Académique Documents
Professionnel Documents
Culture Documents
Short-Circuit Calculations
4.1Symmetrical Components
Symmetrical components are the traditional method used to calculate short-circuit currents and voltages for AC power systems. Dr. C. L.
Fortescue developed this method while investigating problems of singlephase railway systems in 1918. Symmetrical components allow the use of
single-phase loop or node equations to develop short-circuit currents
and voltages on single-phase, two-phase, or three-phase systems. The big
advantage of symmetrical components is the elimination of the need to
include transformer turns ratios and winding connections in calculations.
(Transformer data is used to develop base values and to incorporate phase
shifts into calculations.)
Three-phase loop or node equations can be used to calculate short-circuit
values on simple power systems (one machine, one line, one transformer).
However, for the typical power system, loop and node equations become
unwieldy, even with todays computing capability, because transformer
turns ratios and transformer winding connections need to be included
when traditional loop (Kirchoffs Laws) and node (Nortons Laws) calculations are used for circuit analysis.
When unusual power system configurations, such as a single-phase
transformer connected line-to-line on the primary and line-to-ground on
the secondary, are addressed, it is a good idea to use symmetrical components to calculate short-circuit values and loop or node equations to verify
the results.
The fundamental principles of symmetrical components are as follows:
58
3. Each sequence has its own line conductors, transformer equivalent circuits, generator equivalent circuits, etc.
4. Each sequence is independent of the other sequences (for balanced fault conditions).
5. Per unit quantities are used in calculations.
6. Single phase-to-ground faults are calculated as A to ground
faults.
7. Phase-to-phase faults are calculated as B to C faults.
8. Currents are calculated at the fault bus. Current dividers are used
to calculate currents at other points in each sequence network.
9. Voltages are calculated at the fault bus. Voltage dividers are used
to calculate voltages at other points in each sequence network.
10. Positive sequence voltage is maximum at a generator and minimum at a fault bus.
11. Negative and zero sequence voltages are maximum at a fault bus
and zero at their respective reference buses.
12. Phase voltage (or current) can be calculated if sequence voltage (or
current) is known.
13. Sequence voltage (or current) can be calculated if phase voltage
(or current) is known.
Theories, rules, equivalent circuits, methods to calculate squence impedances, etc., have been developed to allow easy application of symmetrical
components. A brief introduction to symmetrical components follows.
A single-line diagram of a simple system that consists of two generators, two transformers, and one transmission line is shown in Figure 4.1.
This simple system will be used to demonstrate the use of symmetrical
components.
Various generator impedances are provided by the manufacturer in
percent at rated generator voltage and MVA. For short-circuit analysis, use
of the following impedance values should be considered. Xd (generator
subtransient reactance) is the generator impedance at the instant a threephase fault occurs on the terminals of a generator. Xd (generator transient
reactance) is the generator impedance a few cycles after a three-phase fault
occurs on the terminals of a generator. Xd (generator synchronous reactance) is the generator impedance after a three-phase fault persists on the
terminals of a generator. Xd is used as the generator impedance in most
calculations. Xd, Xd, and other generator impedances may be used when
developing specific calculations to analyze generator parameters, circuit
breaker-interrupting capability, stuck circuit-breaker conditions, etc.
Transformer impedances are provided by the manufacturer in percent
at rated transformer voltage and MVA. Although transformer impedance
varies with tap position, the nominal transformer impedance, nominal
2009 by Taylor & Francis Group, LLC
59
Short-Circuit Calculations
Generator 1
320 MVA, 23 KV
Xd = 18.5%
Xd = 52.3%
Xd = 104%
Bus 1
Bus 2
Z1L = 1.7 + j 19.0
Generator 2
410 MVA, 13.8 KV
Xd = 20.2%
Xd = 56.4%
Xd = 108%
Transformer 2
400 MVA, 13.8230 KV
X= 13.21%
13.8 KV:
230 KV: Y-Grd
Bus 1
Z1 Trans 1
Bus 2
Z1 Line
Z1 Trans 2
Figure4.2
Positive sequence network for the system shown in Figure4.1.
Z1 Gen 2
RB1
60
reference bus, RB1, the common point to which one terminal of all power
sources in the positive sequence are connected, is needed for network
analysis.
Bus 1
Z2 Trans 1
Bus 2
Z2 Line
Z2 Gen 2
Z2 Trans 2
RB2
Figure4.3
Negative sequence network for the system shown in Figure4.1.
61
Short-Circuit Calculations
Bus 2
Z0 Gen 1
RB0
RB0
Z0 Trans 1
Z0 Line
Z0 Trans 2
Z0 Gen 2
RB0
RB0
Figure4.4
Zero sequence network for the system shown in Figure4.1.
4.5Operators
Symmetrical components utilize a unit vector, designated a, to transform phase quantities to sequence quantities and to transform sequence
quantities to phase quantities.
2009 by Taylor & Francis Group, LLC
62
Ea1 = Ea1
Ea1
Eb1
Figure4.5
Positive sequence voltage vectors.
63
Short-Circuit Calculations
Ea2 = Ea2
Ea2
Ec2
Figure4.6
Negative sequence voltage vectors.
64
RB1
Z1 Gen 1
Bus 2
Bus 1
Z1 Trans 1
I1
Z1 Line
Z1 Gen 2
RB1
Z1 Trans 2
Figure4.8
Positive sequence network for a three-phase fault at Bus 1.
RB1
Z1 Gen 1
Bus 2
Bus 1
Z1 Trans 1
Z1 Line
I1
Z1 Gen 2
RB1
X Z1 Trans 2
Figure4.9
Positive sequence network for a three-phase fault at Bus 2.
65
Short-Circuit Calculations
Bus 1
RB1
Z1 Trans 1 X
Z2 Gen 1
RB2
Bus 1
X
Z2 Trans 1
RB1
I1
Z1 Line
Z1 Trans 2
Bus 2
I2
Z2 Line
Z2 Gen 2
Z2 Trans 2
RB2
Figure4.10
Positive and negative sequence networks for a phase-to-phase fault at Bus 1.
4.9Per-Unit Quantities
When developing power system calculations, per-unit quantities are used
because per-unit quantities are simpler to use than amperes, ohms, and
volts. (Percent quantities are per-unit quantities multiplied by 100.) This is
2009 by Taylor & Francis Group, LLC
66
Z1 Gen 1
RB1
Z1 Trans 1 X
Z2 Gen 1
RB2
RB0
Bus 2
I1
Z1 Line
Bus 1
Z2 Trans 1 X
I2
Z2 Line
Z0 Trans 1 X
Z1 Gen 2
RB1
Z1 Trans 2
Bus 2
Bus 1
Z0 Gen 1
RB0
Bus 1
Z2 Gen 2
RB2
Z2 Trans 2
Bus 2
I0
Z0 Line
Z0 Trans 2
Z0 Gen 2
RB0
RB0
Figure4.11
Positive, negative, and zero sequence networks for a phase-to-ground fault at Bus 1.
due to the fact that per-unit quantities can be manipulated for transformer
turns ratios or connections after circuit analysis has been completed.
Therefore, all impedances, currents, and voltages are converted to perunit quantities using the following rules.
Base Current =
Base MVA
67
Short-Circuit Calculations
MVA (new)
MVA (given)
KV 2 (given )
KV 2 ( new)
4.10Sample Calculations
Using the information presented in Figure 4.1, short-circuit currents
will be calculated through the use of symmetrical components and per
unit impedances.
The base MVA will be 100 MVA (100 MVA is closer to the generator and
transformer MVA ratings in Figure4.1 than is 10 MVA) and base voltages
will be 230 KV for the transmission system, 23 KV for Generator 1, and
13.8 KV for Generator 2.
One of the first steps is to place all impedances on a common, 100 MVA
base. For transformers and generators, this is accomplished by normalizing published values:
68
{
= 251 {.099 90 .118 88.5}
69
Short-Circuit Calculations
RB1
Z1 Gen 1
j.058
Bus 1
Bus 2
I1
Z1 Line
Z1 Trans 1
X
.003 + j.036
j.041
Z1 Gen 2
j.049
RB1
Z1 Trans 2
j.033
Figure4.12
Positive sequence network for a three-phase fault at Bus 1.
per-unit method will be used to calculate A-N voltage. (Voltage is calculated assuming generator internal voltage is 1.00 pu. Voltage drop, I Z, is
calculated for each element.)
Generator 1 terminal voltage = 1.00 pu 10.10 pu 90 j.058 =
0.414 pu = 5.5 KV ( N), 9.5 KV (e c)
Bus 1 voltage = 1.00 pu 10.10 pu 90 (j.058 + j.041) = 0 pu
Generator 2 terminal voltage = 1.00 pu 8.47 pu 88.5 j.049 =
0.585 pu 1.0 = 4.66 KV ( N), 8.07 ( )
Bus 2 voltage = 1.00 pu 8.47 pu 88.5 (j.049 + j.033) = 0.306 pu
3.3 = 40.6 KV ( N), 70.3 KV ( )
For three-phase faults, phase current and voltage are balanced; therefore, voltage and current magnitudes apply to all three phases.
Ia1 =
70
Z1 Gen 1
j.058
RB1
Bus 1
Z1 Trans 1 X
j.041
Z2 Gen 1
j.058
RB2
Bus 1
X
Bus 2
I1
RB1
Z1 Trans 2
j.033
Z1 Line
.003 + j.036
Bus 2
I2
Z2 Trans 1
j.041
Z1 Gen 2
j.049
Z2 Line
.003 + j.036
Z2 Gen 2
j.049
Z2 Trans 2
j.033
RB2
Figure4.13
Positive and negative sequence networks for a phase-to-phase fault at Bus 1.
Short-Circuit Calculations
71
Ia1 = Ia 2 = Ia0 =
100 MVA
3 230 KV (Z1 + Z 2 + Z 0 )
Ia1 = 251 { 0.054 89.3 + 0.054 89.3 + (j.041 0.028 + j.119 + j.033)}
Ia1 = 251 {0.054 89.3 + 0.054 89.3 + 0.03287.8}
Ia1 = 251 0.114089
Ia1 = 1790 amps 89 Ia2 = 1790 amps 89 Ia0 = 1790 amps 89
Ia1 = 7.13 pu 89
Ig = Ia1 + Ia2 + Ia0 = 3 1790 amps 89 = 5372 amps 89
3I0 Gen 1 source = 5372 amps 89 0.155 79.6 0.193 81.7 =
4258 amps 91.7
3I0 Gen 2 source = 5372 amps 89 0.041 90 0.193 81.7 =
1129 amps 80.7
Note that for three-phase faults, the division of current is 55% from
Generator 1 source and 45% from Generator 2 source, but for single phaseto-ground faults, the division of current is 79% from Generator 1 source
and 21% from Generator 2 source.
When calculating phase voltages for phase-to-ground faults, positive
sequence, negative sequence, and zero voltages must be calculated as is
shown for Bus 1.
Positive Sequence Voltage (Ea1 = Egen I1Z1)
Bus 1 voltage = 1.00 pu 7.13 pu 89 0.054 89.3 = 0.616 pu 0.2
2009 by Taylor & Francis Group, LLC
72
Bus 2
Z1 Gen 1
j.058
RB1
Z1 Trans 1 X
j.041
Z2 Trans 1 X
j.041
RB0
I2
Z0 Trans 1 X
j.041
RB1
Z1 Trans 2
j.033
Bus 2
Z2 Line
.003 + j.036
Bus 1
Z0 Gen 1
RB0
Z1 Line
.003 + j.036
Bus 1
Z2 Gen 1
j.058
RB2
I1
Z1 Gen 2
j.049
Z2 Gen 2
j.049
RB2
Z2 Trans 2
j.033
Bus 2
I0
Z0 Line
.028 + j.119
Z0 Trans 2
j.033
Z0 Gen 2
RB0
RB0
Figure4.14
Positive, negative, and zero sequence networks for a phase-to-ground fault at Bus 1.
73
Short-Circuit Calculations
Bus 2
I1
Z1 Line
.003 + j.036
Bus 1
Z2 Line
.003 + j.036
Bus 1
RB1
Z1 Trans 2
j.033
Bus 2
I2
Z1 Gen 2
j.049
Z2 Gen 2
j.049
RB2
Z2 Trans 2
j.033
Bus 2
I0
Z0 Line
.028 + j.119
Z0 Trans 2
j.033
Z0 Gen 2
RB0
RB0
Figure4.15
Positive, negative, and zero sequence networks for a single phase-to-ground fault at Bus 1
with generator 1 and transformer 1 off-line.
74
Bus 2
Z1 Trans 1
X
j.041
I1
Z1 Line
.003 + j.036
Bus 1
Z2 Trans 1
X
j.041
Z2 Line
.003 + j.036
Bus 1
RB0
Z0 Trans 1 X
j.041
RB1
Z1 Trans 2
j.033
Bus 2
I2
Z1 Gen 2
j.049
Z2 Gen 2
j.049
Z2 Trans 2
j.033
RB2
Bus 2
I0
Z0 Line
.028 + j.119
Z0 Trans 2
j.033
Z0 Gen 2
RB0
RB0
Figure4.16
Positive, negative, and zero sequence networks for a single phase-to-ground fault at Bus 1
with generator 1 off-line.
75
Short-Circuit Calculations
Bus 2
Bus 1
Generator 1
320 MVA, 23 KV
Xd = 18.5%
Generator 2
410 MVA, 13.8 KV
Xd = 20.2%
Transformer 2
400 MVA, 13.8230 KV
X= 13.21%
13.8 KV:
230 KV: Y-Grd
Transformer 1
300 MVA, 23230 KV
X = 12.35%
23 KV:
230 KV: Y-Grd
Figure4.17
One-line diagram showing transformer connections and component impedances, second
transmission line on same structures as first transmission line.
Bus 1
RB1
Z1 Line
.003 + j.036
Bus 2
Z1 Gen 2
j.049
Z1 Gen 1
j.058
Z1 Trans 1
j.041
I1
Z1 Line
.003 + j.036
RB1
Z1 Trans 2
j.033
Figure4.18
Positive sequence network for a three-phase fault at Bus 1.
Bus 1
Bus 2
Z0L-S Z0L-M
Z0L-S Z0L-M
Z0L-M
Figure4.19
Zero sequence equivalent for two parallel transmission lines, all circuit breakers closed.
Z1eq = 0.050 89.6, which is slightly less than the positive sequence impedance for the network with one line (Z1eq = 0.054 89.5).
The zero sequence representation of two parallel, mutually coupled
transmission lines, for through faults, such as a fault at Bus 1 with all
circuit breakers closed, is shown in Figure4.19 and the zero sequence network for this fault is shown in Figure4.20.
The zero sequence impedance of this network for a fault at Bus 1 is
Z0eq = 0.031 87.3, which is almost the same as the zero sequence impedance for the network with one line (Z0eq = 0.032 87.8). Taken together, the
change in positive and zero sequence impedance will have little effect on
2009 by Taylor & Francis Group, LLC
76
Bus 1
Z0L-S Z0L-M
.026 + j.047
Bus 2
Z0 Gen 1
RB0
RB0
Z0 Gen 2
Z0 Trans 1
j.041
Z0L-S Z0L-M
.026 + j.047
Z0L-M
.024 + j.072
Z0 Trans 2
j.033
RB0
RB0
Figure4.20
Zero sequence network for the system shown in Figure4.17 with per-unit impedances.
the total fault current. However, the current through each line will change
significantly.
Ia1 = Ia 2 = Ia0 =
77
Short-Circuit Calculations
Bus 2
Bus 1
Generator 1
320 MVA, 23 KV
Xd = 18.5%
Generator 2
410 MVA, 13.8 KV
Xd = 20.2%
Transformer 1
300 MVA, 23230 KV
X= 12.35%
Line End
Fault
Transformer 2
400 MVA, 13.8230 KV
X = 13.21%
Figure4.21
One-line diagram showing line-end fault with circuit breaker open at Bus 2.
Bus 2
Z0L-S Z0L-M
Bus 1
Z0L-M
Z0L-S Z0L-S
M
X
Figure4.22
Zero sequence equivalent for two parallel transmission lines, line-end fault, one circuit
breaker open.
Bus 1
Z0L-S Z0L-M
.026 + j.047 Bus 2
Z0 Gen 1
RB0
RB0
Z0 Gen 2
Z0 Trans 1
j.041
Z0L-M
.024 + j.072
Z0L-S Z0L-M
.026 + j.047
Z0 Trans 2
j.033
RB0
RB0
Figure4.23
Zero sequence network for the system shown in Figure 4.21 with per-unit impedances,
circuit breaker at Bus 2 open.
3I0 Gen 1 source = 3277 amps 86.7 0.080 87.1 0.195 81.7 =
1243 amps 81.3
3I0 Gen 2 source = 3277 amps 86.7 0.116 78.0 0.195 81.7 =
1.945 amps 90.4
The preceding calculations illustrate that the magnitude and division
of zero sequence current needs to be carefully considered as mutual coupling and ground banks combined with other system parameters complicate analysis of fault conditions.
2009 by Taylor & Francis Group, LLC