Académique Documents
Professionnel Documents
Culture Documents
There are various benefits for grounding and bonding ac transmission and
distribution power systems. The basis for selection of a given grounding
system type depends on its ability to provide personnel safety and equipment
protection. Primarily, the electric power industry is concerned with reducing
shock and flash hazards to personnel working with electrical systems, limiting
damages to the electrical system components due to transient over voltages,
and minimizing interruption to the commercial or industrial processes that the
electrical system supports.
Based on these criteria, the prevailing grounding design philosophy is to
provide a grounded system over an ungrounded one for satisfying these
objectives. Nevertheless, an understanding of the basic operation of each
type of system is necessary for matching the appropriate grounding topology
to the electrical system performance. Commercial buildings, with most of their
equipment operating at 600 V and less, seem to have standardized on a solid
grounding and bonding approach. Proper application of this approach is done
through the lens of the National Electrical Code.
minimizes circulating third harmonic currents that can affect ground-fault over
current devices.
Paralleled generators grounding can be implemented with a common neutral
bus connected to a single ground bus, or with individual neutral buses
connected to their respective ground buses. In order to use the parallel lineup
with the common neutral bus, the switchboard with generator over current
devices has to be adjacent to the generators themselves. This is because the
neutral-to-ground connection on the SDS has to be at the generators or at the
first disconnecting means downstream of the generators (250.30(A)(1) NEC).
By this code requirement, if the generator switchboard were to be located
remotely from the generators themselves, then the neutral-to-ground bond
would have to be at the integral over current device of each generator. It must
be stressed here that this application of solid grounding for generators
described above is not common practice for generators with voltages above
600 V. This is because the single line-to-ground faults under solid grounding
at these higher voltages tend to be greater than the 3-phase bolted faults that
generator manufacturers design their generators to handle.
Conclusion
There are several schemes for grounding and bonding transformers and
generators. They include ungrounded, impedance grounded, and solidly
grounded. The impedance grounded systems are sub-divided into high
resistance, low resistance, reactance, and tuned reactance. Ungrounded
systems, which at one time were one of the most widely used grounding
systems, are currently the least used grounding method. The ungrounded
system is designed to allow the first ground fault to exist indefinitely to
facilitate service continuity while the fault is located. Unfortunately, the system
under this condition, tended to develop transient over voltages which led to
equipment and conductor insulation failures.
In an effort to strike a balance between service continuity and the reduction of
transient over voltages, other impedance grounding schemes and solid
grounding were developed. At voltages above 600 V, solid grounding is not as
widely used because of the higher point-of-fault energy levels. However, at
600 V and less, solid grounding is the de facto standard for commercial
buildings transformers and generators. At this lower voltage, solid grounding,
with its inclusive coordinated over current devices, is designed to quickly
isolate ground-faults. In this way, only the faulted portion of the system is out
of service, while the remainder of the system continues to operate.
Explanation of terms
A grounded electrical system is one in which at least one conductor from
the system, or point on the conductive system, is connected to either earth or
some other conducting body that serves in place of the earth. This connection
can be with or without an intermediary impedance device. With an extremely
low-impedance device, the system is said to be solidly or effectively grounded.
With an impedance device, the system can be either resistively or reactively
grounded.
A bonded electrical system is one in which the non-current-carrying
conductive materials of the electrical system are connected together in such a
way that they present a low-impedance path for ground-fault currents. This
bonded connection permits phase-to-ground-fault currents on the grounded
system to flow back to the electrical source for subsequent safety actions by
the system. Because of the interconnectivity of a grounded and bonded
system, a bonded system also aids the objective of a grounded system.