Vous êtes sur la page 1sur 20

MiCOM C264 LHMI

Configuration
PACiS Technical Training Level 2
CS&P Support Team

PCL

Content
 GHU Board Configuration
 Bitmaps configuration
 LCD configuration
 LED assignment

Schneider Electric - CS&P C264 LHMI Configuration E01

Content
 GHU Board Configuration
 Bitmaps configuration
 LCD configuration
 LED assignment

Schneider Electric - CS&P C264 LHMI Configuration E01

Configure the GHU board


1) C264 with or without LCD => 2 possible GHU boards

2) GHU attributes

HMI Type :
- Simple : no LCD and LED#4 is not
configurable
- Complete : LCD, LED#4 is configurable and
GHU should be linked to a graphic object
typed Computer Workspace

Schneider Electric - CS&P C264 LHMI Configuration E01

GHU Board Sons & Relations


Board status MPS

Set of LED :
LED#4 not configurable if GHU type = Simple

Relation with graphic configuration :


Completed if GHU type = Complete

Schneider Electric - CS&P C264 LHMI Configuration E01

Content
 GHU Board Configuration
 Bitmaps configuration
 LCD configuration
 LED assignment

Schneider Electric - CS&P C264 LHMI Configuration E01

What for?
1) On C264 LCD, in bay panels
= > Single Line Diagrams
- static objects (lines, bitmaps)
- animated objects

2) Graphic table for bitmaps (up to 150)

Note : Starting database is containing bitmap table (IEC)

Schneider Electric - CS&P C264 LHMI Configuration E01

Bitmap Attributes
Short Name :
Rule : put bitmap index in prefix

Bitmap index :
Bitmap index = bitmap identification used at
LCD configuration level

Bitmap type :
-5-uple = animated
-single = non-animated

Schneider Electric - CS&P C264 LHMI Configuration E01

Bitmap Representation (1)


Default
Open*
Closed*

* associated
information in
Closed/Set or
Open/Reset state
Note : bitmap max size = 64x64 pixels
Schneider Electric - CS&P C264 LHMI Configuration E01

Bitmap Representation (2)

Default

Open

Closed

Withdrawn
Open

Withdrawn
Closed

Note : withdrawn = combination of DPS position + withdrawn SPS


Schneider Electric - CS&P C264 LHMI Configuration E01

10

Content
 GHU Board Configuration
 Bitmaps configuration
 LCD configuration
 LED assignment

Schneider Electric - CS&P C264 LHMI Configuration E01

11

Add / Configure a Computer Workspace


1) Graphic Part / Computer Workspace

2) Attributes

Short Name
L/R password protection :
Operator has to enter password when
changing bay control mode (Local/Remote)

Schneider Electric - CS&P C264 LHMI Configuration E01

12

Add / Configure a Bay Mimic


1) Graphic Part / Computer Workspace

2) Attributes
Short Name
MV bargraph :
Horizontal / Vertical
Advise to not use

Module Name display


3) Relations => relation with the represented bay
Mimic rank :
one bay can be represented on 1 or 2
mimics
Schneider Electric - CS&P C264 LHMI Configuration E01

13

Add Graphic Objects in Bay Mimic (1)


1) Typical Bay Mimic (128x128 pixels)
Time :
optional

Mandatory :
- Bay L/R
- Interlock bypass (local activation)
- Synchrocheck bypass (local activation)

Controllable devices :
- LHMI Gen Modules
- up to 9 per mimic

Static graphics :
lines, single bitmaps

Note : no graphics outside of area => C264 failure


Schneider Electric - CS&P C264 LHMI Configuration E01

14

Add Animated Objects in Bay Mimic (2)


2) Add a LHMI Gen Module

3) Configure a LHMI Gen Module


Short Name :
different from displayed name

Control availability :
Yes = controllable from LCD

4) LHMI Gen Module Sons


Graphic object with datapoint relation
is managed by SPS or DPS

Displayed name
4 characters

Representing bitmap index


Schneider Electric - CS&P C264 LHMI Configuration E01

15

Add Animated Objects in Bay Mimic (3)


5) Add a LHMI Transformer

6) LHMI Transformer configuration


Graphic object with TPI relation
is managed by TPI

Minimum, Current and


Maximum TPI values
are mandatory

Bitmap index
Schneider Electric - CS&P C264 LHMI Configuration E01

16

Content
 GHU Board Configuration
 Bitmaps configuration
 LCD configuration
 LED assignment

Schneider Electric - CS&P C264 LHMI Configuration E01

17

Reminder
1) LED can be animated by SPS or DPS status

13 available LED for Complete HMI


12 available LED for Simple HMI (LED#4 = C264 Local/Remote)

LED can be :
- Off
- On
- Blinking fast
- Blinking slow

Schneider Electric - CS&P C264 LHMI Configuration E01

18

Assign a SPS/DPS to LED


1) Under SPS, add the relation has state displayed on LED

2) Complete the relation

Complete the relation


by selecting LED of
the GHU board
Schneider Electric - CS&P C264 LHMI Configuration E01

19

Assign a SPS/DPS to LED


3) Configure the relation for behaviour of LED :

LED Behaviour :
- For status
- For alarm

LED Behaviour per status :


Closed / OPEN / Invalid behaviour
Off / On / Blinking Slow / Blinking Fast

LED Behaviour for alarm :


Off / On / Blinking Slow / Blinking Fast

Note 1 : 1 LED represents only 1 datapoint


Note 2 : behaviour for alarm will depend on alarm
definition in datapoint profile of this DP.
Schneider Electric - CS&P C264 LHMI Configuration E01