Vous êtes sur la page 1sur 42

Vietcombank - Chiller Plant Sizing for Tender

1/04/2010

Plant total load


7860.5 kW
*
Plant total load with diversity
7074.5 kW
apply further 10% diversity for people, lighting and equipment
Data centers load
1230.6 kW
allow for 350Tr; no diversity on data centres loads
Data centers load
0.6153 kW/sqm
Data center area
2000 sqm
estimate
Office average load
0.181 kW/sqm
Office load@2000 sqm
362.2 kW
Plant sizing revise =Plant total load with diversity-(Office load@2000sqm)+(Data center load@2000sqm )
Plant sizing revise =
7943 kW
3 main chillers =
2 standby/low load chillers =

2648 kW
1324 kW

756 Tr
378 Tr

say 750 Tr
say 375 Tr

* Coincident air system cooling loads (includes solar/facade diversity) from E-20 Cal (R1)*
* Facade glass U=1.6W/m2K; SC=0.5

P:\Projects\2009 MIS\bkk0906000 - Vietcombank, PCP\1 - Eng\02 - Calcs & Design Data\02 - AC\100326 Facade Glass Performance and Cooling Load Study.xls

Cooling Plant Sizing Summary for VCB Plant(8.00-18.00)


VietcomBank
eec

03/25/2010
04:09PM

1. Plant Information:
Plant Name .................................................................. VCB Plant(8.00-18.00)
Plant Type .................................................................. Generic Chilled Water
Design Weather ................................................... Ho Chi Minh City, Vietnam
2. Cooling Plant Sizing Data:
Maximum Plant Load ............................................................................ 7860.5 kW
Load occurs at ................................................................................. Mar 1500
m/kW ......................................................................................................... 5.6 m/kW
Floor area served by plant .................................................................. 44042.1 m
3. Coincident Air System Cooling Loads for Mar 1500

Air System Name


00-B1-01
00-B1-02
00-G-A-01
00-G-A-02
00-G-A-03
00-M-A-01
00-M-A-02
L-01-A-01
L-01-A-02
L-02-A-01
L-02-A-02
L-03- A-01
L-03- A-02
L-04-A-01
L-04-A-02
L-05-A-01
L-05-A-02
L-07-A-01
L-07-A-02
L-08to11-A-01
L-08to11-A-02
L-12to20-A-01
L-12to20-A-02
L-21-A-01
L-21-A-02
L-22to23-A-01
L-22to23-A-02
L-24to25-A-01
L-24to25-A-02
L-26to28-A-01
L-26to28-A-02
L-29to30-A-01
L-29to30-A-02
L-31to32-A-01
L-31to32-A-02
L-33to34-A-01
L-33to34-A-02
00-B1-03
L8-L32 Tenant Server Room
00-B1-04
00-G-A-04

Mult.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
4
9
9
1
1
2
2
2
2
3
3
2
2
2
2
2
2
1
25
1
1

System
Cooling
Coil Load
( kW )
15.8
8.5
33.9
17.9
150.4
142.0
173.8
134.6
125.1
133.5
114.5
133.5
133.1
133.0
128.9
131.5
135.7
65.2
64.6
98.9
96.8
98.9
97.4
98.9
96.1
97.6
95.5
85.4
86.5
86.3
86.3
85.9
86.7
80.3
79.6
80.3
79.6
85.2
29.1
91.6
2.3

System loads are for coils whose cooling source is ' Chilled Water ' or ' Any ' .

Hourly Analysis Program v.4.2

Page 1 of 1

Air System Sizing Summary for 00-B1-01


Project Name: VietcomBank
Prepared by: OO

03/26/2010
09:29AM

Air System Information


Air System Name .......................................... 00-B1-01
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 126.0 m?
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 13.4
Sensible coil load .................................................. 12.6
Coil L/s at Mar 1400 ............................................ 1000
Max block L/s ...................................................... 1000
Sum of peak zone L/s .......................................... 1000
Sensible heat ratio .............................................. 0.942
m?/kW ................................................................... 9.4
W/m? .................................................................. 106.2
Water flow @ 7.0 ?K rise ...................................... 0.46

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Mar 1400


OA DB / WB ................................................... 34.9 / 25.1
Entering DB / WB ........................................... 24.7 / 17.6
Leaving DB / WB ............................................ 14.2 / 13.5
Coil ADP .................................................................. 13.0
Bypass Factor ........................................................ 0.100
Resulting RH ............................................................... 51
Design supply temp. ................................................. 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

?C
?C
?C
?C
%
?C
OK
?K

Precool Coil Sizing Data


Total coil load ........................................................ 2.1
Sensible coil load ................................................... 1.2
Coil L/s at Mar 1500 ............................................... 49
Max coil L/s ............................................................ 49
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 ?K rise ...................................... 0.07

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 ?C
Entering DB / WB ........................................... 35.1 / 25.2 ?C
Leaving DB / WB ............................................ 15.0 / 14.3 ?C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s ..................................................... 1000 L/s
Standard L/s ......................................................... 998 L/s
Actual max L/(s-m?) ............................................. 7.94 L/(s-m?)

Fan motor BHP ........................................................ 1.86 BHP


Fan motor kW .......................................................... 1.39 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................... 49 L/s
L/(s-m?) ................................................................ 0.39 L/(s-m?)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.41 l/s/person

Page 1 of 1

Air System Sizing Summary for 00-B1-03


Project Name: VietcomBank
Prepared by: OO

03/26/2010
09:40AM

Air System Information


Air System Name .......................................... 00-B1-03
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 723.0 m?
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 68.1
Sensible coil load .................................................. 63.3
Coil L/s at Mar 1500 ............................................ 6000
Max block L/s ...................................................... 6000
Sum of peak zone L/s .......................................... 6000
Sensible heat ratio .............................................. 0.929
m?/kW .................................................................. 10.6
W/m? .................................................................... 94.2
Water flow @ 7.0 ?K rise ...................................... 2.33

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2
Entering DB / WB ........................................... 24.2 / 18.2
Leaving DB / WB ............................................ 15.5 / 14.9
Coil ADP .................................................................. 14.5
Bypass Factor ........................................................ 0.100
Resulting RH ............................................................... 56
Design supply temp. ................................................. 15.9
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

?C
?C
?C
?C
%
?C
OK
?K

Precool Coil Sizing Data


Total coil load ....................................................... 18.7
Sensible coil load .................................................. 10.6
Coil L/s at Mar 1500 ............................................. 439
Max coil L/s .......................................................... 439
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 ?K rise ...................................... 0.64

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 ?C
Entering DB / WB ........................................... 35.1 / 25.2 ?C
Leaving DB / WB ............................................ 15.0 / 14.3 ?C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s ..................................................... 6000 L/s
Standard L/s ........................................................ 5987 L/s
Actual max L/(s-m?) ............................................. 8.30 L/(s-m?)

Fan motor BHP ...................................................... 11.18 BHP


Fan motor kW .......................................................... 8.33 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 439 L/s
L/(s-m?) ................................................................ 0.61 L/(s-m?)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.95 l/s/person

Page 1 of 1

Air System Sizing Summary for 00-B1-04


Project Name: VietcomBank
Prepared by: OO

03/26/2010
09:44AM

Air System Information


Air System Name .......................................... 00-B1-04
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones ........................................................... 1


Floor Area .............................................................. 780.0 m?
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 70.9
Sensible coil load .................................................. 65.5
Coil L/s at Mar 1200 ............................................ 6300
Max block L/s ...................................................... 6300
Sum of peak zone L/s .......................................... 6300
Sensible heat ratio .............................................. 0.923
m?/kW .................................................................. 11.0
W/m? .................................................................... 90.9
Water flow @ 7.0 ?K rise ...................................... 2.42

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Mar 1200


OA DB / WB ................................................... 33.2 / 24.7
Entering DB / WB ........................................... 24.1 / 18.2
Leaving DB / WB ............................................ 15.5 / 14.9
Coil ADP .................................................................. 14.6
Bypass Factor ........................................................ 0.100
Resulting RH ............................................................... 56
Design supply temp. ................................................. 15.8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

?C
?C
?C
?C
%
?C
OK
?K

Precool Coil Sizing Data


Total coil load ....................................................... 20.4
Sensible coil load .................................................. 11.6
Coil L/s at Mar 1500 ............................................. 478
Max coil L/s .......................................................... 478
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 ?K rise ...................................... 0.70

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 ?C
Entering DB / WB ........................................... 35.1 / 25.2 ?C
Leaving DB / WB ............................................ 15.0 / 14.3 ?C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s ..................................................... 6300 L/s
Standard L/s ........................................................ 6286 L/s
Actual max L/(s-m?) ............................................. 8.08 L/(s-m?)

Fan motor BHP ...................................................... 11.73 BHP


Fan motor kW .......................................................... 8.75 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 478 L/s
L/(s-m?) ................................................................ 0.61 L/(s-m?)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.90 l/s/person

Page 1 of 1

Air System Sizing Summary for 00-G-A-01


Project Name: VietcomBank
Prepared by: eec

03/25/2010
04:04PM

Air System Information


Air System Name ........................................ 00-G-A-01
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 105.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 36.4
Sensible coil load .................................................. 32.8
Coil L/s at Jan 1500 ............................................. 2276
Max block L/s ...................................................... 2276
Sum of peak zone L/s .......................................... 2276
Sensible heat ratio .............................................. 0.901
m/kW .................................................................... 2.9
W/m .................................................................. 346.4
Water flow @ 7.0 K rise ....................................... 1.24

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Jan 1500


OA DB / WB ................................................... 33.4 / 24.6
Entering DB / WB ........................................... 25.5 / 17.7
Leaving DB / WB ........................................... 13.5 / 12.8
Coil ADP .................................................................. 12.2
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 48
Design supply temp. ................................................ 13.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Supply Fan Sizing Data


Actual max L/s ..................................................... 2276 L/s
Standard L/s ........................................................ 2271 L/s
Actual max L/(s-m) ............................................ 21.67 L/(s-m)

Fan motor BHP ........................................................ 2.12 BHP


Fan motor kW .......................................................... 1.58 kW
Fan static .................................................................. 375 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 119 L/s
L/(s-m) ................................................................. 1.13 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.25 l/s/person

Page 1 of 1

Air System Sizing Summary for 00-G-A-02


Project Name: VietcomBank
Prepared by: eec

03/25/2010
04:04PM

Air System Information


Air System Name ........................................ 00-G-A-02
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area ................................................................ 98.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 18.6
Sensible coil load .................................................. 17.7
Coil L/s at Dec 1500 ............................................ 1331
Max block L/s ...................................................... 1331
Sum of peak zone L/s .......................................... 1331
Sensible heat ratio .............................................. 0.951
m/kW .................................................................... 5.3
W/m .................................................................. 189.4
Water flow @ 7.0 K rise ....................................... 0.63

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Dec 1500


OA DB / WB ................................................... 32.9 / 24.1
Entering DB / WB ........................................... 24.6 / 17.2
Leaving DB / WB ........................................... 13.6 / 12.9
Coil ADP .................................................................. 12.4
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 48
Design supply temp. ................................................ 13.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ........................................................ 2.5
Sensible coil load ................................................... 1.4
Coil L/s at Mar 1500 ............................................... 59
Max coil L/s ............................................................ 59
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.09

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s ..................................................... 1331 L/s
Standard L/s ........................................................ 1328 L/s
Actual max L/(s-m) ............................................ 13.58 L/(s-m)

Fan motor BHP ........................................................ 1.24 BHP


Fan motor kW .......................................................... 0.92 kW
Fan static .................................................................. 375 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................... 59 L/s
L/(s-m) ................................................................. 0.60 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 5.02 l/s/person

Page 1 of 1

Air System Sizing Summary for 00-G-A-03


Project Name: VietcomBank
Prepared by: eec

03/25/2010
04:04PM

Air System Information


Air System Name ........................................ 00-G-A-03
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 800.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 131.5
Sensible coil load ................................................ 120.8
Coil L/s at May 1400 ............................................ 9213
Max block L/s ...................................................... 9213
Sum of peak zone L/s .......................................... 9213
Sensible heat ratio .............................................. 0.919
m/kW .................................................................... 6.1
W/m .................................................................. 164.4
Water flow @ 5.6 K rise ....................................... 5.66

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................ May 1400


OA DB / WB ................................................... 33.8 / 24.5
Entering DB / WB ........................................... 24.6 / 17.4
Leaving DB / WB ........................................... 13.7 / 13.0
Coil ADP .................................................................. 12.5
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 14.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 26.0
Sensible coil load .................................................. 14.8
Coil L/s at Mar 1500 ............................................. 610
Max coil L/s .......................................................... 610
Sensible heat ratio .............................................. 0.568
Water flow @ 5.6 K rise ....................................... 1.12

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s ..................................................... 9213 L/s
Standard L/s ........................................................ 9193 L/s
Actual max L/(s-m) ............................................ 11.52 L/(s-m)

Fan motor BHP ...................................................... 17.16 BHP


Fan motor kW ........................................................ 12.80 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 610 L/s
L/(s-m) ................................................................. 0.76 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.12 l/s/person

Page 1 of 1

Air System Sizing Summary for 00-G-A-04


Project Name: VietcomBank
Prepared by: eec

03/25/2010
04:04PM

Air System Information


Air System Name ........................................ 00-G-A-04
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area ................................................................ 12.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 2.1
Sensible coil load ................................................... 2.0
Coil L/s at Mar 1400 ............................................. 157
Max block L/s ....................................................... 157
Sum of peak zone L/s ........................................... 157
Sensible heat ratio .............................................. 0.946
m/kW .................................................................... 5.8
W/m .................................................................. 171.8
Water flow @ 7.0 K rise ....................................... 0.07

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Mar 1400


OA DB / WB ................................................... 34.9 / 25.1
Entering DB / WB ........................................... 24.2 / 17.2
Leaving DB / WB ........................................... 13.8 / 13.2
Coil ADP .................................................................. 12.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 13.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ........................................................ 0.3
Sensible coil load ................................................... 0.2
Coil L/s at Mar 1500 ................................................. 7
Max coil L/s .............................................................. 7
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.01

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s ...................................................... 157 L/s
Standard L/s ......................................................... 156 L/s
Actual max L/(s-m) ............................................ 13.05 L/(s-m)

Fan motor BHP ........................................................ 0.15 BHP


Fan motor kW .......................................................... 0.11 kW
Fan static .................................................................. 375 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 7 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.90 l/s/person

Page 1 of 1

Air System Sizing Summary for L-01-A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ........................................ L-01-A-01
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 859.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 115.4
Sensible coil load ................................................ 106.8
Coil L/s at Feb 1600 ............................................ 7561
Max block L/s at Jan 1600 ................................... 8581
Sum of peak zone L/s .......................................... 8581
Sensible heat ratio .............................................. 0.925
m/kW .................................................................... 7.4
W/m .................................................................. 134.4
Water flow @ 7.0 K rise ....................................... 3.95

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Feb 1600


OA DB / WB ................................................... 34.3 / 25.1
Entering DB / WB ........................................... 24.7 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 22.3
Sensible coil load .................................................. 12.6
Coil L/s at Mar 1500 ............................................. 522
Max coil L/s .......................................................... 522
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.76

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Jan 1600 .................................. 8581 L/s
Standard L/s ........................................................ 8562 L/s
Actual max L/(s-m) .............................................. 9.99 L/(s-m)

Fan motor BHP ...................................................... 15.98 BHP


Fan motor kW ........................................................ 11.92 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 522 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.94 l/s/person

Page 1 of 1

Air System Sizing Summary for L-01-A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ........................................ L-01-A-02
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 743.3 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 107.3
Sensible coil load ................................................ 100.0
Coil L/s at Apr 1500 ............................................. 7050
Max block L/s at Apr 1500 ................................... 7833
Sum of peak zone L/s .......................................... 7833
Sensible heat ratio .............................................. 0.933
m/kW .................................................................... 6.9
W/m .................................................................. 144.3
Water flow @ 7.0 K rise ....................................... 3.67

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1500


OA DB / WB ................................................... 35.1 / 25.2
Entering DB / WB ........................................... 24.8 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 19.1
Sensible coil load .................................................. 10.8
Coil L/s at Mar 1500 ............................................. 447
Max coil L/s .......................................................... 447
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.65

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Apr 1500 .................................. 7833 L/s
Standard L/s ........................................................ 7815 L/s
Actual max L/(s-m) ............................................ 10.54 L/(s-m)

Fan motor BHP ...................................................... 14.59 BHP


Fan motor kW ........................................................ 10.88 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 447 L/s
L/(s-m) ................................................................. 0.60 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.99 l/s/person

Page 1 of 1

Air System Sizing Summary for 00-M-A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ........................................ 00-M-A-01
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 791.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 119.0
Sensible coil load ................................................ 105.9
Coil L/s at Apr 1600 ............................................. 7474
Max block L/s ...................................................... 7474
Sum of peak zone L/s .......................................... 7474
Sensible heat ratio .............................................. 0.890
m/kW .................................................................... 6.6
W/m .................................................................. 150.4
Water flow @ 7.0 K rise ....................................... 4.07

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1600


OA DB / WB ................................................... 34.9 / 25.1
Entering DB / WB ........................................... 24.8 / 17.3
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 48
Design supply temp. ................................................ 12.8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 24.4
Sensible coil load .................................................. 13.9
Coil L/s at Mar 1500 ............................................. 573
Max coil L/s .......................................................... 573
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.84

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s ..................................................... 7474 L/s
Standard L/s ........................................................ 7458 L/s
Actual max L/(s-m) .............................................. 9.45 L/(s-m)

Fan motor BHP ...................................................... 13.92 BHP


Fan motor kW ........................................................ 10.38 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 573 L/s
L/(s-m) ................................................................. 0.72 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.27 l/s/person

Page 1 of 1

Air System Sizing Summary for 00-M-A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ........................................ 00-M-A-02
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area .............................................................. 782.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 153.9
Sensible coil load ................................................ 137.7
Coil L/s at Jan 1500 ............................................. 9526
Max block L/s ...................................................... 9526
Sum of peak zone L/s .......................................... 9526
Sensible heat ratio .............................................. 0.895
m/kW .................................................................... 5.1
W/m .................................................................. 196.8
Water flow @ 7.0 K rise ....................................... 5.26

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Jan 1500


OA DB / WB ................................................... 33.4 / 24.6
Entering DB / WB ........................................... 24.8 / 17.2
Leaving DB / WB ........................................... 12.8 / 12.1
Coil ADP .................................................................. 11.5
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 47
Design supply temp. ................................................ 12.8
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 27.6
Sensible coil load .................................................. 15.7
Coil L/s at Mar 1500 ............................................. 647
Max coil L/s .......................................................... 647
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.94

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s ..................................................... 9526 L/s
Standard L/s ........................................................ 9505 L/s
Actual max L/(s-m) ............................................ 12.18 L/(s-m)

Fan motor BHP ...................................................... 17.74 BHP


Fan motor kW ........................................................ 13.23 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 647 L/s
L/(s-m) ................................................................. 0.83 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 3.92 l/s/person

Page 1 of 1

Air System Sizing Summary for L-02-A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ........................................ L-02-A-01
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 851.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 113.7
Sensible coil load ................................................ 105.2
Coil L/s at Feb 1600 ............................................ 7445
Max block L/s at Jan 1600 ................................... 8454
Sum of peak zone L/s .......................................... 8454
Sensible heat ratio .............................................. 0.925
m/kW .................................................................... 7.5
W/m .................................................................. 133.6
Water flow @ 7.0 K rise ....................................... 3.89

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Feb 1600


OA DB / WB ................................................... 34.3 / 25.1
Entering DB / WB ........................................... 24.7 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 22.0
Sensible coil load .................................................. 12.5
Coil L/s at Mar 1500 ............................................. 517
Max coil L/s .......................................................... 517
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.75

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Jan 1600 .................................. 8454 L/s
Standard L/s ........................................................ 8435 L/s
Actual max L/(s-m) .............................................. 9.93 L/(s-m)

Fan motor BHP ...................................................... 15.75 BHP


Fan motor kW ........................................................ 11.74 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 517 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.94 l/s/person

Page 1 of 1

Air System Sizing Summary for L-02-A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ........................................ L-02-A-02
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 704.3 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 98.8
Sensible coil load .................................................. 92.0
Coil L/s at Apr 1500 ............................................. 6489
Max block L/s at Apr 1600 ................................... 7214
Sum of peak zone L/s .......................................... 7214
Sensible heat ratio .............................................. 0.931
m/kW .................................................................... 7.1
W/m .................................................................. 140.3
Water flow @ 7.0 K rise ....................................... 3.38

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1500


OA DB / WB ................................................... 35.1 / 25.2
Entering DB / WB ........................................... 24.8 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 18.0
Sensible coil load .................................................. 10.2
Coil L/s at Mar 1500 ............................................. 423
Max coil L/s .......................................................... 423
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.62

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Apr 1600 .................................. 7214 L/s
Standard L/s ........................................................ 7198 L/s
Actual max L/(s-m) ............................................ 10.24 L/(s-m)

Fan motor BHP ...................................................... 13.44 BHP


Fan motor kW ........................................................ 10.02 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 423 L/s
L/(s-m) ................................................................. 0.60 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 5.00 l/s/person

Page 1 of 1

Air System Sizing Summary for L-03- A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ....................................... L-03- A-01
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 851.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 113.7
Sensible coil load ................................................ 105.2
Coil L/s at Feb 1600 ............................................ 7445
Max block L/s at Jan 1600 ................................... 8454
Sum of peak zone L/s .......................................... 8454
Sensible heat ratio .............................................. 0.925
m/kW .................................................................... 7.5
W/m .................................................................. 133.6
Water flow @ 7.0 K rise ....................................... 3.89

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Feb 1600


OA DB / WB ................................................... 34.3 / 25.1
Entering DB / WB ........................................... 24.7 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 22.0
Sensible coil load .................................................. 12.5
Coil L/s at Mar 1500 ............................................. 517
Max coil L/s .......................................................... 517
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.75

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Jan 1600 .................................. 8454 L/s
Standard L/s ........................................................ 8435 L/s
Actual max L/(s-m) .............................................. 9.93 L/(s-m)

Fan motor BHP ...................................................... 15.75 BHP


Fan motor kW ........................................................ 11.74 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 517 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.94 l/s/person

Page 1 of 1

Air System Sizing Summary for L-03- A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ....................................... L-03- A-02
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 801.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 113.5
Sensible coil load ................................................ 105.6
Coil L/s at Apr 1500 ............................................. 7450
Max block L/s at Apr 1500 ................................... 8266
Sum of peak zone L/s .......................................... 8266
Sensible heat ratio .............................................. 0.930
m/kW .................................................................... 7.1
W/m .................................................................. 141.7
Water flow @ 7.0 K rise ....................................... 3.88

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1500


OA DB / WB ................................................... 35.1 / 25.2
Entering DB / WB ........................................... 24.8 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 20.7
Sensible coil load .................................................. 11.7
Coil L/s at Mar 1500 ............................................. 485
Max coil L/s .......................................................... 485
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.71

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Apr 1500 .................................. 8266 L/s
Standard L/s ........................................................ 8248 L/s
Actual max L/(s-m) ............................................ 10.32 L/(s-m)

Fan motor BHP ...................................................... 15.40 BHP


Fan motor kW ........................................................ 11.48 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 485 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.95 l/s/person

Page 1 of 1

Air System Sizing Summary for L-04-A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ........................................ L-04-A-01
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 847.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 113.3
Sensible coil load ................................................ 104.9
Coil L/s at Feb 1600 ............................................ 7405
Max block L/s at Jan 1600 ................................... 8384
Sum of peak zone L/s .......................................... 8384
Sensible heat ratio .............................................. 0.926
m/kW .................................................................... 7.5
W/m .................................................................. 133.8
Water flow @ 7.0 K rise ....................................... 3.87

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Feb 1600


OA DB / WB ................................................... 34.3 / 25.1
Entering DB / WB ........................................... 24.7 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 21.8
Sensible coil load .................................................. 12.4
Coil L/s at Mar 1500 ............................................. 512
Max coil L/s .......................................................... 512
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.75

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Jan 1600 .................................. 8384 L/s
Standard L/s ........................................................ 8365 L/s
Actual max L/(s-m) .............................................. 9.90 L/(s-m)

Fan motor BHP ...................................................... 15.62 BHP


Fan motor kW ........................................................ 11.65 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 512 L/s
L/(s-m) ................................................................. 0.60 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.96 l/s/person

Page 1 of 1

Air System Sizing Summary for L-04-A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ........................................ L-04-A-02
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 791.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 109.6
Sensible coil load ................................................ 101.8
Coil L/s at Apr 1500 ............................................. 7178
Max block L/s at Apr 1500 ................................... 7964
Sum of peak zone L/s .......................................... 7964
Sensible heat ratio .............................................. 0.929
m/kW .................................................................... 7.2
W/m .................................................................. 138.5
Water flow @ 7.0 K rise ....................................... 3.75

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1500


OA DB / WB ................................................... 35.1 / 25.2
Entering DB / WB ........................................... 24.8 / 17.1
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 20.4
Sensible coil load .................................................. 11.6
Coil L/s at Mar 1500 ............................................. 479
Max coil L/s .......................................................... 479
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.70

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Apr 1500 .................................. 7964 L/s
Standard L/s ........................................................ 7946 L/s
Actual max L/(s-m) ............................................ 10.07 L/(s-m)

Fan motor BHP ...................................................... 14.83 BHP


Fan motor kW ........................................................ 11.06 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 479 L/s
L/(s-m) ................................................................. 0.60 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.96 l/s/person

Page 1 of 1

Air System Sizing Summary for L-05-A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ........................................ L-05-A-01
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 817.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 113.7
Sensible coil load ................................................ 105.6
Coil L/s at Jan 1500 ............................................. 7453
Max block L/s at Jan 1600 ................................... 8448
Sum of peak zone L/s .......................................... 8448
Sensible heat ratio .............................................. 0.928
m/kW .................................................................... 7.2
W/m .................................................................. 139.2
Water flow @ 7.0 K rise ....................................... 3.89

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Jan 1500


OA DB / WB ................................................... 33.4 / 24.6
Entering DB / WB ........................................... 24.7 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 21.1
Sensible coil load .................................................. 12.0
Coil L/s at Mar 1500 ............................................. 494
Max coil L/s .......................................................... 494
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.72

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Jan 1600 .................................. 8448 L/s
Standard L/s ........................................................ 8430 L/s
Actual max L/(s-m) ............................................ 10.34 L/(s-m)

Fan motor BHP ...................................................... 15.74 BHP


Fan motor kW ........................................................ 11.73 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 494 L/s
L/(s-m) ................................................................. 0.60 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.96 l/s/person

Page 1 of 1

Air System Sizing Summary for L-05-A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ........................................ L-05-A-02
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 809.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ..................................................... 116.2
Sensible coil load ................................................ 108.2
Coil L/s at Apr 1500 ............................................. 7624
Max block L/s at Apr 1600 ................................... 8457
Sum of peak zone L/s .......................................... 8457
Sensible heat ratio .............................................. 0.931
m/kW .................................................................... 7.0
W/m .................................................................. 143.6
Water flow @ 7.0 K rise ....................................... 3.97

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1500


OA DB / WB ................................................... 35.1 / 25.2
Entering DB / WB ........................................... 24.8 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 20.9
Sensible coil load .................................................. 11.9
Coil L/s at Mar 1500 ............................................. 490
Max coil L/s .......................................................... 490
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.71

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Apr 1600 .................................. 8457 L/s
Standard L/s ........................................................ 8438 L/s
Actual max L/(s-m) ............................................ 10.45 L/(s-m)

Fan motor BHP ...................................................... 15.75 BHP


Fan motor kW ........................................................ 11.75 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 490 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.96 l/s/person

Page 1 of 1

Air System Sizing Summary for L-07-A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ........................................ L-07-A-01
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 397.5 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 57.3
Sensible coil load .................................................. 51.0
Coil L/s at Jan 1500 ............................................. 3517
Max block L/s at Dec 1500 ................................... 3997
Sum of peak zone L/s .......................................... 3997
Sensible heat ratio .............................................. 0.889
m/kW .................................................................... 6.9
W/m .................................................................. 144.3
Water flow @ 7.0 K rise ....................................... 1.96

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Jan 1500


OA DB / WB ................................................... 33.4 / 24.6
Entering DB / WB ........................................... 25.0 / 17.3
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.6
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 47
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ........................................................ 9.3
Sensible coil load ................................................... 5.3
Coil L/s at Mar 1500 ............................................. 219
Max coil L/s .......................................................... 219
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.32

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Dec 1500 ................................. 3997 L/s
Standard L/s ........................................................ 3988 L/s
Actual max L/(s-m) ............................................ 10.06 L/(s-m)

Fan motor BHP ........................................................ 7.45 BHP


Fan motor kW .......................................................... 5.55 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 219 L/s
L/(s-m) ................................................................. 0.55 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 5.50 l/s/person

Page 1 of 1

Air System Sizing Summary for L-07-A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ........................................ L-07-A-02
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 281.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 56.4
Sensible coil load .................................................. 45.7
Coil L/s at Mar 0900 ............................................ 3198
Max block L/s at Jan 1500 ................................... 3465
Sum of peak zone L/s .......................................... 3465
Sensible heat ratio .............................................. 0.811
m/kW .................................................................... 5.0
W/m .................................................................. 200.6
Water flow @ 7.0 K rise ....................................... 1.93

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Mar 0900


OA DB / WB ................................................... 29.3 / 23.7
Entering DB / WB ........................................... 24.9 / 17.8
Leaving DB / WB ........................................... 13.0 / 12.4
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 11.1
Sensible coil load ................................................... 6.3
Coil L/s at Mar 1500 ............................................. 260
Max coil L/s .......................................................... 260
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.38

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Jan 1500 .................................. 3465 L/s
Standard L/s ........................................................ 3458 L/s
Actual max L/(s-m) ............................................ 12.33 L/(s-m)

Fan motor BHP ........................................................ 6.45 BHP


Fan motor kW .......................................................... 4.81 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 260 L/s
L/(s-m) ................................................................. 0.93 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 3.70 l/s/person

Page 1 of 1

Air System Sizing Summary for L-08to11-A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-08to11-A-01
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 577.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 89.4
Sensible coil load .................................................. 83.5
Coil L/s at Dec 1500 ............................................ 5893
Max block L/s at Dec 1500 ................................... 6640
Sum of peak zone L/s .......................................... 6640
Sensible heat ratio .............................................. 0.934
m/kW .................................................................... 6.5
W/m .................................................................. 154.9
Water flow @ 7.0 K rise ....................................... 3.06

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Dec 1500


OA DB / WB ................................................... 32.9 / 24.1
Entering DB / WB ........................................... 24.8 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 15.1
Sensible coil load ................................................... 8.6
Coil L/s at Mar 1500 ............................................. 353
Max coil L/s .......................................................... 353
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.52

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Dec 1500 ................................. 6640 L/s
Standard L/s ........................................................ 6625 L/s
Actual max L/(s-m) ............................................ 11.51 L/(s-m)

Fan motor BHP ...................................................... 12.37 BHP


Fan motor kW .......................................................... 9.22 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 353 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.90 l/s/person

Page 1 of 1

Air System Sizing Summary for L-08to11-A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-08to11-A-02
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 616.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 83.4
Sensible coil load .................................................. 77.3
Coil L/s at Apr 1500 ............................................. 5470
Max block L/s at Apr 1600 ................................... 6146
Sum of peak zone L/s .......................................... 6146
Sensible heat ratio .............................................. 0.927
m/kW .................................................................... 7.4
W/m .................................................................. 135.4
Water flow @ 7.0 K rise ....................................... 2.85

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1500


OA DB / WB ................................................... 35.1 / 25.2
Entering DB / WB ........................................... 24.7 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 16.0
Sensible coil load ................................................... 9.1
Coil L/s at Mar 1500 ............................................. 375
Max coil L/s .......................................................... 375
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.55

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Apr 1600 .................................. 6146 L/s
Standard L/s ........................................................ 6132 L/s
Actual max L/(s-m) .............................................. 9.98 L/(s-m)

Fan motor BHP ...................................................... 11.45 BHP


Fan motor kW .......................................................... 8.54 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 375 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.93 l/s/person

Page 1 of 1

Air System Sizing Summary for L-12to20-A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-12to20-A-01
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 577.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 89.4
Sensible coil load .................................................. 83.5
Coil L/s at Dec 1500 ............................................ 5893
Max block L/s at Dec 1500 ................................... 6640
Sum of peak zone L/s .......................................... 6640
Sensible heat ratio .............................................. 0.934
m/kW .................................................................... 6.5
W/m .................................................................. 154.9
Water flow @ 7.0 K rise ....................................... 3.06

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Dec 1500


OA DB / WB ................................................... 32.9 / 24.1
Entering DB / WB ........................................... 24.8 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 15.1
Sensible coil load ................................................... 8.6
Coil L/s at Mar 1500 ............................................. 353
Max coil L/s .......................................................... 353
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.52

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Dec 1500 ................................. 6640 L/s
Standard L/s ........................................................ 6625 L/s
Actual max L/(s-m) ............................................ 11.51 L/(s-m)

Fan motor BHP ...................................................... 12.37 BHP


Fan motor kW .......................................................... 9.22 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 353 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.90 l/s/person

Page 1 of 1

Air System Sizing Summary for L-12to20-A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-12to20-A-02
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 621.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 83.9
Sensible coil load .................................................. 77.7
Coil L/s at Apr 1500 ............................................. 5501
Max block L/s at Apr 1600 ................................... 6181
Sum of peak zone L/s .......................................... 6181
Sensible heat ratio .............................................. 0.927
m/kW .................................................................... 7.4
W/m .................................................................. 135.0
Water flow @ 7.0 K rise ....................................... 2.87

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1500


OA DB / WB ................................................... 35.1 / 25.2
Entering DB / WB ........................................... 24.7 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 16.1
Sensible coil load ................................................... 9.1
Coil L/s at Mar 1500 ............................................. 378
Max coil L/s .......................................................... 378
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.55

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Apr 1600 .................................. 6181 L/s
Standard L/s ........................................................ 6167 L/s
Actual max L/(s-m) .............................................. 9.95 L/(s-m)

Fan motor BHP ...................................................... 11.51 BHP


Fan motor kW .......................................................... 8.58 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 378 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.93 l/s/person

Page 1 of 1

Air System Sizing Summary for L-21-A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ........................................ L-21-A-01
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 577.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 89.4
Sensible coil load .................................................. 83.5
Coil L/s at Dec 1500 ............................................ 5893
Max block L/s at Dec 1500 ................................... 6640
Sum of peak zone L/s .......................................... 6640
Sensible heat ratio .............................................. 0.934
m/kW .................................................................... 6.5
W/m .................................................................. 154.9
Water flow @ 7.0 K rise ....................................... 3.06

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Dec 1500


OA DB / WB ................................................... 32.9 / 24.1
Entering DB / WB ........................................... 24.8 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 15.1
Sensible coil load ................................................... 8.6
Coil L/s at Mar 1500 ............................................. 353
Max coil L/s .......................................................... 353
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.52

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Dec 1500 ................................. 6640 L/s
Standard L/s ........................................................ 6625 L/s
Actual max L/(s-m) ............................................ 11.51 L/(s-m)

Fan motor BHP ...................................................... 12.37 BHP


Fan motor kW .......................................................... 9.22 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 353 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.90 l/s/person

Page 1 of 1

Air System Sizing Summary for L-21-A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ........................................ L-21-A-02
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 609.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 82.8
Sensible coil load .................................................. 76.7
Coil L/s at Apr 1500 ............................................. 5433
Max block L/s at Apr 1600 ................................... 6106
Sum of peak zone L/s .......................................... 6106
Sensible heat ratio .............................................. 0.927
m/kW .................................................................... 7.4
W/m .................................................................. 135.9
Water flow @ 7.0 K rise ....................................... 2.83

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1500


OA DB / WB ................................................... 35.1 / 25.2
Entering DB / WB ........................................... 24.7 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 15.8
Sensible coil load ................................................... 9.0
Coil L/s at Mar 1500 ............................................. 371
Max coil L/s .......................................................... 371
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.54

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Apr 1600 .................................. 6106 L/s
Standard L/s ........................................................ 6092 L/s
Actual max L/(s-m) ............................................ 10.03 L/(s-m)

Fan motor BHP ...................................................... 11.37 BHP


Fan motor kW .......................................................... 8.48 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 371 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.93 l/s/person

Page 1 of 1

Air System Sizing Summary for L-22to23-A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-22to23-A-01
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 572.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 91.1
Sensible coil load .................................................. 85.2
Coil L/s at Dec 1500 ............................................ 6006
Max block L/s at Dec 1500 ................................... 6754
Sum of peak zone L/s .......................................... 6754
Sensible heat ratio .............................................. 0.936
m/kW .................................................................... 6.3
W/m .................................................................. 159.2
Water flow @ 7.0 K rise ....................................... 3.11

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Dec 1500


OA DB / WB ................................................... 32.9 / 24.1
Entering DB / WB ........................................... 24.8 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 14.9
Sensible coil load ................................................... 8.5
Coil L/s at Mar 1500 ............................................. 350
Max coil L/s .......................................................... 350
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.51

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Dec 1500 ................................. 6754 L/s
Standard L/s ........................................................ 6739 L/s
Actual max L/(s-m) ............................................ 11.81 L/(s-m)

Fan motor BHP ...................................................... 12.58 BHP


Fan motor kW .......................................................... 9.38 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 350 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.90 l/s/person

Page 1 of 1

Air System Sizing Summary for L-22to23-A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-22to23-A-02
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 616.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 82.2
Sensible coil load .................................................. 76.1
Coil L/s at Apr 1400 ............................................. 5386
Max block L/s at May 1500 .................................. 6031
Sum of peak zone L/s .......................................... 6031
Sensible heat ratio .............................................. 0.926
m/kW .................................................................... 7.5
W/m .................................................................. 133.4
Water flow @ 7.0 K rise ....................................... 2.81

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1400


OA DB / WB ................................................... 34.9 / 25.1
Entering DB / WB ........................................... 24.7 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 16.0
Sensible coil load ................................................... 9.1
Coil L/s at Mar 1500 ............................................. 375
Max coil L/s .......................................................... 375
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.55

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at May 1500 ................................. 6031 L/s
Standard L/s ........................................................ 6017 L/s
Actual max L/(s-m) .............................................. 9.79 L/(s-m)

Fan motor BHP ...................................................... 11.23 BHP


Fan motor kW .......................................................... 8.38 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 375 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.93 l/s/person

Page 1 of 1

Air System Sizing Summary for L-24to25-A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-24to25-A-01
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 522.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 74.9
Sensible coil load .................................................. 69.5
Coil L/s at Jan 1600 ............................................. 4898
Max block L/s at Jan 1600 ................................... 5577
Sum of peak zone L/s .......................................... 5577
Sensible heat ratio .............................................. 0.929
m/kW .................................................................... 7.0
W/m .................................................................. 143.4
Water flow @ 7.0 K rise ....................................... 2.56

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Jan 1600


OA DB / WB ................................................... 33.2 / 24.5
Entering DB / WB ........................................... 24.8 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 13.6
Sensible coil load ................................................... 7.7
Coil L/s at Mar 1500 ............................................. 320
Max coil L/s .......................................................... 320
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.47

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Jan 1600 .................................. 5577 L/s
Standard L/s ........................................................ 5564 L/s
Actual max L/(s-m) ............................................ 10.68 L/(s-m)

Fan motor BHP ...................................................... 10.39 BHP


Fan motor kW .......................................................... 7.75 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 320 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.90 l/s/person

Page 1 of 1

Air System Sizing Summary for L-24to25-A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-24to25-A-02
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 566.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 73.8
Sensible coil load .................................................. 68.2
Coil L/s at Apr 1500 ............................................. 4825
Max block L/s at Apr 1600 ................................... 5462
Sum of peak zone L/s .......................................... 5462
Sensible heat ratio .............................................. 0.924
m/kW .................................................................... 7.7
W/m .................................................................. 130.4
Water flow @ 7.0 K rise ....................................... 2.52

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1500


OA DB / WB ................................................... 35.1 / 25.2
Entering DB / WB ........................................... 24.7 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 14.7
Sensible coil load ................................................... 8.3
Coil L/s at Mar 1500 ............................................. 344
Max coil L/s .......................................................... 344
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.50

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Apr 1600 .................................. 5462 L/s
Standard L/s ........................................................ 5450 L/s
Actual max L/(s-m) .............................................. 9.65 L/(s-m)

Fan motor BHP ...................................................... 10.17 BHP


Fan motor kW .......................................................... 7.59 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 344 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.94 l/s/person

Page 1 of 1

Air System Sizing Summary for L-26to28-A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-26to28-A-01
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 566.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 73.6
Sensible coil load .................................................. 68.0
Coil L/s at Apr 1500 ............................................. 4810
Max block L/s at Apr 1600 ................................... 5447
Sum of peak zone L/s .......................................... 5447
Sensible heat ratio .............................................. 0.924
m/kW .................................................................... 7.7
W/m .................................................................. 130.0
Water flow @ 7.0 K rise ....................................... 2.51

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1500


OA DB / WB ................................................... 35.1 / 25.2
Entering DB / WB ........................................... 24.7 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 14.7
Sensible coil load ................................................... 8.3
Coil L/s at Mar 1500 ............................................. 344
Max coil L/s .......................................................... 344
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.50

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Apr 1600 .................................. 5447 L/s
Standard L/s ........................................................ 5435 L/s
Actual max L/(s-m) .............................................. 9.62 L/(s-m)

Fan motor BHP ...................................................... 10.15 BHP


Fan motor kW .......................................................... 7.57 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 344 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.94 l/s/person

Page 1 of 1

Air System Sizing Summary for L-26to28-A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-26to28-A-02
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 566.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 73.6
Sensible coil load .................................................. 68.0
Coil L/s at Apr 1500 ............................................. 4810
Max block L/s at Apr 1600 ................................... 5447
Sum of peak zone L/s .......................................... 5447
Sensible heat ratio .............................................. 0.924
m/kW .................................................................... 7.7
W/m .................................................................. 130.0
Water flow @ 7.0 K rise ....................................... 2.51

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1500


OA DB / WB ................................................... 35.1 / 25.2
Entering DB / WB ........................................... 24.7 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 14.7
Sensible coil load ................................................... 8.3
Coil L/s at Mar 1500 ............................................. 344
Max coil L/s .......................................................... 344
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.50

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Apr 1600 .................................. 5447 L/s
Standard L/s ........................................................ 5435 L/s
Actual max L/(s-m) .............................................. 9.62 L/(s-m)

Fan motor BHP ...................................................... 10.15 BHP


Fan motor kW .......................................................... 7.57 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 344 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.94 l/s/person

Page 1 of 1

Air System Sizing Summary for L-29to30-A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-29to30-A-01
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 518.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 75.5
Sensible coil load .................................................. 70.2
Coil L/s at Jan 1600 ............................................. 4942
Max block L/s at Jan 1600 ................................... 5625
Sum of peak zone L/s .......................................... 5625
Sensible heat ratio .............................................. 0.930
m/kW .................................................................... 6.9
W/m .................................................................. 145.7
Water flow @ 7.0 K rise ....................................... 2.58

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Jan 1600


OA DB / WB ................................................... 33.2 / 24.5
Entering DB / WB ........................................... 24.8 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 13.5
Sensible coil load ................................................... 7.7
Coil L/s at Mar 1500 ............................................. 317
Max coil L/s .......................................................... 317
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.46

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Jan 1600 .................................. 5625 L/s
Standard L/s ........................................................ 5612 L/s
Actual max L/(s-m) ............................................ 10.86 L/(s-m)

Fan motor BHP ...................................................... 10.48 BHP


Fan motor kW .......................................................... 7.81 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 317 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.90 l/s/person

Page 1 of 1

Air System Sizing Summary for L-29to30-A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-29to30-A-02
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 562.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 74.2
Sensible coil load .................................................. 68.7
Coil L/s at Apr 1500 ............................................. 4858
Max block L/s at Apr 1600 ................................... 5502
Sum of peak zone L/s .......................................... 5502
Sensible heat ratio .............................................. 0.925
m/kW .................................................................... 7.6
W/m .................................................................. 132.1
Water flow @ 7.0 K rise ....................................... 2.54

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1500


OA DB / WB ................................................... 35.1 / 25.2
Entering DB / WB ........................................... 24.7 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 14.6
Sensible coil load ................................................... 8.3
Coil L/s at Mar 1500 ............................................. 341
Max coil L/s .......................................................... 341
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.50

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Apr 1600 .................................. 5502 L/s
Standard L/s ........................................................ 5489 L/s
Actual max L/(s-m) .............................................. 9.79 L/(s-m)

Fan motor BHP ...................................................... 10.25 BHP


Fan motor kW .......................................................... 7.64 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 341 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.94 l/s/person

Page 1 of 1

Air System Sizing Summary for L-31to32-A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-31to32-A-01
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 434.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 74.4
Sensible coil load .................................................. 69.9
Coil L/s at Dec 1500 ............................................ 4922
Max block L/s at Dec 1500 ................................... 5541
Sum of peak zone L/s .......................................... 5541
Sensible heat ratio .............................................. 0.940
m/kW .................................................................... 5.8
W/m .................................................................. 171.4
Water flow @ 7.0 K rise ....................................... 2.54

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Dec 1500


OA DB / WB ................................................... 32.9 / 24.1
Entering DB / WB ........................................... 24.8 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 45
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 11.3
Sensible coil load ................................................... 6.4
Coil L/s at Mar 1500 ............................................. 266
Max coil L/s .......................................................... 266
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.39

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Dec 1500 ................................. 5541 L/s
Standard L/s ........................................................ 5528 L/s
Actual max L/(s-m) ............................................ 12.77 L/(s-m)

Fan motor BHP ...................................................... 10.32 BHP


Fan motor kW .......................................................... 7.70 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 266 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.90 l/s/person

Page 1 of 1

Air System Sizing Summary for L-31to32-A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-31to32-A-02
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 478.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 69.5
Sensible coil load .................................................. 64.7
Coil L/s at Apr 1500 ............................................. 4568
Max block L/s at May 1500 .................................. 5137
Sum of peak zone L/s .......................................... 5137
Sensible heat ratio .............................................. 0.932
m/kW .................................................................... 6.9
W/m .................................................................. 145.3
Water flow @ 7.0 K rise ....................................... 2.37

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1500


OA DB / WB ................................................... 35.1 / 25.2
Entering DB / WB ........................................... 24.8 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 12.4
Sensible coil load ................................................... 7.0
Coil L/s at Mar 1500 ............................................. 290
Max coil L/s .......................................................... 290
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.42

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at May 1500 ................................. 5137 L/s
Standard L/s ........................................................ 5125 L/s
Actual max L/(s-m) ............................................ 10.75 L/(s-m)

Fan motor BHP ........................................................ 9.57 BHP


Fan motor kW .......................................................... 7.13 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 290 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.95 l/s/person

Page 1 of 1

Air System Sizing Summary for L-33to34-A-01


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-33to34-A-01
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 434.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 74.4
Sensible coil load .................................................. 69.9
Coil L/s at Dec 1500 ............................................ 4922
Max block L/s at Dec 1500 ................................... 5541
Sum of peak zone L/s .......................................... 5541
Sensible heat ratio .............................................. 0.940
m/kW .................................................................... 5.8
W/m .................................................................. 171.4
Water flow @ 7.0 K rise ....................................... 2.54

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Dec 1500


OA DB / WB ................................................... 32.9 / 24.1
Entering DB / WB ........................................... 24.8 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 45
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 11.3
Sensible coil load ................................................... 6.4
Coil L/s at Mar 1500 ............................................. 266
Max coil L/s .......................................................... 266
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.39

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at Dec 1500 ................................. 5541 L/s
Standard L/s ........................................................ 5528 L/s
Actual max L/(s-m) ............................................ 12.77 L/(s-m)

Fan motor BHP ...................................................... 10.32 BHP


Fan motor kW .......................................................... 7.70 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 266 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.90 l/s/person

Page 1 of 1

Air System Sizing Summary for L-33to34-A-02


Project Name: VietcomBank
Prepared by: eec

03/17/2010
04:45PM

Air System Information


Air System Name ................................. L-33to34-A-02
Equipment Class .......................................... CW AHU
Air System Type .................................................. VAV

Number of zones .......................................................... 1


Floor Area .............................................................. 478.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................. Peak zone sensible load
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 69.5
Sensible coil load .................................................. 64.7
Coil L/s at Apr 1500 ............................................. 4568
Max block L/s at May 1500 .................................. 5137
Sum of peak zone L/s .......................................... 5137
Sensible heat ratio .............................................. 0.932
m/kW .................................................................... 6.9
W/m .................................................................. 145.3
Water flow @ 7.0 K rise ....................................... 2.37

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Apr 1500


OA DB / WB ................................................... 35.1 / 25.2
Entering DB / WB ........................................... 24.8 / 17.0
Leaving DB / WB ........................................... 13.0 / 12.3
Coil ADP .................................................................. 11.7
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 46
Design supply temp. ................................................ 14.3
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Precool Coil Sizing Data


Total coil load ....................................................... 12.4
Sensible coil load ................................................... 7.0
Coil L/s at Mar 1500 ............................................. 290
Max coil L/s .......................................................... 290
Sensible heat ratio .............................................. 0.568
Water flow @ 7.0 K rise ....................................... 0.42

kW
kW
L/s
L/s

Load occurs at ................................................. Mar 1500


OA DB / WB ................................................... 35.1 / 25.2 C
Entering DB / WB ........................................... 35.1 / 25.2 C
Leaving DB / WB ........................................... 15.0 / 14.3 C
Bypass Factor ........................................................ 0.100

L/s

Supply Fan Sizing Data


Actual max L/s at May 1500 ................................. 5137 L/s
Standard L/s ........................................................ 5125 L/s
Actual max L/(s-m) ............................................ 10.75 L/(s-m)

Fan motor BHP ........................................................ 9.57 BHP


Fan motor kW .......................................................... 7.13 kW
Fan static .................................................................. 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s ................................................. 290 L/s
L/(s-m) ................................................................. 0.61 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 4.95 l/s/person

Page 1 of 1

Air System Sizing Summary for L8-L32 Tenant Server Room


Project Name: VietcomBank
Prepared by: eec

03/24/2010
10:47AM

Air System Information


Air System Name .......... L8-L32 Tenant Server Room
Equipment Class .......................................... CW AHU
Air System Type ............................................. SZCAV

Number of zones .......................................................... 1


Floor Area ................................................................ 20.0 m
Location .............................. Ho Chi Minh City, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ......................... Sum of space airflow rates
Space L/s ..................... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 29.2
Sensible coil load .................................................. 29.1
Coil L/s at Mar 1300 ............................................ 2329
Max block L/s ...................................................... 2329
Sum of peak zone L/s .......................................... 2329
Sensible heat ratio .............................................. 0.997
m/kW .................................................................... 0.7
W/m ................................................................ 1458.3
Water flow @ 7.0 K rise ....................................... 1.00

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................. Mar 1300


OA DB / WB ................................................... 34.2 / 25.0
Entering DB / WB ........................................... 24.7 / 17.4
Leaving DB / WB ........................................... 14.3 / 13.6
Coil ADP .................................................................. 13.2
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 50
Design supply temp. ................................................ 13.0
Zone T-stat Check ................................................. 1 of 1
Max zone temperature deviation ................................ 0.0

C
C
C
C
%
C
OK
K

Supply Fan Sizing Data


Actual max L/s ..................................................... 2329 L/s
Standard L/s ........................................................ 2324 L/s
Actual max L/(s-m) .......................................... 116.46 L/(s-m)

Fan motor BHP ........................................................ 1.45 BHP


Fan motor kW .......................................................... 1.08 kW
Fan static .................................................................. 250 Pa

Outdoor Ventilation Air Data


Design airflow L/s ..................................................... 0 L/s
L/(s-m) ................................................................. 0.00 L/(s-m)

Hourly Analysis Program v.4.2

l/s/person ................................................................. 0.00 l/s/person

Page 1 of 1

Vous aimerez peut-être aussi