SEUE001D.F26 / LIE / 12.04.2007

AS400FUE
SoftEdge
H27-510

wiring diagramme
adjustment instructions

GB
Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

230/400V / 50Hz
min. 5x2,5mm
24V DC
2007ff

main supply
connecting lead
control voltage
year of manufacture

Subject to technical changes!


Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

title page

H27-510

Gesamt

Blatt

23

Table of contents
Page

Spalte X: eine automatisch erzeugte Seite wurde manuell nachbearbeitet

Page name

additional page field

SEUJ005D.F06/LIE/12.04.2007

date

person in charge

title page

05.01.2009

ws21

contents

05.01.2009

ws21

mains supply

05.01.2009

J.A.Steppke

impulse device

05.01.2009

lie

contact bar

05.01.2009

Lie

output module

05.01.2009

ADM

photocell

05.01.2009

Lie

option

05.01.2009

Lie

radio

05.01.2009

Lie

10

terminal connection diagramme X%0 X0

05.01.2009

ws21

11

terminal connection diagramme X%0 X1

05.01.2009

ws21

12

terminal connection diagramme X%0 X1

05.01.2009

ws21

13

terminal connection diagramme X%0 X4

05.01.2009

ws21

14

terminal connection diagramme X%0 X8

05.01.2009

ws21

15

terminal connection diagramme X%0 X9

05.01.2009

ws21

16

terminal connection diagramme X%0 X10

05.01.2009

ws21

17

connection diagramme X%0 X2

05.01.2009

ws21

18

connection diagramme X%0 X3

05.01.2009

ws21

19

connection diagramme X%0 X3

05.01.2009

ws21

20

cable overview

05.01.2009

ws21

21

parts list

05.01.2009

ws21

22

parts list

05.01.2009

ws21

23

parts list

05.01.2009

ws21

3
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

contents

H27-510

Gesamt

Blatt

23

circuit board

Technical connection requirements, including those from the


local energy supplier, and national electrotechnical regulations
must be observed

+24

A1

L1

L2

L3

X9

PE

X8

10

GND

11

X9

32

PE

X501

X4

PE

PE

PE

/ X9:3 6.1

R1

F2

100R / 100W

6A

1
/ X1:4 6.1

/ X1:7 4.1

/ X2:8 7.0

F1
16AT

T1

T2

T3

L1

L2

L3

G1

PE

Q1
X2
PE

PE

PE

W2
lflex-110
18x0,5mm
control cable

15

16

PE

15

16

PE

W1
LIYCY-JZ
4x1,5mm
motor cable

SH=WH

PE

The connection must be made by licenced


personnel

X0

L1

L2

L3

X1

PE

PE

10

11

12

E1

PE

M1

A1

M
3~

Y1

PE
A2

mains supply
230/400V / 50Hz

connecting lead:
5x2,5mm fuse: 16A
slow-acting

external devices
230V AC

external devices
24V DC

brake

operator

4
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

mains supply

H27-510

Gesamt

Blatt

23

circuit board

24V
3

E201
F201
=NA=

E211
F211

IN1
E101
24V

SK2
watchdog

X7

IN2
E102

4
1

X8

10

11

IN3
E103

24V

12

13

IN5
E105

24V

14

15

IN6
E106

24V

16

19

IN7
E107

24V

20

21

IN8
E108

24V

22

23

24V

24

25

26

S7

mergency-OFF
cabinet door

/ X1:13 8.3

X1:9 3.4 /

/ X1:7 8.3

X1

WS31
lflex-110
2x0,75mm
external emergency-OFF 2

WS32
lflex-110
2x0,75mm
impulse up
1

S31

emergency-OFF
cabinet door

13

14

WS33
lflex-110
2x0,75mm
impulse down
3

S32

external
emergency-OFF 2

15

16

WS34
lflex-110
2x0,75mm
impulse operation
3

S33

impulse up

17

WS35
lflex-110
2x0,75mm
deactivation
3

S34

impulse down

WS36
lflex-110
2x0,75mm
intermediate stop
3

S35

impulse operation

no photocell 2 for
jumper

locking in EU

deactivation of
hold-open phase

S36

intermediate stop
(optional)

5
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

impulse device

H27-510

Gesamt

Blatt

23

circuit board
E360
F361/F363/F364

+24

IN10
E110

P750

+24

GND1

X8

27

X2
W2control cable

X3
WA5.1
LIYY_757
5x0,5mm
contact bar

A5.1

X20

X8

X8

12

13

14

10

11

12

13

14

10

11

67

68

69

65

66

BN

WH

GN

YE

GY

BN

WH

+24

GND

GN

contact bar

30

29

X9

YE

GY

crash protection

S51.2

WA5.2
LIYY_757
4x0,14mm
Diodes

WH

BN

YE

Activation

GN

A5.2
6

1
9

BAT

11

10

2x1,5V

WS30.1
LIYY_757
3x0,14mm
contact bar receiver

BN

WH

GN

S30.1

battery

WS30.2
LIYY_757
3x0,14mm
contact bar
transmitter

S30.2

contact bar receiver

BN

WH

GN

WS51
LIYY_757
2x0,14mm
crash protection

BN

WH

S51.1

NC

crash protection

contact bar
transmitter

6
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

contact bar

H27-510

Gesamt

Blatt

23

circuit board
P704

P704

E000/E050/E090

F752
485A
485B

X9

X9

X9:10 3.4 /

/ X1:1 9.0

X1:3 3.4 /

/ X1:3 9.0

X1

F1

F2

F3

F4

-WF
Flach
4x0,14mm
membrane keypad

GND
+12

E211
F211
+24NA
NA

X8

37

35

33

38

X2

W2control cable

X3

WH1
lflex-110
3x0,75mm
traffic light

H1

-SF
N

red traffic light

flashing light flashing


beacon green traffic
light
optional

1.4

1.2

1.6

1.3

1.5

1.1

2.1
1

2.2

S10
crank handle

2.3

DES
2.5

2.4
2.6

F0

thermal
contact

S50
optional
pull switch

traffic light

door open signal

DES

(Optional)
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

membrane keypad

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

output module

H27-510

Gesamt

Blatt

23

circuit board
IN4
E104

24V
GND

X8

31

32

18

X1:12 3.4 /

/ X1:10 8.3

X2
W2control cable

X3

EWS

61

63

64

BN

BU

WH

62

W3
ASD_757
4x0,34mm
photocell
transmitter

transmitter

ELG6

X3

W4
ASD_757
4x0,34mm
photocell
receiver

61

63

64

BN

BU

WH

X3

WS41.1
ASD_757
5x0,34mm
photo grille transmitter

S41.1

Out

photocell transmitter

photocell receiver

6
Datum

63

101

102

BN

WH

BU

BK

GY

Gepr.
Name

Norm

X3

WS41.2
ASD_757
5x0,34mm
photo grille
receiver

61

62

63

64

103

BN

BK

BU

WH

GY

X3

W(S41.1)
ASD_ILG
3x0,14mm
photo grille transmitter

61

63

104

BN

BU

WH

X3

W(S41.2)
ASD_ILG
4x0,14mm
photo grille receiver

61

62

63

64

BN

BK

BU

WH

06.01.2009
Urspr.

Ers.f.

S41.2

S41.1_ILG

+24

GND

TE

S41.2_ILG

+24

COM GND

NO

photo grille
transmitter

photo grille receiver

photo grille transmitter

photo curtain receiver

optional

optional

optional

optional

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Datum

100

EWE

NC

RES

nderung

61

ILG

Ers.d.

photocell

H27-510

Gesamt

Blatt

23

circuit board

A3

IN5
E105

24V
E501

X8

E502

24V

GND

X8

19

32

IN1
E101

IN6
E106

P704
output

GND

19

X8

20

11

32

11

X8

12

X1:9 4.6 /

/ X1:7 9.0

X2:8 7.1 /

/ X1:11 9.0

X1:14 4.6 /

/ X1:13 9.0

21

22

X9

S11
2

PE

X1

18

19

20

X1

21

WA4
lflex-110
4x0,75mm
photocell 2 (optional)

10

17

L1

photocell 2 (optional)

10

13

radar (optional)

X10

W10
lflex-110
5x0,75mm
locking

.X10

PE

PE

PE

2. operator control

locking 2. door
option

7
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

A7
1

induction loops
(optional)

WA7
lflex-110
4x0,75mm
radar

A4

L2

X1

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

option

H27-510

Gesamt

Blatt

23

circuit board

A6.1
E401

X1:4 6.2 /

X9:3 6.2 /

X1:13 8.6 /

X1:8 8.6 /

X1:10 8.6 /

X1

11

X1

13

14

External radio receiver HER1 must be mounted opposite to and as far as possible from
control cabinet.
XA

A6.2

10

11

A6

colours according to IEC757

impulse up

radio

radio

BK

black

GY

grey

BN

brown

WH

white

RD

red

PK

pink

OG

orange

GD

gold

YE

yellow

TQ

turquoise

GN

green

SR

silver

BU

blue

GNYE green-yellow

VT

purple

violet

10
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

radio

H27-510

Gesamt

Blatt

23

mains supply
230/400V / 50Hz

PE

L3

connecting lead:
5x2,5mm fuse: 16A slow-acting
=

L1

Klemmennummer

L2

X0

11
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

terminal connection diagramme


X%0 X0

H27-510

Gesamt

Blatt

23

10

Gepr.

nderung
Datum
Name
Norm
Urspr.

Datum

Bearb.

06.01.2009
Ers.f.
Ers.d.

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen
3

S33
4

2
3

1
4

3
4
4

A4

terminal connection diagramme


X%0 X1

H27-510

L1
N
+24

3
8

1
2

L
1
N

L2

23

14

1L01

21

20

19

impulse up

radio

17
4

impulse up

+24

GND

10
3

+24

7
2

18

+24

17
1

lflex-110
4x0,75mm

+24

induction loops (optional)

S32

WA4

2
4

photocell 2
(optional)
=

15

16

lflex-110
2x0,75mm

WS33

H1

no photocell 2 for jumper

2
4

+24

13
2

14

+24
1

lflex-110
2x0,75mm

WS32

NO

6
3

impulse down

NC
3
G

lflex-110
3x0,75mm

GND

12

GND

11

impulse up

GND

10

+24

PE

+24

WH1

+24

(Optional)

traffic light

4
PE

external
devices 24V DC
=

1L01

Klemmennummer
1

X1

external
devices
=
230V AC

0
9

supply terminals

2
5
4
8

A6

10
12

=
+

Gesamt
Blatt

11

+24

GND

+24

13

10

13

GND
11

Klemmennummer

+24

supply terminals

X1

WA7

1
5

3
11

lflex-110
4x0,75mm

1
1

2
2

4
4

3
2

radar
(optional)
=

A7

radio

A6.2

11

13
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

terminal connection diagramme


X%0 X1

H27-510

Gesamt

Blatt

23

12

PE

SH

3
W

PE
PE

SH
PE

LIYCY-JZ
4x1,5mm

1
U

PE

W1

Klemmennummer

motor connection

X4

PE

2
V
U

M
3~
PE

operator

M1

12

14
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

terminal connection diagramme


X%0 X4

H27-510

Gesamt

Blatt

23

13

25

26

2
4

2
2

WS36

lflex-110
2x0,75mm

24

23

WS34

WS35

22

2
4

2
2

lflex-110
2x0,75mm

1
1

21

lflex-110
2x0,75mm

16

21

15

20

10

19

18

lflex-110
2x0,75mm

WS31

Klemmennummer

terminal strip on mainboard

X8

18
4

deactivation of
hold-open phase
=

S35

locking in
EU
=

impulse operation

S34

external
emergency-OFF 2
=

induction loops (optional)

S31

S36

intermediate
stop (optional)
=

X1

13

15
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

terminal connection diagramme


X%0 X8

H27-510

Gesamt

Blatt

23

14

NO
1

NC
5

door open
signal
=

Klemmennummer

COM

output module

X9

14

16
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

terminal connection diagramme


X%0 X9

H27-510

Gesamt

Blatt

23

15

1
3

PE

PE
PE

lflex-110
5x0,75mm

W10

Klemmennummer

terminal strip
lock

X10

PE

2
4

3
1

locking 2.
door
option

.X10

15

17
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

terminal connection diagramme


X%0 X10

H27-510

Gesamt

Blatt

23

16

emergency-OFF

8
7

9
8

10
9

11

10

12

11

13

12

14

13

14

13

14

15

16

15

16

15

16

PE
PE

W2
lflex-110 18x0,5mm
brake

Anschlu

plug-in connector 16pin.

dig. limit
switch

X2

brake

61

63

10

64

65

11

66

12

67

68

69

A2

PE

A1

PE

A1

PE

4
65

66

67

68

crash protection

Activation

+24

GND

69

E1

64

brake

63

Y1

61

contact bar

transmitter

X3

DES

A2
4

16

18
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

connection diagramme X%0 X2

H27-510

Gesamt

Blatt

23

17

nderung
Datum
Name
Gepr.

Norm
Urspr.

Datum

Bearb.

06.01.2009
Ers.f.
Ers.d.
4

GY

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

WS41.2
ASD_757 5x0,34mm
photo grille
receiver

BK

BU

WH

GY

W(S41.1)
ASD_ILG 3x0,14mm
photo curtain
transmitter

BN

BU

BN
BU

+24
GND

WH

WH

TE

+24

BN
BU
BK

BN
BU
BK

+24
GND COM

64
WH

WH

NO

WA5.1
LIYY_757 5x0,5mm
+24

W(S41.2)
ASD_ILG 4x0,14mm
photo curtain
receiver

65
66

YE

connection diagramme X%0 X3

H27-510

67

YE
GY
BN

YE
GY

GY

BN

+24

BN

GND

BK

BN

62

+24

NC

GY

63

A5.1

BU

WS41.1
ASD_757 5x0,34mm
photo grille
transmitter

WH

WH

61

Activation

Out

BN

BU

crash protection

Out

BK

63 104

photo curtain receiver

WH

BN

61

S41.2_ILG

GY

64 103

photo curtain receiver

BU

BK

S41.1_ILG

BU

63

photo grille transmitter

RES

BN

WH

62

RES

WH

BN

61

1.1
-

WH

61 100 63 101 102

BU

S41.2

BN

62

photo grille receiver

BU

BN

WH

64

BU

63

BN

61

1.6

64

S41.1

1.5

63

W4
ASD_757 4x0,34mm
photocell
receiver

photo grille transmitter

1.4

61

1.3

1.2

EWE

W3
ASD_757 4x0,34mm
photocell
transmitter

EWS

3
dig. limit
switch

dig. limit
switch

X3

transmitter

1.1

DES

Anschlu

DES

DES

0
8
9

limit switch box


68
WH

WH

WH

YE

17
19

=
+

Gesamt
Blatt

23
18

X3
Anschlu

limit switch box

69

WA5.1
LIYY_757 5x0,5mm
+24

GN

GN

GN

contact bar

A5.1

GN

18

20
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

connection diagramme X%0 X3

H27-510

Gesamt

Blatt

23

19

cable overview

SEUS001D.F10 / LIE / 12.04.2007


Spannung

Page

W1

X4

M1

LIYCY-JZ

1,5

motor cable

W2

X2

X3;Y1;E1

lflex-110

18

18

0,5

control cable

W3

X3

EWS

ASD_757

0,34

photocell transmitter

W4

X3

EWE

ASD_757

0,34

photocell receiver

W10

X10

.X10

lflex-110

0,75

locking

W(S41.1)

X3

S41.1_ILG

ASD_ILG

0,14

photo grille transmitter

W(S41.2)

X3

S41.2_ILG

ASD_ILG

0,14

photo grille receiver

WA4

X1

A4

lflex-110

0,75

photocell 2 (optional)

WA5.1

X3

A5.1

LIYY_757

0,5

contact bar

WA5.2

A5.2

S51.2-S;S51.2-E

LIYY_757

0,14

Diodes

WA7

X1

A7

lflex-110

0,75

radar
membrane keypad

WF

X9

SF

Flach

0,14

WH1

X1

H1

lflex-110

0,75

traffic light

WS30.1

A5.2

S30.1

LIYY_757

0,14

contact bar receiver

WS30.2

A5.2

S30.2

LIYY_757

0,14

contact bar transmitter

WS31

X8

S31

lflex-110

0,75

external emergency-OFF 2

WS32

X1

S32

lflex-110

0,75

impulse up

WS33

X1

S33

lflex-110

0,75

impulse down

WS34

X8

S34

lflex-110

0,75

impulse operation

WS35

X8

S35

lflex-110

0,75

deactivation

WS36

X8

S36

lflex-110

0,75

intermediate stop

WS41.1

X3

S41.1

ASD_757

5x

0,34

photo grille transmitter

WS41.2

X3

S41.2

ASD_757

5x

0,34

photo grille receiver

WS51

A5.2

S51.1

LIYY_757

0,14

crash protection

19

21
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

cable overview

H27-510

Gesamt

Blatt

23

20

parts list

SEUO001D.F01 / LIE / 12.07.2007

TERM

MENGE
ME
1

SCHEMATIC LOCATION

A3

MANUFACTURER
Sarel GmbH

Erweiterungsplatine
einkanaliger Schleifendetektor

TST-SVEK-1

800244

Erweiterungsplatine
zweikanaliger Schleifendetektor

TST-SVEK-2

800245

Lichtschranke mit Reflektor

Gehuse Kabellose Impulsbertragung

OPT-CF 1163
10004300

5.0

A5.2

Platine Kabellose Impulsbertragung

800232

FRABA AG

013551

FRABA AG
FRABA AG

Batterie fr kabellose Impulsbertragung

MN 1400, 9800mAH

5.0

Carl Scobel GmbH

A5.2

Batteriehalter 2XUM2 Softedge

Halter 2xUM2-DK

5.0

Reichelt Elektronik

A6

Funkempfnger HER1 868,3 MHz

HER1 868,3MHZ

Platine Funkempfnger 868,3MHz1K

Funkempfnger 433 E - 11 poliger Sockel

LW433E2-43840

SMD Funk

9.1

RS Component

A7

Radar-Bewegungsmelder

MWD BP-A

Digitaler Endschalter

DES

GFA

6.7

GFA

EWS

Lichtschranke Einweg o. Kabel EWS/EWE

Sicherungsautiomat, 3-fach, 16AT

Sicherungsautomat B6A

3.1

F2

CA60N16A-D
27091

Schneider Electric

370493

MULTI9 C60 N 6A B

Schneider Electric

370433.1

Schneider Electric

Bremsgleichrichter 275V schaltbar

011157

Ampelgehuse Rot/Grn Nr. 0671/s-2-E

800252

Hauptschalter VCD0 Not-Aus

3.5

H1
6.1

Q1

010681
010073

3.2

G1

800403

Witt Sensorik

7.1

F1

013561

800187.1

8.5

DES

013562

011948

9.0

A6.2

013550

800456

9.2

A6.1

POS.

010797.2

Deutsche Telemecanique

FRABA AG

5.0

A5.2

ARTICLE NUMBER

8.3

A5.1

BG

SPACIAL 3D

8.0

A4

MODEL NUMBER

Schaltschrank 400x600 mm
RAL 7035

8.0

A3

DESIGNATION

VCD0

Deutsche Telemecanique

3.1

Schneider Electric

380003

20

22
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

parts list

H27-510

Gesamt

Blatt

23

21

parts list

SEUO001D.F01 / LIE / 12.07.2007

TERM
SCHEMATIC LOCATION

R1

DESIGNATION

MODEL NUMBER

MENGE
ME
1

Bremswiderstand 100W/100R

BWD250100 100R

Not-Aus Taster

XB7ES542P
XB7 ES542P

MANUFACTURER

4.0

Stck

S7

4.0

Deutsche Telemecanique
Tlmecanique

Not-Aus Schild

Deutsche Telemecanique

Stck

S11

Schneider Electric

Schalter E 221-10

E221-10

Opto Empfng.kabell. Datenbertr. Antr.s.

FRABA AG

5.5

FRABA AG

S30.2

Opto Sender kabell. Datenbertr. Lagers.

FRABA AG

5.6

FRABA AG

S41.1

Lichtgitter Relaisausgang /S

ELG6-1380R523S02

7.3

Sick
RS Component

S41.1_ILG

Lichtgitter ILG Bauhhe 1590mm

685-ILG-24/06-L-K1-10

7.7

Strack Lift Automation


Strack Lift Automation

S41.1_ILG

Lichtgitter ILG Bauhhe 510mm

685-ILG-06/06-L-K1-10

7.7

Strack Lift Automation


Strack Lift Automation

S51.1

Feder m.Schalter 7000mm

Felsch Spritzgu GmbH

5.8

Felsch Spritzgu GmbH

S51.2

Federschalter m. Diode Antr.seite rechts

5.3

S51.2
SF

78-004-006

Felsch Spritzgu GmbH

78-004-007

Felsch Spritzgu GmbH

Federschalter m. Diode Antr.seite links

5.3

800464
800465
011864
013563
013564

ZEW

Weidmller

012337

Reihenklemme 1,5mm
1xSchneidklemm/1xZugfeder

IDU 1.5N/ZF

Weidmller

012338

PE-Reihenklemme 1,5mm
1xSchneidklemm/1xZugfeder

IPE 1.5N/ZF

Weidmller

012339

Endplatte

IAP1.5N

Weidmller

012340

Endwinkel

ZEW

Weidmller

012337

17

Reihenklemme 1,5mm
1xSchneidklemm/1xZugfeder

IDU 1.5N/ZF

Weidmller

012338

3.2

X1

800226

370079

3.2

X1

013724

Endwinkel

3.2

X0

013725

3.2

X0

011442

Folientastatur klein 100x60mm

3.2

X0

011440

6.5

X0

3.2

POS.

370018

8.8

S30.1

ARTICLE NUMBER

011461

3.7

S7

BG

21

23
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

parts list

H27-510

Gesamt

Blatt

23

22

parts list

SEUO001D.F01 / LIE / 12.07.2007

TERM

MENGE
ME
2

SCHEMATIC LOCATION

X1

MODEL NUMBER

MANUFACTURER
Weidmller

012339

Endplatte

IAP1.5N

Weidmller

012340

Steckverbinder Anbaugehuse 16pol.

ILME GmbH

370500

5.4

ILME GmbH

X2

ARTICLE NUMBER

IPE 1.5N/ZF

3.2

X2

BG

PE-Reihenklemme 1,5mm
1xSchneidklemm/1xZugfeder

3.2

X1

DESIGNATION

Steckverbinder Buchseneinsatz 16pol. CNF

ILME GmbH

5.4

ILME GmbH

POS.

370550

22
Datum

Hrmann KG
Verkaufsgesellschaft
D-33803 Steinhagen

Bearb.
Gepr.
nderung

Datum

Name

Norm

06.01.2009
Urspr.

Ers.f.

Ers.d.

parts list

H27-510

Gesamt

Blatt

23

23

Instruction Manual

TST FUE1SE
TST FUE2SE
TST FU3.1SE
Date : 11.11.2005

Hrmann KG Verkaufsgesellschaft
D-33803 Steinhagen

H_FUX_GB

11.11.2005

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx

page 2 of 19

General hints
Copyright 2003 by
HRMANN KG VERKAUFSGESELLSCHAFT

This manual is dedicated to those persons projecting and planning the TST FUE control system of HRMANN KG
VERKAUFSGESELLSCHAFT. Initiation should only be done by a skilled electronics engineer who is acquainted
with the safety standards of electric driving- and automation systems. A description of the control system resp.
relevant excerpts hereof have to be put at the users disposal when passing on the control system.
The data indicated in this manual may be altered without previous notice.
With the edition of this manual, all previous editions become void.
Composition of the information given in this manual has been done to the best of our knowledge. HRMANN KG
VERKAUFSGESELLSCHAFT does not guarantee the correctness of the details given in these instructions and may
not be held liable for damages ensuing from incorrect installation.
Description of the products, their application, features and performance data are no assured characteristics and are
subject to technical alterations.
Since, despite of all our efforts, errors may not be completely avoided, we are always grateful for your useful tips.
The installation instructions given in this manual are based on advantageous boundary conditions. HRMANN KG
VERKAUFSGESELLSCHAFTS does not give any guarantee promise for perfect function of the control system in a
cross surrounding.
Warranty claims towards HRMANN KG VERKAUFSGESELLSCHAFT are restricted to the customer and may not
be transferred. The warranty promise comprises only those products delivered by HRMANN KG
VERKAUFSGESELLSCHAFT. We are non-liable for the whole system.

Software
HRMANN KG VERKAUFSGESELLSCHAFT reserves the right to alter or extend its software without prior notice,
as long as functionality remains untouched resp. is adjustable. Before applying individual software, the correctness
of the software has to be acknowledged and a written declaration of consent regarding these alterations has to be
obtained from by the customer
Our guarantee comprises repair in our workshop. The software versions resulting hereof have to be installed by the
customer. Guarantee for software is restricted to reproducable errors.
HRMANN KG VERKAUFSGESELLSCHAFT has no obligation to make alterations to products already delivered.

Please read the operating - and safety instructions thoroughly before


setting the control system into operation!
The customer or third parties are not permitted to change the program.
VERKAUFSGESELLSCHAFT may not be held liable for defects ensuing from these changes.

H_FUX_GB

11.11.2005

HRMANN

KG

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx

page 3 of 19

CONTENTS
1
2
3
4

Installation of the control system------------------------------------------------------------4


Electric connection -------------------------------------------------------------------------------4
Safety instructions--------------------------------------------------------------------------------5
Standard configuration of the control system ------------------------------------------6
4.1
4.2
4.3
4.4

5
6
7

Standard configuration and input functions -----------------------------------------------------------------6


Standard configuration and function of the key pad ------------------------------------------------------7
Standard configuration and function of optional plug-in modules -------------------------------------7
Standard configuration and function of outputs ------------------------------------------------------------7

Customer parameters----------------------------------------------------------------------------8
General instructions for parameter adjustment mode ----------------------------- 10
Use of electronic limit switches ----------------------------------------------------------- 13
7.1
Application of the absolute value transmitter DES ------------------------------------------------------ 13
7.1.1
Initiation of the door system with absolute value transmitter DES as limit switch ----------13

Appendix A: trouble-/error messages diagnosis and trouble-shooting ------- 15


APPENDIX B: list of messages ------------------------------------------------------------------ 19

H_FUX_GB

11.11.2005

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx

page 4 of 19

Installation of the control system


Please check the control system with regard to transport- or other damages prior to assembly.
Damages inside the control system may lead to serious consequential damages at the control
system.
This control system is intended to be installed directly at the wall. Fixing is done with the help of
mounting lugs, which are located at the bottom side. The control system has to be installed in a
way that the cable entries point towards the bottom. Please make sure, that mechanical vibrations
caused by the door are not transmitted on the control system (e.g. installation on a brick wall).
In a distance of 10 centimeters above and below the control system housing there must not be
any objects obstructing the air circulation arround the heat sink located at the back side of the
control system.
The position for installation has to be chosen in a way that direct insolation as well as other
atmospheric influences are avoided. In order to provide dead mans operation by the key pad, the
door has to be visible from the place of installation of the control system.
Please avoid touching the electronic parts and especially parts of the processor circuit, since this
circuit contains very sensitive electrostatic components, which might be damaged or destroyed by
electrostatic discharge.

Electric connection
Please observe the rules for the prevention of accidents as well as operating- and installation
instructions (such as DIN-VDE0100/0113/0160) when installing and commisioning.
Connection, testing and maintenance work on the control system should only be done when the
door is stationary. Please observe especially those points indicated under safety regulations.
This control system is designed for a nominal voltage of FUE1/FUE2 :230V 50Hz / 60Hz FU3 : 400
V, 50...60Hz. The permissible supply voltage has to be between FUE1/FUE2 :160VAC bis 265AC
FU3 : 200 ... 480 VAC 10% (180 ... 528 VAC). In case of supply voltages of more than FUE1/FUE2
:270VAC FU3 : 540 VAC, the control system may be seriously damaged.
The supply line has to be protected with 16A, type c trip curve (circuit breaker).
In case that the control system is protected by an earth leakage device, you have to take into
consideration that the leakage current of the EMV-filters and the shieldings of the power supply
leads may be higher than 30mA when the motor is running. The leakage current depends
considerably on the length of shielded cable and increases if the clock frequency of the output
transformer is intensified. The leakage current of a motor not running is 3,5 mA.
The control voltage of 24V for external devices, control circuits, all insert cards and for the
electronic limit switch is protected by a self-resetting semiconductor fuse. After having operated
the fuse, resetting is done after removing the cause of the overload or short circuit and a switchedoff time of at least five seconds.
All control voltage inputs are galvanicly separated from the supply network by the P.C.B.
insulation. Furthermore, all components to be connected to the control system have to have at
least one base isolation with a rated voltage of > 230 V.
As experience shows, high-speed pvc / plastic doors are very susceptible to high electrostatic
charging of the curtain. Discharge is done against the nearest point having a protective conductor
cover. In case that a discharge on the mass-bearing control inputs is caused by incorrect wiring,
the control system may be damaged. Especially the connections of the safety edge are extremely
endangered. As a countermeasure, we recommend a charge elimination device at the curtain.
For pin configuration, please refer to the enclosed wiring diagram.
Connections of the cables inserted into the control system should be short and lead directly to the
connecting terminal, if possible. (No kinks or loops).
In order to conform to the EMV rules, only shielded motor cables are allowed to be used. The
shield has to be connected to both sides (motor- and control side).
With regard to the inside of the control system, please make sure that the motor wiring is not cable
tied up with the supply main or control wiring. A maximum of 30m motor cable length is allowed.
Connections of induction loops have to be kept separate of all other conncecting lines and with the
greatest possible distance towards the motor wiring and live lines. Loop connections have to be
twisted in pairs up to the internal terminals of the control system.
When using incremental transmitters and absolute value transmitters for position indication, we
also recommend connection by shielded cables.
For wiring diagram, please see separate drawing in the appendix.
W A R N I N G: Never leave swarf or cable off-cuts in the enclosure of the control system.
Conductive elements may lead to severe damages at the printed card.

H_FUX_GB

11.11.2005

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx

page 5 of 19

Safety instructions

Please read the following installation- and connection instructions carefully prior to
initiation and operation of the control system:
All installation, commisioning and maintenance work has to be carried out by qualified
engineers.
The Following Standards have to be observed : VDE 0100, VDE0105, VDE0113, VDE0160,
VDE0700.
The control system may only be opened if the mains supply is switched off.
Do not operate the control system with the panel door open.
Even five minutes after switching off the supply mains, dangerous voltages occur at the
secondary circuit capacitor. The discharge time to reach voltages below 60VDC is 5 minutes max.
It is dangerous to touch internal control components within this period of time.
In case of a faulty power supply, the discharge time of the secondary circuit capacitors to reach a
voltage below 60VDC may be considerably extended. In this case, discharge times of up to 10
minutes are possible (e.g. fuse F3 is defective)
If the control voltage of 24V is shorted-out or extremely overloaded, the power supply does not
start, although the secondary circuit capacitors have been charged.
After having switched off the supply mains, the power supply is still supplied by the secondary
circuit capacitors for some seconds and keeps up its supply function for a certain period of time,
depending on the power supply load.
The processor circuit with seven segment display, EPROM and multiplexers are connected
directly with the supply mains by earth bonding. In case of control measurement to be carried out
, this has to be strictly observed (do not use measuring instruments with PE-cover on the voltage
circuit when measuring in the processor circuit)
Do not operate the control system without an earth cable being connected. If the earth cable is
not connected, dangerous voltages occur at the housing of the control system, due to induced
capacitance. Connection of the earth cable has to be carried out according to EN50178, chapter
5.2.11.1 concerning increased leakage current >3,5mA.
Do not operate the control system with a defective keypad or window. Defective keypads or
windows have to be replaced. In order to avoid damages at the keypad, do not touch it with sharp
objects. In general, the keypad is designed for finger-touch operation only.
Prior to the initial connection of the control supply, you have to make sure that the safety edge
evaluation card is placed in the right position. If the card is plugged in at the wrong place, severe
damages at the control system may be caused.
When operating the door in dead mans operation, you have to make sure that the door opening
can be seen by the operator, since in this operation mode, safety devices such as safety edge or
safety beam do not work.
Disregard of the safety instructions may endanger your health or lead to damages at the control
system.
There is no guarantee for the completeness of these safety instructions. Should you have questions
concerning our product, please contact your supplier.
The manufacturer has thoroughly checked hardware and software, as well as the product
information, but however, cannot guarantee for absolute correctness.
Marking of the device (type plate with name and address of the manufacturer, serial number, model
designation, supply voltage and temperature range) has to be done by the user.

H_FUX_GB

11.11.2005

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx

page 6 of 19

Standard configuration of the control system

4.1
Input

Standard configuration and input functions


Message Connec-

Functional description

tion
terminal

standard contact type


n.c.

NA1

E.211

78

EMERGENCY STOP external 1

NA 2

E.212

9 10

EMERGENCY STOP external 2

IN 1

E.101

OPEN 1
11 12 Opening until upper end of travel, activation of auto close- and safety

IN 2

E.102

13 14 CLOSE

n.o.

E.103

GO - Pullswitch
15 16 Stepping switch function : OPENE*CLOSEOPEN (2x operation

n.o.

IN 3

Emergency shutdown by safety circuit


n.c.

Emergency shutdown by safety circuit


n.o.

clearance time
Automatic access without safety clearance time

until Eo) without auto close time, with safety clearance time
n.c.

Light Barrier
IN 4

E.104

17 18

Active in upper end of travel and part open stop, as well as acces:
after reversing auto close time as before,
after reversing approach of the last final upper position
n.c.

Light Barrier 2, detektion of through passing


Active in upper end of travel and part open stop, as well as acces:
after reversing auto close time as before,
after reversing approach of the last final upper position!

IN 5

E.105

19 20

IN 6

E.106

21 22 Locking in close end postion

n.o.

IN 7

E.107

23 24 Switch off of the open holding time

n.o.

IN 8

E.108

25 26 Switch off of part open

n.o.

IN 9

E.109

27 28 Open 3

n.o.

IN 10

E.110

29 30 Reference switch

n.c.

H_FUX_GB

Approach of part open, activation open holding and safety clearing time

11.11.2005

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx

4.2

page 7 of 19

Standard configuration and function of the key pad


Input

Connector
plug No.

Standard configuration

Membrane key OPEN

X12.1 X12.2

OPEN

Membrane key STOP

X12.1 X12.3

STOP

Membrane key CLOSE

X12.1 X12.4

CLOSE

4.3

Standard contact type

Dead man + automatic opening to part open limit and


fully open limit, with auto close type
STOP and wait for next command

n.o.

Dead man + automatic closing close limit switch

n.o.

n.o.

Standard configuration and function of optional plug-in modules

optional
plug-in modules

Connector
plug No.

Evaluation for safety


contact edge with closing
function
alternative:
evaluation for safety
contact edge with opening
function
Induction loop detector,
channel 1

X10 X11

X10 X11

X5 X6

Induction loop detector,


channel 2

X5 X6

Radio module channel 1

X8 X9

Radio module channel 2

X8 X9

4.4

Standard function

Standard
configuration

Standard function

Plug-in module type

switched off,
(self-identification of plugin card when switching on
current supply)
switched off,
(self-identification of plugin card when switching on
current supply)
OPEN

Stop / reverse with dual safety stop circuit and line


monitoring 1,2k or 8,2k (optional)

TST SUKSA-A

Stop / reverse with dual safety stop circuit and line


monitoring 1,2k or 8,2k (optional)

TST SSKS-A

Opening to fully open position with auto close time

TST SVEK1-A

Channel 1 : OPEN
Channel 2 : OPEN

Channel 1: opening to upper end position with auto


close time.
Channel 2: opening to upper end posion with auto
close time
Opening to upper end position without auto close time

TST SVEK2-A

Opening to upper end position without auto close time

TST SFFE2-A FM 433MHz

single-channel:
OPEN / STOP
/CLOSE/STOP
2x single-channel:
OPEN/STOP//CLOSE/
STOP

TST SFFE2-A FM 433MHz

Standard configuration and function of outputs

Outputs
Relay
K3
Relay
K4
Relay
K5

Connecting
terminal No.
7 8- 9
S C -
no com - nc
1 3 5
S - C -
no com nc
2 4 6
S - C -
no - com nc

H_FUX_GB

Standard
configuration

Standard function

Standard-contact type

brake supply
with 230VAC

Supply for brake 230VAC, alternative volt-free clearing of brake


e.g. DC circuit without fuse J11

volt-free position
indication door open

operated when final open position or part open stop is reached, or


phase-selective message with plugged-in fuse J12 (3,15A-max.)

change-over contact

volt-free position
indication door closed

operated when final close position is reached or phase-selective


message with plugged-in fuse J13 (3,15A max.)

change-over contact

11.11.2005

n.o., contact max. 1A


(protected with J11)

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx

page 8 of 19

Customer parameters

This control system offers the customer a simple possibility to change a small selection of parameters
without activating the service system.
Operating
control

1.
STOP

3.

Operate
emergency stop
STOP
(permanent)
OPEN
(permanent)

OPEN
or
CLOSE

1.

3.
oder

4.

STOP (short)
Open
Close
STOP (long)

oder

5.

Display

prevent each run


operate STOP-key and hold it
actuated
additionally operate OPEN-key
and hold it
Parameter selection in open
parameter adjustment mode
select the desired parameter

pending messages are shown on the


display, e.g.:
after having waited for 2 seconds:
in parameter adjustment mode

the parameter value may be viewed or


changed (see below)
Display varies according to selection

# N A #
E. 2 0 1
P. 0 0 0
P. . . .

Parameter processing in case of


selected parameter
Control system in parameter
indication of the desired parameter name
adjustment mode

C
2.

Reaction

Opening of the level customer


parameters

A
2.

Function / remarks

STOP (short)

STOP (short)

P. 0 1 0
the current parameter value is indicated:
Viewing of parameter
1 0
Open-key, in order to increase if the current parameter value is changed,
the decimal points will flash
1 1
parameter value
Close-key, in order to reduce
0 9
parameter value
the parameter is stored when no more
store the adjusted parameter value
points are flashing
1 1
abnormal termination, the initial
reject the adjusted parameter value parameter value is indicated again
1 0
change over to indication of
indication of paramter name
P. 0 1 0
parameter name
go on to B or D

D
STOP

Release
emergency stop
(pull)

H_FUX_GB

Leaving parameter adjustment


mode
Parameter adjustment mode is
abandoned immediately, door
operation is re-activated

11.11.2005

Paramer adjustment mode may be


abandoned at any time. The last value
stored is kept automatically.

....

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx

page 9 of 19

The following parameters are accessible to the end user and may be changed.
ex
works

Range Customer parameters

P.
000

cT

010
011
920

To
T1
FS

pres.
Condition

Display of door cycle counter


Display: 1234567 1234. -actuate .567
Display:
67
67
Auto close time 1 (upper end of travel - Eo)

[s]
0..200 0: closing automatism de-activated
[s]
Auto close time 2 (Part open position - E1)
0..200 0 = switched off
Display error memory / disorders

10
10

opening by repeat operation of foil-stop,


change over by foil-open/foil-close
closing by operating foil-stop
leaving by termination "Eb-".

Eb 1 error messages 1 (current)

Eb
Eb
Eb
Eb

1
2 Eb 2 error messages 2
3 Eb 3 error messages 3
4 Eb 4 error messages 4

Eb

- Eb - termination

resp.
resp.
resp.
resp.

Er-Er-Er-Er--

Eb 1

(display noEr: no errors)

H_FUX_GB

11.11.2005

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx

General instructions for parameter adjustment mode


Operating
control

1.

Pull mains plug


or switch off
main switch

0/off

2.
SERVICE

3.
1
on

4.
STOP

Switch on
Service DIPSwitch S1

oder

5.

OPEN
or
CLOSE

STOP (short

STOP (long)
STOP (short)

Reject adjusted parameter value

CLOSE

STOP (short)

Release emergency stop (pull)

If service mode is active, the first


decimal point flashes

Change over to indication of


parameter name
proceed from B or D
Leaving parameter adjustment
mode
Parameter adjustment mode is
abandoned immediately, door
operation is re-activated

. . . .

Contents of indication depends on control


status
The parameter adjustment mode may be
activated directly with the mushroomshaped emergency shutdown key

Parameter selection in open


parameter adjustment mode
Select the desired parameter
WARNING:
Not all parameters can be seen and The parameter value may be looked at or
changed (see below)
changed directly. This depends on
Display varies according to selection
the password indicated under
P.999 and the pre-adjusted
positioning under P.200
Parameter processing in case of
selected parameter
Indication of desired parameter name
Control system in parameter
adjustment mode
The current parameter value is indicated:
Reading of parameter
Open-key, in order to increase
parameter value
Close-key, in order to reduce
parameter value
Store adjusted parameter value

OPEN

D
STOP

Service operation is activated,


close switch cabinet

direct change-over from door to


parameter adjustment mode

1.

4.

Display

7-segment display extinguishes delayed


after some seconds

(observe safety regulations)

Operate
emergency stop

Switch off all-pole supply

Switch on control system

oder

Reaction

Plug in mains
plug or switch
on main switch

3.

Function /
remarks
Opening of parameter adjustment
mode

2.

page 10 of 19

P 0 0 0
P. . . .

P. 0 1 0
1 0
If the current parameter value is changed,
the decimal points will flash
1 1
0 9
The parameter is stored, when no more
points are flashing
1 1
Abnormal termination, the initial
parameter value is indicated again
1 0
Indication of parameter name
P. 0 1 0

Parameter adjustment mode may be left


at any time using emergency shutdown.
The last value stored is kept
automatically.

....

After service operation, the DIP-switch S1 has to be in OFF position again!


Therefore, the control system has to be switched off as well.

H_FUX_GB

11.11.2005

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx

page 11 of 19
ex
works

Range Commisioning parameters

P.

Display of door cycle counter


Display: 1234567 1234. -operate .567
Display:
67
67
[s]
Auto close time 1 from full open position
0..200 (upper end of travel - Eo) see also. P.5x4

000

cT

010

To

011

T1

[s]
Auto close time 2 from part open position
0..200 (part open stop position - E1) see also P.5x4

140
145
210

bo

[%]
0..30
[%]
0..30
0..5

221
231
310
350

uK

read only

10

0: auto close deactivated

10

0 = switched off

bc
Ei

oK

F1
F5

Voltage increase of U/f-characteristic curve (Boost) when opening

Performance increase in the lower speed range

Voltage increase of U/f-characteristic curve (Boost) when closing

Performance increase in the lower speed range

Selection of the position to be calibrated by dead mans operation ("teach


in"):
0: no none/abortion
1: Eu lower and fully open limit switch, (for part open stop, see "e1")
2: Eo fully open limit switch (for part open stop, see "e1")
3: uo upper and lower limit switch
4: E1 limit switch part open stop ("e1" is ignored)
5: al (all) upper and lower limit switches & part open stop
Correction value for lower end of travel

[Ink]
125 (is set on 0 in case of re-calibration!)
[Ink] Correction value for upper end of travel
60 (is set on 0 in case of re-calibration!)
[Hz] Prorated frequency for quick opening
6..200 (operating frequency until upper pre-limit switch) adjust pre-limit switch, if necessary
[Hz] Prorated frequency for quick closing
6..200 (operating frequency until lower pre-limit switch) adjust pre-limit switch, if necessary

0
0
60
40

WARNING: observe closing pressure at safety edge!

910

An

0..14

Selection of display mode


(on demand, by STOP-key resp. while motor is running)

Au
control sequence (automatic)
F
[Hz] present frequency
i
[A] present motor current (> 1A)
u
[V] present motor voltage
I
[A] part open circuit current (active current)
U
[V] part open circuit voltage
c
[C] temperature of output transformer
C
[C] temperature of brake resistor
L
[100ms] latest running time
only useful for electronic limit switches:
P
[Ink] actual postion running
r
[Ink] actual reference postion
K1
[dig] actual channel 1-value of TST PB / GFA-DES
K2
[dig] actual channel 2-value of TST PB
a
[dig] actual driver voltage (18V)
b
[dig] actual reference voltage (2,5V)

H_FUX_GB

11.11.2005

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx

920

Display of error memory / failure

FS

opening by re-operating the foil-stop,


change-over by foil-open/foil-closed
closing gy operating foil-stop.
leaving by abortion "EB-".

Eb 1
Eb 2
Eb 3
Eb 4
Ebcl
Eb -

980

SE

page 12 of 19

0..3

(Display noEr: no errors)


Eb 1 error messages 1 (latest)
resp. Er- Eb 2 error messages 2
resp. Er- Eb 3 error messages 3
resp. Er- Eb 4 error messages 4
resp. Er- Ebcl delete the complete error memory
Eb - abortion
Extended service
0: Au automatic (impulse opening- and closing)
1: Hc dead man Closed (manual closing/automatic opening)
2: Hd dead man (manual opening- and closing)
3: nF*1 emergency run (WARNING: all safety regulations are ignored!)
*1

999

PA

H_FUX_GB

1..3

Eb 1

Adjustment gets lost after switching off (is set on manual mode)

Selection of parameter adjustment mode (adjustment gets lost after switching off):
you can...
... change the customer- and initiation parameters
... read all parameters and change only the initiation parameters
... read and change all parameters (extended parameter adjustment mode)

11.11.2005

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx

7
7.1

page 13 of 19

Use of electronic limit switches


Application of the absolute value transmitter DES

7.1.1 Initiation of the door system with absolute value transmitter DES as limit switch
The following chart may be used as an instruction for the testing and adjustment of door systems with
the absolute value transmitter TST PB-A (or GfA-DES) as a limit switch, and contains some important
hints to be observed. For parameterization handling, please refer to the chapter General instructions
for parameter adjustment mode.
The paramters listed below are only a small excerpt from the available parameters necessary for
commissioning.
Display

1. Switch off the control system and bring the door in neutral position.
Check the electric supply according to pin configuration plan!
2. Put the DIP-switch S1 on service mode (ON-position)
3. Operate the EMERGENCY STOP PUSHBUTTON, plug in the mains plug resp. switch
on the current supply.
4. Select parameter P.100 (for nominal motor frequency, see type plate)
5.

Open the parameter nominal motor frequency and compare it with the data on the type plate of the
motor according to the following chart:
In case of deviation, the values have to be corrected!

6. Select parameter P.101 nominal motor current


7. Open parameter motor current and compare it to the indications on the type plate. Motor
current on the actuator type plate and set value should be identical,
in case of deviation, the value has to be adjusted appropriately!
Maximum value for 0,75kW converter 4,7A
Maximum value for 1,5kW converter 9,0A
Maximum value for 4kW converter TST-FU3
10A
This parameter is the basis of motor protection and control functions. However, it is still
necessary to connect a thermoelectric sensing device for temperature control of the motor in the
safety circuit.

8. Select parameter P.102 power factor cos


9. Open the parameter power factor and compare it with the indications on the motor type
plate.
Both values should be identical, if not, the parameter value has to be adapted!
The given standard value 80 corresponds to power factor cos 0,80
10. EMERGENCY STOP pull button

11. Open the calibration mode with STOP

P. 0 0 0
P. 1 0 0
1 0 0
P. 1 0 1
4. 7

P. 1 0 2
8 0
E. I C H
E. I. E. u.
E. 0 5 0

1. Bring the door in the desired end position by using the CLOSE button

E. I. E. u.
E. 0 9 0

If the door moves in the wrong direction: wrong motor connections, switch off the
control system and exchange 2 motor connections, proceed from 16.
3. Store the desired fully closed position with STOP (long)
2.

E. I. E. o.
E. 0. 0. 0.

4. Bring the door in the desired fully open position.

H_FUX_GB

11.11.2005

E. 0 0 0
Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx

page 14 of 19

E. I. E. o.
5. Store the desired fully open position with STOP (long)

E. 0 5 0

6. After having stored the fully open position, the display indicates ' Hd '

`
#
P.
~

7. Press the EMERGENCY STOP button, select P.980, open it and change
the value to 0 (automatic mode)
8. After having stored the operation mode automatic, the display shows Eo . Now, the
control system is released for automatic operation.
9.

H
N
9
E

d
A
8
o

When using automatic operation, the close stop position has to be checked and adjusted, if
necessary:
close stop position ...... too high :
reduce limit switch band uE (P.223) and correct
end of travel with parameter P.221, if necessary (adjust negative values)

extend limit switch band uE (P.223) and correct end of travel with
parameter P.221, if necessary (adjust positive values)
10. When using automatic operation, the fully open position has to be checked and adjusted,
if necessary: fully open position...
... too high: reduce limit switch band oE (P.233) and correct end of travel with
parameter P.231 (adjust negative values)
... too low: extend limit switch band oE (P.233) and correct end of travel with
parameter P.231 (adjust positive values)
11. In order to terminate adjustment, switch off the control system and bring DIPswitch S1 in OFF position (service mode off).
After that, current supply may be switched on again. The control system is ready for
work.
... too low:

Further extensive adjustment possibilities of the control system can be taken from the chapter
General plan of parameters. Several parameters are not visible/adjustable before switching
on the extended parameter adjustment mode (see also parameter P.999).

H_FUX_GB

11.11.2005

Hrmann KG Verkaufsgesellschaft

#
0
~

instruction manual TST-FUx

page 15 of 19

Appendix A: trouble-/error messages diagnosis and trouble-shooting


Meaning

Symbol

F.0
F.000

Condition of
control system

Possible cause

Door position outside at the top

Condition:
Closing:

failure
dead man

parameter value for upper emergency limit switch is too small fully
open limit switch range (limit switch band is too small
mechanical brake is defective or adjusted incorrectly

Door position outside at the bottom

Condition:
Opening:

failure
automatic
or dead man

parameter value for lower emergency limit switch is too small,


lower limit switch range (limit switch band ) is too small
mechanical brake is defective or adjusted incorrectly

F.020

Operation time has been exceeded


(during opening, closing or dead man)

Condition:
Closing:
Opening:

failure
dead man
dead man

F.030

Contouring error (change in position of


door is smaller than expected)

Condition:
Closing:
Opening:

failure
dead man
dead man

present motor operation time has exceeded pre-set maximum


operation time
in case that mechanical limit switches are used, one of the limit
switches has not operated
door or motor is blocked
performance is too low for starting torque
speed is too low
mechanic limit switch has not been freed or is defective
Fixing device at axle of poti / of incremental transmitter has not
been tightened.
wrong positioning system (P.200)

(dead man operation only


for pre-set contouring
error time; after that,
repeat operation)

Actual direction of rotation differs from


the expected direction

Condition:
Closing:
Opening:

failure
dead man
dead man

F.043

Failure of pre-limit switch for the safety


beam

Condition:
Closing:
Opening:

failure
dead man
automatic

F.050

Position of reference switch deviates


from the admitted range by more than
15%

Condition:
Closing:
Opening:

failure
dead man
dead man

F.2

Safety- /
emergency stop chain

Condition: emergency
stop
No travelling motion
possible!

F.201

internal emergency "mushroom key" is


operated

or watchdog (computer control)

F.211

external emergency stop 1 is operated

F.212

external emergency stop 2 is operated

F.3
F.300

Comment

bring back to admitted end-of travel range by dead man s closing

increase parameter value for upper emergency switch(P.239)

Increase parameter value fo fully open limit switch range (P.232)


when failure is eliminated, automatic change of condition towards STOP
or upper end of travel

bring back to admitted end of travel range by dead man/automatic


opening

increse parameter value for lower emergency limit switch (P.229)

increaase parameter value for lower limit switch range (P.222)


as soon as failure has been eliminated, autom. change of condition
towards STOP, "lower end of travel" or opening mode

parameter values for operation time control are too low


(P.410 / P.415 /P.419)
switch off the control and turn it on again

The values of the electronic position transmitter serve as a basis in order to


check whether the door has exceeded the adjusted values of the upper
emergency limit switch (P.239) or the fully open limit switch range (P.232)

Motor operation time is monitored by the control system. In case that it


exceeds the maximum operation times (P.410 / P.415 / P.419) the
control system changes over to "trouble" and immediately brakes the motor

check, whether the door is mechanically blocked and eliminate


increase voltage (boost) of the corresponding direction of motion
(P.140 / P.145)

increase speed of the corresponding direction of motion (P.310 /


P.350)

extend rise time of the contouring error detection (P.450)

check position and function of the mechanical limit switches


Check fixture of poti axle/ incremental transmitter with regard to tight fit
after repair, operate the door once again, disorder is volatile
switch the control system off and on again

if incremental transmitters are used:interchange channels A and B

increase parameter values for the release of the mechanical brake


(P.185 / P.186)

Despite of active operation, no change of position of the door/actuator is


recognized during a defined period of time

check switch position resp- function, re-adjust resp. exchange, if


necessary

deactivate pre-limit switch function, if not needed (P.403)


as soon as disorder is eliminated, automatic change of condition towards
STOP (short dead man closing, if necessary)
Place reference switch closer to selected end of travel

The control system checks the pre-limit switch of the safety beam in cyclic
periods. This pre-limit switch has operated in a not permitted position.

General state of door

F.005

F.031

Trouble-shooting
(corresponding parameters P.XXX)

Failure of safety edge


Number of edge-treleass for closing
mode has reached the adjusted limit

H_FUX_GB

Condition:
Closing:
Opening:

if incremental transmitters are used:channels A and B have been


mixed up
sense of rotation of motor has been mixed up compared to
calibration
too much sagging when started, brake is released too early
the pre-limit switch or the safety beam remains occupied in middleresp. upper end of travel

reference switch triggers permanently (defective)


reference switch is situated too far away from the selected reference
end of travel
reference switch is fixed at wrong end of travel

The values of the electronic position transmitter serve as a basis in order to


check whether the door has exceeded the value of the lower emergency limit
switch (P.229) or the lower limit switch range (P.222) .

Change of position takes place opposed to expected direction

The reference switch for the synchronization of the incremental transmitter


is situated off the permitted range.

emergency stop chain was interrupted from input internal


emergency shutdown without a parameterization mode having been
selected.
internal parameters or EEPROM-checks were faulty, more details
regarding possible cause are released by pressing the STOPmembrane key.
emergency stop chain was interrupted from input 1 (connection
terminals 1 and 2)

automatic, hint for internal error memory is filed.

automatic, hint for internal error memory is filed.

emergency stop chain was interrupted from input 2 (connection


terminals 3 and 4)

automatic, hint for the internal error memory is filed

Travelling motions may be avoided resp. interrupted by the emergency


shutdown switch located at the housing of the control system.
Furthermore, the emergency shutdown switch may be used in order to
switch over to the parameterization mode. This error message is only
emitted, if the emergency shutdown switch has been operated without the
parameterization mode being active.
Each of the single emergency stop chains is controlled separately. As soon
as an interruption in the emergency stop chain is recognized, this error
message is emitted and filed in the error memory.
Hereby, even subsequent interruptions become diagnosable

parameterized, maximum number of safety edge releases during one


door cycle has been exceeded

remove obstacle in door sector


dead man closing until lower end of travel has been reached and
recognized

The control system counts the number of safety edge releases during each
closing mode of a door cycle. In case that the reading of the counter exceeds
the maximum number of reversions, the control system stops the door in the

failure
dead man
automatic

11.11.2005

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx


Meaning

Symbol

page 16 of 19
Condition of
control system

Possible cause

F.301

Failure of safety edge (message is


emitted by module)

F.311

Failure of pre-limit switch for the safety


edge

F.350

Defective safety edge recognition


(coding pin or parameter adjustment)

no module is plugged in, but logged in by parameter


the control system has been set into operation with another module
than the one presently plugged-in

F.391

redundant system: 2. Release is wrong


(redundancy)

F.392

Tested system: test is not successful (no


release inEu)

moving load in non-defined area


evaluation module is defective/module for tested system has been
plugged in
wrong adjustment of safety edge pre-limit switch, or defective
defective evaluation module
defective safety edge

line break towards safety edge, no edge connected, wrong edge


moving load
safety edge evaluation has been selected with parameter P.400
but module is not plugged in (in connection with message F.400)
pre-limit switch used for switch-off of the safety edge resp. reversion
of safety edge release remains occupied also in upper end of travel.

Trouble-shooting
(corresponding parameters P.XXX)

Comment

recognized

increaase parameter value for number of reversions. (P.401)


as soon as disorder is eliminated, automatic change of condition towards
STOP

repair edge resp. wiring


as soon as failure is eliminated, automatic chnage of condition towards
STOP

the maximum number of reversions, the control system stops the door in the
upper position.

The control system checks the pre-limit switch of the safety edge in cyclic
periods. This pre-limit switch is operated in a non-permitted position.

check switch position resp. function, re-adjust resp. exchange, if


necessary

deactivate pre-limit switch function, if unnecessary


as soon as disorder has been eliminated, automatic change of condition
towards STOP (short dead man closing, if necessary)

reintegrate plug-in module


deactivate/activate safety edge (P.400)
as soon as failure has been eliminated, automatic change of condition
towards STOP

repair edge resp. moving load

exchange evaluation module


switch off control system and turn it on again

reduce parameter value of safety edge pre-limit switch (P.440)

repair safety edge


switch off control system and turn it on again

When the insert card is logged on, the control system checks if this card is
really connected. By using parameter P.400 Furthermore, the control
system checks, if a card has been plugged in but has not been logged on by a
parameter.
The control system has recognized an error between the safety edge and the
the evaluation module. This means that one of the two channels is disturbed.
Safety edge is checked in the lower end of travel. For this purpose, the edge
resp. the evaluation module has to transmit a release during a defined period
of time after having passed the pre-limit switch in closing mode.

general hardware

F.4
F.400

Hardware-reset of control system has


been recognized

Former condition remains


unchanged

severe interferences on the supply voltage


internal watchdog has operated
RAM-error

F.410

Excess current(motor current or FU-total


current

Former condition remains


unchanged

Excess voltage in part open circuit

Former condition remains


unchanged

wrong nominal motor frequency has been adjusted


voltage increase is too high ("boost)
wrong motor dimensioning
defective motor winding
brake resistor is disturbed/ defective / not existing)
supply voltage is too high
motor feeds too much energy in generating service, since it has to
reduce the doors kinetic energy

F.420

F.430

Excess temperature in heat sink

Condition:
Closuing:
Openingt:

failure
dead man
automatic

load on output transformers resp. brake resistor is too high


clock frequency of output transformer is too high (parameter
P.160)

F.440

Excess temperature of brake resistor

Condition:
Closing:
Opening:

failure
dead man
automatic

load on output transformers resp. brake resistor is too high

F.5

The safety edge evaluation module indicates a failure, which lasts longer
than a defined period of time

automatic trouble-shooting

time-controlled, volatile
adjust nominal motor frequency (P.100)
reduce voltage increase (boost) of the corresponding direction of
motion (P.140 / P.145)

check supply voltage with regard to excess values

reduce generating service of the motor (self-locking gear)

reduce parameter values for the coreesponding end of travel (P.310


/ P.350)

increase parameter values for ramp times of the corresponding


direction of motion (P.321 / P.341 / P.361 / P.381)
as soon as disorder has been eliminated, automatic change of condition
towards STOP

let the control system cool down

reduce clock frequency, if necessary (P.160)


as soon as the temperature has dropped below the limit, the control
system automatically changes to STOP condition

let the control system cool down.

reduce speed (P.310 / P.350)


as soon as temperature has dropped below the limit, the control system
changes automatically to STOP condition

Safety The control system has received a hardware-conditioned reset. All


internal checks are carried out and the control system is initialized, if
necessary This may lead to the situation that a current process is interrupted
or a new command is ignored.
The overall current of the motor circuit has exceeded the first of two limits.

The control system monitors the voltage of the part open circuit, which has
exceeded the first peak value. Reason for this is the motors generating
service, which means that the motor is driven by the door during the
stopping process.

The temperature of the heat sink for the power semiconductor has exceeded
a first limit. The door can be moved up to the upper end of travel in
automatic mode and remains in this position until the heat sink temperature
has fallen below a defined value. Dead man operation is still possible.
The temperature of the brake resistor has exceeded a first limit. The door
can be moved up to the upper end of travel and remains in this position until
the temperature of the brake resistor has fallen below a certain value. Dead
man operation is still possible.

general hardware failure / errors

F.510

Excess voltage

Condition:
failure
Travelling motion is
temporarily impossible!

wrong nominal frequency has been adjusted


excess voltage increase ("boost)
wrong motor dimensioning
defective motor windings

F.515

Motor protection has recognized excess


current

Condition:
failure
Travelling motion is
temporarily impossible!

wrong adjustment of motor diagram (nominal motor current)


excess voltage increase ("boost")
wrong motor dimension
defective motor winding

H_FUX_GB

time-controlled, volatile
adjust nominal motor frequency (P.100)
reduce voltage increase (bost) of the corresponding direction of
motion (P.140 / P.145)
defect has been eliminated, automatic change towards STOP

time-controlled, volatile

coordinate initiation parameters with motor data (see type plate)


(P.100 / P.101 / P.102)

reduce voltage increase (boost) of the corresponding direction of


motion (P.140 / P.145)
as soon as disorder has been eliminated, automatic change of condition
towards STOP

11.11.2005

The overall current of the motor circuit has exceeded a second limit
although a failure has been recognized.

During a longer period of time the control systems internal motor


protectiom function has recognized a motor current which exceeds the
parameterized limit curve (P.101)

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx


Meaning

Symbol

page 17 of 19
Condition of
control system

Possible cause

Trouble-shooting
(corresponding parameters P.XXX)

Comment

time-controlled, volatile
adjust nominal motor frequency (P.100)
reduce voltage increase (boost) of corresponding direction of motion
(P.140 / P.145)
as soon as disorder has been eliminated, automatic change of condition
towards STOP

check supply voltage with regard to excess values

reduce generating operation of the motor (self-locking gear)

increase parameter values for the corresponding direction of motion


(P.321 / P.341 / P.361 / P.381)
re-start FUE (switch off and on again)

install separate supply line with appropriate conductor cross section


as soon as disorder has been eliminated, automatic change of condition
towards STOP
Check the load on ther 24V supply and eliminate excess load, if necessary
as soon as disorder has been eliminated, automatic change of condition
towards STOP

let the control system cool down

reduce clock frequency (P.160)


as soon as temperature has fallen below the limit, the control system
automatically changes to STOP condition

let the control system cool down

reduce speed (P.310 / P.350)


as soon as temperature has fallen below the limit, the control system
automatically changes to STOP condition

The overall current of the motor circuit has exceeded its utmost limit which
leads to a hardware emergency shutdown.

F.519

IGBT-driver component has recognized


excess current

Condition:
failure
Travelling motion is
temporarily impossible!

short circuit at motor terminal


wrong adjustment of nominal motor frequency
excess voltage increase ("boost")
wrong motor dimensioning
defective motor winding

F.520

Excess voltage in part open circuit

Condition:
failure
Travelling motion is
impossible!

brake resistor is disturbed / defective /not existing


input supply voltage is too high
motor feeds too much energy back into the generating service, since
it has to reduce the doors kinetic energy

F.521

Undervoltage in part open circuit

input supply voltage is too low


excess load / disorder of output transformers resp. brake resistor

F.524

no external 24 V supply

overload, but no short circuit.


in case of a short circuit of the 24V the control supply is not started!

F.530

Excess temperature of heat sink

Condition:
failure
Travelling motion is
temporarily impossible!
Condition:
failure
Travelling motion is
impossible!
Condition:
failure
Travelling motion is
impossible!

excess loadd on output transformers resp. brake resistor


clock frequency of output transformer is too high.

F.540

Excess temperature of brake resistor

Condition:
Closing:
opening:

load on output transformers resp. brake resistor is too high

for electronic limit switches: after invocation of works parameter


activation, (parameter P.990) the corresponding positioning system
has not been parameterized
for mechanical limit switches: at least one limit switch does not
conform to the parameterized active condition.

use a shielded cable

error will be volatile, as soon as a correct transmission is carried out


as soon as the error has been eliminated, the control system automatically
changes to STOP condition

use a shielded cable

error will be volatile, as soon as correct transmission is carried out.


as soon as the error has been eliminated, the control system automatically
changes to STOP condition

use shielded cable

error will be volatile, as soon as transmission is carried out


as soon as the error is eliminated, the control system automatically
changes to STOP condition

use shielded cable

error will be volatile, as soon as the position is within window range


as soon as the error has been eliminated, the control system automatically
changes to STOP condition

use shielded cable

error is volatile, as soon as the distance of the two channels has been
corrected
as soon as the error has been eliminated, the control system changes to
STOP condition

initialize/correct limit switch in calibration mode by dead man


operation
error will be volatile, as soon as calibration has been carried out resp. the
causes do not exist anymore.
as soon as the error has been eliminated, the control system automatically
changes to STOP condition

Position indication (e.g. upper and lower


limit switch simultaneously)

F.720

Synchronization of position indication


by incremental transmitter

F.750

Log transmission error

Condition:
Closing:
Opening:

failure
dead man
dead man

defective hardware or disturbed environment

F.751

Synchronization FUB <-> Poti


evaluation of TST PB-A

Condition:
Closingt:
Opening:

failure
dead man
dead man

defective hardware or disturbed environment


TST PB evaluation electronics is defective (plug-in module)

F.752

Timeout during log transmission

Condition:
Closing:
Opening:

failure
dead man
dead man

interface circuit is defective/ interrupted


defective evaluation electronics TST PB (plug-in module)
defective hardware or disturbed environment

F.760

Position is off window range

Condition:
Closing:
Opening:

failure
dead man
dead man

potentiometer drive resp. potentiometer is defective


defective TST PB evaluation electronics (plug-in module)
defective hardware or disturbed environment

F.761

Distance between channel 1 and channel


2 is exceeds the permitted window

Condition:
Closing:
Opening:

failure
dead man
dead man

potentiometer drive is defective


defective TST PB evaluation electronics (plug-in module)
defective hardware or disturbed environment

F.762

Wrong lower end of travel or


channel switching values

Condition:
Closing:
Opening:

disorder
dead man
dead man

fully open limit switch Eo resp. part open limit switch E1 has
exceeded the valid limit range
control system has not yet been initialized
rated positions during calibration were wrong resp. are no longer
plausible

F.9

The control system monitors the voltage of the part open circuit, which has
exceeded a second peak value. Rason for this is the generating operation of
the motor, which means that the motor is driven by the door during stopping
mode.
The control system monitors the voltage of the part open circuit. This serves
as supply voltage for the converter. In case that the voltage of the part open
circuit is too low, the door may be operated only under restricted conditions.
The control system monitors the supply voltage and emits this error message
in case of overload.
Temperature of the power semiconductors heat sinkhas exceeded the fully
open limit.

The temperature of the brake resistor has exceeded a second limit. The door
can only be operated in dead mans mode, until the temperature of the brake
resistor has fallen below a certain value.

general positioning

F.7
F.700

disorder
dead man
dead man

set parameter sfor adjustment of active conditions (P.594 and


P.604) on the limit switches used
set parameter for adjustment of position indication (P.200) on the
appropriate positioning mode

The control system permanently checks the plausibility of the door position.
The condition, that limit switches in the upper and lower positions are
operated simultaneously, is recognized as error.

The positions detected by the displacement transducer are transmitted to the


control system by an interface. These transmissions are permanently
checked. In case of incorrect logs, this error message is emitted.
The positions detected by the displacement transducer are transmitte to the
control system by an interface. These datea transmission have to take place
within a certain period of time. In case that this time cannot be obserfedeven
after several trials, the appropriate error message is emitted.
the positions detected by the displacment transducer are transmitted to the
control system by an interface. The control system expects new data within
a certain period of time. However, if no transmission has taken place after
certain time, this error message is emitted.
The data detected by the position evaluation device deviate extremely from
the data acquired before (position skip). In case that the value exceeds the
defined window range even after several checks, this value is considered to
be not plausible.
The position evaluation device TST PB acquires and transmits the position
in two separate channels, so that the control system always gets two position
values. These two values differ by a certain amount. If the amount is too
small, this error message is emitted.
The control system periodically checks its position data. If one of these
values seems to be no plausible, this error message is emitted.

internal systematic errors:

H_FUX_GB

11.11.2005

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx


Meaning

Symbol

F.920

internal 5 V-supply is defective

F.921

internal18 V-supply is defective

F.922

Emergency stop chain is incomplete

page 18 of 19
Condition of
control system
Condition:
failure
Travelling motion is
impossible!
Condition:
failure
Travelling motion is
impossible!
Condition:
failure
Closing:
dead man
Opening:
dead man

exchange control system, if defective

hardware failures

exchange control system, if defective

not all EMERGENCY STOP inputs are bridged separately,


althought the whole emergency stop chain is bridged
redundancy check of emergency stop chain has operated

bridge all inputs of the emergency stop chain separately (i.e. terminal
1with 2 and terminal 3 with 4), do not mix (see terminal connecting
plan)

defective hardware or disturbed environment

re-start FUE (switch off and on again)


if error occurs again, call customer service

wrong EPROM-Code
defective hardware or disturbed environment

defective hardware or disturbed environment

defective hardware or disturbed environment

new EPROM-version with changed parameters


control system has not yet been initialized

re-start FUE (switch off and on again)


error will be volatile, as soon as new factory setting P.990) has been
carried out
automatic change of condition towards STOP or to the corresponding end
of travel, if error has been eliminated.

All parameters which are permanently filed in the control system, are
secured by a test sum, so that possible disorders may be recognized and
eliminated. Should these data be irretrievably destroyed, this error message
is emitted.

new EPROM-Version with changed EEPROM structure


control system has not yet been initialized

re-start FUE (switch off and on again)


error will be volatile, as soon as new factory settinghas been carried out
(P.990)
automatic change of condition towards STOP or to corresponding end of
travel, as soon as error has been eliminated

Apart from the parameters, the control system also stores other important
ratings in a special sector of its memory. These permanently stored values
are secured by a check sum, so that possible failurescan be detected and
eliminated. In case that these data are irretrievably destroyed, this error
message is emitted.

new EPROM version


control system has not yet been initialized

re-start FUE (switch off and on again)


error will be volatile, as soon as converter parameters are plausible again
(P.140 bis P.160)
automatic change of condition towards STOP or to corresopnding end of
travel, as soon as error is eliminated

re-start FUE (switch off and on again)


error will be volatile, as soon as ramp parameters are plausible again
(P.310 bis P.399)
automatic change of condition towards STOP or to corresponding end of
travel, as soon as error has been eliminated.

re-start FUE (switch off and on again)


error will be volatile, as soon as all ratings are correct
as soon as the error has been eliminated, the control system automatically
changes to parameterization mode
check parameters or call original set of parameters (P.990)

The integrated converter has its own block of parameters. These data are of
great importance to the safety of the system. Prior to each travel, the control
system checks this parameter block. In case that these values are not
plausible, this error message is emitted.

F.931

ROM-failure

F.932

RAM-failure

F.952

Interrupt system is disturbed

F.960

Wrong parameter check sum

F.961

Check sum exceeds calibration values


etc.

F.962

Converter parameters are not plausible

F.963

Ramp pameters are not plausible

Condition:
disorder
Travelling motion is
impossible!

new EPROM version


control system has not yet been initialized

F.964

Program version / manufacturers code

Condition:
failure
Travelling motion
impossible!

new EPROM version


control system has not yet been initialized

F.970

Plausibility parameter block is disturbed

Condition:
Closing:
Opening:

new EPROM version


control system has not yet been initialized
one of the parameters is not plausible

failure
dead man
automatic

Comment

hardware failures

External watchdog is defective

Condition:
failure
Travelling motion is
impossible!
Condition: emergency
stop
Travelling motion is
impossible!
RUN-LED shines
permanently
Condition: emergency
stop
Travelling motion
impossible!
RUN-LED shines
permanently
Condition:
failure
Travelling motion is
impossible!

Trouble-shooting
(corresponding parameters P.XXX)

F.930

H_FUX_GB

Condition:
failure
Travelling motion is
impossible!
Condition:
failure
Travelling motion is
impossible!
Condition:
disorder
Travelling motion is
impossible!

Possible cause

re-start FUE (switch off and on again)


if error occurs again, exchange EPROM, otherwise call customer
service

re-start FUE (switch off and on again)

if error occurs again, call customer service


automatic acknowledgement and change of condition towards STOP

11.11.2005

switch off and on again, call customer service, if necessary

The internal supply voltage exceeds the valid range, which impairs safe
functioning of the control system. The cause of this may be a failure in the
hardware.
The supply voltage exceeds the valid range, which impairs safe functioning
of the control system. One reason for this may be a failure in the hardware.
The control system performs cyclic checks of the emergency stop inputs. If
a defined hierarchy is not observed during a release, the control system
recognizes that there must be an error in the evaluation electronics resp. that
the wiring is defective.
Parallel to the internal watchdog, the control system is monitored by an
external watchdog. For safety purposes, this part of the circuit is checked.
This message occurs, if the external watchdog is defective.
The control system carries out cyclic checks of its program memory, the
EPROM. If the program recognizes a wrong check sum, all functions
leading to a movement of the door are immediately blocked.
The control system carries out cyclic checks of its working memory, called
RAM. In case that the program recognizes a defective storage location, all
control functions leading to a movement of the door are immediately
blocked for safety reasons.
The control system carries out cyclic checks of its interrupt system. During
this check, an error has been detected.

The control system has a block of parameters, which is responsible for the
behaviour of the actuator. These data are of special importance to the safety
of the system. Apart from global parameters, the control system checks this
parameter block prior to each travel. Should these values not be plausible,
this error message is emitted.
An automatic check is carried out in order to prevent that, due to the
exchange of program memories resp. change of program versions, an
uncontrollable behaviour of the control system is created by wrong
parameters.
An internal test has proved that at least one parameter is not plausible.

Hrmann KG Verkaufsgesellschaft

instruction manual TST-FUx


APPENDIX B: list of messages
STOP
_Eu_
Eu
Clo
-EoEo
OP
-E1E1
FAIL
EICH
NA
NOTF
'Hd'
ParA
SYNC
'Au'
'Hc'
FUE
E.i.E.u.
E.i.E.o.
E.i.E.1.
S.y.E.u.
S.y.E.o.
S.y.E.1.
S.y.op
S.y.cL
S.y.c
Hd.cL
Hd.oP
Hd.Eu
Hd.Eo
Hd.Ao
I.100
I.150
I.160
I.199
I.200
I.202
I.203
I.300
I.301

Stop / Reset condition, wait for the next incoming command


lower end of travel Eu
lower end of travel has been locked opening mode impossible (e.g. lock)
active closing
upper end of travel Eo
upper end of travel has been locked closing mode impossible (e.g. safety loop)
active opening
middle end of travel E1 (part open stop position)
middle end of travel is locked closing mode impossible (e.g. safety loop)
failure only dead man operation possible, eventually automatic opening
calibration adjustment of end of travel positions during dead man travel
(for absolute value transmitter "TST PB-A") start operation with stop-key
emergency shutdown operation impossible, hardware safety chain is interrputed
emergency service dead man operation without considering safety etc.
Manual operation dad man operation
parameterization
synchronization (incremental position transmitter /limit switch pos. Unknown
automatic marks change from condition "manual operation to automatic
semiautomatic service marks change of conndition from "manual operation to"
Hsemiautomatic"
first display after switch-on (power Up and self-test)
Status messages during calibration
calibration of lower end of travel is requested (in dead man service)
calibration of upper end of travel is requiested (in Totmannfahrt)
calibration of part open stop position E1 (in dead man service)
Status messages during synchronization:
synchronization of lower end of travel is requested
(dead man service or wait for start conditions)
Synchronization of upper end of travel is requested
(dead man service or wait for start conditions)
synchronization of part open stop position E1 (in dead man service)
automatic opening up to mechanical limit stop, after that automatic synchronization of
upper end of travel
automatic closing down to mechanical limit stop, observing safeties, then automatic
synchronization in lower end of travel
automatic closing is locked , cause is indicated upon request
Status messages during dead man service:
dead man closing (membrane key: Closed)
dead man opening (membrane key: OPEN)
lower end of travel has been reached, no further dead man closing possible
upper end of travel has been reached, no further dead man opening possible rreicht,
keine
weitere the
Totmann-Auffahrt
mglich
has exceeded
permitted Eo-position
(dead man opening impossible)
Information messages during automatic operation:
too much speed when upper end of travel is reached
too much speed when lower end of travel is reached
permanent-OPEN is still active
door cycle counter is not plausible (initialize again parameter)
reference position has been recognized and taken over (for the first time)
no reference position
failure of reference position
locked via sluice
open command will be given to door 2

noEr
Er-Prog

Information messages during parameterization:


error memory: no error stored
error memory: error, but no corresponding message has been found
programming message during execution of original param. resp. default set

Prog

programming message during execution of original param. resp. default set

H_FUX_GB

page 19 of 19
E.0
E.000
E.050
E.090
E.1
E.101
E.102
E.103
E.104
E.105
E.106
E.107
E.108
E.109
E.110

Failure messages F.000....F.499:

general inputs
OPEN-key on key pad
STOP-key on key pad
CLOSE-key on key pad
input 1:
input 2:
input 3:
input 4:
input 5:
input 6:
input 7:
input 8:
input 9:
input 10:

Standard configuration (see also P.5xxx)


open-command
close-command
single-channel command
safety beam
external stop
intern. stop positi / referemce.sw.
upper pre-limit switch
lower pre-limit switch
upper e.o.t. switch / incremental 1
lower e.o.t. switch / Incremental 2

config.param.
P.51x
P.52x
P.53x
P.54x
P.55x
P.56x
P.57x
P.58x

terminal
11
13
15
17
19
21
23
25

+24
(12)
(14)
(16)
(18)
(20)
(22)
(24)
(26)

P.59x
P.60x

27
29

(28)
(30)

E.2
E.201
E.211
E.212

Safety / emergency stop chain


internal emergency shutdown "mushroom key" is released
external emergency shutdown 1 is released
external emergency stop 2 is released

E.3
E.360
E.363
E.370
E.373
E.379

General safety edge (plug-in module)


safety edge short circuit (from integrated evaluation)
safety edge open circuit (from integrated evaluation)
safety edge activated (from optional plug in module)
safaty edge evaluation plug in module indicates failure
safaty edge evaluation plug in module recognized

E.4
E.401
E.402

Wireless plug-in module


radio channel 1
radio channel 2

E.5
E.501
E.502

Induction loop evaluation device -plug-in module


detector channel 1
detector channel 2

E.9
E.900

Internal inputs:
fault signal of triggering component

r.xxx
T.xxx

8
8
10

general door status


upper door position is off permitted range
lower door position is off permitted range
operation time has been exceeded (during opening, closing or dead man)
contouring error (change of door position is smaller than expected)
acquired sense of rotation deviates from expected sense of rotation
failure of pre-limit switch for the safety beam
reference switch position deviates from permitted range by more than 15%.

F.2
F.201
F.211
F.212

Safety / emergency stop chain


intern. emerg. Stop "mushroom key" or watchdog (compu. Monit.) is operated
external emergency stop 1 is operated
external emergency stop 2 is operated

F.3
safety edge / Integrated evaluation

Failure of safety edge


Safety edge / plug in module

F.360
F.361
F.362
F.363
F.364
F.365

Short circuit at safety edge


number of activations exceeded
redundancy short circuit
safety edge open circuit
test in endposition not successful
redundancy open circuit

F.4
F.400
F.410
F.420
F.430
F.440

general hardware
hardware-reset of control system has been recognized
excess current (motor current or FU-overall current)
excess voltage in part open circuit
excess temperature of heat sink
excess temperature of brake resistor

F.371
F.372
F.373
F.374
F.379

number of activations exceeded


redundancy active
safety edge fault
test in endposition not successful
plug in module not recognized

error messages F.500...F.999:

Service displays:

F.xxx
I.xxx
i.xxx
U.xxx
u.xxx
c.xxx
C.xxx
L.xxx
P.xxx
P xxx
K xxx
K.xxx
a.xxx
b.xxx

X
79-

F.0
F.000
F.005
F.020
F.030
F.031
F.043
F.050

[Hz] present frequency


[A] present part open circuit current (active current)
[A] present motor current
[V] present part open circuit voltage
[V] present motor voltage
[C] present heat sink temperature
[C] present temperature of brake resistor
[100 ms] latest measured operation time
[Inc] present position indication
[Inc] present unfiltered position indication
[digit] present value channel 1
[digit] present value channel 2
[V] present driver voltage (18V)
[b] present reference voltage (2,5V)
Expiration of delay times:
expiration of safety clearance phase before automatic closing resp. opening
expiration of auto close time

11.11.2005

F.5
F.510
F.515
F.519
F.520
F.521
F.524
F.530
F.540

general hardware failures / -errors


excess current
motor protection has detected excess current
IGBT-driver component has detected excess current

F.7
F.700
F.720
F.750
F.751
F.752
F.760
F.761
F.762

general positioning
position indication (e.g. upper and lower limit switch simultaneously)
synchronization of position indication by incremental detection
log transmission errror
synchronization FUB <-> pot evaluation of TST PB-A
time-out during log transmission
position exceeds the window range
distance channel <-> channel 2 exceeds the permitted window
wrong lower end of travel or channel change values

F.9
F.920
F.921
F.922
F.930
F.931
F.932
F.952

internal systematic errors:


internal 5 V supply is defective
parameter check sum
F.960
internal 20 V-supply is defective
check sum via calibration values
F.961
incomplete emergency stop chain
converter param.not plausible
F.962
external watchdog is defective
ramp param. Not plausible
F.963
ROM-error
new program version!
F.964
p
RAM-error
Param.
Processing is disturbed
F.970
Iinterrupt system is disturbed

excess voltage in part open circuit


undervoltage in part open circuit
ext. 24 V supply is missing (possibly short-circuit)
excess temperature of heat sink
excess temperature of brake resistor

Hrmann KG Verkaufsgesellschaft

Hrmann KG Verkaufsgesellschaft

2 Possibilities of adjustment

4 Outputs and LED-display

2.1

4.1

Sensitivity

By adjusting the sensitivity, you determine a change of inductivity for each


channel, which a vehicle has to cause in order to set the appropriate output
of the detector.
Sensitivity adjustment is done separately for each channel with the help of 2
DIP-switches.

Signal indication is done via open-collector outputs pin 4 and 5 at plug X1.
GND-reference is X1 pin 3.
Open-Coll. output 1/2

D-33803 Steinhagen
Sensitivity level

Operating instructions
plug-in induction loop detector
TST SVEK1 - 1-channel detector
TST SVEK2 - 2-channel detector
2.2

Service

(0,27% f/f)

ON
1

OFF/OFF

(0,09% f/f)

ON
1

ON/OFF

(0,03% f/f)

ON
1

OFF/ON

4 high

(0,01% f/f)

ON
1

ON/ON

Holding time

Channel 2

Channel 1

Channel 1: DIP-switch 3
Channel 2: DIP-switch 7

5 minutes

ON
1

infinite

ON
1

8
8

4.3

OFF
ON

LED green

2.3

LED red

The actual frequency of the detector can be adjusted in two levels with the
help of DIP- switches 4 and 8.

Please read the operating- and safety


instructions thoroughly before putting the
traffic detector into operation !
General

Characteristic features:
The induction loop detector TST SVEK1/2 is a system for inductive
detection of vehicles with the following characteristic features:
evaluation of 1 (TST SVEK1) or 2 (TST SVEK2) loops
galvanic separation between loop and detector electronics
automatic system alignment immediately after activation
continuous resetting of frequency drifts
no mutual influence of loop 1 and 2 by multiplex processes on TST
SVEK2
sensitivity is independent of loop inductivity
occupied-message on LED-display
open-collector outputs
indication of loop frequency via LED
diagnosis possibility in connection with diagnostic unit VEK FG2

Frequency adjustment and rebalancing

ON
1

Loop occupied / loop fault

OFF

high

ON
1

ON

Green LED
Loop
control

Red LED
Loop
condition

Detector condition

off

off

No supply voltage

flashes

off

Alignment or frequency indication

on

off

Detector ready, loop free

on

on

Detector ready, signal indication

off

on

Loop fault

Indication of loop frequency

Approx. 1 s after the detector has been aligned, the loop frequency is
indicated via flash signals of the green LED. First, the 10kHz-digit is
indicated. In steps of a loop frequency of 10kHz, the green LED of the
detector channel will flash one time. After a break of 1s, the 1kHz-digit is
indicated in the same way. If the units digit has the significance of '0', 10
flash signals will be emitted. The 1kHz-flash signals will be a little shorter
than those of the 10kHz-digit.

units

5x 10kHz

7x 1kHz

5 Technical data

The admissible frequency range is 30kHz to 130kHz. The frequency


depends on the loop geometry, number of turns, inductivity resulting from
the loop supply line and the chosen frequency level.
A rebalancing can be manually triggered by changing the frequency
adjustment of a channel.
As soon as switched on, the detector automatically carries out an
adjustment of the loop frequency. In case of a short-term voltage loss of
<0,1s no rebalancing will take place.

3 Connections
Type
Supply
Supply
Open-Collector
Open-Coll. output
Open-Coll. output
Loop 2a
Loop 2b
--Loop 1a
Loop 1b

LED-display

The appliance may only be used for the purpose intended by the
manufacturer.
Please hand out the operating instructions to all users and keep it in an
easily accessible place.
Unacceptable changes as well as the use of spare parts and special
features which are not sold or recommended by the manufacturer of the
appliance, may cause fire, electric shocks and injuries. Therefore, such
measures lead to nonliability of the manufacturer and a lapse of all
warranty claims.
The appliance is subject to the manufacturers guarantee regulations in
the version valid at the time of purchase. We cannot be held liable for
improper or faulty manual or automatic adjustment of parameters resp.
improper use of the appliance.
Repair work may only be carried out by the manufacturer.
Installation, initiation, maintenance, measuring and adjustment of the
traffic detector should only be carried out by electricians with a good
knowledge of the rules for prevention of accidents.
When handling appliances that come into contact with electricity, the valid
VDE-regulations have to be observed. In particular, these are (list may be
incomplete): VDE 0100, VDE 0550/0551, VDE 0700, VDE 0711, VDE
0860, VDE 0105 as well as the rules for the prevention of accidents and
fire, VBG4.
All labour that is carried out on the appliance as well as its initiation, has
to conform to the national as well as the local electric regulations.
The user has to make sure that the appliance is installed and operated
according to the technical rules of the country of installation as well as
other regional regulations. Cable dimensions, protection, grounding,
disconnection, insulation control and excess current protection should be
especially considered.
According to machine directive 89/392/EWG, appendix IV, as well as
directive ZH1/494 of the German employers liability insurance
association, the appliance must not be used as a safety component
Systems with a high danger potential need additional safety contrivances!

1s

GND (PE)
24V DC
GND
Channel 2 *)
Channel 1
*)
*)

*) only TST SVEK2

Notice: GND-pin X1 / 1 has to be connected externally with PE !


H_SVEK

low

Example of a loop frequency of 57 kHz:


tens

Channel 1: DIP-switch 4
Channel 2: DIP-switch 8

low

Connection
X1 / 1
X1 / 2
X1 / 3
X1 / 4
X1 / 5
X2 / 1
X2 / 2
X2 / 3
X2 / 4
X2 / 5

Loop free / Reset / rebalancing

The green LED indicates that the detector is operable. The red LED
indicates activation of the relay output in dependence on the seizure
condition of the loop.

Holding time

Frequency

4.2

Detector conditions

high

Channel 1: DIP-switch 1, 2
Channel 2: DIP-switch 5, 6

The holding time can be adjusted with the help of DIP-switches 3 and 7.
After the holding time has expired, a "loop free" signal is emitted, followed
by an automatic rebalancing of the loops. The holding time starts as soon
as the loop is seized.

LED green
LED red
8 Frequency
7 Holding time
6 Sensitivity b
5 Sensitivity a
4 Frequency
3 Holding time
2 Sensitivity b
1 Sensitivity a

1 low

6 Safety instructions

Outputs

07.09.04

Dimensions
Protection class

80 x 45 x 17 mm (LxWxH without plug)


IP 00

Current supply

24V DC 20% max. 2,0W

Working temperature
Storage temperature
Air moisture

-20 C to +70 C
-20 C to +70 C
max. 95 % non-thawing

Loop inductivity
Frequency range
Sensitivity
Holding time

20-800 H, recommended 75-400uH


30-130 kHz in 2 levels
0,01 % to 0,27 % (f/f) in 4 levels
0,02 % to 0,54 % (L/L)
5 min. or infinite

Loop lead in
Loop resistance

max. 100 m
max. 20 Ohm (incl. supply line)

Open-Collector output

45V / 100mA / 100mW

Slow operation
Signal duration
Fall-delay time

50ms TST SVEK1, 100ms TST SVEK2


> 200 ms
25ms TST SVEK1, 50ms TST SVEK2

Connection

2x MOLEX-socket, series 3215, 5-pole

CE- standards

EN 61000-6-2, March 2000


EN 50081-1, March 1993

Notice
The indications made in these operating instructions may be altered without
previous notice.
With the edition of these instructions, all previous editions become void.
Composition of the information given in this manual has been done to the
best of our knowledge. Hrmann KG Verkaufsgesellschaft does not
guarantee the correctness of the details given in these instructions and may
not be held liable for damages ensuing from incorrect installation.
Since, despite all our efforts, errors may not be completely avoided, we are
always grateful for your useful tips.
The installation instructions given in this manual are based on
advantageous boundary conditions. Hrmann KG Verkaufsgesellschaft does
not give any guarantee promise for perfect function of the traffic detector in
cross surroundings.

Technische Mitteilung TM-EL19

Technical Bulletin TM-EL19

von

: Michael Lienenkmper

Author

: Michael Lienenkmper

Datum

: 17.11.06

Date

: 17.11.06

Verteiler

: Gruppe A, B, C, D, E, F

Distribution

: Gruppe A, B, C, D, E, F

ber

: Handsender HS-SEU

about

: Hand Transmitter HS-SEU

hier

: Programmieranleitung
.-.-.-.-.-.-.-.-.-.-

here

: Programming Manual
.-.-.-.-.-.-.-.-.-.-

Wichtige Hinweise
Handsender gehren nicht in Kinderhnde!

Important
Keep hand transmitters out of reach of children at all times!

Handsender drfen nun von Personen benutzt werden, die in die Funktionsweise der ferngesteuerten
Toranlage eingewiesen sind! Die Benutzung der Fernsteuerung muss mit Sichtkontakt zum Tor erfolgen! Die
Programmierung der Fernsteuerung ist immer in der Garage in Antriebsnhe vorzunehmen! Fr die
Inbetriebnahme der Steuerung sind ausschliesslich Originalteile zu verwenden!

Die Gerte sind vor direkter Sonneneinstrahlung zu schtzen!


Die Handsender sind vor Feuchtigkeit und Staubbelastung zu schtzen!

Hand transmitters should only be used by persons who know to operate the remote controlled door system.
Only use the remote control when the door is in your line of vision! Always programme the remote control
inside the garage near the door operator. When putting the remote control into operation, use original
components only!

Protect equipment from direct sunlight.


Protect hand transmitters against dampness and dust.

Bei Nichtbeachtung kann durch einen Feuchtigkeitseintritt die Funktion beeintrchtigt werden!

If damp is allowed to penetrate through non-observance of the above, the function of the
unit can be seriously impaired.

Zulssige Umgebungstemperatur : -20C is +65C


Die rtlichen Gegebenheiten knnen Einfluss auf die Reichweite der Fernsteuerung haben!
Erweitern der Fernsteuerung mit weiteren Handsendern HS-SEU1, HS-SEU2, HS-SEU4 oder HS-SEU6
Hinweis : Ist kein seperater Zugang zur Garage vorhanden, so ist jede nderung oder Erweiterung von
Programmierungen innerhalb der Garage durchzufhren. Bei der Programmierung und Erweiterung der
Fernsteuerung ist darauf zu achten, dass sich im Bewegungsbereich des Tores keine Personen und
Gegestnde befinden.
1. Der Sender, der den Code vererben soll (Vererbungssender) und den Sender, der den Code lernen
soll (Lernsender), direkt nebeneinander halten.
2. Die gewnschte Taste des Vererbungssenders drcken und gedrckt halten. Die LED des
Vererbungssenders leuchtet nun kontinuierlich.
3. Sofort danach die gewnschte zu lernende Taste des Lernsenders drcken und gedrckt halten die
LED des Lernsenders blinkt zuerst fr 4 Sek. langsam und beginnt bei erfolgreichem Lernvorgang
schneller zu blinken.
4. 4. Die Tasten vom Vererbungssender und vom Lernsender loslassen.
Eine Funktionsprfung durchfhren! Bei einer Fehlfunktion die Schritte 1 4 wiederholen.
Achtung! Whrend des Lernvorganges kann bei Bettigung des Vererbungssenders eine Torfahrt
ausgelst werden, wenn sich ein darauf programmierter Empfnger in der Nhe befindet!
Hinweis : Wenn whrend des langsamen Blinkens die Taste des Lernsenders losgelassen wird, wird der
Lernvorgang abgebrochen.

Hrmann KG Verkaufsgesellschaft

D-33803 Steinhagen

Temperature range : -20C to +60C

Local conditions may affect the range of the remote control.


Extending the remote control set by adding further hand transmitters HS-SEU1, HS-SEU2,
HS-SEU4 or HS-SEU6
Note : If the garage does not have a seperate entrance, you should carry out any programming alterations
or expansion inside the garage. When programming or expanding the remote control set, ensure that no
persons or objects are within the door`s range of movement.
1. Hold the transmitter which is to teach the code (teaching transmitter) and the transmitter which is to
learn the code (learning transmitter) directly alongside each other.
2. Press and hold the desired button on the teaching transmitter the LED on the teaching transmitter now
glows continuously.
3. Immediately after having done this, press and hold the button which is to learn on the learning
transmitter the LED on the learning transmitter initially flashes slowly for about 4 seconds, but then
starts flashing more rapidly once the learning procedure has been successfully completed.
4. Release the buttons on the teaching transmitter and learning transmitter.
Check that the transmitters are functioning correctly. If not, repeat steps 1 4.

CAUTION! Activation of the teaching transmitter during the learning procedure could set the
door in motion if there is an appropriately programmed receiver near to where you are
standing!
Note : The learning procedure will be aborted if you release the button on the learning transmitter during the
slow-flashing period.

Hrmann KG Verkaufsgesellschaft

D-33803 Steinhagen

Technische Mitteilung TM-EL20

Technical Bulletin TM-EL20

von

: Michael Lienenkmper

Author

: Michael Lienenkmper

Datum

: 17.11.06

Date

: 17.11.06

Verteiler

: Gruppe A, B, C, D, E, F

Distribution

: Gruppe A, B, C, D, E, F

ber

: Funkempfnger

about

: Radio Remote Control

hier

: Steckplatine 868MHz, Programmieranleitung

here

: receiver on p.c.b. 868MHz, 1 channel

.-.-.-.-.-.-.-.-.-.-

.-.-.-.-.-.-.-.-.-.-

Hinweis : GSM900 Handys knnen bei gleichzeitiger Benutzung die Reichweite der Funkfernsteuerung
beeinflussen.

Note : GSM 900 mobile phones used at the same time may influence the range of the radio remote control.

1. Die rote Taste (Programmiertaster) am Empfnger kurz bettigen die rote LED beginnt langsam zu
blinken.
2. Die gewnschte zu programmierende Taste des Handsenders mindestens 1 Sek. drcken. Der Abstand
zwischen dem Sender und dem Empfnger muss min. 1m betragen.
3. Bei erfolgter Programmierung beginnt die rote LED im Empfnger schneller zu blinken.
4. Die Taste des Handsenders loslassen.

1. Briefly press red button P (programming button) on the receiver the red LED starts flashing slowly.
2. Press the button you wish to programme on the hand transmitter for at least 1 second. The distance
between the transmitter and the receiver should be at least 1m.
3. When the programming has been completed, the red LED starts flashing more rapidly.
4. Release the button on the hand transmitter.

Nach Beendigung des Blinkens ist der Empfnger empfangsbereit.

Once the flashing stops, the receiver is ready for operation.

Zur berprfung ist die programmierte Taste des Senders zu bettigen, die rote LED des Empfngers
leuchtet auf.

To test the function, press the programmed button on the transmitter the red LED lights up when the output
is active.

Hinweis : Wenn 30Sek. nach Druck auf den Programmiertaster keine Programmierung erfolgt, erlischt die
langsam blinkende rote LED im Empfnger wieder.

Note : If no programming is carried out within 30 seconds of processing the P-button, the slow flashing red
LED on the receiver goes out again.

Abbrechen der Programmierung : Wenn der Programmiertaster 3-mal kurz innerhalb von 2 Sek. bettigt
wird, erlischt die rote LED und der Programmiervorgang wird abgebrochen.

Aborting the programming procedure : If after pressing the programming button this is pressed 3 times
within 2 seconds, the red LED goes off and the programming procedure is aborted.

Empfang : Wenn der Empfnger die Sendecodes empfngt, wird der Signalausgang fr 0,5 Sek. aktiv.
Whrend dieser Zeit leuchtet die LED am Empfnger.

Reception : When the receiver receives the transmitting codes that were programmed the signal output is
active for 0,5 seconds. During this time the LED on the receiver is on.
P-button

P-Taste

Hrmann KG Verkaufsgesellschaft

D-33803 Steinhagen

Hrmann KG Verkaufsgesellschaft

D-33803 Steinhagen

Wireless Impulse Transmission


Technical Data

Wireless Impulse Transmission


Technical Data
HOE_OPTOC_GB.DOC

1. Failure Diagnosis
1.2. OPT-CM 1163, #013550

1.1. OPT-CF 1163

YELLOW

Condition
active

Test

YELLOW

- wiring to control panel

Condition

Action

- change batteries

- none

2s

inactive

- wiring to control panel

safety edge activated

- wiring of safety edge

1s

2s

4 Hz

- mounting of safety edge


crash or missing light
transmission

RED

- alignment (straight way of light)

condition

Action
- change OPT-CM 1163

- optical axis interrupted


- dirt
- wiring Crash-Switch

- none

- batteries OPT-CM 1163


no operating voltage

RED

- wiring to control panel

condition

Action
- change OPT-CF 1163

- none

Hrmann KG Verkaufsgesellschaft

D-33803 Steinhagen

Hrmann KG Verkaufsgesellschaft

D-33803 Steinhagen

1.

2.

OPTOC_BAT.DOC