Vous êtes sur la page 1sur 9

1472 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO.

3, JULY 2008

Validation of Voltage Sag Simulation Tools: ATP and


Short-Circuit Calculation Versus Field Measurements
Jose Maria Carvalho Filho, Roberto Chouhy Leborgne, Member, IEEE, José Policarpo G. de Abreu,
Eder G. C. Novaes, and Math H. J. Bollen, Fellow, IEEE

Abstract—Two methods to calculate voltage sags are validated the high cost of buying and installing power quality monitors
against actual measurements. One of the methods is a short-circuit in the whole network. Furthermore, the changes in the network
calculation program resulting directly in sag magnitude during the topology and the installation of new generation plants change
fault. The other is an electromagnetic transient program resulting
in voltage waveform as a function of time. Individual sag character- the expected voltage sags statistics.
istics and system performance obtained by deterministic simula- Considering that most of the severe voltage sags are caused
tion and measurement are compared. The influence of the random by faults in the networks, fault simulation has been used for
variables (prefault voltage, fault location and fault impedance) is voltage sag estimation [2], [4]. Both electromagnetic transient
investigated. programs and short-circuit calculation programs are available
Index Terms—Measurement, power quality (PQ), simulation, for fault analysis.
voltage sag (dip). The power system performance obtained from the method of
fault positions was compared with measurements [5]. However,
NOMENCLATURE the accuracy of the computational tools used for the determin-
istic assessment of voltage sags has not been investigated in
depth. To provide this missing information, this paper investi-
gates the accuracy of the simulation of voltage sag magnitude
PQ Power quality.
and frequency.
ATP Alternative Transients Program. The random variables that affect voltage sag characteristics
SARFI System average rms variation frequency index. are analyzed. An ideal 1.0 p.u. prefault voltage and the actual
prefault voltage are simulated. The estimated fault location
LG Line-to-ground fault. and a variation of % of the line length are admitted for
LL Line-to-line fault. simulation. Several fault impedances (0, 5, 25, and 40 ) are
considered.
LLG Double line-to-ground fault.
LLL Three-phase fault. II. VOLTAGE SAG SIMULATION
Simulation methods are an inexpensive choice to obtain
voltage sags characteristics, thus avoiding long and expensive
I. INTRODUCTION
periods of measurements. The two main tools used to calcu-
late voltage sag magnitude are electromagnetic transient and

V OLTAGE sags are a temporary reduction of the rms


voltage at a point of the electrical system below a certain
threshold. Voltage sags are mainly evaluated in terms of mag-
short-circuit calculation programs [5], [6].
Electromagnetic transient programs calculate the voltage
waveform and therefore provide a complete characterization of
nitude, duration, and frequency of occurrence [1]. the disturbance [7], [8].
The sag characteristics can be obtained through measure- Short-circuit calculation programs are more popular for
ments or simulations. The system performance can be assessed voltage sag assessment due to their easy application and simple
by long-term measurements or stochastic simulations [2]. network modeling. The voltage sag magnitude is obtained from
The main limitation of a measurement program is the long the bus impedance matrix. The sag duration can be estimated
time needed to obtain accurate results [3]. Another limitation is using a typical fault-clearing time [9], [10].
In this paper, sag magnitude and sag frequency are consid-
ered for the simulation validation. The sag frequency (SARFI)
Manuscript received January 29, 2007; revised August 29, 2007. This work
was supported by the CAPES (Brazil). Paper no. TPWRD-00032-2007.
represents the system performance. This index can be estimated
J. M. C. Filho and J. P. G. de Abreu are with Itajuba Federal University, Ita- for one bus, a group of buses, or the whole network. The system
juba 37500-903, Brazil (e-mail: jmaria@unifei.edu.br; polica@unifei.edu.br). performance can be calculated through stochastic or determin-
R. C. Leborgne is with the Federal University of Rio Grande do Sul (UFRGS),
Porto Alegre 90035-190, Brazil (e-mail: rcl@ece.ufrgs.br).
istic simulation.
E. G. C. Novaes is with Petrobras, Rio de Janeiro 01311-936, Brazil (e-mail: The stochastic assessment gives the expected performance
egcnovaes@yahoo.com.br). of the network. The method of fault positions and the Monte
M. H. J. Bollen is with STRI AB, Ludvika 771 80, Sweden. He is also with Carlo simulation are used for stochastic assessment [11], [12].
the Luleå University of Technology, Skellefteå 931 87, Sweden (e-mail math.
bollen@stri.se). The random variables, such as fault location, fault type, fault
Digital Object Identifier 10.1109/TPWRD.2008.916752 impedance, etc., are modeled by a probability distribution. This
0885-8977/$25.00 © 2008 IEEE

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO GRANDE DO SUL. Downloaded on March 11,2010 at 16:00:51 EST from IEEE Xplore. Restrictions apply.
FILHO et al.: VALIDATION OF VOLTAGE SAG SIMULATION TOOLS 1473

Fig. 1. Reduced diagram of the monitored power system.

simulation approach can be used to analyze the likelihood of The fault location is performed by the distance relays using
a system performance obtained from short-term measurements current and voltage information at only one of the line termi-
[13]. nals. This terminal is called “From” in Table IX. The difference
The deterministic assessment of the system performance between the actual fault location and the location estimated by
is carried out using sag measurements or simulating a set the relays does not exceed 5% of the line length. Table IX shows
of recorded faults. The fault-events are characterized by the the fault location in kilometers from the bus “From.”
location, type, impedance, and system configuration. The result There are no fault impedance estimators in the system.
of this assessment shows the system performance for a specific Therefore, the actual fault impedance is unknown and 0 fault
period. impedance is adopted for the base case.

III. STUDY CASE


B. Calculation Programs
A. Power System
A reduced version of the system studied is shown in Fig. 1. The electromagnetic transient program used here is the
The whole network contains 67 transmission lines (138 and 230 well-known Alternative Transients Program (ATP) [14]. The
kV) with a total length of 6619 km. There are 46 substations short-circuit calculation program employed in this research
with a transformer-installed capacity of 2076 MVA. The gen- is the ANAFAS [15]. As different programs use similar algo-
eration capacity is larger than the present demand. The excess rithms, the choice of program is not expected to impact the
of generated power is exported to another regional grid through results.
the substation where the PQ-monitor P9 is installed. The ATP calculates the instantaneous voltage waveform.
A total of 12 buses located at five substations were selected The model of the large generators includes the effect of the
for voltage sag monitoring. The measured buses voltage regulation. The long transmission lines are modeled by
are indicated in Fig. 1. The criteria for the bus choice were distributed parameters. The model of the transformers takes
network topology, load concentration, sensitive-loads location, account of the short-circuit impedance, the saturation, and the
main generation plants, and transformer connections. phase shift between the primary and the secondary voltages.
The monitoring system consists of 12 synchronized PQ mon- Usually the loads are modeled as constant resistances and reac-
itors. The synchronization was needed to do a correct cause/ef- tances. However, in a grid with a high penetration of induction
fect correlation. machines a more detailed load modeling is needed.
The measurements included: sag magnitude, sag duration and The ANAFAS calculates the voltage magnitude using the
voltage phasors. The measurements are based on phase-to-neu- bus impedance matrix. The generators are modeled as an
tral voltages. The time resolution of the rms values and pha- ideal voltage source behind the sub-synchronous reactance of
sors were 8.33 ms (half cycle). The selected sag threshold was the machines. The model adopted for the transmission lines
0.85 p.u. to avoid the overload of the PQ-monitor system with considers the resistance and the reactance, neglecting the shunt
shallow sags. capacitance. The transformer model includes the short-circuit
During the six-month monitoring period a total of 30 events impedance and the phase shift due to the winding configuration.
had the fault characterized by the location and the fault type, Usually, the loads are neglected when performing this static
according to Table IX. simulation, with the exception of large motor loads.

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO GRANDE DO SUL. Downloaded on March 11,2010 at 16:00:51 EST from IEEE Xplore. Restrictions apply.
1474 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 3, JULY 2008

TABLE I
SYSTEM MODELING

Fig. 2. Histogram of errors of simulated voltage sag magnitude.


Table I summarizes the system modeling for the ATP and the
short-circuit program. The system models were given by the TABLE II
utility. MAGNITUDE ERROR FOR ATP AND FAULT CALCULATION PROGRAM
The prefault voltage adopted by the ATP was the result of the
steady-state solution of the network. The prefault voltage used
by the short-circuit program was 1.0 p.u. Therefore, in order
to be able to compare the results obtained from both programs,
the loads simulated by the ATP have been slightly adjusted to
obtain prefault voltages close to 1.0 p.u. This adjustment was
done considering historical values of P and Q.
Using the ATP and the short-circuit calculation program, each
fault is simulated to obtain the sag indices at the 12 monitored Note: the average error and standard deviation is calculated considering the
absolute value of the errors.
buses. Therefore, the sag assessment is indeed deterministic.
Then, the simulated indices are compared with the measured
ones to evaluate the accuracy of the simulation approach. values are given. In most of the cases (91% and 93% for the
ATP and the fault calculation program, respectively) the abso-
IV. SAG MAGNITUDE VALIDATION lute error is less than 0.10 p.u. However, some of the results de-
viate considerably. The largest errors are 0.57 and 0.64 p.u. for
A. Sag Magnitude Error—Base Case the ATP and the fault calculation program, respectively. These
errors on the magnitude estimation are found for the same event
The set of simulation described in this section is called base registered at P6. This event is the No. 2 shown in Table IX,
case. The fault location is the one given by the distance relays, caused by a LG fault in a 230-kV line close to P6.
the fault impedance is 0 and the prefault voltages have not The accuracy of the results is affected by some uncertainties
been adjusted. such as the prefault voltage, the precise location of the fault,
The magnitude of the three-phase sags is determined by the and the fault impedance. The results are also affected by some
sag magnitude of the critical phase (i.e., the minimum rms value errors associated to the measurement system, such as voltage
of the three phases). The error of the simulated sag magnitude transformers and PQ-monitor.
is estimated using (1) In the next sections the results of a new set of simulations are
described, compared with the measurements and the previous
(1) simulated results. These new results are obtained after making
some changes in the three variables considered responsible for
where and are the measured and simulated the actual divergences: prefault voltage, fault location, and fault
voltage sag magnitudes in per unit. impedance.
The histograms of the sag magnitude error obtained using the
ATP and the short-circuit calculation program are shown in Fig.
B. Adjusting Prefault Voltage
2. The error distribution for the ATP is more symmetrical around
zero; there is a similar probability of over and underestimating In some cases, the measured prefault voltage reached values
the sag magnitude when using the ATP. On the other hand, the below 0.92 p.u., whereas the ATP simulated prefault voltages
fault calculation program estimates sag magnitudes larger than were about 0.98 p.u. and the ones adopted for the short-circuit
the measured ones in 73% of the cases. calculation program were 1.0 p.u. Hence, these variations were
The errors are summarized in Table II, where the average recorded and the largest absolute variation at each monitor lo-
values, the standard deviation, the minimum, and the maximum cation is presented in Table III.

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO GRANDE DO SUL. Downloaded on March 11,2010 at 16:00:51 EST from IEEE Xplore. Restrictions apply.
FILHO et al.: VALIDATION OF VOLTAGE SAG SIMULATION TOOLS 1475

TABLE III
LARGEST ABSOLUTE PREFAULT VOLTAGE VARIATIONS (IN p.u.)

Fig. 3. Sag magnitude error obtained by using the ATP after considering pre-
fault voltage adjustment.

TABLE IV
MAGNITUDE ERROR FOR ATP AND FAULT CALCULATION
PROGRAM AFTER PREFAULT VOLTAGE NORMALIZATION

Note: the average error and standard deviation are calculated considering the
absolute value of the errors. Fig. 4. Sag magnitude error obtained by using the short-circuit program after
considering prefault voltage adjustment.

The deviations are lower than 0.10 p.u. as expected consid-


ering normal system operation and the voltage regulation ac- The error variation on the voltage magnitude obtained using
cepted by the national standards. the ATP is shown in Fig. 3. With most of the monitored buses,
The voltage sag magnitude at bus due to symmetrical fault the error is lower when the results are normalized using the pre-
at bus is given by (2) fault voltages. On the other hand, the results obtained using the
short-circuit calculation program do not show the same favor-
(2) able trend. Just half of the monitored buses improved the results
when the sag magnitude was normalized considering the pre-
where and are the prefault voltages at the fault voltage, as shown in Fig. 4. However, the average errors
buses and , respectively. is the transfer impedance be- are still below 5% at most of the buses.
tween bus and , and is the driving point impedance at The sag magnitude adjustment is partial because the prefault
bus [16]. voltage at the fault location is not known. Therefore, there is still
Therefore, in order to avoid the error due to the use of dif- a considerable error in the simulations according to Table IV.
ferent prefault voltage at the monitored bus, the error estimated However, the error could be a consequence of other variables,
using (1) is recalculated normalized by the prefault voltages (3) such as the exact fault location and the fault impedance.

(3) C. Adjusting Fault Location


The fault location is calculated by the distance relays used for
where and are the measured and simulated the line protection. The utility stated that the maximum error of
voltage sag magnitudes and are the the fault location is lower than 5% of the line length. This result
prefault voltages obtained from the measurements and simula- was obtained comparing the actual fault location and the loca-
tions at the monitored bus. tion given by the relays. Therefore, it was decided to repeat the
The new average errors are shown in Table IV. The average simulation considering two new fault locations at the boundaries
magnitude error for the ATP results decreased from 0.050 to of the uncertainty interval.
0.044 p.u. However, the average error for the short-circuit cal- The sag magnitude errors obtained for the new fault locations
culation program is still 0.050 p.u. are presented in Figs. 5 and 6 for the ATP and the short-circuit

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO GRANDE DO SUL. Downloaded on March 11,2010 at 16:00:51 EST from IEEE Xplore. Restrictions apply.
1476 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 3, JULY 2008

Fig. 7. Sag magnitude error obtained at P6 by using the short-circuit program


Fig. 5. Sag magnitude error obtained by using the ATP after considering a 5% after considering a 5% variation of the fault location.
variation of the fault location.

Fig. 8. Sag magnitude error obtained by using the ATP after considering var-
Fig. 6. Sag magnitude error obtained by using the short-circuit program after ious fault impedances.
considering a 5% variation of the fault location.

program, respectively. The variations are related to the average


error found at each bus, estimated using (3).
In order to analyze the sag magnitude error variation at a spe-
cific bus for each simulated event, the results obtained at the bus
P6 are shown in Fig. 7. The event 2 is the one with the largest
error and also the one whose error varies most when the fault lo-
cation is adjusted. The initial error was 0.64 p.u. and for the new
fault location the error reduced to 0.32 p.u. This large variation
is a consequence of the close location of the event 2 from the
bus P6. After adjusting the fault location, the error obtained in
the calculated sag magnitude is still considerable large. There-
fore, another variable such as the fault impedance is suspected
of influencing this result. Fig. 9. Sag magnitude error obtained by using the short-circuit program after
considering various fault impedances.

D. Adjusting Fault Impedance


The consideration of a 0- fault impedance for the base case The average magnitude errors acquired at each bus are
affects the sag magnitude, especially for systems where large plotted in Figs. 8 and 9. The simulations are done considering
fault impedances are common. Therefore, the sag magnitude es- the former fault location provided by the utility.
timation must be redone considering other values of fault imped- The results indicate that at most of the buses, the magnitude
ances. According to the utility experience, another three values error increases in negative values when larger fault impedances
are simulated (5, 25, and 40 ). are chosen. This was expected, because the simulated sag mag-
In order to quantify the influence of the fault impedance, the nitude increases when the fault impedance increases according
sag assessment is repeated for the 17 faults to ground consid- to (3). The fault impedance, that minimizes the error, could be
ering the aforementioned fault impedances. the best choice to simulate fault for forecast purposes.

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO GRANDE DO SUL. Downloaded on March 11,2010 at 16:00:51 EST from IEEE Xplore. Restrictions apply.
FILHO et al.: VALIDATION OF VOLTAGE SAG SIMULATION TOOLS 1477

TABLE VII
VOLTAGE SAG FREQUENCY FOR DIVERSE THRESHOLDS

Both the average of absolute errors and standard deviation


are slightly sensitive to variations of the fault location and fault
Fig. 10. Sag magnitude error obtained at P6 by using the short-circuit program
after considering various fault impedances.
impedance. Moreover, the ATP and the short-circuit program re-
sults show the same trend. In addition, both of them presented
better performance for magnitude estimation when the fault lo-
TABLE V cation is shifted by 5% (i.e., when the fault location is shifted
MAGNITUDE ERROR FOR ATP
towards the bus called “From”) in Table IX.
The fault impedance greatly influenced the estimated sag
magnitude when the fault was located close to the observation
bus. When the fault impedance is increased the maximum
magnitude error becomes lower. However, the average absolute
error increases. Therefore, it is not possible to improve all the
results by changing the fault impedance. The impedance value
that minimizes the error for the system could not be the same
Note: the average error and std. deviation are calculated considering the as the one that minimizes the error at each monitored bus.
absolute value of the errors.

TABLE VI V. SAG FREQUENCY VALIDATION


MAGNITUDE ERROR FOR FAULT CALCULATION PROGRAM
A. SARFI-X Error-Base Case
The sag frequency index is deterministically calculated for
each of the monitored buses. Three different sag thresholds are
chosen (0.85, 0.70, and 0.50 p.u.). The system indices for the
three sag thresholds are shown in Table VII. The results indi-
cate that the ATP overestimates the number of sags for the three
analyzed thresholds, whereas the fault calculation program es-
Note: the average error and standard deviation are calculated considering the timates a number of sags closer to the actual values.
absolute value of the errors.
The sag frequency as a function of the sag magnitude
obtained by the two simulation approaches and by the mea-
The magnitude error for each voltage sag obtained at P6 is surements is shown in Fig. 11. The frequency error is rather
shown in Fig. 10 for several fault impedances. It is interesting small for sags with magnitude below 0.45 p.u. After that
to see that the event 2, the one that presented the largest mag- the frequency deviation is to some extent proportional to the
nitude error, is the one that presents the largest variation when number of sags. It seems that the frequency deviation is mainly
higher values of fault impedance are considered. The error is due to line-to-ground faults that give more shallow sags. The
minimized when a fault impedance of 40 is considered. This deviation may be due to an inaccurate representation of the
is a consequence of the close fault location to the bus P6; there- zero sequence impedance.
fore, the sag magnitude at P6 for the event 2 is highly sensitive The SARFI-85% obtained for each bus is presented in Fig. 12.
to the fault impedance used in the simulation. In some buses, the simulated sag frequency diverges consider-
ably from the measured one. One of the reasons of the high di-
E. Summary for Sag Magnitude vergence is that the selected threshold (0.85 p.u.) is in the region
where most of the sags are located, as shown in Fig. 11. Conse-
The error of the sag magnitude is summarized in Tables V and
quently, for this threshold, the largest variations are expected.
VI for each of the analyzed cases for the ATP simulation and the
short-circuit calculation. The sag magnitude error for the base
B. Adjusting Prefault Voltage
case was presented before in Table II and the sag magnitude
error after the adjustment of prefault voltage was presented in After the sag magnitudes have been adjusted by the pre-
Table IV. fault voltage, the sag frequency is again estimated. The new

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO GRANDE DO SUL. Downloaded on March 11,2010 at 16:00:51 EST from IEEE Xplore. Restrictions apply.
1478 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 3, JULY 2008

Fig. 14. SARFI-85% for each monitored bus after the fault location has shifted
Fig. 11. Cumulative frequency of sags.
0 5%.

Fig. 12. SARFI-85% for each monitored bus.


Fig. 15. SARFI-85% for each monitored bus after the fault location has shifted
+ 5%.

increased in one sag when the fault is shifted 5% for the ATP
and the short-circuit calculation. In this case, the new simulated
sag frequencies diverge more from the actual frequencies than
in the base case.

D. Adjusting Fault Impedance


The influence of the fault impedance on the calculated sag
frequency is shown in Figs. 16 and 17 for the impedance values
of 25 and 40 , respectively. The number of sags obtained by
Fig. 13. SARFI-85% for each monitored bus after prefault voltage adjustment.
simulation is reduced when the fault impedance increases, as
expected. A fault impedance of 40 improves the sag frequency
SARFI-85% obtained for each of the monitored buses is pre- index in most of the buses. However, in some buses, such as P4
sented in Fig. 13. and P6, considering larger fault impedance increases the error
The adjustment of the prefault voltage keeps the tendency of the index. .
of the base case: The simulated sag frequency is greater than The fault impedance is a random variable. However, it would
the measured one, with the exception of bus P6. But this bus be better to choose an impedance value to perform the voltage
presented a larger actual frequency than the simulated one for sag calculations. The analysis performed permits the calibration
the base case. of the simulation programs to minimize the errors. Nevertheless,
The sag frequency at the bus P7 is the same for simulations the adjusting is not unique. The values of fault impedance that
and measurement after the adjustment. On the other hand, the minimize the error for a given bus can be different from the
sag frequency at the bus P12 obtained after the adjustment is values that minimize the error at another bus or at a system level.
not as good as the base case result. The choice of the right fault impedance is mostly affected by the
fault distance from the monitored bus.
C. Adjusting Fault Location
As shown in Figs. 14 and 15, the variation of the fault loca- E. System Frequency Index
tion in 5% has a small influence on the calculated sag fre- The frequency index estimated for the whole system is pre-
quency. For example, at the buses P1, P2, P3, the sag frequency sented in Table VIII for the several simulated cases: prefault

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO GRANDE DO SUL. Downloaded on March 11,2010 at 16:00:51 EST from IEEE Xplore. Restrictions apply.
FILHO et al.: VALIDATION OF VOLTAGE SAG SIMULATION TOOLS 1479

TABLE IX
LIST OF REGISTERED FAULTS

Fig. 16. SARFI-85% considering a fault impedance of 25


.

Fig. 17. SARFI-85% considering a fault impedance of 40


.

TABLE VIII
SARFI-85% FOR THE SEVERAL SIMULATED CASES

the simulated cases, the error of the sag magnitude is lower than
10%. The few cases that presented large errors are due to faults
located near the monitored bus where the exact fault location
voltage adjustment, fault location shifted, and other values of and fault impedance significantly affect the calculated sag mag-
fault impedance. nitude.
The system frequency index estimated by simulation over- The simulated frequency is larger than the actual one at most
estimates the actual value for most of the simulated scenarios. of the monitored buses. The prefault voltage and the exact fault
Moreover, the best result for the system index is found by the location do not have a great impact on the simulated frequency.
short-circuit program for a fault impedance of 25 . However, the fault impedance has large influence on the sim-
ulated sag frequency, particularly for the events that happened
close to the observed buses.
VI. CONCLUSION
We conclude that for the study case the simulations agreed
In order to estimate the accuracy of voltage sag magnitude well with the measurements. However, the choice of the right
and frequency obtained by an electromagnetic transient pro- values for the fault characteristics is still a great challenge when
gram and a short-circuit calculation program, the result of a running simulations.
six-month sag survey was compared with the simulation of the The choice of an electromagnetic transient program or a
faults recorded during this period. short-circuit calculation program depends on the kind of study.
Voltage sag magnitudes obtained from the simulations are in The short-circuit program is recommended for stochastic calcu-
general very close to the measured ones. In more than 90% of lation of the system performance, because of simpler equipment

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO GRANDE DO SUL. Downloaded on March 11,2010 at 16:00:51 EST from IEEE Xplore. Restrictions apply.
1480 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 3, JULY 2008

modeling and faster computation algorithm. In contrast to that, [16] P. M. Anderson, Analysis of Faulted Power Systems. New York: IEEE
the ATP is advisable for the detailed study of individual events. Press Ser. Power Eng., 1995.

José Maria Carvalho Filho received the M.Sc. and D.Sc degrees in electrical
APPENDIX engineering from the Itajubá Federal University, Itajubá, Brazil, in 1996 and
2000, respectively.
The recorded faults are listed in Table IX. These faults have Currently, he is Associate Professor at Itajubá Federal University and a Power
Quality Study Group Member. His fields of interest include voltage sags and
been simulated to estimate the voltage sag characteristics. other power-quality issues. He is also a Specialized Consultant in industrial
planning.
REFERENCES
[1] Voltage Sags Indices, IEEE Std. P1564 draft 6, Jan. 2004.
[2] M. R. Qader, M. H. J. Bollen, and R. N. Allan, “Stochastic prediction Roberto Chouhy Leborgne (M’01) received the electrical engineering degree
of voltage dips in large transmission system,” IEEE Trans. Ind. Appl., and the M.Sc. degree in electric power engineering from the Itajubá Federal
vol. 35, no. 1, pp. 152–162, Jan./Feb. 1999. University, Itajubá, Brazil, in 1998 and 2003, respectively, and the Ph.D. degree
[3] M. H. J. Bollen, Understanding Power Quality Problems—Voltage from Chalmers University of Technology, Gothenburg, Sweden, in 2007.
Dips and Interruptions. New York: IEEE Press, 1999. He was with ABB-Daimler Benz Transportation Brazil, São Paulo, and
[4] L. Conrad, K. Little, and C. Grigg, “Predicting and preventing prob- Teyma Abengoa, Montevideo, Uruguay. Currently, he is an Associate Re-
lems associated with remote fault-clearing voltage dips,” IEEE Trans. searcher at the Federal University of Rio Grande do Sul, Porto Alegre, Brazil.
Ind. Appl., vol. 27, no. 1, pp. 167–172, Jan./Feb. 1991. His fields of interest include power quality and power system planning and
[5] J. M. C. Filho, J. P. G. Abreu, R. C. Leborgne, T. C. Oliveira, D. operation.
M. Correia, and J. F. Oliveira, “Comparative analysis between mea-
surements and simulations of voltage sags,” presented at the 10th
IEEE Power Eng. Soc. Int. Conf. Harmonics Quality of Power, Rio de
Janeiro, Brazil, Oct. 2002. José Policarpo G. de Abreu was born on Madeira Island, Portugal, in 1952. He
[6] W. Xu, “Component modeling issues for power quality assessment,” received the B.S.E.E. and M.Sc. degrees from the Itajubá Federal University, Ita-
IEEE Power Eng. Rev., vol. 21, no. 11, pp. 12–17, Nov. 2001. jubá, Brazil, in 1975 and 1980, respectively, and the D.Sc. degree in electrical
[7] M. H. J. Bollen, G. Yalcinkaya, and G. Hazza, “The use of electromag- engineering from the University of Campinas, Campinas, Brazil, in 1991. From
netic transient programs for voltage sags analysis,” presented at the 8th 1999 to 2000, he attended a postdoctoral program at Worcester Polytechnic In-
IEEE Power Eng. Soc. Int. Conf. Harmonics Quality of Power, Athens, stitute, Worcester, MA, on leave from the University of Campinas.
Greece, Oct. 1998. He is a Full Professor at the Itajubá Federal University, where he also is the
[8] J. A. Martinez and J. Martin-Arnedo, “Voltage sag stochastic prediction Power Quality Study Group Coordinator. His research interests include power-
using an electromagnetic transients program,” IEEE Trans. Power Del., quality issues, such as power definitions, harmonics, imbalance, and voltage
vol. 19, no. 4, pp. 1975–1982, Oct. 2004. sags. induction motors, transformers, and converter transformers.
[9] G. Olguin, “Voltage dip (sag) estimation in power system based on sto-
chastic assessment and optimal monitoring,” Ph.D. dissertation, Div.
Elect. Power Eng., Chalmers Univ. Technol., Gothenburg, Sweden,
2005.
[10] J. M. C. Filho, J. P. G. Abreu, H. Arango, and J. C. C. Noronha, “Elec- Eder G. C. Novaes was born in São Paulo, Brazil, in 1981. He received the
tric power system under voltage sag: A tool for achieving compati- B.S.E.E. and the M.Sc. degrees from the Itajubá Federal University, Itajubá,
bility,” in Proc. 9th IEEE Power Eng. Soc. Int. Conf. Harmonics Quality Brazil, in 2003 and 2007, respectively.
of Power, Orlando, FL, Oct. 2000, vol. 3, pp. 784–789. He is currently with Petrobras, Rio de Janeiro, Brazil. His fields of interest
[11] G. Olguin, D. Karlsson, and R. C. Leborgne, “Stochastic assessment of include power quality, electrical transients in power systems, and stability of
voltage sags (dips): The method of fault positions versus a Monte Carlo electric power systems.
simulation approach,” presented at the IEEE St. Petersburg PowerTech
Conf., St. Petersburg, Russia, Jun. 2005.
[12] J. M. C. Filho, J. P. G. Abreu, T. C. Oliveira, O. A. S. Carpinteiro, C.
B. R. Junior, F. A. Oliveira, R. P. Gomes, S. G. Carvalho, and D. N. Math H. J. Bollen (F’04) received the M.Sc. and Ph.D. degrees from Eindhoven
Gonçalves, “A software for voltage sags strategic studies,” presented at University of Technology, Eindhoven, The Netherlands, in 1985 and 1989, re-
the 11th IEEE Power Eng. Soc. Int. Conf. Harmonics Quality of Power, spectively.
Lake Placid, NY, Sep. 2004. Dr. Bollen is Manager of EMC and Power Quality at STRI AB, Ludvika,
[13] T. C. Oliveira, J. M. C. Filho, J. P. G. Abreu, and R. C. Leborgne, Sweden, and Guest Professor at EMC-On-Site, Luleå University of Technology,
“Voltage sags: Statistical evaluation of monitoring results based on pre- Skellefteå, Sweden. Before joining STRI in 2003, he was a Research Asso-
dicted stochastic simulation,” presented at the 12th IEEE Power Eng. ciate at the Eindhoven University of Technology from 1989 to 1993; Lecturer at
Soc. Int. Conf. Harmonics Quality of Power, Cascais, Portugal, Oct. the University of Manchester Institute of Science and Technology, Manchester,
2006. U.K., from 1993 to 1996; and Professor in Electric Power Systems at Chalmers
[14] CAUE-Comite Argentino de Usuarios de EMTP-ATP, ATP—Rule University of Technology, Gothenburg, Sweden, from 1997 to 2003. His re-
Book. Buenos Aires, Argentina, Dec. 2001. search interests cover a wide range of power system issues, with a special em-
[15] “Programa de análise de faltas simultâneas-ANAFAS, versão 3.0, phasis on power quality and reliability. He has published a number of funda-
manual do usuário,” (in Portuguese) Cepel-Centro de Pesquisas de mental papers on voltage dip analysis and two textbooks on power quality. He
Energia Elétrica, Dec. 1998. is active in several IEEE, CIGRE, and IEC working groups on power quality.

Authorized licensed use limited to: UNIVERSIDADE FEDERAL DO RIO GRANDE DO SUL. Downloaded on March 11,2010 at 16:00:51 EST from IEEE Xplore. Restrictions apply.

Vous aimerez peut-être aussi