIG 21
51 O/L
ACTIVE
START
TRIP
INITIATE 400KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 400KV TIE CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
DISPLAY
RAEDK1
NDR
ACTIVE
START
TRIP
INITIATE 400KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 400KV TIE CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV MAIN CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INITIATE 220KV TBC CB GR-A 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
DISPLAY
MAIN LBB
INITIATION
86-GR-A
MASTER TRIP RELAY
86-GR-B
MASTER TRIP RELAY
96 BB
BUSBAR RELAY
RAICA
ACTIVE
START
TRIP
INITIATE TIE CB 86-GR-B 3-PH TRIP UNIT ( INTURN IT WILL TRIP 3-POLES )
INTER TRIP TO 220KV LV MAIN CB
INTER TRIP TO 220KV LV TBC CB
CLOSE INTERLOCK OF MAIN CB & TIE CB
DISPLAY
TIE LBB
INITIATION
1-PH TRIP RELAYS OF
MAIN-1 PROTECTION
OF LINE-1(BAY1)
RAICA
ACTIVE
START
TRIP
86-GR-B
MASTER TRIP RELAY
DISPLAY
86-GR-A
MASTER TRIP RELAY
86-GA
MASTER
TRIP /
HIGH
SPEED
TRIP
RELAY
86-GB
MASTER
TRIP /
HIGH
SPEED
TRIP
RELAY
86-GB
MASTER
TRIP /
HIGH
SPEED
TRIP
RELAY
TRIP COIL -2
MAIN CB
TIE CB
TRIP COIL-2
86-GA
MASTER
TRIP /
HIGH
SPEED
TRIP
RELAY
TRIP COIL-1
TRIP COIL -1
BUCHHOLZ TRIP
OL RELAY 51OL
PRD-1 TRIP
HV O/L+E/F PROT 67
PRD-2 TRIP
86 AY
LV O/L+E/F PROT 67
86 BY
186Y1
186B1
186R2
186Y2
186B2
286R1
286Y1
286B1
286R2
286Y2
286B2
86GR-A
86GR-B
96BB
186Y1
186B1
186R2
186Y2
186B2
286R1
286Y1
286B1
286R2
286Y2
286B2
86GR-A
86GR-B
96BB
ISOLATOR
INTERLOCKS
S.NO
ISOLATOR
OPEN/CLOSE
EQUIPMENT-1
EQUIPMENT-2
EQUIPMENT-3
EQUIPMENT-4
BAY - 1
1
1 - 89
ISO
BB189 E
189 AE
189 E
152 CB
1 89 E
ES
189 A
189
--
--
1 89 A
ISO
189 AE
189 E
152 CB
--
1 89 AE
ES
189 A
189
--
--
1 89 L
ISO
189 LE
152 CB
252 CB
--
1 89 LE
ES
189 L
UV RELAY
--
--
2 89 A
ISO
289 BE
289 AE
252 CB
--
2 89 AE
ES
289 B
289 A
--
--
2 89 B
ISO
289 BE
289 AE
252 CB
--
10
2 89 BE
ES
289 B
289 A
--
--
11
3 89
ISO
BB289 E
389 AE
389 E
352 CB
12
3 89 E
ES
389 A
389
--
--
13
3 89 A
ISO
389 AE
389 E
352 CB
--
14
3 89 AE
ES
389 A
389
--
--
15
3 89 T
ISO
LV89 E2
389 TE
252 CB
352 CB
16
3 89 TE
ES
389 T
LV89 T
--
--
BAY - 2
BAY - 3
BB189E
1-89AE
1-89E
1-52CB
1-52CB
1-89AE
1-89E
1-52CB
1-89LE
2-52CB
1-89
1-89A
1-89
1-89A
1-89L
U/V RLY
OPEN
OPEN
OPEN
& OPERATION
1-89
1-89E
OPEN
1-89AE
OPEN
2-89AE
OPEN
OPEN
& OPERATION
1-89A
3-89E
3-89AE
OPEN
OPEN
OPEN
2-89BE
& OPERATION
86GR-A
1-89L
86GR-B
96BB
OPEN
OPEN
&
&
86GR-A
OPERATION
1-89AE
86GR-A
86GR-B
OPEN
ACTED
1-89E
86GR-B
OPEN
OPEN
OPERATION
&
OPERATION
1-89LE
96BB
2-89A
2-52CB
2-89AE
2-89BE
OPEN
OPEN
OPEN
2-89B
& OPERATION
2-89A
2-89A
2-89B
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
CLOSE
OPEN
LOCAL
CLOSE
& 1-52CB
RESET
& 2-52CB
REMOTE
CLOSE
& 1-52CB
REMOTE
CLOSE
& 2-52CB
RESET
OPEN
OPEN
OPEN
OPEN
&
REMOTE
CLOSE
OPEN
3-89A
OPERATION
&
& OPERATION
2-89BE
OPEN
OPEN
OPEN
3-89T
OPERATION
OPEN
&
OPEN
OPEN
3-89E
3-89AE
3-52CB
& OPERATION
2-89AE
OPEN
OPEN
& 3-52CB
RESET
RESET
&
LOCAL
CLOSE
RESET
RESET
3-89
OPERATION
LOCAL
CLOSE
RESET
RESET
OPEN
3-89TE
OPERATION
OPERATION
OPERATION
2-52CB
2-89AE
2-89BE
&
&
&
BB289E
3-89AE
3-89E
3-52CB
3-52CB
3-89AE
3-89E
3-52CB
3-89TE
2-52CB
LV89E2
OPEN
OPEN
3-89
3-89A
OPEN
OPEN
OPEN
OPEN
3-89
3-89A
3-89T
LV89T
OPEN
OPEN
OPEN
& OPERATION
2-89B
86 GR-A
86 GR-B
+ VE
T N C
CB REMOTE CLOSE
MAIN CB
21M1 AR
21M2 AR
86 GR-A
86 GR-B
+ VE
T N C
TIE
AR
TIE CB
CB REMOTE CLOSE
B.
1.
2.
3.
4.
ADVANTAGES:
DISADVANTAGES
EQUIPMENT
CONVENTIONAL
SYSTEM
1.
CIRCUIT
BREAKERS
1 No
CURRENT
TRANSFORMERS
2.
3 CT METHOD
% INCREASE
IN COST
3 Nos
50%
HALF DIA
% INCREASE
(FOR 1 FEEDER)
IN COST
2 Nos
100%
50%
2 Sets
100%
4 Sets
100%
2 Sets
100%
5 CT METHOD
5 Sets
125%
3 Sets
200%
6 CT METHOD
6 Sets
200%
3 Sets
200%
3 SETS
30%
2 SETS
30%
4 CT METHOD
1 Set
I SET
3.
CONTROL &
RELAY PANELS
4.
BAY
MARSHALLING
BOXES
1 No
3 Nos
50%
2 Nos
30%
5.
CONTROL
CABLES
8 KM
30 KM
100%
20 KM
150%
NORMALLY EXTRA PANEL IS TIE BAY PANEL. IT IS ARROUND 30% COST OF MAIN
PANEL. BECAUSE IT IS NOT HAVING PROTECTION RELAYS( M-1 & M-2 AND OTHER
RELAYS) . ONLY TIE CB TRIPPING RELAYS & ASSOCIATED RELAYS(A/R +LBB).
OTHER
INFORMATION
REGARDING
RELAYS AND
TESTING
EQUIPMENT
PREPARED BY
GOPALA KRISHNA PALEPU
ADE/MRT(PROTECTION)
ABB RELAYS
ABB Network Partner AG
REL 521
REL 316*4
10
11
12
13
14
15
16
C
E
EE
ABB Relays
ABB Network Partner AG
REL 512
c
E
ALSTOM RELAYS
P445
P443
P437
E-PAC
P442
GE MULTILIN
RELAYS
SIEMENS
RELAYS
SEL RELAYS
ENABLED
TARGET
RESET
TRIP
IA =250.10 A
IB =250.10 A
IC =250.10 A
VAB =400.0 KV
VBC =400.0 KV
VCA =400.0 KV
ESC
ENT
INST
TIME
COMM
SOTF
ZONE 1
ZONE 2
ZONE 3
ZONE 4
PH - A
PH - B
PH - C
GND
50
51
79 RESET
79 LOCKOUT
2ENABLED
3
ZONE
TRIP
EN
FAULT TYPE
51
MC
ENABLED
COMM
ENABLED
RECLOSE
ENABLED
ALT
SETTINGS
CB
CLOSED
RELAY
TEST
CB
OPEN
SEL- 321- 5 - 2
TARGET
RESET
TRIP
SPT
ENABLED
PROTECTION
AUTOMATION
CONTROL
50
O/C
SEL
SEL- 421
PROTECTION
AUTOMATION
CONTROL
SEL
RELAY HARDWARE
16 / 32 BIT
PC
MODEM
IRIG-B
RE/CC
NORMALLY
400KV
RELAYS
SUPPLIED
WITH
CONFIGUARATION/HARDWARE
1. MIN 4Nos MAX 8Nos COMMAND/TRIP OUTPUTS
2. MIN 24Nos SIGNAL OUTPUTS
3. MIN 14 LED INDICATIONS
4. MIN 24 BINARY INPUTS
FOLLOWING
MAIN-2
REL 316
REL 512
MICOM P437
E-PAC 3000,
OPTIMHO
CURVES
T/F PROTECTION
ET
DIFFERENTIAL
RET 521 / 670
RET 316
DIR O/L,E/F
REL 505
REX 521
QUAD
/
MHO
MICOM P633
KBCH/ MBCH
MICOM P141
MICOM P127
AREVA
(ALSTOM)
MAIN-1
REL 521
REL 670
MICOM
P443/P444/
P442/P445
SIEMENS
( SIPROTEC )
SIPROTEC
7SA62/3
QUAD/
MHO
SIPROTEC
7SA522
QUAD
/
MHO
7UT 613/ 2
7UT 513/ 2
7SJ 62/3/4/5
7SJ 52/3/4/5
SEL
SEL 421
QUAD/
MHO
SEL 321
SEL 311C
QUAD
/
MHO
SEL 387
SEL 351
GE
MULTILIN
D-60,
ALPS
QUAD/
MHO
L-60/L-90
D-30
QUAD
/
MHO
T-35 / T-60
SR 7465
F-60
SR 750/60
EASUN
REYROLL
THR 4 PE 24
MHO
THR 4 PE 16
THR 3 PE 18
MHO
---
MIT
NXT
PHASE
L-PRO
QUAD/
MHO
L-PRO
LENS/
TOMAT0
T-PRO
F-PRO
VA TECH
REYROLL
OHMEGA 402
QUAD/
MHO
OHMEGA 311/308
QUAD/
MHO
DUOBIAS M
ARGUS
ABB
QUAD
QUAD/
MHO
QUAD
/BULL
400KV SUBSTATION
MAMIDIPALLY (HYDERABAD)
2.
NURNOOR (KURNOOL)
3.
KALAPAKA (VISHAKHAPATNAM)
4.
VEMAGIRI (RAJHAMUNDRY)
5.
CAPACITY
FEEDERS
(2 + 1**) X
315 MVA
(2 + 1**) X
315 MVA
2 X 315 MVA
1. SRISAILAM 1&2
2. GHANAPUR (PGCIL)
3. KHAMMAM 1&2(PGCIL)
4. YEDDUMAILARAM 1&2**
1. SRISAILAM
2. GHANAPUR (PGCIL)
3. GOOTY (PGCIL)
4. NARASARAOPETA**
2 X 315 MVA
1. KALAPAKA 1&2
2. GAJUWAKA 1&2 (PGCIL)*
3. NUNNA 1&2 (PGCIL)*
4. GUNTUR 1&2*
1. TALLAPALLY
2. RAICHUR
2. KADAPA
6.
CHITTOR(VEPANJIR)
7.
NELLORE(MANUBOLU)
(1 + 2**) X
315 MVA
(1 + 1**) X
315 MVA
2 X 315 MVA
8.
DICHPALLY* (NIZAMABAD)
2 X 315 MVA
1. RAMAGUNDAM
9.
GAJWEL* (MEDAK)
2 X 315 MVA
1. RAMAGUNDAM
3. BTPS 1&2**
2. GHANAPUR
4. YEDDUMAILARAM 1&2**
10.
NARASARAOPETA* (GUNTUR)
2 X 315 MVA
1. SRISAILAM 1&2
2. NUNNA 1&2
3. VEMAGIRI 1&2
4. KURNOOL**
11.
MALKARAM** (SECUNDRABAD)
2 X 315 MVA
1. RAMAGUNDAM
2. NAKEREKALLU 1&2**
2. GHANAPUR
12.
3 X 315 MVA
1. GAJWEL 1&2
2. MAMIDIPALLY 1&2
13.
NAKEREKALLU** (NALGONDA)
2 X 315 MVA
1. VTPS 1&2
2. MALKARAM 1&2
400KV SUBSTATION
1.
RAMAGUNDAM(NTPC)
2.
GHANAPUR (HYDERABAD)
3.
GAJUWAKA (VISHAKHAPATNAM)
4.
NUNNA (VIJAYAWADA)
5.
TALLAPALLY
(NAGARJUNA SAGAR)
6.
BUDIDAMPADU (KHAMMAM)
7.
GOOTY
8.
CHINAKAMPALLY
9.
NELLORE(MANUBOLU)
10.
MULUGU* (WARANGAL)
CAPACITY
2 X 200 MVA
2 X 250 MVA
1 X 315 MVA
3 X 315 MVA
(1 + 1*) X
315 MVA
(1 + 1*) X
315 MVA
3 X 315 MVA
(1 + 1*) X
315 MVA
(1 + 1**) X
315 MVA
(1 + 1**) X
315 MVA
2 X 315 MVA
FEEDERS
1. GHANAPUR 1&2
2. GAJWEL(GHNP3)
3. MALKARAM(GHNP4)
4. TALLAPALLY 1&2
5. DICHPALLY*
6. KHAMMAM (WRNGL)
7. CHANDRAPUR 1&2
1. RAMAGUNDAM 1&2
2. MAMIDIPALLY
3. GAJWEL(RMGNDM3)
4. NAGARJUNA SAGAR
5. KURNOOL
6. MALKARAM(RMGNDM4)
1. NUNNA
2. KALAPAKA1&2
3. VEMAGIRI 1&2
4. JAIPUR(HVDC)
1. GAJUWAKA
2. SRISAILAM 1&2(NRSPT)
3. VEMAGIRI 1&2
4. VEMAGIRI 3&4(VTPS)
5. KHAMMAM
6. NELLORE 1&2
1. RAMAGUNDAM 1&2
2. GHANAPUR
3. MAHABOOBNAGAR
4. GOOTY
5. CHINAKAMPALLY 1&2
1. RAMAGUNDAM (WRGL)
2. NUNNA
4. MAMIDIPALLY 1&2
5. KALAPAKA 1&2
1. TALLAPALLY
2. SOMANAHALLY
3. KURNOOL
4. NEELAMANGALA
5. RAICHUR 1&2*
1. TALLAPALLY 1&2
2. SOMANAHALLY
3. KOLAR
4. CHITTOR
1. NUNNA 1&2
2. CHENNAI(ALAMATHI)
1&2
1. RAMAGUNDAM
2. KHAMMAM
3. BTPS(KTPS) 1&2
1. AT RAMAGUNDAM 1NO 315 MVA TRANSFORMER IS TO BE REMOVED AND DICHPALLY FEEDER IS PLANNED TO CONNECT.
2. RAMAGUNDAM TO GHANAPUR CKT-1 IS PROPOSED TO TAKE LILO AT GAJWEL (APTRANSCO) SS.
3. RAMAGUNDAM TO GHANAPUR CKT-2 IS PROPOSED TO TAKE LILO AT MALKARAM (APTRANSCO) SS.
4. GAJUWAKA TO NUNNA CKT-2&3 IS PROPOSED TO TAKE LILO AT VEMAGIRI (APTRANSCO) SS.
5. RAMAGUNDAM TO KHAMMAM CKT IS PROPOSED TO TAKE LILO AT WARANGAL SS.
400KV NETWORK IN AP
GUNTUR
NELLORE
ALAMETHI
/ CHENNAI
NKRKL
SRISAILAM
KURNOOL
CHITTOR
GOOTY
RAICHUR
MAMIDIPALLY
CHINAKAMPALLY
CHENNAI
KHAMMAM
CHANDRAPUR
(MAHARASTRA)
KOLAR
VTPS
YEDDUMAILARAM
NUNNA
GHANAPUR
BANGALORE
IPP2
VEMAGIRI
MBNGR
IPP1
TALLAPALLY
BANGALORE
IPP4
DICHPALLY
MALKARAM
IPP3
BTPS
GAJWEL
KALAPAKA
WARANGAL
HVDC
JAIPUR
RAMAGUNDAM
SIMHADRI
GAJUWAKA
315MVA,
400/220KV
AUTO
TRANSFORMER-I
315MVA,
400/220KV
AUTO
TRANSFORMER-II
GUNTUR I
GUNTUR II
KOPCL II
VPGCL I
VPGCL II KOPCL I
GMR VASAVI GMR VASAVI KONASEEMA KONASEEMA
GVK EXT I
FUTURE II
PHES
GVK EXT II
DISPLAY