Vous êtes sur la page 1sur 16

FACTORY AUTOMATION

AS-INTERFACE
MAINTENANCE AND
TROUBLESHOOTING GUIDE

Table of Contents
AS-Interface Basics................................................................. 3
Addressing Modules................................................................ 4
Handheld Programmer
(Reading Inputs and Settings Outputs).................................. 5
Gateway Quick Start................................................................ 6
Gateway Advanced Features.................................................. 7
Exchanging SafetyNodes......................................................... 8
Exchanging SafetyMonitors.................................................... 9
LED Functionality (Modules)................................................. 10
LED Functionality (SafetyMonitors)...................................... 11
Repeaters................................................................................ 12
Terminator and Tuner............................................................. 13
Power Supplies....................................................................... 14
Analyzer................................................................................... 15

Subject to modifications without notice


Copyright Pepperl+Fuchs
www.pepperl-fuchs.com

As-Interface Basics
Use only certified modules, gateways/scanners, and power supplies.
Total segment cable length is 100 m. (See page 12.) This includes the
total of all trunk and drop lines.
One AS-Interface power supply is required per segment. For
example, a network with 2 repeaters requires 3 power supplies.
Exactly one gateway/scanner is required per network.
31 addresses maximum; extended addressing, 1-31a and 1-31b, is
permitted on 2.1 and 3.0 spec. networks for a total of 62 nodes.
Address 0 (the factory default address) is used for automatic
addressing and is not permitted on a running system.
Modules with extended addressing and 4-in/4-out are permitted only
on networks where an M4 (3.0) master is used.
Update time per module is 150 s. The formula for scan time is
150 s x (number of addresses + 2)




- Single addresses require 1 scan


- Dual addresses (a and b) require 2 scans
-D
 ual addresses (a and b) 3.0 4-in/4-out require 2 scans for inputs
and 4 scans for outputs
- Analog modules (2.1) require 7 scans per point
- Analog modules (3.0) require 3 or 4 scans per point

Network cable can be run in any topology.


No shield or termination is required.
Specification-compliant flat or round cable must be used.
Do not ground either AS-i + or under any circumstances anywhere
on the network (ground fault). The network has a differential
communication signal.
Subject to modifications without notice
Copyright Pepperl+Fuchs
www.pepperl-fuchs.com

Addressing Modules
If only one module has failed:
remove failed module
connect new module

As long as the new module is identical (i.e., has the same I/O and
ID codes and has address 0 before connection), no additional steps
are necessary.

If more than one module has failed:


remove all failed modules
use handheld programmer VBP-HH1 to manually assign
addresses to all but one replacement module
the last replacement module will receive its address automatically

Note: The VAZ-PK-1.5M-V1-G addressing cable is required to work


with any module using an addressing jack.

Setting an Address Using Handheld Programmer


1. Connect the module to the handheld using
either the addressing cable, M12 receptacle, or
direct connection.
2. Press the ADR button to display the current
address of the module
3. Use arrow buttons to choose new
address
4. Press PRG button to set selected address
5. Press ADR button to confirm address
The diagnostic LEDs on the gateway/scanner
indicate a fault when one or more modules are
missing or are not properly connected to network.

Subject to modifications without notice


Copyright Pepperl+Fuchs
www.pepperl-fuchs.com

E
MOD
PRG
ADR

Handheld Programmer
The handheld programmer is a diagnostic tool that is used to read the
inputs or set the outputs on a module. This is often done to isolate and
troubleshoot a specific I/O point.

Procedure to Read Inputs and Set Outputs


Make sure the handheld is in ADDR mode. This
allows the address to be read. Press the MODE
button until the ADDR mode is selected.
Press ADR button and verify address is not zero.
(If zero, see previous page to set valid address.)
Change mode to DATA by pressing the MODE
button 4x or 7x depending on module type. (Menu
will repeat if you go to far.)
MOD

Use arrow buttons to select output value

E
PRG

Press and hold PRG button to turn outputs on

ADR

Press and hold ADR button to read inputs


Note: T
 he chart below shows which inputs or outputs
are activated when the hexadecimal digit is displayed.
Display
Inputs
Outputs

none

I1

I2

I1, I2

I3

I1, I3

I2, I3

I1, I2, I3

none

O1

O2

O1, O2

O3

O1, O3

O2, O3

O1, O2, O3

Display
Inputs
Outputs

I4

I4, I1

I4, I2

I4, I2, I1

I4, I3

O4

O4, O1

I4, I3, I1 I4, I3, I2

F
I4, I3, I2, I1

O4, O2 O4, O2, O1 O4, O3 O4, O3, O1 O4, O3, O2 O4, O3, O2, O1

Subject to modifications without notice


Copyright Pepperl+Fuchs
www.pepperl-fuchs.com

Gateway Quick Start


When modules are added or removed from the network, the gateway
detects this and indicates a Config Error. For gateways with a graphical
display, use the following procedure to make the detected configuration
(i.e., all modules found on the network) the active configuration.
Config Error LED ON
Press OK

.5

WARNING:
OUTPUTS MAY BE
RESET

Press OK

Press OK

Press

Press

DEVICENET
QUICK SETUP
SETUP
IO + PARAM. TEST

Press OK
STORE AS-I
CONFIGURATION
OK
STORE + PRJ MODE

STORE AS-I
CONFIGURATION
STORE + RUN
STORE + PRJ MODE

Press ESC twice


Config Error LED OFF

.
CONFIGURATION OK

Gateway LED Fuctionality


LED
Power
Config Error
U AS-i

Indication

Meaning

On (Green)

Power on

On (Red)

One slave missing or extra slave on the network

Flashing (Red)

Peripheral fault on network

On (Green)

AS-i network is sufficiently powered

AS-i Active

On (Green)

AS-i network operating normally in either configuration or


protected mode

PRG Enable

On (Green)

Exactly one slave is missing in protected operating mode


and automatic addressing is allowed

PRJ Mode

On (Yellow)

AS-i master is in configuration mode

Subject to modifications without notice


Copyright Pepperl+Fuchs
www.pepperl-fuchs.com

Gateway Advanced Features


Some gateways have advanced diagnostic
features that can assist in finding network
problems. The built-in fault detector will display
new and old network errors. All advanced
diagnostics are found on the display by going to
ADV. DIAGNOSIS > AS-I CIRCUIT x > ...

PO
W
E
MN R
S
CO
NF
IG
AS ER
-i R
AS
-i A
PR CTIV
G
E
EN
PR A
J M BLE
OD
E

RS 232

Error Counters
If a node requires at least 2 consecutive retries,
counts will appear on the display next to that
node address. A clean network will have few
or no retries. Single retries are automatically
handled at the AS-Interface chip level and
cannot be detected using the gateway. (Counts
always go up by 2.)
If any node has 6 consecutive retries, it appears
in the LCS with an X by the node address. (This
node caused a configuration error.)

Fault Detector
The following errors occurred in the past (HISTORIC)
or are currently happening (ACTUAL). Duplicate
addresses are also displayed on this screen.
EFLT: An earth or ground fault has occurred.
Check to make sure that AS-i + or - is not
touching machine ground anywhere.
OVRV: A power spike occurred on AS-i such that
the AS-i voltage was too high.

ESC
+ASI-

Mode

Set

OK

ASI
+ASI- +PWR- NC NC

ERROR COUNTERS
RESET
1A - 0
2A - 0
RESET
APF -
2A -
4A - x

I
I
I

1A - x
3A 5A -

FAULT DETECTOR
RESET
HISTORIC:
EFLT OVRV NOIS
ACTUAL:
EFLT OVRV NOIS
DUP ASI ADR:
0
I 31B
HELP:
EFLT EARTH FAULT
NOIS NOISE
DUP ASI ADR
DUPLICATE ASI
SLAVE ADDRESS

NOIS: Noise was detected. Route AS-i cable away


from potential noise sources.
Subject to modifications without notice
Copyright Pepperl+Fuchs
www.pepperl-fuchs.com

Exchanging SafetyNodes
Compared to standard modules, exchanging a SafetyNode requires a few
additional steps. See procedure for single and multiple node replacement.

Exchanging a Single Failed SafetyNode


1. Remove SafetyNode.
2. Lightly press the Service button on all affected SafetyMonitors.
LEDs 1, 2, and 3 will cycle slowly on the SafetyMonitor.
3. Connect replacement SafetyNode, make sure it receives an AS-i
address and its inputs are closed so that full safety-code sequences
are received by the SafetyMonitor.
4. Press the Service button on all affected SafetyMonitors. If successful,
LEDs 1, 2, 3 will turn off and the SafetyMonitor will start normally.

Exchanging Multiple Failed SafetyNodes


1. Remove all defective SafetyNodes.
2. Use handheld programmer VPB-HH1 to manually assign all addresses.
(See page 4.) Confirm there is no configuration error on gateway/
scanner. (Make sure all e-stops are pressed, all gates are open, and all
light curtains are broken such that S1 and S2 safety input LEDs are off
on all recently replaced SafetyNodes.)
3. The safety sequence must now be taught by following the procedure
in Exchanging a Single Failed SafetyNode. Repeat this procedure for
every recently replaced SafetyNode on the network.
ATTENTION! After replacing the defective SafetyNodes, make
certain to check the new modules for correct functionality.

Subject to modifications without notice


Copyright Pepperl+Fuchs
www.pepperl-fuchs.com

Exchanging SafetyMonitors
1. Disconnect the failed SafetyMonitor from the 24 VDC power supply.
Both L+ and M must be removed!
2. Use the special download cable, VAZ-SIMON-RJ45. Connect the
new and old SafetyMonitors together.

Service

Service

Removable
terminal
release tabs

The replacement SafetyMonitor must be new with no configuration


or have a configuration that is not validated.

3. Power up replacement SafetyMonitor by connecting both L+ and M.


4. Press the Service button on replacement SafetyMonitor.

On the replacement SafetyMonitor, active transmission is indicated


when the yellow READY LED is illuminated. Transfer is complete
when the GREEN and YELLOW LEDs are both lit.

5. Disconnect defective SafetyMonitor and move all cables to


replacement SafetyMonitor. (Version 2.14 has keyed removable
terminals. Press the release tab in at the top of the monitor and pull
terminals straight up to remove.)
Subject to modifications without notice
Copyright Pepperl+Fuchs
www.pepperl-fuchs.com

Led Functionality (Modules)


IN1
IN2

O1 O2
IN3

I3

IN4

I4

PWR
FAULT
AUX

LED
PWR
AS-i

FAULT

PWR/FLT

AUX
I
In
O
Out

10

Indication

Meaning

Off

No power

On (Green)

Normal

Flashing (Green)

Address 0 (FAULT LED on) or peripheral fault (FAULT


LED flashing)

Off

Normal

On (Red)

No AS-i communication; check address

Flashing (Red)

Peripheral fault; check I/O

Off

No power

On (Green)

Normal

On (Red)

No AS-i communication; check address

Alternating (Red/Yellow)

Address 0

Alternating (Red/Green)

Peripheral fault; check I/O

OFF

No AUX power; check black AS-Interface cable

ON

Normal

OFF

Input OFF; no AUX power or wire broken

ON

Input ON

OFF

Output OFF; no AUX power or output not set by PLC

ON

Output ON

ON

Output shorted/overloaded (if supported by module)

Subject to modifications without notice


Copyright Pepperl+Fuchs
www.pepperl-fuchs.com

LED Functionality (SafetyMonitors)


not used
LED AS-i 1
Service

LED AS-i 2
Output circuit 1

LED

AS-i

Indication

1
2
3

1 READY
2 ON
3 OFF/FAULT

1
2
3

Output circuit 2
(on dual channel units only)

Meaning

Off

No 30 V AS-i connection to AS-i+ and AS-i- terminals

On (Green)

Normal

Off

Normal operation

On (Red)

No AS-i communication or monitor address not stored in


gateway/scanner

On (Yellow)

Waiting for start condition or door unlock condition

Flashing (Yellow)

Safety module test, local acknowledge required, or


diagnostic stop enabled

On (Green)

Contacts of the output switching elements closed

Flashing (Green)

Delay time runs in event of Stop Category 1

On (Red)

Contacts of the output switching elements open

Flashing (Red)

Error on level of the monitored AS-i components

1 READY
2 ON
3 OFF/FAULT

Simultaneously
flashing rapidly

Internal device error; power cycle is required

1 READY
2 ON
3 OFF/FAULT

Cycling slowly

Learning safety code sequences

1 READY
2 ON
3 OFF/FAULT

Off

No 24 V supply connected to L+ and M terminals

AS-i 1

AS-i 2

1 READY

2 ON
3 OFF/FAULT

Subject to modifications without notice


Copyright Pepperl+Fuchs
www.pepperl-fuchs.com

11

Repeaters
The communication path between an AS-i module and gateway/
scanner must not go through more then 2 repeaters. This example
shows a network with 5 segments, 4 repeaters and a total length of
500 m. Note the position of the gateway in the middle segment.
AS-Interface
Power Supply

AS-Interface
Power Supply

AS-Interface
Power Supply

AS-Interface
Scanner/Gateway

I/O
Module

100 m total cable length

I/O
Module

100 m total cable length

30 m

I/O
Module

100 m total cable length

30 m

30 m
30 m

20 m

AS-Interface
Power Supply

20 m

30 m

20 m

20 m

Repeater

20 m

30 m

20 m

20 m

Repeater

5m

Repeater

20 m

20 m

30 m

30 m

Repeater

20 m

30 m

I/O
Module

25 m

I/O
Module

AS-Interface
Power Supply

I/O
Module

100 m total cable length

I/O
Module

100 m total cable length

PWR
FAULT

Off

Meaning

12

AS-Interface
segment 2

No power supply connected

On (Green) Normal
Off

Normal

On (Red)

No communication

A network that is properly setup will have:





FL
T2
PW
R

Indication

PW

LED

R
FL 1
T1

A repeater adds a second galvanically isolated segment to the AS-i


network. Because only communication passes through the repeater
a second power supply is required. Never put more than one power
supply on a segment!

AS-Interface
segment 1

One gateway/scanner
One power supply per segment
No segment with more than 100 m total cable length
No module separated from the gateway/scanner by more than 2
repeaters

Subject to modifications without notice


Copyright Pepperl+Fuchs
www.pepperl-fuchs.com

Terminator and Tuner


The fixed terminator, VAZ-TERM, extends the network to 200 m, and the
tuner, VAZ-TUNER, extends the AS-i network to 300 m. These devices,
however, will not correct problems caused by noise or bad AS-i cable.

Requirements for installation


The best network to extend is linear. A network that has many
drops/branches may not be extendable.
The power supply must be located at one end of the network
segment and the terminator/tuner at the other end.
If a repeater is to be used an Advanced repeater is required. The
advanced repeaters VAR-G4F or VAR-KE3-TERM (with termination
switch built in) have a faster response time, which is required to
couple long segments together.
Always use analyzer VAZ-ANALYZER to verify network integrity.

Tuning procedure
Gateway/scanner:
1. Put in configuration mode by
holding mode button for
5 seconds.
Tuner:
1. Rotate mode switch to 2
(tuning)
2. Press set button until
LEDs strobe red, yellow,
green, red...

Tuner LED Indication

LED

Indication

Error

On (Red)

Meaning

Warning

On (Yellow) 1% to 5% retries

Green

On (Green) Less than 1% retries

Greater than 5% retries

Terminator LED Indication

Indication
Off

Meaning
No power or voltage below 18.5 V

On (Yellow) Voltage above 18.5 V


On (Green) Voltage above 26 V

4. When strobing stops (this


may take several minutes), rotate mode switch to 3 (run)
Subject to modifications without notice
Copyright Pepperl+Fuchs
www.pepperl-fuchs.com

13

Power Supplies
Exactly one AS-Interface power supply is required for each segment.
Only one ground/earth fault detection circuit should be used in each
segment. This circuit could be on the power supply, gateway, or
SafetyMonitor.
Some gateways have duplicate address detection. To operate, the
power supply must be connected directly to the dedicated terminal
(labeled +PWR-) on the gateway.

Power supplies with


ground fault detection
Floating EFD output

PE
N
L

Attach standard AC
input voltage here
13 14 + + GND - -

115/230 V switch
(Only on K24 supply)

VAN-115/230AC-K21-EFD

LED Power (Green)

DC OK
EFD
Reset

LED Overload (Red)

EFD int.
EFD ext.

DeviceNet connector
AS-i 1 V+ (Red)
2 CAN H AS-i
(White)
+
3 Shield
4 CAN L (Blue)
Ground
5 V- (Black)

PO
W
E
MN R
S
CO
NF
U IG E
AS R
-i R
AS
-i A
PR CTIV
G
E
E
PR NA
J M BLE
OD
E

RS 232

DeviceNet connector
1
2
3
4
5

Connect AS-i segment here


(Connect Ground terminal to machine
ground and the shield of AS-i cable if used)

V+ (Red)
CAN H (White)
Shield
CAN L (Blue)
V- (Black)
L

Connect to AS-i segment here


(Connect Ground terminal to
machine ground and the shield
of AS-i cable if used)
Power OK (Green)
Ground fault indication LED (Red)
Reset button:
press < 1 s simulates ground fault,
> 2 s to reset ground fault

RS press
232

PO
W
E
MN R
S
CO
NF
U IG E
AS R
-i R
AS
-i A
PR CTIV
G
E
E
PR NA
J M BLE
OD
E

Standard power
supply wiring

Internal/external ground fault switch:


EFD int. shuts off on ground fault,
use pushbutton to reset
EFT ext. automatically recovers
from ground fault (default)

Display

Display

Attach standard AC input voltage here

Power supply connection for gateways


ESC
Ground

+ASI-

AS-i Network

14

Mode

Set

OK

ESC

ASI
+ASI- +PWR- NC NC

Ground

AS-i Power Supply

Subject to modifications without notice


Copyright Pepperl+Fuchs
www.pepperl-fuchs.com

Mode
Set

OK

ASI1
ASI2
+ASI- +PWR- +ASI2- +PWR-

AS-i Network 1
AS-i Network 1
Power Supply

AS-i Network 2
Power Supply
AS-i Network 2

Analyzer
The network analyzer, VAZ-ANALYSER, provides information about
network stability and allows detailed analysis of protocol-specific
communication detail.
There are two modes of operation. The first is online statistics where the
overall health of the network is read. The second is trace mode where
individual AS-i telegrams are recorded, filtered, and viewed for later
analysis. This mode is often used to track down specific input, output
or timing problems.

Online Statistics
Advance statistics (check for)
- Little or no missing telegrams
- No slave telegrams without
master call
Consecutive errors
- Make sure consecutive
errors are kept to
a minimum. (6x =
configuration error)
Network overview
- Check to make sure all
connected nodes are
green
I/O data
- Verify that the input and output data is correct
- Find out if a certain input is flickering or turning on for a short time by
running a trace on that input

Subject to modifications without notice


Copyright Pepperl+Fuchs
www.pepperl-fuchs.com

15

Contact
Pepperl+Fuchs Inc.
1600 Enterprise Parkway
Twinsburg, Ohio 44087 USA
Tel. +1 330 486-0001 Fax +1 330 405-4710
E-mail: fa-info@us.pepperl-fuchs.com
Worldwide Headquarters
Pepperl+Fuchs GmbH Mannheim Germany
E-mail:fa-info@de.pepperl-fuchs.com
USA Headquarters
Pepperl+Fuchs Inc. Twinsburg USA
E-mail: fa-info@us.pepperl-fuchs.com
Asia Pacific Headquarters
Pepperl+Fuchs Pte Ltd Singapore
Company Registration no. 199003130E
E-mail: fa-info@sg.pepperl-fuchs.com

www.pepperl-fuchs.com
Subject to modifications 2008 PEPPERL+FUCHS, INC. Printed in USA Part No. 912040 09/08 00

Vous aimerez peut-être aussi