Vous êtes sur la page 1sur 2

62LCN/62LCT

92LCN/92LCT

15/25kV Deadbreak Elbow


Product Data Sheet
The Richards 15/25kV Deadbreak Elbow
is a medium voltage cable accessory
used to terminate/splice cables and
equipment rated up to 25kV Class.
Our Elbow is molded in the USA from
EPDM compounds produced in-house
by our polymer production division. The
Deadbreak T-body is fully-shielded,
submersible and available with or
without a capacitive test point.
A variety of accessories are available
for insulating, testing, grounding and
paralleling circuits. The current-rating
of the Deadbreak Elbow housing is
determined by the metallic components
utilized to make the connection. If
all-copper components are used, the
Deadbreak Elbow assembly has a 900A
rating. Otherwise, the assembly is rated
for 600A.

Basic Dimensions
Features
12.57in
(319.35mm)

<<100% EPDM Composition


<<Injection Molded & Peroxide-Cured

10.88in
(276.23mm)

<<Made in the USA


<<Fully-Shielded/Deadfront
<<Submersible
<<Optional Capacitive Test Point

8.35in
(212.09mm)

Richards Manufacturing, Inc. | 517 Lyons Avenue, Irvington, NJ 07111 | 973.371.1771 | www.Richards-Mfg.com

3.58in
(91.03mm)

0615

62LCN/62LCT
92LCN/92LCT

15/25kV Deadbreak Elbow


Detail View
Installation
Stack Height = 1/2in

Deadbreak Elbow 62LCN/LCT installation is covered by:


RP-II-62LCN
Related Products
P625HIP-STUD

P925HIP-STUD

Aluminum Threaded Stud

Copper Threaded Stud

P6AL-X

P9CU-X

Aluminum Compression Connector

Copper Compression
Connector

IEEE 386
Interface 11

P7ALCU-X
Copper-Top Compression
Connector

Deadbreak Elbow
Housing

(15/25kV Class
Interface)

Lug
(shown crimped)

Optional Test Point


(shown without)

P625CA-W
Cable Adapter

P625HIP

P925HIP

Aluminum Insulating Plug

Copper Insulating Plug

Cable Adapter
(IEEE 386 Interface 17)

Cable Conductor

Production Testing
IEEE requires a Partial Discharge test and choice between AC
withstand and Impulse.

Product Ratings
Voltage Class, Phase-to-Phase

15kV 25kV

Richards runs 3/3 tests on ALL Medium Voltage products


governed by IEEE 386.

Maximum Voltage Rating (phase to ground)


Corona Voltage Level (partial discharge extinction voltage)

19kV

100% Routine Electrical Test:

AC Withstand, 1 minute

40kV

<<Partial Discharge - 22kV CEV


<<AC Withstand - 42kV
<<Impulse Withstand - 162kV BIL
Exceeds IEEE 386 required minimum test level

15.2kV

Impulse-Withstand Voltage (BIL)

125kV BIL

Continuous Current
Aluminum

600A

Copper

900A

Short-Time Current
Richards Deadbreak Elbows are designed to allow for production
testing at 200kV BIL. For more information see our 200kV BIL
Product Data Sheets or contact the factory.

Aluminum

25kA, 10c. and 10kA, 3s

Copper

40kA, 10c. and 10kA, 3s

The 15/25kV Deadbreak Elbow is qualified to the following industry standards:


<<IEEE Std 386: For Separable Insulated Connector Systems
<<ANSI C119.4: For Electric Connectors
<<IEEE Std 592: For Exposed Semiconducting Shields

Richards Manufacturing, Inc. | 517 Lyons Avenue, Irvington, NJ 07111 | 973.371.1771 | www.Richards-Mfg.com

0615