EPS 8000

5551125 kVA
Technical Specifications
06/2015

www.schneider-electric.com

Legal Information
The Schneider Electric brand and any registered trademarks of Schneider Electric
Industries SAS referred to in this guide are the sole property of Schneider Electric
SA and its subsidiaries. They may not be used for any purpose without the owner's
permission, given in writing. This guide and its content are protected, within the
meaning of the French intellectual property code (Code de la proprit
intellectuelle franais, referred to hereafter as "the Code"), under the laws of
copyright covering texts, drawings and models, as well as by trademark law. You
agree not to reproduce, other than for your own personal, noncommercial use as
defined in the Code, all or part of this guide on any medium whatsoever without
Schneider Electric's permission, given in writing. You also agree not to establish
any hypertext links to this guide or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the guide or its
content, except for a non-exclusive license to consult it on an "as is" basis, at your
own risk. All other rights are reserved.
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
As standards, specifications, and designs change from time to time, please ask for
confirmation of the information given in this publication.

5551125 kVA

Table of Contents
Important Safety Information .....................................................................5
Safety Precautions .....................................................................................6

Technical Data .............................................................................................8


Model List ..................................................................................................8
Input Power Factor .....................................................................................8
Efficiency in Normal Operation.....................................................................8
Efficiency Curves ..................................................................................9
Derating due to Load Power Factor ............................................................12
625 kVA/562 kW .................................................................................12
800 kVA/720 kW .................................................................................12
1000 kVA/900 kW ...............................................................................13
1100 kVA/990 kW................................................................................13
1125 kVA/1125 kW ..............................................................................14
Batteries ..................................................................................................14
Efficiency DC to AC.............................................................................14
Battery Run-Times Schneider Electric Qualified VRLA Batteries .............14
Battery Material Safety Data Sheet.......................................................16
Communication and Management .............................................................17
Auxiliary Wiring...................................................................................17
Compliance..............................................................................................18

Facility Planning ........................................................................................19


Input Specifications ..................................................................................19
Input Specifications for 555800 kVA Systems ......................................19
Input Specifications for 10001125 kVA Systems ..................................19
Bypass Specifications ...............................................................................20
Bypass Specifications for 555800 kVA Systems ..................................20
Bypass Specifications for 10001125 kVA Systems ...............................21
Output Specifications ................................................................................21
Output Specifications for 555800 kVA Systems ...................................21
Output Specifications for 10001125 kVA Systems ................................22
Battery Specifications ...............................................................................23
Battery Specifications for 555800 kVA Systems...................................23
Battery Specifications for 10001125 kVA Systems ...............................23
Recommended Cable Sizes ......................................................................24
Recommended Cable Sizes for 555800 kVA Systems..........................24
Recommended Cable Sizes for 10001125 kVA Systems ......................25
Physical ...................................................................................................25
Weights and Dimensions .....................................................................25
Shipping Weights and Dimensions .......................................................26
Clearance ..........................................................................................27
Environmental ..........................................................................................28
Elevation Derating Table......................................................................28
Heat Dissipation .................................................................................28

Drawings ....................................................................................................29
EPS 8000 800 kVA Single Module with Internal Bypass ...............................30
EPS 8000 800 kVA with Maintenance Bypass Cabinet.................................31
EPS 8000 1100 kVA Bottom Feed ...........................................................32
9905236B-001

5551125 kVA

EPS 8000 1100 kVA Top Feed ................................................................33


EPS 1100 kVA with Maintenance Bypass Cabinet Bottom Feed.................34
EPS 1100 kVA with Maintenance Bypass Cabinet Top Feed......................35

Options .......................................................................................................36
Hardware Options.....................................................................................36
Management ......................................................................................36
Configuration Options ...............................................................................36

Schneider Electric Limited Factory Warranty........................................37

9905236B-001

Important Safety Information

5551125 kVA

Important Safety Information


Read these instructions carefully and look at the equipment to become familiar with
it before trying to install, operate, service or maintain it. The following safety
messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a
procedure.

The addition of this symbol to a Danger or Warning safety


message indicates that an electrical hazard exists which will result in
personal injury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potential


personal injury hazards. Obey all safety messages with this symbol
to avoid possible injury or death.

DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.

WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.

NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.

Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
9905236B-001

5551125 kVA

Important Safety Information

Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

The product must be installed according to the specifications and


requirements as defined by Schneider Electric. It concerns in particular the
external and internal protections (upstream circuit breakers, battery circuit
breakers, cabling, etc.) and environmental requirements. No responsibility is
assumed by Schneider Electric if these requirements are not respected.

After the UPS system has been electrically wired, do not start up the system.
Start-up must only be performed by Schneider Electric.

Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
The UPS System must be installed according to local and national regulations.
Install the UPS according to:

IEC 60364 (including 60364441- protection against electric shock, 60364


442 - protection against thermal effect, and 60364443 - protection against
overcurrent), or

NEC NFPA 70

depending on which one of the standards apply in your local area.


Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

Install the UPS system in a temperature controlled area free of conductive


contaminants and humidity.

Install the UPS system on a non-inflammable, level and solid surface (e.g.
concrete) that can support the weight of the system.

Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
The UPS is not designed for and must therefore not be installed in the following
unusual operating environments:

Damaging fumes

Explosive mixtures of dust or gases, corrosive gases, or conductive or radiant


heat from other sources

Moisture, abrasive dust, steam or in an excessively damp environment

Fungus, insects, vermin

Salt-laden air or contaminated cooling refrigerant

Pollution degree higher than 2 according to IEC 60664-1

Exposure to abnormal vibrations, shocks, and tilting

Exposure to direct sunlight, heat sources, or strong electromagnetic fields

Failure to follow these instructions will result in death or serious injury.

9905236B-001

Important Safety Information

5551125 kVA

WARNING
HAZARD OF OVERHEATING
Respect the space requirements around the UPS system and do not cover the
products ventilation openings when the UPS system is in operation.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

WARNING
HAZARD OF EQUIPMENT DAMAGE
Do not connect the UPS output to regenerative load systems including
photovoltaic systems and speed drives.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

9905236B-001

5551125 kVA

Technical Data

Technical Data
Model List

EPS 8000 555 kVA

EPS 8000 625 kVA

EPS 8000 750 kVA

EPS 8000 800 kVA

EPS 8000 1000 kVA

EPS 8000 1100 kVA

EPS 8000 1125 kVA

Input Power Factor


UPS Rating

25% load

50% load

75% load

100% load

555 kVA/500 kW

0.88

0.88

0.88

0.89

625 kVA//562 kW

0.87

0.87

0.88

0.89

750 kVA/675 kW

0.80

0.83

0.88

0.86

800 kVA/720 kW

0.80

0.83

0.85

0.87

1000 kVA/900 kW

0.83

0.85

0.86

0.88

1100 kVA/990 kW

0.83

0.85

0.88

0.88

1125 kVA/1125 kW 480 V

0.86

0.92

0.92

0.922

1125 kVA/1125 kW 575 V

0.96

0.95

0.95

0.96

1125 kVA/1125 kW 600 V

0.94

0.91

0.90

0.90

Contact Schneider Electric for enhanced input power factor options.

Efficiency in Normal Operation

UPS Rating

25% load

50% load

75% load

100% load

555 kVA/500 kW

88.7%

93.0%

93.2%

93.1%

625 kVA//562 kW

92.4%

93.5%

93.3%

93%

750 kVA/675 kW

92.0%

94.0%

94.2%

94.0%

800 kVA/720 kW

92.0%

94.0%

94.0%

93.9%

1000 kVA/900 kW

90.1%

92.2%

92.1%

91.4%

1000 kVA/1000 kW 575 V

90.70%

93.20%

93.80%

93.90%

1000 kVA/1000 kW 600 V

91.00%

93.60%

94.00%

93.90%

1100 kVA/990 kW

90.1%

92.2%

92.0%

91.0%

1100 kVA/1100 kW 575 V

91.70%

93.40%

93.80%

93.80%

1100 kVA/1100 kW 600 V

91.50%

93.80%

94.00%

93.70%

1125 kVA/1125 kW 480 V

87.58%

93.60%

93.74%

93.43%

1125 kVA/1125 kW 575 V

91.70%

93.40%

93.80%

93.80%

1125 kVA/1125 kW 600 V

91.50%

93.80%

94.00%

93.70%

9905236B-001

Technical Data

5551125 kVA

Efficiency Curves
555 kVA/500 kW

625 kVA/562 kW

9905236B-001

5551125 kVA

Technical Data

750 kVA/675 kW

800 kVA/720 kW

1000 kVA/900 kW

10

9905236B-001

Technical Data

5551125 kVA

1100 kVA/990 kW

1125 kVA/1125 kW

9905236B-001

11

5551125 kVA

Technical Data

Derating due to Load Power Factor


625 kVA/562 kW
line voltage

PF

kVA

Lagging
480

0.8

580

480

0.9

625

Unity
480

562.5

Leading
480

0.95

515

480

0.9

480

800 kVA/720 kW
line voltage

PF

kVA

480

0.8

750

480

0.9

800

Unity
480

720

Leading
480

0.95

650

480

0.9

550

12

9905236B-001

Technical Data

5551125 kVA

1000 kVA/900 kW
line voltage

PF

kVA

480

0.8

900

480

0.9

1000

Unity
480

900

575

1000

600

1000

Leading
480

0.95

850

480

0.9

600

1100 kVA/990 kW
line voltage

PF

kVA

480

0.8

1000

480

0.9

1100

Unity
480

990

575

1100

600

1100

Leading
480

0.95

900

480

0.9

600

9905236B-001

13

5551125 kVA

Technical Data

1125 kVA/1125 kW
line voltage

PF

kVA

480

0.8

1125

480

0.9

1125

Unity
480

1125

575

1125

600

1125

Leading
480

0.95

956

480

0.9

619

Batteries
Efficiency DC to AC

Efficiency at
nominal
battery voltage
(%)

555 kVA/
500 kW

625 kVA/
562 kW

750 kVA/
675 kW

800 kVA/
720 kW

1000 kVA/
900 kW

1100 kVA/
990 kW

1125 kVA/
1125 kW

96

96

96

96

96

96

96

Battery Run-Times Schneider Electric Qualified VRLA Batteries


NOTE: These battery runtimes are approximations calculated from battery
manufacturer data. Please consult Schneider Electric for details. Variables such as
site installation, battery condition, temperature and power factor will cause
deviations from these runtimes.

Battery Cabinet with GNB S12V370(F)


0.9 PF

3 Strings

4 Strings

5 Strings

6 strings1

kVA

Minutes

Minutes

Minutes

Minutes

555 kVA

11

625 kVA

750 kVA

800 kVA

1000 kVA

1100 kVA

1. Contact Schneider Electric regarding six string configurations.


14

9905236B-001

Technical Data

5551125 kVA

Battery Cabinet with EnerSys 12HX400


0.9 PF

3 Strings

4 Strings

5 Strings

6 strings2

kVA

Minutes

Minutes

Minutes

Minutes

555

12

625

10

750

800

1000

1100

Battery Cabinet with GNB S12V500


0.9 PF

3 Strings

4 Strings

5 Strings

6 strings2

kVA

Minutes

Minutes

Minutes

Minutes

555

12

18

625

15

750

10

800

1000

1100

1125

Battery Cabinet w/C&D Technologies UPS12-300MR


0.9 PF

3 Strings

4 Strings

5 Strings

kVA

Minutes

Minutes

Minutes

555

625

Battery Cabinet w/C&D Technologies UPS12-400MR


0.9 PF

3 Strings

4 Strings

5 Strings

6 strings2

kVA

Minutes

Minutes

Minutes

Minutes

555

13

625

10

750

800

1000

1100

Battery Cabinet w/C&D Technologies UPS12-490MR


0.9 PF

3 Strings

4 Strings

5 Strings

6 strings2

kVA

Minutes

Minutes

Minutes

Minutes

555

12

18

625

15

2. Contact Schneider Electric regarding six string configurations.


9905236B-001

15

5551125 kVA

Technical Data

0.9 PF

3 Strings

4 Strings

5 Strings

6 strings3

kVA

Minutes

Minutes

Minutes

Minutes

750

10

800

1000

1100

Battery Cabinet w/Enersys 12HX300


0.9 PF

3 Strings

4 Strings

5 Strings

kVA

Minutes

Minutes

Minutes

555

625

Battery Cabinet w/ Enersys 12HX505


0.9 PF

3 Strings

4 Strings

5 Strings

6 strings3

kVA

Minutes

Minutes

Minutes

Minutes

555

13

18

625

11

15

750

12

800

10

1000

10

1100

1125

Battery Cabinet w/ GNB S12V285(F)


0.9 PF

3 Strings

4 Strings

5 Strings

kVA

Minutes

Minutes

Minutes

555

625

Battery Material Safety Data Sheet


NOTE: For Material Safety Data Sheet (MSDS), go to the Knowledge Base http://
www.apc.com/site/support/us/en/faq/ and type MSDS to get the latest MSDS
information.

3. Contact Schneider Electric regarding six string configurations.


16

9905236B-001

Technical Data

5551125 kVA

Communication and Management


Auxiliary Wiring
Drawings are published for reference only and are subject to change without
notice. Contact Schneider Electric for installation details.

9905236B-001

17

5551125 kVA

Technical Data

Compliance
Regulatory Approvals

cUL Listed

UL 1778

OSHPD

FCC rules and regulations of Part 15, subpart J, class A

IEEE 587-1980/ANSI C62.41 1980, Standards for Surge


Withstand ability

ISO 9001 Quality Standard

Seismic

IBC2006

Standard Warranty

1 year repair or replace

18

9905236B-001

Facility Planning

5551125 kVA

Facility Planning
Input Specifications
Input Specifications for 555800 kVA Systems
555 kVA/500 kW

625 kVA/562 kW

750 kVA/675 kW

800 kVA/720 kW

480 V

480 V

600 V

480 V

600 V

480 V

600 V

600 V

Connections

3PH + G

Input voltage
(V)

480 +10/-15%

Input
frequency
(Hz)

60

THDI

Less than 5% at full load

Nominal
input current
(A)3

719

575

817

654

1034

725

1103

866

Maximum
input current
(A)4

825

678

923

757

1126

832

1195

989

Input current
limitation
and Q1
rating (A)5

1200

Maximum
short circuit
withstand
current (kA)

100

Rectifier
input fuses

700 A/600 VAC, 4 PLS Fast

1 KA/600 VAC, 4 PLS Fast

DC bus/
inverter
input fuses

700 A/600 VAC, 4 PLS Fast

1.0 KA 550 VAC, 4 PLS Fast

1600

Input Specifications for 10001125 kVA Systems


1000 kVA/
900 kW

1000 kVA/
1000 kW

1000 kVA/
1000 kW

1100 kVA/
990 kW

1100 kVA/
1100 kW

1100 kVA/
1100 kW

1125 kVA/
1125 kW

1125 kVA/
1125 kW

1125 kVA/
1125 kW

Input
voltage
(V)

480 +10/15%

575 10%

600 10%

480 +10/15%

575 10%

600 10%

480 10%

575 10%

600 10%

Connections

3PH + G

Input
frequency
(Hz)

60

Inrush
current

600% of nominal input current for less than 1 cycle

THDI

Less than 5% at full load

Nominal
input
current (A)

1338

1314

1260

1573

1329

1274

1195

1145

1472

3. Input current based on rated load and batteries fully charged.


4. Input current based on full battery recharge current, nominal voltage, and rated load.
5. Set for 150% nominal input current.Programmable up to input circuit breaker rating.
9905236B-001

19

5551125 kVA

Facility Planning

1000 kVA/
900 kW

1000 kVA/
1000 kW

1000 kVA/
1000 kW

1100 kVA/
990 kW

1100 kVA/
1100 kW

1100 kVA/
1100 kW

1125 kVA/
1125 kW

1125 kVA/
1125 kW

1125 kVA/
1125 kW

Input
voltage
(V)

480 +10/15%

575 10%

600 10%

480 +10/15%

575 10%

600 10%

480 10%

575 10%

600 10%

Maximum
input
current (A)

1502

1305

1250

1636

1435

1375

1716

1452

1391

Input
current
limitation
and Q1
rating (A)7

2000

2500

2000

2000

Maximum
short
circuit
withstand
current
(kA)

65

Rectifier
input fuses

1.4 KA 700 VAC fast

DC bus/
inverter
input fuses

700 A 700 VAC fast

2000

Bypass Specifications
Bypass Specifications for 555800 kVA Systems
555 kVA/500 kW

625 kVA/562 kW

750 kVA/675 kW

800 kVA/720 kW

480 V

600 V

480 V

600 V

480 V

600 V

480 V

600 V

534

752

601

900

722

960

770

Connections

3PH + N + G

Input
frequency
(Hz)

60

Nominal
bypass
current (A)

668

Q4S circuit
breaker
rating (A)

1000

1200

6. Input current based on full battery recharge current, nominal voltage, and rated load.
7. Set for 150% nominal input current. Programmable up to input CB rating.
20

9905236B-001

Facility Planning

5551125 kVA

Bypass Specifications for 10001125 kVA Systems


1000 kVA/900 kW
Nominal
bypass
voltage
(V)

480

Connections

3PH + N + G

Input
frequency
(Hz)

60

Nominal
bypass
current (A)
Q4S CB
rating (A)

1100 kVA/990 kW

1125 kVA/1125 kW

575

600

480

575

600

480

575

600

1203

1004

962

1323

1104

1058

1353

1130

1083

2000

16008

16008

2000

16008

16008

2000

16008

16008

Output Specifications
Output Specifications for 555800 kVA Systems
555 kVA/500 kW

625 kVA/562 kW

750 kVA/675 kW

800 kVA/720 kW

Nominal
output
voltage (V)

480

480

600

480

600

480

600

Connections

3PH + N + G

Output
voltage
range

480 V 5% (adjustable)

Overload
capacity

10 minutes at 125% load


60 seconds at 150% load

Nominal
output
current (A)

668

752

601

900

722

960

770

Output
frequency
(sync to
mains) (Hz)

60

Slew rate

1.0 Hz/Sec Programmable 0.5 to 2 Hz/Sec.

THDU
(phase to
phase)

2%

Output
power factor

0.9

Dynamic
load at full
load
response

5%

Output
voltage
regulation
(RMS)

1% for 100% balanced loads, 2% for 100% unbalanced loads

600

534

8. 100% rated
9905236B-001

21

5551125 kVA

Facility Planning
555 kVA/500 kW

625 kVA/562 kW

750 kVA/675 kW

800 kVA/720 kW

Nominal
output
voltage (V)

480

480

480

480

Q5N output
circuit
breaker
ratings (A)

1000

1200

Output
inverter load
fuses

1.250 KA 600 V Fast

1.40 KA 650 V Fast

600

600

600

600

Output Specifications for 10001125 kVA Systems


1000 kVA/
900 kW

1000 kVA/
1000 kW

1000 kVA/
1000 kW

1100 kVA/
990 kW

1100 kVA/
1100 kW

1100 kVA/
1100 kW

1125 kVA/
1125 kW

1125 kVA/
1125 kW

1125 kVA/
1125 kW

Nominal
output
voltage
(V)

480

575

600

480

575

600

480

575

600

Connections

3PH + N + G

Output
voltage
range

Nominal output voltage 5%

Overload
capacity

10 minutes at 125%
60 seconds at 150%

Nominal
output
current (A)

1203

1323

1104

1058

1353

1130

1083

Output
frequency
(sync to
mains)
(Hz)9

60

Slew rate

1.0 Hz/Sec Programmable 0.5 to 2 Hz/Sec. Default = 1 Hz/Sec

THDU
(phase to
phase)

2%

Output
power
factor

0.9

Dynamic
load at full
load
response

5%

Output
voltage
regulation
(RMS)

1% for balanced loads


2% for 100% unbalanced loads

Q5N
output
breaker
ratings (A)

2000

Output
inverter
load fuses

2 KA 600 VAC Fast

1004

1.0

160010

962

1.0

160010

0.9

1.0

1.0

1.0

1.0

1.0

2000

160010

160010

2000

160010

160010

9. Contact Schneider Electric for 50 Hz configurations


10. 100% rated 6 PLS
22

9905236B-001

Facility Planning

5551125 kVA

Battery Specifications
Battery Specifications for 555800 kVA Systems
555 kVA/500 kW

625 kVA/562 kW

750 kVA/675 kW

800 kVA/720 kW

Type

VRLA or Vented Lead Acid

Nominal voltage (VDC)

480

Float voltage (VDC)11

545

End of discharge voltage


(VDC)11

400

End voltage

1.67 V/Cell

Battery current at full


load and 480 VDC (A)

1106

1245

1495

1596

Maximum current at 400


VDC (end of discharge)
(A)

1301

1465

1766

1884

Maximum charging
power at full load (kW)

50

56

67

72

Typical re-charge time

C10

Battery Specifications for 10001125 kVA Systems


1000 kVA/
900 kW

1000 kVA/
1000 kW

1000 kVA/
1000 kW

1100 kVA/
990 kW

1100 kVA/
1100 kW

1100 kVA/
1100 kW

1125 kVA/
1125 kW

1125 kVA/
1125 kW

1125 kVA/
1125 kW

Input
voltage (V)

480

575

600

480

575

600

480

575

600

Type

VRLA or Vented Lead Acid

Nominal
voltage
(VDC)

480

Float
voltage
(VDC)11

545

End of
discharge
voltage
(VDC)11

400

End
voltage

1.67 V/Cell

Battery
current at
full load
and 480
VDC (A)

1993

2187

2187

2187

2407

2407

2461

2461

2461

Maximum
current at
400 VDC
(end of
discharge)
(A)

2344

2631

2631

2578

2894

2894

2960

2960

2960

11. Programmable contact Schneider Electric for more information


9905236B-001

23

5551125 kVA

Facility Planning

1000 kVA/
900 kW

1000 kVA/
1000 kW

1000 kVA/
1000 kW

1100 kVA/
990 kW

1100 kVA/
1100 kW

1100 kVA/
1100 kW

1125 kVA/
1125 kW

1125 kVA/
1125 kW

1125 kVA/
1125 kW

Max.
charging
power at
full load
(kW)

90

100

100

99

110

110

109

113

113

Typical recharge
time

C10

Recommended Cable Sizes


Recommended Cable Sizes for 555800 kVA Systems

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
All wiring must comply with all applicable national and/or electrical codes.
Failure to follow these instructions will result in death or serious injury.
Cable sizes in this manual are based on table 310-16 of the National Electrical
Code (NEC) with the following assertions:

75C conductors for 75C termination

Use of copper conductors

Ground wires are sized in accordance with NEC Article 250-122 and Table 250122.
Power and control cables must be routed in separate conduits.
Upstream and downstream bypass cable type and lengths must be equal for all
UPSs installed in each integrated parallel system.
555 kVA/500 kW

625 kVA/562 kW

750 kVA/675 kW

800 kVA/720 kW

Input

350 MCM x 5

350 MCM x 5

500 MCM x 6

500 MCM x 6

Bypass

350 MCM x 4

350 MCM x 4

500 MCM x 4

500 MCM x 4

Output

350 MCM x 4

350 MCM x 4

500 MCM x 4

500 MCM x 4

Battery

500 MCM x 5

500 MCM x 5

500 MCM x 6

500 MCM x 6

24

9905236B-001

Facility Planning

5551125 kVA

Recommended Cable Sizes for 10001125 kVA Systems

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
All wiring must comply with all applicable national and/or electrical codes.
Failure to follow these instructions will result in death or serious injury.
Cable sizes in this manual are based on table 310-16 of the National Electrical
Code (NEC) with the following assertions:

75C conductors for 75C termination

Use of copper conductors

Ground wires are sized in accordance with NEC Article 250-122 and Table 250122.
Power and control cables must be routed in separate conduits.
Upstream and downstream bypass cable type and lengths must be equal for all
UPSs installed in each integrated parallel system.
1000 kVA/
1000 kW

1000 kVA/
1000 kW

1100 kVA/
1100 kW

1100 kVA/
1100 kW

1125 kVA/
1125 kW

1125 kVA/
1125 kW

1125 kVA/
1125 kW

575 V

600 V

575 V

600 V

480 V

575 V

600 V

Input (MCM)

5 x 600

5 x 600

5 x 600

5 x 600

7 x 500

5 x 600

5 x 600

Bypass
(MCM)

5 x 400

5 x 400

5 x 400

5 x 400

6 x 500

5 x 400

5 x 400

Output (MCM)

5 x 400

5 x 400

5 x 400

5 x 400

6 x 500

5 x 400

5 x 400

Battery (MCM)

6 x 600

6 x 600

6 x 600

6 x 600

7 x 500

6 x 600

6 x 600

Physical
Weights and Dimensions
UPS Rating

Cabinet

Weight
kg (lbs)

Height
mm (in)

Width
mm (in)

Depth
mm (in)

555 kVA

I/O cabinet

2820 (6200)

2083 (82)

1543 (60.75)

991 (39)

UPS cabinet

2720 (6000)

2083 (82)

1543 (60.75)

991 (39)

I/O cabinet

2820 (6200)

2083 (82)

1543 (60.75)

991 (39)

UPS cabinet

2720 (6000)

2083 (82)

1543 (60.75)

991 (39)

I/O cabinet

3227 (7100)

2083 (82)

1543 (60.75)

991 (39)

UPS cabinet

3136 (6900)

2083 (82)

1543 (60.75)

991 (39)

I/O cabinet

3227 (7100)

2083 (82)

1543 (60.75)

991 (39)

UPS cabinet

3136 (6900)

2083 (82)

1543 (60.75)

991 (39)

UPS cabinet 1

3567 (7864)

2289 (90)

1797 (70)

1139 (44.83)

UPS cabinet 213

4158 (9167)

2289 (90)

1797 (70)

1139 (44.83)

UPS cabinet 1

3567 (7864)

2289 (90)

1797 (70)

1139 (44.83)

UPS cabinet 213

4158 (9167)

2289 (90)

1797 (70)

1139 (44.83)

625 kVA

750 kVA12

800 kVA12

1000 kVA

1100 kVA

12. Contact Schneider Electric for maintenance bypass cabinet option


13. 45 kg (100 lbs) must be added if a maintenance bypass cabinet is provided.
9905236B-001

25

5551125 kVA

Facility Planning

UPS Rating

Cabinet

Weight
kg (lbs)

Height
mm (in)

Width
mm (in)

Depth
mm (in)

1125 kVA

UPS cabinet 1

4545 (10020)

2289 (90)

1797 (70)

1139 (44.83)

UPS cabinet 214

4423 (9750)15

2289 (90)

1797 (70)

1139 (44.83)

Auxiliary cabinets

236306 (520675)

2289 (90)

610 (24)

1139 (44.83)

Maintenance bypass
cabinet

612 (1350)

2289 (90)

610 (24)

1139 (44.83)

Shipping Weights and Dimensions


Contact Schneider Electric for exact shipping details physical details may vary
depending in your selected options.
UPS Rating

Weight
kg (lbs)

Height
mm (in)

Width
mm (in)

Depth
mm (in)

555 kVA16

5670 (12500)

2337 (92)

2261 (89)

1092 (43)

625 kVA16

5670 (12500)

2337 (92)

2261 (89)

1092 (43)

750 kVA16

6623 (14600)

2337 (92)

2261 (89)

1092 (43)

800 kVA 16

6623 (14600)

2337 (92)

2261 (89)

1092 (43)

1000 kVA16

8087 (17827)

2388 (94)

3658 (144)

1219 (48)

1100 kVA16

8087 (17827)

2388 (94)

3658 (144)

1219 (48)

1125 kVA16

8968 (19770)17

2388 (94)

3658 (144)

1219 (48)

14.
15.
16.
17.
26

45 kg (100 lbs) must be added if a maintenance bypass cabinet is provided.


4808 kg (10600 lbs) for 575 V and 600 V systems
Shipped in two cabinets
9353 kg (20620 lbs) for 575 V and 600 V systems
9905236B-001

Facility Planning

5551125 kVA

Clearance
NOTE: Clearance dimensions are published for airflow and service access only.
Consult with the local safety codes and standards for additional requirements in
your local area.
NOTE: No rear service access required. Rear space requirement is 51 mm (2 in)
in systems with seismic bracket and 13 mm (0.5 in) without seismic bracket.

914 mm (36 in)

914 mm (36 in)

9905236B-001

27

5551125 kVA

Facility Planning

Environmental
Operating temperature

Storage temperature

UPS recommended: 20 to 25 C (68 to 77 F) at sea level

UPS extreme: 30C (86 F) at sea level with redundant fan

UPS: -20 to 50 C ( -4 to 122 F)

Battery -17 to 45 C ( 0 to 113 F)

Higher storage temperature decreases battery storage life


Humidity

0- 95% non-condensing

Operating elevation

No derating < 3000 feet


See elevation derating table below

Storage elevation

0-30000 feet (0-9144 meters)

Audible noise at 100% load

Measured 5 feet from front of unit:

555 kVA: 74 dBA

625 kVA: 74 dBA

750 kVA: 78 dBA

800 kVA: 78 dBA

Measured 5 feet from front of unit:

Colour

1000 kVA: 76.5 dBA

1100 kVA: 76.5 dBA

1125 kVA: 76.5 dBA

Light grey (RAL 9002)

Elevation Derating Table


Elevation in Feet

Power Rating Multiplier

3000

1.00

4500

0.85

6000

0.79

6900

0.75

9000

0.69

12000

0.61

Heat Dissipation
Heat Dissipation for 555800 kVA Systems

Heat dissipation
(BTU/hr)

555 kVA/
500 kW

625 kVA/
562 kW

750 kVA/
675 kW

800 kVA/
720 kW

127 000

145 000

147 000

160 000

Heat Dissipation for 10001125 kVA Systems

Heat dissipation
(BTU/hr)

28

1000 kVA/
900 kW

1000 kVA/
1000 kW

1100 kVA/
990 kW

1100 kVA/
1100 kW

1125 kVA/
1125 kW

1125 kVA/
1125 kW

480 V

575/600 V

480 V

575/600 V

480 V

575/600 V

290 000

222 000

335 000

253 000

270 000

260 000

9905236B-001

Drawings

5551125 kVA

Drawings
NOTE: A comprehensive set of drawings is available on the engineering website at
engineer.apc.com.
NOTE: These drawings are for reference ONLY subject to change without
notice.

9905236B-001

29

5551125 kVA

Drawings

EPS 8000 800 kVA Single Module with Internal Bypass

30

9905236B-001

Drawings

5551125 kVA

EPS 8000 800 kVA with Maintenance Bypass Cabinet

9905236B-001

31

5551125 kVA

Drawings

EPS 8000 1100 kVA Bottom Feed

32

9905236B-001

Drawings

5551125 kVA

EPS 8000 1100 kVA Top Feed

9905236B-001

33

5551125 kVA

Drawings

EPS 1100 kVA with Maintenance Bypass Cabinet Bottom


Feed

34

9905236B-001

Drawings

5551125 kVA

EPS 1100 kVA with Maintenance Bypass Cabinet Top


Feed

9905236B-001

35

5551125 kVA

Options

Options
Hardware Options
Management

MultiSlot DIN - Extension Module for Com Card

U-Talk/Basic Acquisition Card

MultiSlot NEMA HID

SNMP/Web Card

Environment Sensor for Network Management Cable

Configuration Options

36

Output distribution

Battery monitoring

Graphical user interface with network connection

Continuous duty and momentary duty static switch cabinet

Critical synchronization module

Ground fault detection

Battery cabinet

Input isolation transformer

External maintenance bypass

9905236B-001

Schneider Electric Limited Factory


Warranty

5551125 kVA

Schneider Electric Limited Factory


Warranty
Three Phase Power Products or Cooling Solutions OneYear Factory Warranty
The limited warranty provided by Schneider Electric in this Statement of Limited
Factory Warranty applies only to products you purchase for your commercial or
industrial use in the ordinary course of your business.

Terms of Warranty
Schneider Electric warrants that the product shall be free from defects in materials
and workmanship for a period of one year from the date of product start-up when
start-up is performed by Schneider Electric-authorized service personnel and
occurs within six months of the Schneider Electric shipment date. This warranty
covers repairing or replacing any defective parts including on-site labor and travel.
In the event that the product fails to meet the foregoing warranty criteria, the
warranty covers repairing or replacing defective parts at the sole discretion of
Schneider Electric for a period of one year from the shipment date. For Schneider
Electric cooling solutions, this warranty does not cover circuit breaker resetting,
loss of refrigerant, consumables, or preventive maintenance items. Repair or
replacement of a defective product or part thereof does not extend the original
warranty period. Any parts furnished under this warranty may be new or factoryremanufactured.

Non-transferable Warranty
This warranty is extended to the first person, firm, association or corporation
(herein referred to by You or Your) for whom the Schneider Electric product
specified herein has been purchased. This warranty is not transferable or
assignable without the prior written permission of Schneider Electric.

Assignment of Warranties
Schneider Electric will assign you any warranties which are made by
manufacturers and suppliers of components of the Schneider Electric product and
which are assignable. Any such warranties are assigned AS IS and Schneider
Electric makes no representation as to the effectiveness or extent of such
warranties, assumes no responsibility for any matters which may be warranted by
such manufacturers or suppliers and extends no coverage under this Warranty to
such components.

Drawings, Descriptions
Schneider Electric warrants for the warranty period and on the terms of the
warranty set forth herein that the Schneider Electric product will substantially
conform to the descriptions contained in the Schneider Electric Official Published
Specifications or any of the drawings certified and agreed to by contract with
Schneider Electric if applicable thereto (Specifications). It is understood that the

9905236B-001

37

Schneider Electric Limited Factory


Warranty

5551125 kVA

Specifications are not warranties of performance and not warranties of fitness for a
particular purpose.

Exclusions
Schneider Electric shall not be liable under the warranty if its testing and
examination disclose that the alleged defect in the product does not exist or was
caused by end user or any third person misuse, negligence, improper installation
or testing. Further, Schneider Electric shall not be liable under the warranty for
unauthorized attempts to repair or modify wrong or inadequate electrical voltage or
connection, inappropriate on-site operation conditions, corrosive atmosphere,
repair, installation, start-up by non-Schneider Electric designated personnel, a
change in location or operating use, exposure to the elements, Acts of God, fire,
theft, or installation contrary to Schneider Electric recommendations or
specifications or in any event if the Schneider Electric serial number has been
altered, defaced, or removed, or any other cause beyond the range of the intended
use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF
LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED
UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. SCHNEIDER
ELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY,
SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER
ELECTRIC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED,
OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF,
SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER ADVICE OR
SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING
WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER
WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE
CONSTITUTE SCHNEIDER ELECTRIC SOLE LIABILITY AND PURCHASERS
EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES.
SCHNEIDER ELECTRIC WARRANTIES RUN ONLY TO PURCHASER AND ARE
NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS,
AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT,
SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE
USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH
DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT,
NEGLIGENCE OR STRICT LIABILITY OR WHETHER SCHNEIDER ELECTRIC
HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH
DAMAGES, SPECIFICALLY, SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY
COSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT,
LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA,
COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF SCHNEIDER ELECTRIC IS
AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY.
WARRANTY TERMS MAY BE MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED
BY AN SCHNEIDER ELECTRIC OFFICER AND LEGAL DEPARTMENT.

Warranty Claims
Customers with warranty claims issues may access the SCHNEIDER ELECTRIC
worldwide customer support network through the SCHNEIDER ELECTRIC web
site: http://www.SCHNEIDER ELECTRIC.com/support/contact/. Select your
country from the country selection pull-down menu. Open the Support tab at the
top of the web page to obtain contact information for customer support in your
region.

38

9905236B-001

Printed in.
Schneider Electric

Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.schneider-electric.com