TECH
TE
HN
NIC
CA
ALDA
AT
TA

COA
C
ALF
FIR
REDPO
OWE
ER
STA
ATIION
N,BA
ABE
ELA
AN
ELECT
TRICFIREPUMP.Cap
p.2000Gpm@9BaarTotalHeead
DIESELFIREP
PUMPCap.2000Gpm
m@9BarTotalHeaad
JOCK
KEYPUMP
PCap.12M
M3/H@10
00MeterT
TotalHead
d

AU
URORA
A PUMP
P

P ROD
PT.
DA NURMALA
A

13-005-20155

SUBJECT : TECHNICAL REVIEW

: Coal Fired Power Station, Babelan

Project

INDUSTRIAL DIVISION
Qty

No

Description

Set
1

1
1

Set
1

Set
1

Pump and Accessories For Fuel Handling Systems


ELECTRIC FIRE PUMP UL/FM, NFPA-20 STANDARD
Cap. 2000 GPM @ 9 Bar Total Head
"Aurora" Horizontal Split Case
Model : 8-481-21/Single Stage
Pump Material Design, Casing : Cast Iron, Impeller : Bronze,
Shaft : Carbon Steel with Bronze Sleeve, Shaft Seal : Gland Packing
Pump Accessories : Suction and Discharge Gauges, Automatic Air
Release Valve, Casing Relief Valve
"Factory Choice" ODP Electric Motor 250 HP @ 1480 Rpm
With 380V/ 3Ph/ 50Hz
"Tornatech" Electric Fire Pump Controller
Model : GPY
DIESEL FIRE PUMP UL/FM, NFPA-20 STANDARD
Cap. 2000 GPM @ 9 Bar Total Head
"Aurora" Horizontal Split Case
Model : 6-491-14A/single stage
Pump Material Design, Casing : Cast Iron, Impeller : Bronze,
Shaft : Carbon Steel with Bronze Sleeve, Shaft Seal : Gland Packing
Pump Accessories : Suction and Discharge Gauges, Automatic Air
Release Valve, Main Relief Valve, Enclosed Waste Cone
"CLARKE" Diesel Engine JU6H-UFAAS0, 260 HP @ 2100 Rpm
Heat Exchanger Cooling System with cooling loop and double starter
twin solenoid
Engine accessories : Batteries Cables, Battery rack, Silencer,
Flexible Exhaust Connector, Fuel Tank (Supplied by Import)
"Tornatech" Diesel Fire Pump Controller
Model : GPD
- Flow Meter
JOCKEY PUMP
Cap. : 12 M/H @ 100 Meter Total Head
"Aurora" Vertical Multistage In-Line
Model : PVM 10-14
Pump Material Design, Casing : Stainless Steel, Impeller : Stainless
Steel, Shaft : Stainless Steel, Shaft Seal : Mechanical Seal
"Factory Choice" Motor 10 HP @ 2915 Rpm

Page 1 of 2

REFERENCE LIST AURORA PUMP


IN INDONESIA
NO

PROJECT NAME

LOCATION

LINE

DUTY

YEAR

HINDOLI

PALEMBANG

BUILDING

FIRE PUMP

1988

SEMEN CIBINONG

CIBINONG

INDUSTRY

FIRE PUMP, TRANSFER PUMP

1999

MACRO

DENPASAR

BUILDING

FIRE PUMP

1999

BATU HIJAU WTP SECTION I

PLAZA DAGO

MAKRO

JAKARTA

BUILDING

FIRE PUMP

1999

MAKRO

MEDAN

BUILDING

FIRE PUMP

2000

SCHLUMBERGER

BALIKPAPAN

BUILDING

FIRE PUMP

2000

BANDUNG

MINING

FIRE PUMP

1999

BUILDING

FIRE PUMP

1999

BATU HIJAU WTP SECTION II

MINING

FIRE PUMP

2000

10

MULAWARMAN UNIV. PACKAGED I

BUILDING

FIRE PUMP

2000

11

MULAWARMAN UNIV. PACKAGED II

BUILDING

FIRE PUMP

2000

12

MULAWARMAN UNIV.PACKAGED III

BUILDING

FIRE PUMP

2000

13

GS BATTERY

FACTORY

FIRE PUMP

2000

JAKARTA

14

AUTO 2000 TEBET

JAKARTA

SHOWROOM

FIRE PUMP

2001

15

GLOBAL AGROTEK

JAKARTA

BUILDING

FIRE PUMP

2002

16

MALL FANTASI

BALIKPAPAN

BUILDING

FIRE PUMP

2002

17

TEMPO

MEDAN

WAREHOUSE

FIRE PUMP

2002

18

SUSU CAIR INDOMILK

FACTORY

FIRE PUMP

2002

19

PRESIDEN HOTEL

JAKARTA

BUILDING

FIRE PUMP

2002

20

BINTARO TRADE CENTER

JAKARTA

BUILDING

FIRE PUMP

2003

21

MALL KAREBOSI

MAKASSAR

BUILDING

FIRE PUMP

2003

22

MULIA TOWER

JAKARTA

BUILDING

FIRE PUMP

2003

23

BNI46 LADA

JAKARTA

BUILDING

FIRE PUMP

2003

24

EXSPAN KAJI

JAKARTA

BUILDING

FIRE PUMP

2003

25

WTC MANGGA DUA

JAKARTA

BUILDING

PLUMBING

2003

26

TAMAN IMPIAN JAYA ANCOL

JAKARTA

BUILDING

FIRE PUMP

2003

27

SEMEN CIBINONG

CIBINONG

CEMENT INDUSTRY

SEWAGE PUMP

2003

28

PANGRANGO PLAZA

BOGOR

BUILDING

FIRE PUMP

2003

29

ACA

BANDUNG

BUILDING

FIRE PUMP

2003

30

ITC KEBON KELAPA

BANDUNG

MARKET

FIRE PUMP

2003

WAREHOUSE

WATER IN TAKE VERTICAL


TURBINE

2004

31

PUPUK KUJANG

CIKAMPEK

32

MATA PELANGI OFFICE

JAKARTA

BUILDING

FIRE PUMP

2004

33

BSD MARKET

TANGERANG

BUILDING

FIRE PUMP

2004

34

TOTAL INDONESIA

MINING

PROCESS PUMP

2004

35

GRAND SOLO MALL

SOLO

BUILDING

FIRE PUMP

2004

36

CIPUTRA SERAYA MALL

PEKANBARU

BUILDING

FIRE PUMP

2004

37

PUSAT DAGANG INVESTASI

38

BELLAGIO RESIDENCE

JAKARTA

BUILDING

FIRE PUMP

2004

39

PONDOK INDAH MALL 2

JAKARTA

BUILDING

FIRE PUMP, CHILLER PUMP

2004

40

SAN MIGUEL

JAKARTA

FACTORY

FIRE PUMP

2004

41

BAYER

MEDAN

FACTORY

FIRE PUMP

2005

42

BAYER

SURABAYA

FACTORY

FIRE PUMP

2005

43

MEGA GLODOK KEMAYORAN

JAKARTA

BUILDING

FIRE PUMP

2005

44

SEMEN PADANG

PADANG

CEMENT INDUSTRY

COOLING TOWER

2005

45

SEMEN CIBINONG

CIBINONG

CEMENT INDUSTRY

WATER INJECTION

2005

46

SEMEN CIBINONG

CIBINONG

CEMENT INDUSTRY

WATER SPRAY

2005

47

PERTAMINA PRABUMULIH

PRABUMULIH

OIL & GAS

FIRE PUMP

2005

FIRE PUMP

2005

48
49

BATAM

BG JUNCTION / BUBUTAN

BUILDING

SURABAYA

FIRE PUMP

BUILDING

CHILLER & BOOSTER

FACTORY

VERTICAL TURBINE
PUMP

2004

2005
FIRE

50

BAYER

JAKARTA

2005

51

BPKP PRAMUKA

JAKARTA

BUILDING

FIRE PUMP

2005

52

BATAM CITY SQUARE

BATAM

BUILDING

FIRE PUMP

2005

53

MECOINDO

CIKARANG

FACTORY

FIRE PUMP

2006

54

OIL & GAS

FIRE PUMP

2006

55

GRIYA JENGGALA

JAKARTA

RESIDENTIAL

FIRE PUMP

2006

56

SUDIRMAN PARK

JAKARTA

BUILDING

FIRE PUMP

2006

57

PEARL GARDEN

JAKARTA

BUILDING

FIRE PUMP

2006

58

MODERN GOLF APARTEMENT

TANGERANG

BUILDING

FIRE PUMP

2006

59

CITY HOME KLP. GADING

JAKARTA

BUILDING

FIRE PUMP

2006

60

ISLAMIC CENTER

JAKARTA

BUILDING

FIRE PUMP

2006

61

INDONESIA NS FACTORY

JAKARTA

FACTORY

FIRE PUMP

2006

62

PLAZA CIBUBUR

JAKARTA

BUILDING

FIRE PUMP

2006

63

SUDIRMAN PLAZA

JAKARTA

BUILDING

FIRE PUMP

2006

64

WISMA 76

JAKARTA

BUILDING

FIRE PUMP

2006

65

GRAND INDONESIA

JAKARTA

BUILDING

FIRE PUMP, CHILLER PUMP,


PLUMBING PUMP

2006

66

NUSA 2 GOLF RESIDENT

BALI

BUILDING

FIRE PUMP

2006

68

PT. PJB UP MUARAKARANG

JAKARTA

POWER PLANT

FIRE PUMP

2006

69

LAMONGAN INTEGRATED
SHORE BASE

LAMONGAN

SHORE BASE
- WAREHOUSE

FIRE PUMP

2006

70

UPH KARAWACI

TANGERANG

BUILDING

FIRE PUMP

2006

71

XL PEKAN BARU

PEKAN BARU

BUILDING

FIRE PUMP

2006

72

DSS PROJECT

JAKARTA

FACTORY

FIRE PUMP

2006

73

SKF INDONESIA

JAKARTA

FACTORY

FIRE PUMP

2006

74

JOHNSON & SON PROJECT

JAKARTA

FACTORY

FIRE PUMP

2006

75

SENTRA GROSIR

CIKARANG

BUILDING

FIRE PUMP

2006

76

SEMEN BASOWA

SULAWESI

CEMENT INDUSTRY

REGENERATIVE TURBIN PUMP

2006

77

GRAND INDONESIA

JAKARTA

BUILDING

FIRE PUMP

78

KEDUTAAN BELANDA

JAKARTA

BUILDING

FIRE PUMP

BUILDING

VERTICAL TURBINE
PUMP

2006
2006
FIRE

79

HARDA BANK

JAKARTA

2006

80

MENARA PRIMA

JAKARTA

BUILDING

FIRE PUMP

2006

81

WISMA PONDOK INDAH

JAKARTA

BUILDING

FIRE PUMP, CHILLER PUMP

2006

82

SEMEN PADANG

PADANG

CEMENT INDUSTRY

HVAC PUMP

2006

83

ITC KOPO

BANDUNG

BUILDING

FIRE PUMP

2006
2006

84

THE EAST

JAKARTA

BUILDING

FIRE & CHILLER PUMP

85

PERTAMINA SAGATA

KALIMANTAN

OIL & GAS

FIRE PUMP

2006
2006

86

HOLCIM INDONESIA

JAKARTA

CEMENT INDUSTRY

REGENERATIVE TURBINE PUMP

87

SPRING HILL GOLF RESIDENCE

JAKARTA

RESIDENTIAL

FIRE PUMP

2006

88

HOLCIM INDONESIA

JAKARTA

CEMENT INDUSTRY

REGENERATIVE TURBINE PUMP

2006

89

JACC

JAKARTA

BUILDING

FIRE PUMP

2006

90

ETERNIT GRESIK

GRESIK

FACTORY

FIRE PUMP

2006

91

PLAZA ASIA TASIKMALAYA

TASIKMALAYA

BUILDING

CHILLER PUMP

2006

92

IPEKA SCHOOL

JAKARTA

BUILDING

FIRE PUMP

2006

93

PLAZA ASIA TASIKMALAYA

TASIKMALAYA

BUILDING

94

TOYOTA ASTRA MOTOR

JAKARTA

FACTORY

PLUMBING PUMP
SUBMERSIBLE PUMP
DEEP WELL PUMP
FIRE PUMP

95

CARREFOUR CIBINONG

BANDUNG

BUILDING

FIRE PUMP

2007

96

CARREFOUR KIARA CONDONG


MALL

BANDUNG

BUILDING

FIRE PUMP

2007

97

PERFETI VAN MELLE

JAKARTA

FACTORY

FIRE PUMP

2007

98

DATA CENTER

SURABAYA

BUILDING

FIRE PUMP

2007

99

TOYOTA ASTRA MOTOR

JAKARTA

FACTORY

CHILLER PUMP

2007
2007
2007

2007
2007

100

GRAND INDONESIA

JAKARTA

BUILDING

CHILLER PUMP APARTMENT,


CONVENTION HALL

101

CNOOC

OFFCHORE

OFFSHORE OIL RIG

VERTICALTURBINE
SEA WATER FIRE PUMP

102

PASAR BARU SQUARE

BALIKPAPAN

HOTEL AND MALL

FIRE PUMP

2007

103

SEMEN PADANG

PADANG

CEMENT INDUSTRY

HVAC PUMP

2007

104

NESTLE - PASURUAN

PASURUAN

FACTORY

FIRE PUMP

2007

FIRE PUMP, CHILLER PUMP


PLUMBING PUMP, DEEP WELL
PUMP

2007

105

ST. REGIS BALI

BALI

BUILDING

106

CARREFOUR RUNGKUT

SURABAYA

BUILDING

FIRE PUMP

2007

107

PABRIK SUGIZINDO

CIBINONG

FACTORY

FIRE PUMP

2007

108

SEK-NEG DIKLAT CIPETE

JAKARTA

BUILDING

FIRE PUMP

2007

109

THE CITY TOWER

JAKARTA

OFFICE

FIRE PUMP

2007

110

KEM TOWER KEMAYORAN

JAKARTA

BUILDING

FIRE PUMP

2007

111

WATERPLACE RESIDENCE

SURABAYA

BUILDING

FIRE PUMP

2007

112

SEASON CITY

JAKARTA

BUILDING

FIRE PUMP

2007

113

HOTEL MALEOSAN

MANADO

BUILDING

FIRE PUMP

2007

114

APARTMENT BSB

BALIKPAPAN

BUILDING

FIRE PUMP

2007

115

HOLCIM INDONESIA

JAKARTA

BUILDING

WATER SPRAY

2008

116

GRAHA 165

JAKARTA

BUILDING

CHILLER PUMP

2008

117

ARKADIA OFFICE

JAKARTA

BUILDING

FIRE PUMP

2008

118

SAINATH OFFICE

JAKARTA

BUILDING

FIRE PUMP

2008

119

GRAND CITY SURABAYA

SURABAYA

BUILDING

CHILLER PUMP

2008

120

KEM TOWER KEMAYORAN

JAKARTA

BUILDING

PLUMBING PUMP,
CHILLER PUMP,
SUBMERSIBLE PUMP

2008
2008

121

THE ADHIWANGSA RESIDENCE

SURABAYA

RESIDENTIAL

FIRE PUMP

122

DAPENRA

JAKARTA

BUILDING

FIRE PUMP

2008

123

LUCKY SQUARE MALL

BANDUNG

BUILDING

FIRE PUMP

2008

124

BEST WESTERN BALI HOTEL

BALI

BUILDING

FIRE PUMP

2008

125

ASTON VERANDA HOTEL

JAKARTA

BUILDING

FIRE PUMP

2008

126

SEMEN PADANG

PADANG

CEMENT INDUSTRY

HVAC PUMP

2008

127

HOLCIM INDONESIA

CILACAP

CEMENT INDUSTRY

WATER SPRAY

2008

128

CYBER-2

JAKARTA

OFFICE

FIRE PUMP

2008

129

HOTEL HILTON

BANDUNG

HOTEL

FIRE PUMP

2008

130

SUDIRMAN TOWER

JAKARTA

BUILDING

FIRE PUMP

2008

131

FREEPORT

IRIAN JAYA

MINING

CIRCULATION PUMP

2008

132

GRAHA PENA

SURABAYA

BUILDING

FIRE PUMP

2008

133

BPK PENABUR - KELAPA GADING

JAKARTA

BUILDING

FIRE PUMP

2008

134

FLOUR MILLS - CILEGON

CILEGON

FACTORY

FIRE PUMP

2008

135

MEDCO ENERGI

SUMATERA

OIL & GAS

FIRE PUMP

2008

136

PARAGON CITY

SEMARANG

BUILDING

FIRE PUMP

2008

137

MENARA MTH

JAKARTA

BUILDING

FIRE PUMP

2008

138

QATAR EMBASSY

JAKARTA

BUILDING

FIRE PUMP

2008

139

CYBER-2

JAKARTA

OFFICE

HVAC PUMP, PLUMBING PUMP

2008

140

MEDCO II

SUMATERA

OIL & GAS

FIRE PUMP

2008

141

CYBER ANNEX

JAKARTA

BUILDING

FIRE PUMP, HVAC PUMP,


PLUMBING PUMP

2008

142

RENOVASI GEDUNG MAHKAMAH


AGUNG, RI

JAKARTA

BUILDING

FIRE PUMP

2008

143

W HOTEL SEMINYAK

BALI

HOTEL

FIRE PUMP

2008

144

EQUITY TOWER

JAKARTA

BUILDING

FIRE PUMP

2008

145

DEPO PERTAMINA

BOJONEGORO

OIL & GAS

FIRE PUMP

2008

146

SEASON CITY

JAKARTA

BUILDING

HVAC PUMP

2008

147

DUFAN ANCOL

JAKARTA

BUILDING

FIRE PUMP

2008

148

TRANS KALLA

MAKASSAR

BUILDING

FIRE PUMP

2009

149

PUPUK KUJANG

CIKAMPEK

FACTORY

HYDROMATIC PUMP

2009

150

INDOSAT

SUKABUMI

BUILDING

FIRE PUMP

2009

151

IT BATAM

BATAM

BUILDING

FIRE PUMP

2009

152

SAMPOERNA STRATEGIC SQUARE

JAKARTA

BUILDING

HOT WATER PUMP

2009

153

KANTOR
SULUT

JAKARTA

BUILDING

FIRE PUMP

2009

154

LOMBOK AIRPORT

LOMBOK

BUILDING

FIRE PUMP

2009

155

LAN SAMARINDA

SAMARINDA

BUILDING

FIRE PUMP

2009

156

CENTRAL PARK

JAKARTA

BUILDING

HVAC PUMP

2009

157

OFFICE KRAMAT RAYA

JAKARTA

BUILDING

FIRE PUMP

2009

158

BINUS BOARDING HOUSE

JAKARTA

BUILDING

FIRE PUMP

2009

159

BANDARA KUALANAMU

MEDAN

BUILDING

FIRE PUMP, CHILLER


PLUMBING PUMP

160

PPPK PETRA

SURABAYA

BUILDING

FIRE PUMP

2009

161

PUSDIKLAT MAHKAMAH AGUNG

JAKARTA

BUILDING

FIRE PUMP

2009

162

WILMAR NABATI INDONESIA

GRESIK

INDUSTRY

FIRE PUMP

2009

163

PUSDIKLAT MAHKAMAH AGUNG

BOGOR

BUILDING

FIRE PUMP

2009

164

PERTAMINA ACEH EP RANTAU

ACEH

OIL & GAS

FIRE PUMP

2009

165

DINAS PEMADAM
LEBAK BULUS

JAKARTA

BUILDING

FIRE PUMP

2009

166

TEMPO SCAN TOWER

JAKARTA

BUILDING

FIRE PUMP, CHILLER


PLUMBING PUMP

167

CIK DITIRO APARTMENT

JAKARTA

BUILDING

FIRE PUMP

2010

168

CENTRAL PARK CGPP II

JAKARTA

BUILDING

CHILLER PUMP

2010

169

CENTRAL PARK BALL ROOM

JAKARTA

BUILDING

CHILLER PUMP

2010

170

SEASON CITY SCHOOL

JAKARTA

BUILDING

FIRE PUMP

2010

171

PERTAMINA UPMS IV DEPOT


SEMARANG
REWULU

OIL & GAS

FIRE PUMP

2010

172

PERTAMINA UPMS VII

MAKASAR

OIL & GAS

FIRE PUMP

2010

173

KEMANG VILLAGE SCHOOL

JAKARTA

BUILDING

FIRE PUMP

2010

174

KEMANG VILLAGE

JAKARTA

BUILDING

FIRE PUMP

2010

175

RUSUNAMI GADING ICON

JAKARTA

RESIDENTIAL

FIRE PUMP

2010

176

MENARA ALLIANZ

JAKARTA

BUILDING

FIRE PUMP

2010

177

PERTAMINA UPMS VII DEPOT


MAKASAR
MAKASAR

OIL & GAS

VERTICAL
PUMP

178

PERTAMINA UPMS III


BERUNG

BANDUNG

OIL & GAS

FIRE PUMP

2010

179

DPPU AVIASI KUALANAMU MEDAN

MEDAN

OIL & GAS

FIRE PUMP

2010

180

MEDCO ENERGY M-12 TARAKAN

KALIMANTAN

OIL & GAS

FIRE PUMP

2010

PERWAKILAN

PEMDA

KEBAKARAN-

UJUNG

TURBINE

PUMP,

PUMP,

FIRE

2009

2010

2010

KEMANG VILLAGE KVR & RITZ


JAKARTA
TOWER

BUILDING

FIRE PUMP

2010

182

CIPUTRA WORLD

SURABAYA

BUILDING

FIRE PUMP

2010

183

PERTAMINA
BALONGAN

BALONGAN

OIL & GAS

FIRE PUMP

2010

184

PERTAMINA UBEP TARAKAN

TARAKAN

OIL & GAS

FIRE PUMP

2010

185

DPPU SOEKARNO HATTA

CENGKARENG

OIL & GAS

VEHRTICAL SUMP PUMP

2010

186

HOTEL SENTRA KELAPA GADING

JAKARTA

BUILDING

PLUMBING

2010

187

ANCOL MENTION

JAKARTA

BUILDING

FIRE PUMP

2010

188

GEDUNG LEMIGAS CIPULIR

JAKARTA

BUILDING

FIRE PUMP

2010

189

MEDCO EOR RIMAU

PALEMBANG

OIL AND GAS

FIRE PUMP

2010

190

PERTAMINA EP PENDOPO

PRABUMULIH

OIL AND GAS

FIRE PUMP

2010

191

SUNTER OFFICE

JAKARTA

BUILDING

FIRE PUMP

2010

192

KAWASAN
NARAGONG

NARAGONG

BUILDING

FIRE PUMP

2010

193

KRAFT FOOD INDONESIA

CIKARANG

BUILDING

FIRE PUMP

2010

194

HANG LEKIR RESIDANCE

JAKARTA

BUILDING

FIRE PUMP

2010

195

CIPUTRA WORLD

SURABAYA

BUILDING

FIRE PUMP

2010

196

CENTRAL PARK

JAKARTA

HOTEL

FIRE PUMP

2011

197

RS. ADVENT BANDUNG

BANDUNG

BUILDING

FIRE PUMP

2011

198

MENARA CITICON

JAKARTA

BUILDING

FIRE PUMP

2011

199

BINUS SERPONG 3

JAKARTA

BUILDING

FIRE PUMP

181

UPMS

III

LPG

PERGUDANGAN

2011

200

NUSANTARA TURBINE PROPULSI

BANDUNG

INDUSTRY

VERTICAL
PUMP

201

GEDUNG BERSAMA GRAMEDIA

JAKARTA

BUILDING

FIRE PUMP

2011

202

TANGERANG CITY MALL

TANGERANG

BUILDING

CHILLER PUMP

2011

203

BOILER

YOGYAKARTA

INDUSTRY

BOILER PUMP

2011

204

GALERI MODECOR

JAKARTA

BUILDING

FIRE PUMP

2011

205

MALL OF KEDIRI

KEDIRI

BUILDING

FIRE PUMP

2011

206

PERTAMINA
BADAS

SURABAYA

OIL & GAS

VERTICAL
PUMP

207

PERTAMINA EP RANTAU

ACEH

OIL & GAS

FIRE PUMP

2011

208

MALL SERANG BANTEN

BANTEN

BUILDING

FIRE PUMP

2011

209

WHITZ HOTEL

SEMARANG

HOTEL

FIRE PUMP

2011

210

ST.MORITZ

JAKARTA

BUILDINGPRESIDENTIAL

FIRE PUMP

2011

211

ST.MORITZ

JAKARTA

BUILDINGAMBASSADOR

FIRE PUMP

2011

212

SWISS BELL HOTEL

BALI

HOTEL

FIRE PUMP

2011

UPMS

DEPOT

TURBINE

TURBINE

FIRE

FIRE

2011

2011

213

REGENT HOTEL

BALI

214

KAMPUNG ITSB

CIKARANG

215

BANK RIAU

216

HVAC

2011

BUILDING

FIRE PUMP

2011

RIAU

BUILDING

FIRE PUMP

2011

THE STONE BALI

BALI

BUILDING

FIRE PUMP

2011

217

WISMA PONDOK INDAH III

JAKARTA

BUILDING

FIRE PUMP, PLUMBING PUMP,


CHILLER PUMP, SUBMERSIBLE
PUMP

2011

218

HOTEL NOVOTEL GAJAH MADA

JAKARTA

HOTEL

FIRE PUMP, CHILLER PUMP

2011

219

APARTMENT
MADA

JAKARTA

RESIDENTIAL

FIRE PUMP

2011

220

APARTMENT RUSUNAMI SUNTER


JAKARTA
PARK VIEW

RESIDENTIAL

FIRE PUMP

2011

RESIDENTIAL

FIRE PUMP

2011

RESIDENTIAL

FIRE PUMP

2011

221
222

NOVOTEL

GAJAH

APARTMENT RUSUNAMI PURI PARK


JAKARTA
VIEW TOWER A,B & C
APARTMENT RUSUNAMI PURI PARK
JAKARTA
VIEW TOWER E

HOTEL

223

GAJAH MADA PLAZA

JAKARTA

BUILDING

CHILLER PUMP

2011

224

GUDANG DHL

JAKARTA

BUILDING

FIRE PUMP

2011

225

IRMC SHOWROOM & OFFICE

JAKARTA

BUILDING

FIRE PUMP

2011
2011

226

GREEN BAY PLUIT TAHAP I

JAKARTA

BUILDING

PLUMBINGPUMP, SUBMERSIBLE
PUMP

227

HOTEL TRANS & IBIS

BANDUNG

BUILDING

FIRE PUMP, CHILLER PUMP

2011

228

PERTAMINA EP KTI PAPUA

SORONG

OIL & GAS

FIRE PUMP

2011

229

PERTAMINA JAYAPURA DEPOT


PAPUA
SORONG

OIL & GAS

FIRE PUMP

2011

230

ASAM ASAM COAL MINING

KALIMANTAN

MINING

FIRE PUMP

2011

231

LOGO OFFICE

JAKARTA

BUILDING

FIRE PUMP

2011

232

HOLIDAY INN SUNTER

JAKARTA

HOTEL

FIRE PUMP, PLUMBING PUMP,


CHILLER PUP

2011

233

HOLIDAY INN SUNTER

JAKARTA

RUKAN

FIRE PUMP, PLUMBING PUMP

2011

234

GUDANG GARAM TOWER

JAKARTA

BUILDING

FIRE PUMP

2011

235

MEDAN CENTER POINT

MEDAN

BUILDING

FIRE PUMP

2011

236

PERTAMINA UPMS
TANJUNG PERAK

SURABAYA

OIL & GAS

FIRE PUMP

2011

237

SUJ INDOCHEM CILEGON

CILEGON

FACTORY

FIRE PUMP

2011

238

ARMADA JOHNSON CONTROL

CIKAMPEK

FACTORY

FIRE PUMP

2011

239

PERTAMINA
DEPOT

MAKASAR

OIL & GAS

JOCKEY PUMP

2011

240

PLTA BRANTAS

SURABAYA

POWER PLANT

FIRE PUMP

2011

241

PERTAMINA EP PENDOPO

PRABUMULIH

OIL & GAS

FIRE PUMP

242

PERTAMINA
SEMAMPIR

OIL & GAS

VERTICAL
PUMP

MAKASAR

UPMS

LPG

MULTI

DEPOT

SURABAYA

2011
TURBINE

FIRE

2011

243

PERTAMINA LPG TANJUNG PRIOK

JAKARTA

OIL & GAS

FIRE PUMP

2011

244

PERTAMINA
KUPANG

SURABAYA

OIL & GAS

FIRE PUMP

2011

245

PERTAMINA UBEB TANJUNG

KAL-SEL

OIL & GAS

FIRE PUMP

2011

246

PABRIK ROKOK GUDANG GARAM

SEMARANG

FACTORY

FIRE PUMP

2011

247

GEDUNG AUDITORIUM PT. AHM

CIKARANG

FACTORY

FIRE PUMP

2011

248

U RESIDENCE

JAKARTA

BUILDING

FIRE PUMP

2011

249

CIKINI GOLD CENTER

JAKARTA

BUILDING

FIRE PUMP

2011

250

WEST MARK APARTMENT

JAKARTA

RESIDENTIAL

FIRE PUMP

2011

251

GREEN BAY PLUIT TAHAP-1A

JAKARTA

BUILDING

FIRE PUMP

2011

252

GEDUNG EXIM MELATI

JAKARTA

BUILDING

CHILLER PUMP

2011

253

APM ARMADA AUTO PARTS

CIKARANG

FACTORY

FIRE PUMP

2011

254

PERTAMINA
FIELD CEPU

CEPU

OIL & GAS

FIRE PUMP

255

SRC FACTORY KARAWANG

KARAWANG

FACTORY

FIRE PUMP

2012

256

PT. TEMPO JL. KEMUNING

JAKARTA

FACTORY

FLOOD PUMP

2012

257

PERTAMINA
MAUMERE

SURABAYA

VERTICAL TURBINE- FIRE PUMP

2012

258

OTTO PHARMACEUTIAL

BANDUNG

FACTORY

FIRE PUMP

2012

259

PERTAMINA JAYAPURA DEPOT


JAYAPURA
DOBO, TUAL & MERAUKE

OIL & GAS

FIRE PUMP

2012

260

MEDCO M12 TARAKAN

SUMATERA

OIL & GAS

FIRE PUMP

2012

261

PERTAMINA PERTAGAS SUMATERA SUMATERA

OIL & GAS

FIRE PUMP

2012

262

PERTAMINA PRABUMULIH

OIL & GAS

FIRE PUMP

2012

263

PERTAMINA UPMS III JBB DEPOT


TASIKMALAYA
TASIKMALAYA

OIL & GAS

FIRE PUMP

2012

264

PERTAMINA MAKASSAR DEPOT


MAKASSAR
GORONTALO

OIL & GAS

FIRE PUMP

2012

265

PERTAMINA BITUNG

MAKASSAR

OIL & GAS

JOCKEY PUMP

2012

266

PERTAMINA UPMS
PADALARANG

JAWA BARAT

OIL & GAS

FIRE PUMP

2012

267

CNG SEI GELAM

JAMBI

OIL & GAS

FIRE PUMP

2012

268

PERTAMINA BIAK, JAYAPURA

JAYAPURA

OIL & GAS

FIRE PUMP

2012

269

PERTAMINA SEMARANG CILACAP

JAWA TENGAH

OIL & GAS

FIRE PUMP

2012

270

PERTAMINA REWULU

JOGJA

OIL & GAS

JOCKEY PUMP

2012

271

SUGAR
REFINERY
JAKARTA

JAKARTA

FACTORY

FIRE PUMP

2012

272

SUJ CILEGON

CILEGON

FACTORY

FIRE PUMP

2012

273

INDOFOOD CIKUPA - TANGERANG

TANGERANG

FACTORY

FIRE PUMP

2012

UPMS

EP

DPPU

REGION

JAWA

SURABAYA-DEPOT

III

SUMATERA

DEPOT

MARUNDA

OIL & GAS

2012

274

PERTAMINA BALIKPAPAN

KALIMANTAN

OIL & GAS

JOCKEY PUMP

2012

275

REGENT HOTEL

BALI

BUILDING

CHILLER PUMP

2012

276

BANK MEGA CARD CENTER

JAKARTA

BUILDING

FIRE PUMP

2012

277

PUSAT TIKI-JNE

JAKARTA

BUILDING

FIRE PUMP

2012

278

KEMANG VILLAGE INFINITY-TOWER JAKARTA

BUILDING

FIRE PUMP

2012

279

KEMANG
TOWER

JAKARTA

BUILDING

FIRE PUMP

2012

280

DHARMAWANGSA 101 HOTEL

JAKARTA

BUILDING

FIRE PUMP

2012
2012

VILLAGE

INTERCON

281

MENARA PRIMA II

JAKARTA

BUILDING

CHILLER PUMP, SUBMERSIBLE


PUMP

282

RS. AKADEMIKA UGM

JOGYAKARTA

BUILDING

FIRE PUMP

2012

283

HOTEL AMARIS NUSA 2

BALI

BUILDING

FIRE PUMP

2012

284

TRANS STUDIO

BANDUNG

BUILDING

CIRCULATION PUMP

2012

285

THE WINDSOR APARTMENT

JAKARTA

BUILDING

FIRE PUMP

2012

286

STREET GALERY PONDOK INDAH

JAKARTA

BUILDING

FIRE
PUMP

287

GREEN BAY TAHAP II - MALL

JAKARTA

BUILDING

FIRE PUMP

2012

288

PULOMAS PARK CENTER

JAKARTA

BUILDING

FIRE PUMP

2012

289

AKADEMI PERKERETAAPIAN

MADIUN

BUILDING

FIRE PUMP

2012

290

BANDARA SULTAN THAHA

JAMBI

BUILDING

FIRE PUMP

2012

291

BANDARA DEPATI AMIR

BANGKA BELITUNG

BUILDING

FIRE PUMP, PLUMBING PUMP

2012

292

PASAR SINPASA

BEKASI

BUILDING

FIRE PUMP

2012

293

HOLIDAY INN EXPRESS

BALI

BUILDING

FIRE PUMP

2012

294

GREEN LAKE SUNTER-TAHAP I

JAKARTA

BUILDING

FIRE PUMP

2012

295

DSO DJARUM TANDES SURABAYA

SURABAYA

FACTORY

FIRE PUMP

2013

296

BALI DESA NUSA DUA

BALI

BUILDING

FIRE PUMP

2013

297

BANDARA DJUANDA

SURABAYA

BUILDING

FIRE PUMP

2013

298

SIMPRUG BOTANICA

JAKARTA

BUILDING

FIRE PUMP

2013

299

MENARA PRIMA 2

JAKARTA

BUILDING

PLUMBING PUMP

2013

300

CONDOTEL AWANA

BALI

BUILDING

FIRE PUMP

2013

301

SHANGRILA HOTEL

BALI

BUILDING

FIRE PUMP

2013

302

PERTAMINA BALIKPAPAN DEPOT


BALIKPAPAN
SAMARINDA

OIL & GAS

JOCKEY PUMP

2013

OIL & GAS

FIRE PUMP

2013

OIL & GAS

FIRE PUMP

2013

303
304

PERTAMINA BALIKPAPAN DEPOT


PANGKALAN BUN, DEPOT PULAU BALIKPAPAN
PISAU, DPPU JUWATA
PERTAMINA BALIKPAPAN DEPOT
BALIKPAPAN
SINTANG

PUMP,

SUBMERSIBLE

2012

305

PERTAMINA BALIKPAPAN DEPOT


BALIKPAPAN
TARAKAN

OIL & GAS

VERTICAL
PUMP

TURBINE

FIRE

306

PERTAMINA BALIKPAPAN DEPOT


BALIKPAPAN
BANJARMASIN

OIL & GAS

VERTICAL
PUMP

TURBINE

FIRE

307

HOTEL SANTIKA CIKARANG

CIKARANG

BUILDING

FIRE PUMP

2013

308

BALI NUSA
CENTER

BALI

BUILDING

FIRE PUMP

2013

309

GEDUNG BINA MULYA 1

JAKARTA

BUILDING

CHILLER PUMP

2013

310

TOWER PLN BEKASI

BEKASI

PLN

CIRCULATION PUMP

2013

311

PERTAMINA TBBM SERUI

PAPUA

OIL & GAS

FIRE PUMP

2013

312

FLOUR MILL CILEGON

CILEGON

INDUSTRI

FIRE PUMP

2013

313

PERTAGAS JAMBI TEMPINO

JAMBI

OIL & GAS

FIRE PUMP

2013

314

PERTAMINA SANGATTA

KALIMANTAN
TIMUR

OIL & GAS

FIRE PUMP

2013

315

THE MANSION @ DUKUH GOLF


JAKARTA
KEMAYORAN

BUILDING

FIRE PUMP

2013

316

PERTAMINA TJILIK RIWUT

KALIMANTAN
TENGAH

OIL & GAS

FIRE PUMP

2013

317

PERTAMINA LPG DUMAI

RIAU

OIL & GAS

FIRE PUMP

2013

318

PERTAMINA REGION IV SEMARANG


JAWA TENGAH
TBBM LOMANIS CILACAP

OIL & GAS

FIRE PUMP

2013

319

PERTAMINA EP FIELD TAMBUN

OIL & GAS

FIRE PUMP

2013

320

PERTAMINA
REGION
IV
SEMARANG-TBBM
LOMANIS JAWA TENGAH
CILACAP

OIL & GAS

JOCKEY PUMP

2013

321

PERTAMINA TBBM KAIMANA

PAPUA

OIL & GAS

FIRE PUMP

2013

322

PERTAMINA LABUHA

PAPUA

OIL & GAS

FIRE PUMP

2013

323

PERTAMINA UPMS VII SULAWESI


TBBM MOUTONG& TBBM BANGGAI,
TBBM LUWUK & TBBM POSO, TBBM SULAWESI
RAHA,
TBBM
POSO,
TBBM
MOUTONG & TBBM BANGGAI

OIL & GAS

FIRE PUMP

2013

324

PGN LAMPUNG

LAMPUNG

OIL & GAS

FIRE PUMP

2013

325

DSO DJARUM TANDES

JAWA TIMUR

INDUSTRI

FIRE PUMP

2013

326

PANTAI
HOTEL

JAKARTA

BUILDING

FIRE PUMP

2013

327

SAHID SUDIRMAN CENTER

JAKARTA

BUILDING

FIRE PUMP

2013

328

HARRIS HOTEL & YELLO HOTEL


JAKARTA
HAYAM WURUK

BUILDING

FIRE PUMP

2013

329

HOTEL HOLIDAY INN EXPRESS JAKARTA


CIKINI

BUILDING

FIRE PUMP

2013

330

MENTENG PARK

JAKARTA

BUILDING

FIRE PUMP

2013

331

HOTEL AMARIS PASAR MINGGU

JAKARTA

BUILDING

FIRE PUMP

2013

DUA

INDAH

CONVENTION

KAPUK

MAL

JAWA BARAT

&

10

2013
2013

332

HOTEL 101 LEGIAN

BALI

BUILDING

FIRE PUMP

2013

333

HOTEL 101 JOGYAKARTA

JOGYAKARTA

BUILDING

FIRE PUMP

2013

334

UPH KARAWACI

TANGERANG

BUILDING

FIRE PUMP

2013

335

BINTARO PARK VIEW

JAKARTA

BUILDING

FIRE PUMP

2013

336

HOTEL ALILA SCBD

JAKARTA

BUILDING

VERTICAL TURBINE
PUMP,
PLUMBING
SUBMERSIBLE PUMP

337

SOHO PODOMORO CITY

JAKARTA

BUILDING

FIRE PUMP

2014

338

WOLRD VISION INDONESIA

JAKARTA

BUILDING

FIRE PUMP

2014

339

LOBP BATAKAN BALIKPAPAN

KALIMANTAN
TIMUR

OIL & GAS

FIRE PUMP

2014

340

PERTAMINA TBBM NABIRE

PAPUA

OIL & GAS

FIRE PUMP

2014

341

PERTAMINA TBBM MASOHI

MALUKU TENGAH

OIL & GAS

VERTICAL TURBINE

2014

342

PABRIK PENGOLAHAN DAGING DI


JAWA BARAT
PURWAKARTA

INDUSTRI

FIRE PUMP

2014

343

HOTEL BEST WESTERN SOLO

SOLO

BUILDING

FIRE PUMP

2014

344

ELPIS RESIDENCE

JAKARTA

BUILDING

FIRE PUMP

2014

345

BANDARA SUPADIO

PONTIANAK

BUILDING

FIRE PUMP

2014

346

HOTEL 101 BOGOR

BOGOR

BUILDING

FIRE PUMP

2014

347

PURI INDAH FINANCIAL TOWER

JAKARTA

BUILDING

FIRE PUMP

2014

348

ONE BELPARK MALL

JAKARTA

BUILDING

FIRE PUMP

2014

349

BATULICIN

KALIMANTAN
SELATAN

OIL & GAS

VERTICAL TURBINE

2014

350

SENORO

SULAWESI TENGAH OIL & GAS

FIRE PUMP

2014

351

CENTRAL KITCHEN THE DUCK KING TANGERANG

INDUSTRI

FIRE PUMP

2014

352

GEDUNG GIS

JAKARTA

BUILDING

FIRE PUMP

2014

353

THE
MANSION
BOUGENVILLE

JAKARTA

BUILDING

FIRE PUMP

2014

354

MENARA SENTRAYA

JAKARTA

BUILDING

FIRE PUMP

2014

355

HOTEL BEDROCK

BALI

BUILDING

FIRE PUMP

2014

TOWER

11

FIRE
PUMP,

2013

356

GOR PKP CIRACAS

JAWA BARAT

BUILDING

FIRE PUMP

2014

357

GARDEN
WING
KARAWANG

JAWA BARAT

BUILDING

FIRE PUMP

2014

358

HOTEL
ASTON
CENTER, SENTUL

JAWA BARAT

BUILDING

FIRE PUMP

2014

359

PABRIK
PRINTING
SIDOARJO

JAWA TIMUR

INDUSTRI

FIRE PUMP

2014

360

PERTAMINA TBBM KOTA BARU &


KALIMANTAN
DEPOT LPG BALIKPAPAN

OIL & GAS

VERTICAL
PUMP

361

PABRIK DUA BERLIAN

JAKARTA

INDUSTRI

FIRE PUMP

2014

362

PERTAMINA
PLUMPANG

JAKARTA

OIL & GAS

FIRE PUMP

2014

363

PERTAMINA
FIELD

RIAU

OIL & GAS

FIRE PUMP

2014

364

PERTAMINA TBBM SANANA

MALUKU

OIL & GAS

VERTICAL TURBINE

2014

365

MAXX BOX

KARAWACI

BUILDING

FIRE PUMP

2014

366

HOTEL HARRIS BENOA

BALI

BUILDING

FIRE PUMP

2014

367

HOTEL TIJILI SEMINYAK

BALI

BUILDING

FIRE PUMP

2014

368

MALL & HOTEL PIK

JAKARTA

BUILDING

PLUMBING PUMP

2014

369

CONVENTION HALL

SAMARINDA

BUILDING

FIRE PUMP

2014

370

KAMPUS ITB TAHAP II

BANDUNG

BUILDING

FIRE PUMP

2014

371

PERTAMINA
BITUNG

SULAWESI

OIL & GAS

VERTICAL TURBINE

2014

372

PERTAMINA DPPU SAM RATULANGI


SULAWESI
MANADO

OIL & GAS

FIRE PUMP

2014

373

PERTAMINA FIELD TARAKAN

SULAWESI

OIL & GAS

FIRE PUMP

2014

374

PERTAMINA
KOLONEDALE

SULAWESI

OIL & GAS

JOCKEY PUMP

2014

375

PERTAMINA BALONGAN

BALONGAN

OIL & GAS

VERTICAL TURBINE

2014

376

PABRIK ETERNA GELORAPUTRA

CIKUPA

INDUSTRI

FIRE PUMP

2014

377

ANCOL DOUBLE DECKER

JAKARTA

BUILDING

FIRE PUMP

2014

378

CENTENIAL TOWER

JAKARTA

BUILDING

FIRE PUMP

2014

379

HOTEL ALILA SCBD

JAKARTA

BUILDING

VERTICAL
PUMP

APARTMENT
&

TRAINING
FLEXO

ELNUSA
EP

ASSET

AREA

DI

DEPO
1

LIRIK

SULAWESI

SULAWESI

12

TURBINE

FIRE

TURBINE-JOCKEY

2014

2014

380

OAK TOWER

JAKARTA

BUILDING

FIRE PUMP

2014

381

ST. REGIS - HOTEL

JAKARTA

BUILDING

FIRE PUMP

2014

382

ST. REGIS - OFFICE

JAKARTA

BUILDING

FIRE PUMP

2014

383

HOTEL GUNUNG GEULIS

BOGOR

BUILDING

FIRE PUMP

2014

384

NPK GRANULAR
KUJANG

CIKAMPEK

INDUSTRI

FIRE PUMP

2015

385

PGN

JAWA BARAT

OIL & GAS

FIRE PUMP

2015

386

PERTAMINA DEPOT SINTANG

KALIMANTAN
BARAT

OIL & GAS

FIRE PUMP

2015

387

PABRIK KERTAS

CIKARANG BARAT

INDUSTRI

FIRE PUMP

2015

388

PERTAMINA SANGA SANGA

KALIMANTAN

OIL & GAS

FIRE PUMP

2015

389

PABRIK ETERNIT GRESIK

JAWA TIMUR

INDUSTRI

FIRE PUMP

2015

390

PABRIK VALEO

PURWAKARTA

INDUSTRI

VERTICAL TURBINE & JOCKEY


PUMP

2015

391

HOTEL ARCS JAMBULUWUK

BALI

BUILDING

FIRE PUMP

2015

392

MEDAN
CENTER
POINT

MEDAN
APARTMENT CENTRUM & CENTRIA

BUILDING

FIRE PUMP

2015

393

MENARA PALMA II

JAKARTA

BUILDING

FIRE PUMP

2015

394

ST. MORITZ II - OFFICE TOWER

JAKARTA

BUILDING

FIRE PUMP

2015

395

PLAZA SADIRA

PEKANBARU

BUILDING

FIRE PUMP

2015

396

PERTAMINA FIELD TANJUNG

KALIMANTAN
SELATAN

OIL AND GAS

FIRE PUMP

2015

II

PT.

PUPUK

13

Complete Solutions

for Fire Protection Fluid Handling

Typical housed diesel driven fire pump with test meter.

Controllers mounted and wired on diesel pump base.

Aurora Pump is a global manufacturer of pumps and systems for the commercial, municipal,
industrial and fire protection markets. We provide the solutions to meet your pumping needs.

FIRE PUMPS

911 Series

911.5 Series

Single Stage Inline Fire Pump

End Suction Fire Pump

Model 383

Model 384

Flows: 50 to 1,500 GPM (11.3 to 340 m /hr)


Pressures: 40 to 205 PSI (2.7 to 14.1 bar)

Flows: 400 to 750 GPM (90.8 to 170.3 m3/hr)


Pressures: 47 to 105 PSI (3.2 to 7.2 bar)

UL Listed/FM Approved/NFPA-20 Design

UL Listed, FM Approved Performance

For Commercial, Industrial and Marine Use

Electric and Diesel Speeds

Space Saving Vertical Design

Back Pullout Design for Easy Pump Service


without Disconnecting Pipe

Easy Maintenance without Disturbing


Surrounding Piping
Bronze-Fitted Pump Construction

Frame-Mounted Design
Small Footprint Ideal for Retrofit
Designed for Installations such as Schools,
Office Buildings, and Hospitals

912 Series
Horizontal Split Case Electric Drive Fire Pumps
Models 481, 485, 491,
492, 495

Vertical Split Case Electric Drive


Fire Pump
Model 483

Flows: 250 to 5000 GPM (56.8 to 1135 m3/hr)


Pressures: 40 to 490 PSI (2.8 to 33.8 bar)

Flows: 250 to 5000 GPM (56.8 to 1135 m3/hr)


Pressures: 40 to 490 PSI (2.8 to 33.8 bar)

UL Listed/FM Approved/NFPA-20 Design

UL Listed/FM Approved/NFPA-20 Design

For Commercial, Industrial and Marine Use

For Commercial, Industrial and Marine Use

Diesel and Electric Driven Available

Electric Driven Available

Lower Initial Cost

Lower Initial Cost

Quicker Delivery with Red Hot Quick Ship Program

Ease of Maintenance

Ease of Maintenance

NOTE: Front case wearing rings are standard on all size


pumps. Rear case rings are standard on all sizes except
the 2x2x9C. The 2x2x9C does not require a wear ring.

FIRE PUMP SYSTEMS

918 Series

FIRE PUMPS

913 Series

Packaged Fire Pump Systems


UL Listed/FM Approved Aurora Fire Pump

Suction and Discharge Pressure Gauges

UL Listed/FM Approved Fire Pump Controller

Automatic Casing Air Release Valve

ETL Listed Packaged Fire Pump System

Casing Pressure Relief Valve


(Electric Packages)

Aurora Jockey Pump


UL Listed Jockey Pump Controller

Horizontal Split Case Diesel Drive Fire Pumps


Models 481, 485, 491,
492, 495

Pressure Sensing Lines Complete


per NFPA 20

Hose Header with Valves, Caps & Chains


Suction and Discharge Piping per NFPA 20
Removable Lifting Lugs

Listed OS & Y Gate & Butterfly Valves with


Tamper Switches

Flows: 250 to 5000 GPM (56.8 to 1135 m3/hr)


Pressures: 40 to 490 PSI (2.8 to 33.8 bar)
UL Listed/FM Approved/NFPA-20 Design
For Commercial, Industrial and Marine Use
Diesel and Electric Driven Available
Lower Initial Cost
Quicker Delivery with Red Hot Quick Ship Program
Ease of Maintenance

914 Series
Fire Pump Vertical Turbine
Model 483
Flows: 250 to 4500 GPM (56.8 to 1022 m3/hr)
Pressures: 75 to 387 PSI (5.2 to 26.7 bar)

919 Series

UL Listed/FM Approved/NFPA-20 Design


For Commercial, Industrial and Marine Use
Special Materials for Seawater Applications
Diesel and Electric Driven

Compact Fire Pump Systems


Flows: 750 GPM (170.3 m3/hr)
Pressures: 160 PSI (11.0 bar)
UL Listed/FM Approved Aurora Fire Pump
UL Listed/FM Approved Fire Pump Controller
ETL Listed Packaged Fire Pump System

PVM Series

Aurora Jockey Pump


UL Listed Jockey Pump Controller
Pressure Sensing Lines Complete
per NFPA 20

Jockey Pumps
Models PVM,
PVMI, PVMX
Horsepower: 12 to 40
Flows: 50 GPM (11.3 M3/HR)
Capacities: 215 GPM (48.8 M3/HR)
Pressures: 330 PSI (22.7 bar)
Heads: 800 Feet (244 Meters)
Temperatures: 250F (121C)

Listed OS & Y Gate & Butterfly Valves


Suction and Discharge Piping
per NFPA 20
Ideal for Smaller Areas
Fits through a 36" Doorway
Multiple Starting Methods
Available for the Fire Pump with
Optional Automatic Transfer Switch
Optional City Bypass

Space-Saving Design Recommended where


Floor Space is Extremely Limited
Available in Cast Iron or 304 and 316
Stainless Steel Materials

Aurora Pump provides fire protection pumping for a


variety of solutions throughout the world.
With over ninety years of experience, Auroras commitment to excellence goes
beyond the product line by being dedicated to keeping our customers, distributors
and employees constantly educated and updated on the leading developments
in technology. Our computer software programs assist with selecting the best
pumps and systems along with providing pump drawings and specifications. These
programs save valuable time in the selection and evaluation of pumps and systems.
As an ISO 9001 registered company, Aurora Pump is committed to quality. In
addition, to meet your quick ship requirements, the Aurora Distribution Center is
stocked with parts and pumps to handle same day shipments. These components,
along with our outstanding customer service program, will keep your Aurora Pump
system at peak performance for years to come. You can rely on Aurora Pump and
our qualified distribution network to provide total fluid flow solutions.

FIRE PUMP HOUSES

ACCESSORIES

Designed to Meet Specific


Environmental Requirements
All-Steel Building with
Seismic Certification
Easy Access Entries
Electric Heaters with
Built-In Thermostat

Casing Relief Valve/Air Relief Valve


Eccentric Suction Reducers, Concentric
Discharge Increasers
Test Manifold, Hose Valves, Ball Drip Valve
Main Relief Valve, Waste Cone
Flow Metering Systems

Continuous Duty Exhaust Fan

Diesel Batteries, Racks and Cables

AC Motor/Solenoid Operated Louver

Double Wall Fuel Tanks/NFPA-20 & UL-142 Fittings

Interior Fluorescent and Flood Light,


Exterior 70 W HPS Light

Diesel Engine Mufflers

Sprinkler System per NFPA 13

City Bypass

Finished through Wall or


Floor Penetration

Backflow Preverter

Single Point Electrical Connection


State Certification Label

Exhaust Flex Connectors

Insulated Exhaust Piping


Roof Curb for Vertical Turbine Installation and Removal
Alarms and Tamper Switches Pre-Wired to a Common
Juction Box

IT

AU
L

ST
E

HY

UT

DR

IN

IC

NOTE: Aurora Pump reserves the right to make revisions to its products and their specifications, and to this bulletin and related information, without notice.

19 17

AF-02-1001 09/12 2012 Pentair Pump Group, Inc.

ISO 9001

www.aurorapump.com

ST
EGI

ER E D Q U
TY SYSTEM
ALI

3601 Fairbanks Avenue Kansas City, Kansas 66106 Phone: 888-416-9510

800 Airport Road North Aurora, Illinois 60542 Phone: 888-987-8680

qwertyuiopasdfghjklzxcvbnmqwertyui
opasdfghjklzxcvbnmqwertyuiopasdfgh
jklzxcvbnmqwertyuiopasdfghjklzxcvb
ELECTRIC FIRE PUMP
nmqwertyuiopasdfghjklzxcvbnmqwer
SparePartListBook
Aurora
Horizontal Split Case
ControllerModel:GPD
Model : 8-481-21/Single Stage
tyuiopasdfghjklzxcvbnmqwertyuiopas
dfghjklzxcvbnmqwertyuiopasdfghjklzx
cvbnmqwertyuiopasdfghjklzxcvbnmq
wertyuiopasdfghjklzxcvbnmqwertyuio
pasdfghjklzxcvbnmqwertyuiopasdfghj
klzxcvbnmqwertyuiopasdfghjklzxcvbn
mqwertyuiopasdfghjklzxcvbnmqwerty
uiopasdfghjklzxcvbnmqwertyuiopasdf
ghjklzxcvbnmqwertyuiopasdfghjklzxc
vbnmqwertyuiopasdfghjklzxcvbnmrty
uiopasdfghjklzxcvbnmqwertyuiopasdf
ghjklzxcvbnmqwertyuiopasdfghjklzxc

PERTAMINABALIKPAPANDEPOTPANGKALANBUN,
DEPOTPULANGPISAU,DPPUJUWATA
COAL
FIRED POWER STATION,BABELAN

Preparedby:PT.RodaNurmala

Customer
:
Project name : Default

Pump Performance Curve


Encompass 2.0 - 15.1.1.0

EFP.Cap.2000 Gpm @ 9 Bar Total Head


360
Power

Power - hp

270

180

90

0
15.0

Preferred operating region

13.5

12.0

10.5

38

53

63

21.00 in

69

Head - bar

9.0
72
73

7.5

69

63
16.94 in

6.0

4.5
53
3.0

1.5

0.0

500

1,000

1,500

2,000
Flow - USgpm

2,500

3,000

3,500

4,000

Item number

: 012

Size

: 8-481-21

Service

Stages

:1

Quantity

:1

Driver type

: Motor

Quote number

: 259241

Frequency

: 50 Hz

Date last saved

: 13 May 2015 1:59 AM

Speed, rated

: 1,480 rpm

Flow, rated

: 2,000.0 USgpm

Based on curve number

: 184-8X10X21-1480

Differential head /
pressure, rated

: 9.03 bar

Efficiency

: 65.96 %
:

Shutoff head

: 10.07 bar
:

Suction pressure, max

: 0.00 psi.g

Power, maximum

: 250 hp

Section 912 Page 231


Date March 22, 2013

AURORA MODEL 481 PUMPS


ON STANDARD STEEL BASE

OPTIONAL 250# SUCTION AND


DISCHARGE FLANGES

2-1/2

481

CASE
BORE
10B

481

481

10

3
4
5

481

11A
11C
11D

481

15

481

481

11B
11C
15

481

17

481

11

481

11HH

481

14HH

481

15B
15C

481

481

18B
18C
20

481

12

10

4A
5A

481

17B

10

481

21
21A

10 6B

481

24

12

10

481

15C

12

10

481

18

12

10

481

18D

12

12

481

18A

14

6B

7A
7

CP

HY

8
(203)
9*
(228)
10+
(254)
10+
(254)
11
(279)
11**
(279)
12-1/2
(217)
12-1/2
(217)
12-1/2
(217)
16-1/2
(419)
16-1/2
(419)
13-1/2
(343)
14-3/4
(374)
14-3/4
(374)
14-3/4
(374)
14-3/4
(374)
18-1/2
(470)
26
(660)
25
(635)
25
(635)
25
(635)
24
(609)

4
(102)
4-1/2
(114)
5
(127)
5
(127)
5-1/2
(140)
5-1/2
(140)
6-1/4
(159)
6-1/4
(159)
6-1/4
(159)
8-5/8
(219)
7-1/2
(191)
6-3/4
(171)
8
(203
8
(203)
8
(203)
8
(203)
9-1/2
(241)
15
(381)
13-1/2
(343)
13-1/2
(343)
12-1/4
(311)
15
(381

13-1/2
(343)
13-1/2
(343)
14-1/2
(368)
14-1/2
(368)
14-1/2
(368)
16
(406)
16
(406)
16
(406)
16
(406)
18-1/2
(460)
20-1/2
(519)
18
(457)

9-3/4
(247)
10
(254)
11-1/4
(286)
12
(305)
13
(330)
11-1/4
(286)
13-1/4
(336)
14
(355)
11-3/4
(298)
10
(254)
15
(381)
14-1/4
(368)
16
(406)
15-3/4
(400)
17
(431)
17
(431)
18
(457)
20
(508)
17
(431)
18
(457)
20
(508)
18
(457)

4
(102)
4-1/2
(114)
5
(127)
5
(124)
5-1/2
(140)
5-1/2
(140)
6-1/4
(159)
6-1/4
(159)
6-1/4
(159)
8-5/8
(219)
7-1/2
(191)
6-3/4
(171)
8
(203)
8
(203)
9
(228)
8
(203)
9-1/2
(241)
15
(381)
13-1/2
(343)
13-1/2
(343)
12-1/4
(311)
15
(381)

20
(609)
24
(609)
26
(660)
26
(660)
26
(660)
28-1/2
(723)
26-1/2
(673)
28-1/2
(723)
28-1/2
(723)
32-7/8
(835)
36-3/4
(933)
32
(812)
32
(812)
32
(812)
32
(812)
32
(812)
38
(964)
43-7/8
(1114)
38
(964)
38
(964)
43
(1092)
44
(1117)

5
(127)
5
(127)
6
(152)
6
(152)
6
(152)
6
(152)
6
(152)
6
(152)
6
(152)
8
(203)
8
(203)
7
(178)
7
(178)
7
(178)
7
(178)
7
(178)
11
(279)
11
(279)
11
(279)
11
(279)
11-1/2
(292)
11
(279)

18

(457)
18
(457)
18
(457)
18
(457)
21-7/8
(555)
25-1/4
(641)
21-7/8
(555)
21-7/8
(555)
24-1/4
(616)
25-1/4
(615)

NOTES
1. All dimensions are in inches.
2. Dimensions may vary 3/8".
3. Not for construction purposes unless certified.
4. Coupling gap may vary 1/8" thru 2-1/16".
5. Conduit box is shown in approximate location. Dimensions are
not specifed as they vary with each motor manufacturer.
6. Suction and discharge flanges are ANSI standard flat face.
* D is 10-1/2 when using frames 324TS - 365TS.
** D is 12 when using frames 404TS - 445TS.
*** Pump sizes 6-481-11HH & 6-481-14HH are furnished as standard
with 125# suction flange & 250# discharge flange.
+D is 10-1/2 when using frames 404TS - 405T and D is 11 when
using frames 444TS - 445TS.

BASE
5
7
9
10
11
12
13
14
15
16
17

2013 Pentair Ltd.

YY

ZZ

10
(254)
11
(279)
12-3/4
(324)
12-3/4
(324)
14
(355)
13-1/4
(336)
15
1-1/4
(381)
15
(381)
14-1/2
(368)
15
(381)
17
(431)
16-3/4
(425)
18
(457)
18
(457)
17-3/4
(450)
17-3/4
(450)
21
2
(533)
25
(635)
1-1/4
20
(508)
22
(558)
2
24
(610)
23
(584)

HA
12
(305)
13
(330)
15
(381)
18
(457)
18
(457)
18
(457)
18
(457)
18
(457)
22
(558)
22
(558)
22
(558)

HB
38
(964)
42
(1066)
44
(1117)
44
(1117)
48
(1219)
54
(1371)
60
(1524)
65
(1651)
60
(1524)
72
(1828)
84
(2133)

(1143)

MODEL

C
D

APPROX

BASE

9 10 11 10 11 11 11 11 12

BASE

9 10 11 10 11 11 11 11 12

BASE

9 11 11 11 11 11 11 11 11 11 12 12 12 15 15 15 15 15 15 15

BASE

9 11 11 11 11 11 11 11 11 11 12 12 12 15 15 15 15

BASE

9 11 11 11 11 11 11 11 11 11 12 12 12 15 15 15 15

BASE

9 10 11 11 11 11 12 12 12 12 12 12 12 12 15 15 15 15 15 16 15 16

BASE

9 10 11 11 11 11 12 12 12 12 12 12 12 12 15 15 15 15 15 16 15 16

BASE

9 10 11 11 11 11 12 12 12 12 12 12 12 12 15 15 15 15 15 16 15 16

BASE

9 10 11 11 11 11 12 12 12 12 12 12 12 12 15 15 15 15 15 16 15 16

BASE

13

BASE
BASE

15

15

16

16

16

15

16

16

16

16

11 12 12 12 12 12 12 12 12 12 12 13 13 15 15 15 16 16 16 16 16

BASE

10 11 12 12 12 12 12 12 12 12 12 12 13 13 15 15 15 16 16 16 16 16

BASE

10 11 12 12 12 12 12 12 12 12 12 12 13 13 15 15 15 16 16 16 16 16

BASE

10 11 12 12 12 12 12 12 12 12 12 12 13 13 15 15 15 16 16 16 16 16

BASE

10 11 12 12 12 12 12 12 12 12 12 12 13 13 15 15 15 16 16 16 16 16

BASE

14 14 16 16 16 16 16 16 16 17 17

BASE

17 17 17 17

BASE

14 14 14 14 16 16 16 16 16 16 16 17

BASE

14 14 16 16 16 16 16 16 16 17

BASE

16

BASE

16 16 16 16 17 17 17

HE
9
(228)
10
(254)
12
(305)
15
(381)
15
(381)
15
(381)
15
(381)
15
(381)
19
(482)
19
(482)
19
(482)

(1245)

18 21 23 22 24 24 25 25 26 26 28 29 29 28 30 30 33 32 35 34 38 36 40 40 44 45 49

PUMP SIZE
DISCH

MOTOR
FRAME

449T

OPTIONAL 125# SUCTION


FLANGE, 250# DISCHARGE
FLANGE

449TS

STANDARD 125# SUCTION AND


DISCHARGE FLANGES

Supersedes Section 912 Page 231


Dated July 2012

HG
3
(76)
4
(101)
3-3/8
(86)
4
(101)
4
(101)
4
(101)
4
(101)
4
(101)
4
(101)
4
(101)
4
(101)

HH
1/2
(13)
5/8
(15)
5/8
(15)
5/8
(15)
5/8
(15)
5/8
(15)
5/8
(15)
5/8
(15)
5/8
(15)
5/8
(15)
5/8
(15)

HF
17
(431)
17
(431)
19
(482)
42
(1066)
46
(1168)
52
(1320)
35
(888)
40
(1015)
58
(1473)
70
(1778)
82
(2082)

HP
20
(508)
24
(609)
24
(609)
1
(25)
1
(25)
1
(25)
24
(609)
24
(609)
1
(25)
1
(25)
1
(25)

16

17

Section 916 Page 201


Date February 2005

AURORA FIRE PUMPS


STANDARD FIRE PUMP ACCESSORIES

1/2" NPT OUTLET

Supersedes Section 916 Page 201


Dated May 2004

E
FLOAT-OPERATED
AIR RELEASE VALVE
D
1/2" PIPING BY
OTHERS (SEE NOTE 5)
CASING RELIEF VALVE
3/4" NPT OUTLET

3-1/2" (89) DIA. SUCTION AND


DISCHARGE GAUGES WITH
1/4" SHUT-OFF COCKS

C
VALVE INLET SIZE "B"
(PIPING BY OTHERS)

PIPE SIZE
2-1/2-481-10
3-481-10
4-481-11
4-481-15
5-481-11
5-481-15
5-481-17
6-481-11
6-481-11HH
6-481-14HH
6-481-15
6-481-18
6-481-20
8-481-12
8-481-21
10-481-15
10-481-18D
8-481-17
10-481-18
12-481-18

"A" PIPE TAP IN


CASING DISCHARGE

A
TAP SIZE

1-1/4"

CASING RELIEF VALVE


SYSTEM
G.P.M.

2"

ALL VERTICAL
(483) MODELS

3/4"

ALL 2-STAGE
(485) MODELS

1-1/4"

490 MODELS

3/4

Pentair Water

250
500
750
1000
1250
1500
2000
2500
3000
3500
4000

VALVE
INLET
SIZE - B

3/4

4-1/2

(114)

5-1/2
(140)

NOTES:
1. Dimensions are in inches (mm) and may
vary 1/4 (6).
2. Accessories shown are shipped loose for
field installtion.
3. Casing relief valve is to be adjusted to
appropriate pressure upon field installtion
4. Casing relief valve is furnished on electric
motor driven units only.
5. Two stage pumps require both vent taps
piped to air release valve.
6. Suction guage range is 30-0-150 PSI for
suction pressures up to 75 PSI, or 30-0300 PSI for suction pressures over 75 PSI.
7. Discharge gauge range is 0-300-PSI for
pumps with rated discharge pressures up
to 150 PSI, or 0-600 PSI for pumps with
rated discharge pressures over 150 PSI.

FLOAT OPERATED AIR RELEASE VALVE


SYSTEM
OPERATING
PRESSURE
UP TO 175 P.S.I.
OVER 175 P.S.I.

5-7/8 (149) 3-3/4 (95)


6-11/16 (170) 5-5/8 (143)

Section 916 Page


Date June 2002

206

AURORA FIRE PUMPS


AUTOMATIC AIR RELEASE VALVE

Supersedes Section 916 Page 206


Dated July 2001

4-3/4 (121)

1/2 NPT" OUTLET

5-1/4
(133)

HYDR8AC
(VAL-MATIC VM15A)
OR APPROVED EQUAL USED
WITH HORIZONTAL FIRE PUMPS
WORKING PRESSURE UP TO 300 PSI
(FM APPROVED)
1/2" NPT INLET

9-1/2 (241)
2" NPT OUTLET

12
(305)

HYDR8AD
(VAL-MATIC #102)
USED WITH VERTICAL TURBINE FIRE PUMPS
WORKING PRESSURE UP TO 300 PSI

2" NPT INTLET

NOTES:
1. All dimensions are in inches (mm) and may vary 1/4 (6).

Pentair Water

Project:
Customer:
Engineer:
Pump Manufacturer:


#
"
$

Model GPY
 



!  "  

Contents:



  
 


 

  

NOTE: The drawings included in this package are for controllers covered under our standard
offering. Actual AS BUILT drawings may differ from what is shown in this package

-XO\ 2012

Submittal Data Sheet


Model GPY Electric Fire Pump Controller

1M

3L3

From normal
incoming power through
Disconnecting Means
(IS/CB)*

T3

3L2

T2

3L1

T1

CR4

2M

1M

CR5

T5

1S

T4
2M

3L1

CR5

T6

2M
1S

1S

3L2

Line current
% of full load

Starting Method: Reduced Voltage


600
Wye-delta open
Typical Voltage Applied at Start: 100%
Inrush Current: 33% of normal load current
Starting Torque: 33%
210
Motor Type: Wye-delta
No. of Contactors: 2 at 58%, 1 at 33% of motor FLC
Min. ampacity of motor conductors: 6 at 125% x 58% of FLC
Shortcircuit Withstand
Rating
Standard
Optional

Across-the line

starting

Open transition

Locked rotor current


Transition current

Wye delta starting


Full load current

20

208V to 480V - 3ph - 50/60Hz

600V - 3ph - 60Hz

100,000 A
150,000 A

50,000 A
100,000 A

40

60

80

100

Percent of motor speed (%)

Built to NFPA 20 (latest edition)


Standard,
Listings,
Approvals and
Certifications

Enclosure

Underwriters Laboratory (UL)


FM Global
New York City
Optional
CE Mark
Protection Rating
 Standard: NEMA 2 (IP31)
Optional
 NEMA 12
NEMA 3
NEMA 3R
NEMA 4
Accessories
Bottom entry gland plate
Lifting Lugs
Keylock handle

UL218 - Fire pump controllers


CSA C22.2 No. 14 Industrial Control Equipment
Class 1321/1323
Accepted for use in the City of New York by the Department of Buildings
Various EN, IEC & CEE directives and standards

NEMA 4X-304 sst painted


NEMA 4X-304 sst brushed finish
NEMA 4X-316 sst painted
NEMA 4X-316 sst brushed finish
Paint Specifications
Red RAL3002
Powder coating
Glossy textured finish

IP54
IP55
IP65
IP66

*Please see Disconnecting Means details on page 2.

July 2012

Submittal Data Sheet


Model GPY Electric Fire Pump Controller

Surge
Suppression

Disconnecting
Means

Service
Entrance
Rating

Surge arrestor rated to suppress surges above line voltage


Isolating switch and circuit breaker assembly:
Door interlocked in the ON position
Isolating switch rated not less than 115% of motor full load current
Circuit breaker continuous rating not less than 115% of motor full load current
Overcurrent sensing non-thermal type, magnetic only
Instantaneous trip setting of not more than 20 times the motor full load current
Common flange mounted operating handle
Suitable as service entrance equipment

Emergency
Start Handle

Flange mounted
Pull and latch activation
Integrated limit switch
Across the line start (direct on line)

Locked Rotor
Protector

Operate shunt trip to open circuit breaker


Factory set at 600% of motor full load current
Trip between 8 and 20 seconds

Electrical
Readings

Voltage phase to phase (normal power)


Amperage of each phase when motor is running

Pressure
Readings

Continuous system pressure display


Cut-in and Cut-out pressure settings

Pressure and
Event
Recorder

Pressure
Sensing

July 2012

Pressure readings with date stamp


Event recording with date stamp
Under regular maintained operation, events can be stored in memory for up to 5 years.
Data viewable on operator interface display screen
Downloadable by USB port to external memory device
Pressure transducer and run test solenoid valve assembly for fresh water application
Pressure sensing line connection 1/2 Female NPT
Drain connection 3/8"
Rated for 0-500PSI working pressure (calibrated at 0-300psi)
Externally mounted with protective cover

Submittal Data Sheet


Model GPY Electric Fire Pump Controller

Audible Alarm

Visual
Indications and
Alarms

Remote Alarm
Contacts

ViZiTouch
Operator
Interface

4 alarm bell - 85 dB at 10ft. (3m)


Power available
Phase reversal
Motor run
Pump room alarm
Motor trouble
Phase loss
Phase unbalance
Low w ater level

SPDT-8A-250V.AC
Power available
Phase reversal
Motor run
Common pump room alarm
Overvoltage
Undervoltage
temperature
Low pump room temperature
Common motor trouble
Overcurrent
Fail to start
Undercurrent
Ground fault

Manual Start

Stopping
Timers

Manual start
Deluge valve start
Remote automatic start
Remote manual start
Overcurrent
Undercurrent
Undervoltage
Overvoltage

Phase unbalance

Embedded microcomputer with software PLC logic


4.2 color touch screen (HMI technology)
Upgradable software
Automatic Start

Operation

Locked rotor
Periodic test
Fail to start
Low discharge pressure
Low pump room temperature
Pump room temperature (F or C)
Pump on demand/Automatic start
Emergency start

Expandable storage
Multi-language

Start on pressure drop


Remote start signal from automatic device
Start pushbutton
Run test pushbutton
Deluge valve start
Remote start from manual device
Manual with Stop pushbutton
Automatic after expiration of minimum run timer **
Field Adjustable & Visual Countdown

Actuation
Visual Indication
Mode

Sequential start timer (on delay)


Periodic test timer
Pressure
Non-pressure
Automatic
Non-automatic

** Can only be used if approved by the AHJ


Approx. Shipping
Weight in Lbs (Kg)

208V - 240V

380V - 416V

275
(125)

5 - 30
(3.7- 22)
40 - 60
(30 - 45)
75 - 150
(55 - 110)

5 - 50
(3.7 - 37)
60 - 100
(45 - 75)
125 - 350
(90 - 257)

375
(170)
600
(270)

July 2012

440V - 480V

600V

HP Range (kW)
5 - 60
(3.7 - 45)
75 - 150
(55 - 110)
200 - 400
(147- 295)

5 - 75
(3.7 - 55)
100 - 150
(75 - 110)
200 - 500
(147 - 368)

Submittal Data Sheet


Model GPY Electric Fire Pump Controller

A4
A8
A9
A10
A11
A13
A16

B11

B11B
B19
B21
C1
C4
C6
C7
C10
C11
C12
C14
C15
C16
C17
C18
C19
C20
C21
C22
C23
C24
Cx

July 2012

Flow switch provision


Foam pump application w/o pressure transducer
and run test solenoid valve
Low zone pump control function
Medium zone pump control function
High zone pump control function
Non-pressure actuated controller w/o pressure
transducer and run test solenoid valve
Lockout/interlock circuit from equipment installed
inside the pump room
Built in alarm panel (120V.AC supervisory power)
providing indication for:
Audible alarm & silence pushbutton for motor
run, phase reversal, loss of phase.
Pilot lights for loss of phase & supervisory
power available
Built in alarm panel same as B11 but
220-240VAC supervisory power
High motor temperature thermistor relay c/w
visual indication and alarm contact
(Form C-SPDT)
Ground fault alarm detection c/w visual indication
and alarm contact (Form C-SPDT)
Extra motor run alarm contact (Form C-SPDT)
Periodic test alarm contact (Form C-SPDT)
Low discharge pressure alarm contact
(Form C-SPDT)
Low pump room temperature alarm contact
(Form C-SPDT)
High water reservoir level alarm contact
(Form C-SPDT)
High electric motor temperature alarm contact
(Form C-SPDT)
High electric motor vibration c/w visual indication
and alarm contact (Form C-SPDT)
Pump on demand/automatic start alarm contact
(Form C-SPDT)
Pump fail to start alarm contact (Form C-SPDT)
Control voltage healthy alarm contact
(Form C-SPDT)
Flow meter valve loop open c/w visual indication
and alarm contact (Form C-SPDT)
High water reservoir level c/w visual indication
and alarm contact (Form C-SPDT)
Emergency start alarm contact (Form C-SPDT)
Manual start alarm contact (Form C-SPDT)
Deluge valve start alarm contact (Form C-SPDT)
Remote automatic start alarm contact
(Form C-SPDT)
Remote manual start alarm contact
(Form C-SPDT)
High pump room temperature alarm contact
(Form C-SPDT)
Additional visual and alarm contact
(Specify function) (Form C-SPDT)

D1

D1A

D5
D5D
D10
D13
D14
D14A
D14B
D15
D18
D19
D20
D21
D26
D26A
D27
D27A
D28
D34
D35
D36
D36A
D37

Low suction pressure transducer for fresh water


rated at 0-300PSI with visual indication and alarm
contact
Low suction pressure transducer for sea water
rated at 0-300PSI with visual indication and alarm
contact
Pressure transducer and run test solenoid valve
for fresh water rated for 0-500PSI (for calibration
purposes only)
Pressure transducer and run test solenoid valve
for sea water rated for 0-500PSI
Omit mounting feet (when applicable)
High withstand rating (fire pump section only) up
to 480V = 150KA / 600V = 100KA
Anti-condensation heater & thermostat
(fire pump section only)
Anti-condensation heater & humidistat
(fire pump section only)
Anti-condensation heater & thermostat &
humidistat (fire pump section only)
Tropicalization
CE Mark with factory certificate
French labeling
Spanish labeling
Other languages
Modbus RTU provision
Modbus TCP/IP provision
Motor heater connection (external single phase
power source and heater on/off contact)
Motor heater connection (internal single phase
power source and heater on/off contact)
Customized drawing set
Field programmable I/O board - 8 Input / 5 output
Field programmable I/O board - 8 Input / 10 output
Redundant pressure transducer for fresh water
rated for 0-500PSI (calibrated at 0-300PSI)
Redundant pressure transducer for sea water
rated for 0-500PSI (calibrated at 0-300PSI)
Window kit for operator interface

Note: Options chosen from this page are not electrically


represented on the wiring schematics in this submittal
package.

Submittal Data Sheet


Model GPY Electric Fire Pump Controller

ViZiTouch Operator Interface


3

7
8

9
10

11

12

1 - Power LED
2 - Color touch screen
3 - Alarm LED
4 - HOME page button
5 - ALARM page button
6 - CONFIGURATION page button
7 - HISTORY page button

July 2012

13

8 - USB port
9 - START button
10 - Contextual navigation pad
11 - STOP button
12 - RUN TEST button
13 - HELP button

qwertyuiopasdfghjklzxcvbnmqwertyui
opasdfghjklzxcvbnmqwertyuiopasdfgh
jklzxcvbnmqwertyuiopasdfghjklzxcvb
DIESEL FIRE PUMP
nmqwertyuiopasdfghjklzxcvbnmqwer
SparePartListBook
Aurora
Horizontal Split Case
ControllerModel:GPD
Model : 6-491-14 A/Single Stage
tyuiopasdfghjklzxcvbnmqwertyuiopas
dfghjklzxcvbnmqwertyuiopasdfghjklzx
cvbnmqwertyuiopasdfghjklzxcvbnmq
wertyuiopasdfghjklzxcvbnmqwertyuio
pasdfghjklzxcvbnmqwertyuiopasdfghj
klzxcvbnmqwertyuiopasdfghjklzxcvbn
mqwertyuiopasdfghjklzxcvbnmqwerty
uiopasdfghjklzxcvbnmqwertyuiopasdf
ghjklzxcvbnmqwertyuiopasdfghjklzxc
vbnmqwertyuiopasdfghjklzxcvbnmrty
uiopasdfghjklzxcvbnmqwertyuiopasdf
ghjklzxcvbnmqwertyuiopasdfghjklzxc

PERTAMINABALIKPAPANDEPOTPANGKALANBUN,
DEPOTPULANGPISAU,DPPUJUWATA
COAL
FIRED POWER STATION,BABELAN

Preparedby:PT.RodaNurmala

Customer
:
Project name : Default

Pump Performance Curve


Encompass 2.0 - 15.1.1.0

DFP.Cap.2000 Gpm @ 9 Bar Total Head


320

Power

Power - hp

240

160

80

0
15.0

Preferred operating region

13.5

12.0

10.5
51

14.25 in

63

72

80

Head - bar

9.0

84

86
86
84

7.5

80
6.0

11.06 in

72

4.5

3.0

1.5

0.0

500

1,000

1,500

2,000
Flow - USgpm

2,500

3,000

3,500

4,000

Item number

: 012

Size

: 6-491-14A

Service

Stages

:1

Quantity

:1

Driver type

: Engine

Quote number

: 259241

Frequency

: 0 Hz

Date last saved

: 13 May 2015 2:04 AM

Speed, rated

: 2,100 rpm

Flow, rated

: 2,000.0 USgpm

Based on curve number

: 194-6X10X14A-2100

Differential head /
pressure, rated

: 9.03 bar

Efficiency

: 75.93 %
:

Shutoff head

: 10.20 bar
:

Suction pressure, max

: 0.00 psi.g

Power, maximum

: 245 hp

Section 913 Page 291


Date JULY 2013

AURORA MODELS 481, 491


AND 492 PUMPS
SINGLE-STAGE FIRE PUMP
CUMMINS CFP9E DIESEL ENGINE DRIVE

PUMP SIZE
DISCH
5
5
6
6
6
6
8
8
8
8
8
10
10
10
10
10
12

MODEL
491
491
491
491
491
481
491
481
491
481
481
481
481
492
481
491
481

CASE
BORE
14A
18A
14A
18C
19A
20
14A
17B
18A
21/A
24
15C
18
18
18D
20*
18A

SUCTION
8
8
10
10
10
8
12
10
12
10
12
12
12
12
12
16
14

POWER
SERIES
5
5
6B
7
6B
6B
7A
7

NOTES:
1. All dimensions are in inches and may vary 3/8".
2. Not for construction purposes, unless certified.
3. Suction and discharge flanges are ANSI Standard flat face.
4. Refer to individual engine dimension print for reference point
used to determine overall engine length.
5. Left hand (counterclockwise) rotation is not available.

2013 Pentair Ltd.

S
8.25
8.13
9.38
9.38
9.38
8
10.75
8
10.75
9.5
15
13.5
13.5
11.5
12.25
15
15

W
17.63
18.88
20.13
20.13
22.63
18
20.5
18
23.75
21.88
25.25
21.88
21.88
25.56
24.31
25.25
25.25

X
13.5
15
13.25
16
18
15.75
16
17
16
18
20
18
18
21
20
20
18

Z
9.75
10.63
10
11.75
12.13
8
10.75
8
12.5
9.5
15
13.5
13.5
11.5
12.25
15
15

CP
31.69
31.38
31.38
35.88
35.88
32
36.63
32
41.5
38
43.88
38
38
45.81
43
43.88
43.88

YY
17.25
18.75
18.75
20
18
18
22
17.75
22
21
25
20
22
21
24
25
23

ZZ
1
1
1
1
1
1.25
1
1.25
1
1.25
1.25
1.25
1.25
1
1.25
1.25
1.25

HD
27.81
27.81
31.81
31.81
31.81
27.81
31.81
27.81
31.81
27.81
36.81
36.81
36.81
31.81
36.81
36.81
36.81

HY
12.38
11.13
24.38
24.38
21.88
12
24
12
20.75
22.63
19.25
22.63
22.63
18.94
20.25
18.94
19.25

6. The driveshaft is not designed to operate at a 0 angle. The engine crankshaft is to


be parallel offset of 0.50 0.25 inch. The engine crankshaft may be parallel offset
from the pump shaft 0.50 inch right or left.
* Pump size 1049120 is furnished as standard with 125# suction flange and 250#
discharge flange.

PRELIMINARY ONLY

NFPA 20 Piping & Accessories Standard Inform ation


Jockey Pum p 12 M3/H

2000 GPM FIRE PUMP


Suction Pipe

10"

Suction Pipe

Discharge Pipe

10"

Discharge Pipe

2 ''

Relief Valve

6" x 6"

Suction Gate Valve

OS & Y Valve

Waste Cone

8" x 12"

Metering Device

8"

Suction Gate Valve

OS & Y Valve

Scale

NOTE :
This Draw just preliminary only for describe the real condition.
This Draw Property of PT. Roda Nurmala, Shall be use for Corporate purpose. if this draw not used again, so expected to deleted this drawn.

STANDAR INSTALASI NFPA DIESEL, ELECTRIC & J OCKEY FIRE PUMP

Project
Drawn

Single Line Pippe Drawing

PT. RODA NURMALA

Checked
Approved

2 ''

UNSCALE
COAL FIRED STATION B AB ELAN
AY
RZ
FW

Dwg. No :

RN-DK0031300810

08-09-201 5
08-09-201 5
08-09-201 5

MODELS

JU6H-UF32
JU6H-UF34
JU6H-UFM8
JU6H-UFM0

JU6H-UFD0
JU6H-UFD2
JU6H-UF30

FIRE PUMP ENGINES

JU6H-UFM2
JU6H-UF58
JU6H-UF50
JU6H-UF52

JU6H-UF54
JU6H-UF60
JU6H-UF62
JU6H-UFAAQ8

JU6H-UFAAPG
JU6H-UFAARG
JU6H-UF84
JU6H-UFAAS0

FM-UL-cUL APPROVED RATINGS BHP/KW


RATED SPEED
JU6H
MODEL

UFD0
UFD2
UF30
UF32

1470

1760
110

94

70

140

82
104

2100
144
160

2350

107
119

148
148
160
160

110
110
119
119

2600

148

110

160

119

UF34
UFM8
UFM0
UFM2
UF58
UF50
UF52
UF54
UFAAPG
UFAAQ8
UF60
UF62
UFAARG
UF84
UFAAS0

136

138

220

101

103

175
175

131
131

183
183

137
137

207

210

154

157

200
200

149
149

200

149

210
210

157
157

210

157

2800

US-EPA
(NSPS)
Available
Until

3000

160

119

175

131

216

161

216

161

164
227
200

169
149

252

188

240

179

240
240

179
179

240

179
259

260

193

275

205

194

12/31/09
12/31/09
12/31/09
12/31/09
12/31/11
12/31/12 +
12/31/09
12/31/08
12/31/08
12/31/08
12/31/08
12/31/08
12/31/11
N/A
N/A
12/31/08
12/31/08
N/A
12/31/11
N/A

Picture shown represents JU6H-TRWA engine model


USA EPA ((NSPS)) Emissions Compliant.
p
Applies
pp to John
Deere model year per Table 4 of 40 CFR Part 60 Sub Part
IIII.
All Models are available for Export
N/A = Not Applicable / Non-Emissionized
+ Not Available in California
Less than

SPECIFICATIONS

175 HP

Greater than 174 HP

JU6H MODELS
D0

D2

30

32

34

M8

M0

M2

58

50

52

54

60

62

84

AAPG AAQ8 AARG AAS0

ITEM
Number of Cylinders

Aspiration

TRWA

Rotation*
Overall Dimensions in. (mm)

CW
45.8 (1163) H x 57.4 (1457) L x 36.6 (930) W

Crankshaft Centerline Height - in. (mm)

45.8 (1163) H x 58 (1473) L x 36.6 (930) W


14 (356)

Weight lb (kg)

1657 (750)

1693 (766)

Compression Ratio

17.0:1

Displacement cu. in. (L)

414 (6.8)

Engine Type

4 Stroke Cycle Inline Construction

Bore & Stroke in. (mm)

4.19 x 5.00 (106 x 127)

Installation Drawing

D536

Wiring Diagram AC

C07651

Wiring Diagram DC

C072145

Engine Series

C072128

John Deere 6068 Series

Speed Interpolation

Optional

Abbreviations: CW Clockwise T Turbocharged TRWA Turbocharged with Raw Water Aftercooling


*Rotation viewed from Heat Exchanger / Front of engine

L - Length

W Width

H - Height

CERTIFIED POWER RATING

ENGINE RATINGS BASELINES

Each engine is factory tested to verify power and performance.

Engines are to be used for stationary emergency standby fire pump service only. Engines
are to be tested in accordance with NFPA 25.

Although FM-UL ratings are shown at specific speeds, Clarke engines can be
applied
app
ed at aanyy intermediate
te ed ate speed
speed. Too dete
determinee tthee intermediate
te ed ate speed
power; make a linear interpolation from the Clarke FM-UL power curve.
Contact Clarke or your Pump OEM Representative to obtain details.

FM

Engines are rated at standard SAE conditions of 29.61 in. (752.1 mm) Hg barometer and
77F (25C) inlet air temperature [approximates 300 ft. (91.4 m) above sea level] by the
testing laboratory (see SAE Standard J 1349).
A deduction of 3 percent from engine horsepower rating at standard SAE conditions shall
be made for diesel engines for each 1000 ft. (305 m) altitude above 300 ft. (91.4 m)
A deduction of 1 percent from engine horsepower rating as corrected to standard SAE
conditions shall be made for diesel engines for every 10F (5.6C) above 77F (25C)
ambient temperature.


JU6H-UFD0
JU6H-UFD2
JU6H-UF30

FIRE PUMP ENGINES

JU6H-UF32
JU6H-UF34
JU6H-UFM8
JU6H-UFM0

JU6H-UFM2
JU6H-UF58
JU6H-UF50
JU6H-UF52

JU6H-UF54
JU6H-UF60
JU6H-UF62
JU6H-UFAAQ8

MODELS
JU6H-UFAAPG
JU6H-UFAARG
JU6H-UF84
JU6H-UFAAS0

ENGINE EQUIPMENT
EQUIPMENT

STANDARD

OPTIONAL

Air Cleaner

Direct Mounted, Washable, Indoor Service with Drip Shield

Disposable, Drip Proof, Indoor Service Outdoor Type, Single or


Two Stage (Cyclonic)

Alarms

Overspeed Alarm & Shutdown, Low Oil Pressure, Low & High
Coolant Temperature, Low Raw Water Flow, High Raw Water
Temperature

Low Coolant Level, Low Oil Level, Oil Filter Differential Pressure,
Fuel Filter Differential Pressure, Air Filter Restriction

Alternator

12V-DC, 42 Amps with Poly-Vee Belt and Guard

24V-DC, 40 Amps with Poly-Vee Belt and Guard

Coupling

Bare Flywheel

Listed Driveshaft and Guard,


Guard UFD0/D2/30/32/34 CDS20
CDS20-S1;
S1;
UFM8/M0/M2/58/50/52/54/60/62/84 CDS30-S1;
AAPG/AAQ8/AARG/AAS0 CDS50-SC

Engine Heater

115V-AC, 1360 Watt

230V-AC, 1360 Watt

Exhaust Flex Connection

SS Flex, 150# ANSI Flanged Connection, 5

SS Flex, 150# ANSI Flanged Connection, 6

Exhaust Protection

Metal Guards on Manifolds and Turbocharger

Flywheel Housing

SAE #3

Flywheel Power Take Off

11.5 SAE Industrial Flywheel Connection

Fuel Connections

Fire Resistant, Flexible, USA Coast Guard Approved, Supply and


Return Lines

Fuel Filter

Primary Filter with Priming Pump

Fuel Injection System

Stanadyne, Direct Injection

Fuel Solenoid

12V-DC Energized to Stop (ETS)


12V-DC Energized to Run (ETR) JU6H-UFAA models only

Governor, Speed

Constant Speed, Mechanical

Heat Exchanger

Tube and Shell Type, 60 PSI (4 BAR), NPT(F) Connections


Sea Water Compatible

Instrument Panel

English and Metric, Tachometer, Hourmeter, Water Temperature,


Oil Pressure and Two (2) Voltmeters

Junction Box

Integral with Instrument Panel; For DC Wiring Interconnection to


Engine Controller

Lube Oil Cooler

Engine Water Cooled, Plate Type

Lube Oil Filter

Full Flow with By-Pass Valve

Lube Oil Pump

Gear Driven, Gear Type

Manual Start Control

On Instrument Panel with Control Position Warning Light

Overspeed Control

Electronic with Reset and Test on Instrument Panel

Raw Water Cooling Loop


w\Alarms

Galvanized

Seawater, All 316SS, High Pressure

Raw Water Cooling Loop


Solenoid Operation

Automatic from Fire Pump Controller and from Engine Instrument


Panel (for Horizontal Fire Pump Applications)

Not Supplied (for Vertical Turbine Fire Pump Applications)

Run Stop Control

On Instrument Panel with Control Position Warning Light

Starters

Two (2) 12V-DC

Throttle Control

Adjustable Speed Control, Tamper Proof

Water Pump

Centrifugal Type
Type, Poly-Vee Belt Drive with Guard

SS, Braided, cUL Listed, Supply and Return Lines

12V-DC Energized to Run (ETR); 24V-DC Energized to Run (ETR);


24V-DC Energized to Stop (ETS)

Two (2) 24V-DC

Abbreviations :DC Direct Current, AC Alternating Current, SAE Society of Automotive Engineers, NPT(F) National Pipe Tapered Thread (Female) SS Stainless Steel

Fire Protection Products, Inc.


100 Progress Place, Cincinnati, Ohio 45246
United States of America
Tel +1-513-475-(FIRE)3473 Fax +1-513-771-8930
www.clarkefire.com
C13556 revP
13APR15

UK, Ltd.
Grange Works, Lomond Rd., Coatbridge, ML5-2NN
United Kingdom
Tel +44-1236-429946
Fax +44-1236-427274
www.clarkefire.com

Specifications and information contained in this brochure subject to change without notice.

FIRE PUMP MODEL: DS0H-UFAA92


Heat Exchanger Cooled/Turbocharged
Raw Water Charge Cooling
18.3 Liter

723.5

723

722.5

722
(538.5)

722

721.5

721

Non Emissionized
Ref: Engine Emission Label
720.5
2098.5

2099

2099.5

RESTRICTED:

2100
2100.5
ENGINE SPEED - RPM

2101

2101.5

USE ONLY FOR STAND-BY FIRE PUMP APPLICATIONS

ENGINE PERFORMANCE:
STANDARD CONDITIONS: (SAE J1349, ISO 3046)
77F (25C) AIR INLET TEMPERATURE
29.61 IN. (751.1MM) HG BAROMETRIC PRESSURE
#2 DIESEL FUEL (SEE C13940)

KEVIN KUNKLER 28AUG13

NAMEPLATE BHP (MAXIMUM PUMP LOAD)


THIS DRAWING AND THE INFORMATION HEREIN ARE OUR
PROPERTY AND MAY BE USED BY
OTHER ONLY AS AUTHORIZED BY
US. UNPUBLISHED -- ALL RIGHTS
RESERVED UNDER THE
COPYRIGHT LAWS.

CREATED

DATE CREATED

08/28/13

ENGINE MODEL DS0H-UFAA92


DRAWING NO.

C135397

REV

DS0H-UFAA92
INSTALLATION & OPERATION DATA (I&O Data)
USA Produced
Basic Engine Description
Engine Manufacturer
Ignition Type
Number of Cylinders
Bore and Stroke - in (mm)
Displacement - in (L)
Compression Ratio
Valves per cylinder
Intake
Exhaust
Combustion System
Engine Type
Fuel Management Control
Firing Order (CW Rotation)
Aspiration
Charge Air Cooling Type
Rotation, viewed from front of engine, Clockwise (CW)
Engine Crankcase Vent System
Installation Drawing
Weight - lb (kg)
Power Rating
Nameplate Power - HP (kW)
Cooling System - [C051529]
Engine Coolant Heat - Btu/sec (kW)
Engine Radiated Heat - Btu/sec (kW)
Heat Exchanger Minimum Flow
60F (15C) Raw H20 - gal/min (L/min)
100F (37C) Raw H20 - gal/min (L/min)
Heat Exchanger Maximum Cooling Raw Water
Inlet Pressure - psi (bar)
Flow - gal/min (L/min)
Typical Engine H20 Operating Temp - F (C)[1]
Thermostat
Start to Open - F (C)
Fully Opened - F (C)
Engine Coolant Capacity - qt (L)
Coolant Pressure Cap - lb/in (kPa)
Maximum Engine Coolant Temperature - F (C)
Minimum Engine Coolant Temperature - F (C)
High Coolant Temp Alarm Switch - F (C)

Electric System - DC
System Voltage (Nominal)
Battery Capacity for Ambients Above 32F (0C)
Voltage (Nominal)
Qty. Per Battery Bank
SAE size per J537
CCA @ 0F (-18C)
Reserve Capacity - Minutes
Battery Cable Circuit, Max Resistance - ohm
Battery Cable Minimum Size
0-120 in. Circuit Length [2]
121-160 in. Circuit Length [2]
161-200 in. Circuit Length [2]
Charging Alternator Maximum Output - Amp,
Starter Cranking Amps, Rolling - @60F (15C)

180 Series
Compression (Diesel)
10
5.04 (128) X 5.59 (142)
1115 (18.3)
14.6:1
1
1
Direct Injection
Vee, 4 stroke cycle
Mechanical, Inline Pump
1-6-5-10-2-7-8-3-4-9
Twin Turbocharged
Raw Water Cooled
Standard
Closed
D665
3200 (1450)

2100
722 (538.5)
2100
336 (355)
77 (81.2)
45 (170)
55 (208)
60 (4.1)
80 (303)
170 (76.7) - 200 (93.3)
160 (71.1)
185 (85)
33 (31.2)
7 (48.3)
205 (96.1)
160 (71.1)
205 (96.1)

Standard
24

12
2
8D
1400
430
0.0012
00
000
0000
45
315

[C07633]

[65.26101-7153C]
[65.26201-7074D]

NOTE: This engine is intended for indoor installation or in a weatherproof enclosure. 1Engine H2O temperature is
dependent on raw water temperature and flow. 2Positive and Negative Cables Combined Length.

Page 1 of 2

DS0H-UFAA92
INSTALLATION & OPERATION DATA (I&O Data)
USA Produced
Exhaust System (dual exhaust outlets)
Exhaust Flow - ft./min (m/min)[3]
Exhaust Temperature - F (C)
Maximum Allowable Back Pressure - in H20 (kPa)
Minimum Exhaust Pipe Dia. - in (mm) [4] (quantity 2)
Fuel System
Fuel Consumption - gal/hr (L/hr)
Fuel Pressure - lb/in (kPa)
Minimum Line Size - Supply - in.
Pipe Outer Diameter - in (mm)
Minimum Line Size - Return - in.
Pipe Outer Diameter - in (mm)
Maximum Allowable Fuel Pump Suction Lift
with clean Filter - in H20 (mH20)
Maximum Allowable Fuel Head above Fuel pump, Supply or Return - ft (m)
Fuel Filter Micron Size
Heater System
Engine Coolant Heater
Wattage (Nominal)
Voltage - AC, 1 Phase
Part Number

Air System
Combustion Air Flow - ft./min (m/min)
Air Cleaner
Part Number
Type
Cleaning method
Air Intake Restriction Maximum Limit
Dirty Air Cleaner - in H20 (kPa)
Clean Air Cleaner - in H20 (kPa)
Maximum Allowable Temperature (Air To Engine Inlet) - F (C)[5]

2100
3813 (108)
970 (521)
40 (10)
5 (127)
2100
36.3 (137)
17 (117) - 26 (179)
.75 Schedule 40 Steel Pipe
1.05 (26.7)
.50 Schedule 40 Steel Pipe
0.848 (21.5)
54 (1.4)
16 (4.9)
5
Standard

Optional

2500
230 (+5%, -10%)
[C122194]

2500
115 (+5%, -10%)
[C122190]

2100
2271 (64.3)
Standard
[C03244 Qty (2)]
Indoor Service Only,
with Shield
Washable

Optional
[C03330 Qty 2]
Canister,
Single-Stage
Disposable

14 (3.5)
7 (1.7)
130 (54.4)

Lubrication System
Oil Pressure - normal - lb/in (kPa)
Low Oil Pressure Alarm Switch - lb/in (kPa)
In Pan Oil Temperature - F (C)
Total Oil Capacity with Filter - qt (L)

53 (365) - 89 (614)
11.4 (78.6)
156 (68.9) - 230 (110)
37 (35)

Lube Oil Heater


Wattage (Nominal)
Voltage
Part Number

Optional
300
120V (+5%, -10%)
C04559

14 (3.5)
7 (1.7)

Optional
300
240V (+5%, -10%)
C04560

Performance
2100
BMEP - lb/in (kPa)
244 (1680)
Piston Speed - ft/min (m/min)
1957 (597)
Mechanical Noise - dB(A) @ 1m
Consult Factory
Power Curve
C135397
3Engine has dual exhaust outlets. Combined total exhaust flow from both outlets is given. 4Based on Nominal System. Back pressure flow
analysis must be done to assure maximum allowable back pressure is not exceeded. (Note: minimum exhaust Pipe diameter is based on: 15 feet of
pipe, one 90 elbow, and a silencer pressure drop no greater than one half of the maximum allowable back pressure.) 5Review for horsepower
derate if ambient air entering engine exceeds 77F (25C). [ ] indicates component reference part number.

Page 2 of 2
C135404 Rev F
DP 18MAR15

CLARKE
Fire Protection Products

DR8 & DS0


ENGINE MATERIALS AND CONSTRUCTION
Air Cleaner
Type.

Indoor Usage Only


Oiled Fabric Pleats
Material...... Surgical Cotton
Aluminum Mesh
Air Cleaner - Optional
Type.
Canister
Material Pleated Paper
Housing.. Enclosed

Camshaft
Material...... Chromium Molybdenum Steel
Nitride Hardening
Location...... In Block
Drive... Gear
Type of Cam........Ground
Charge Air Cooler
Type.. Raw Water Cooled - All
Materials (in contact with raw water)
Tubes.. 90/10 CU/NI
Tube Header Plate Brass (ASTM C4621)
Inlet/Outlet Covers
Bronze (BC6)
PlumbingGalvanized Steel Pipe
ISO 15540 Hose (Standard)
Other Materials (Optional)
Coolant Pump
Type . Centrifugal
Drive . Belt
Coolant Thermostat
TypeFull Blocking
3
Qty
Cooling Loop (Galvanized)
Tees, Elbows, Pipe
Galvanized Steel
Ball ValvesBrass ASTM B 124
Solenoid Valve Brass
Bronze
Pressure Regulator
StrainerCast Iron (1/2"- 1" Loops)
or Bronze (1.25" - 2" Loops)
Cooling Loop (Sea Water)
Tees, Elbows, Pipe
316 Stainless Steel
Ball Valves316 Stainless Steel
Solenoid Valve 316 Stainless Steel
Pressure Regulator/StrainerCast Brass ASTM B176 C87800
Cooling Loop (Sea Water)
Tees, Elbows, Pipe
316 Stainless Steel
Ball Valves316 Stainless Steel
Solenoid Valve 316 Stainless Steel
Pressure Regulator/Strainer316 Stainless Steel
Connecting Rod
TypeOne Piece, Diagonally Split
Material
Die Forged Steel

Crank Pin Bearings


TypeOne Piece
Material Steel backed, Lead Bronze
Crankshaft
Material Forged Steel
Type of BalanceDynamical, Screwed on Balanced
Weights
Cylinder Block
TypeOne Piece w/ Non-Siamese Cyl.
Material Cast Iron
Cylinder Head
Type..
Individual, 2 Valve
Material Cast Iron
Cylinder Liners
Type..Centrifugal Cast, Wet Liner
Material.Alloy Iron Plateau, Honed
(Effective Dec 2013)
Heat Exchanger - Standard (Sea Water Compatible)
Type
Tube & Shell
Materials (in contact with raw water)
Tubes.... Copper
Shell.. Copper
Headers. Copper
Electrode Zinc
Injection Pump
Type
Drive

In Line
Gear

Lubrication Cooler
Type

Plate

Lubrication Pump
Type
Drive

Gear
Gear

Main Bearings
Type...
Material..

Precision Half Shells


Steel Backed, Lead Bronze

Piston
Type and Material.
Cooling

Aluminum Alloy with Reinforced/Top Groove


Oil Jet Spray

Piston Pin
Type .

Full Floating

Piston Rings
Number/Piston..
Top..
Second
Third

3
Keystone Barrel FacedHard Chrome Coated
Tapered Cast Iron
Hard Chrome Coated
Double Rail Type
with Expander Spring

C134774 revC

CLARKE

Fire Protection Products

www.clarkefire.com

JU6H-UFAAS0
FIRE PUMP DRIVER

NOISE DATA

Mechanical Engine Noise *


RPM

BHP

2100

260

OVERALL 31.5 Hz
dB(A)
dB(A)
107.5

65.6

63 Hz
dB(A)

125 Hz
dB(A)

250 Hz
dB(A)

67.5

81.5

89.1

Octave Band
500 Hz 1k Hz
dB(A)
dB(A)
97.0

100.2

2k Hz
dB(A)

4k Hz
dB(A)

8k Hz
dB(A)

16k Hz
dB(A)

103.7

100.8

96.1

97.6

2k Hz
dB(A)

4k Hz
dB(A)

8k Hz
dB(A)

16k Hz
dB(A)

103.5

100.7

90.4

84

Raw Exhaust Engine Noise **


RPM

BHP

2100

260

OVERALL 31.5 Hz
dB(A)
dB(A)
110.2

63 Hz
dB(A)

125 Hz
dB(A)

250 Hz
dB(A)

99.9

104.3

99

Octave Band
500 Hz 1k Hz
dB(A)
dB(A)
101.2

100.8

* Values above are provided at 3.3ft (1m) from engine block and do not include the raw exhaust noise.
** Values above are provided at 23ft (7m), 90
engine.

horizontal, from a vertical exhaust outlet and does not include noise created mechanically by the

The above data reflects values for a typical engine of this model, speed and power in a free-field environment.
Installation specifics such as background noise level and amplification of noise levels from reflecting off of surrounding objects, will affect the
overall noise levels observed. As a result of this, Clarke makes no guarantees to the above levels in an actual installation.

C135162_revA 18Apr13 dsp

Section 916 Page 201


Date September 2013

AURORA FIRE PUMPS


STANDARD FIRE PUMP ACCESSORIES

Supersedes Section 916 Page 201


Dated February 2005

1/2" NPT OUTLET

E
FLOAT-OPERATED
AIR RELEASE VALVE
D
1/2" PIPING BY
OTHERS (SEE NOTE 5)
CASING RELIEF VALVE
3/4" NPT OUTLET

3-1/2" (89) DIA. SUCTION AND


DISCHARGE GAUGES WITH
1/4" SHUT-OFF COCKS

C
VALVE INLET SIZE "B"
(PIPING BY OTHERS)

PIPE SIZE
2-1/2-481-10
3-481-10
4-481-11
4-481-15
5-481-11
5-481-15
5-481-17
6-481-11
6-481-11HH
6-481-14HH
6-481-15
6-481-18
6-481-20
8-481-12
8-481-21
10-481-15
10-481-18D
8-481-17
10-481-18
12-481-18

"A" PIPE TAP IN


CASING DISCHARGE

A
TAP SIZE

1-1/4

CASING RELIEF VALVE


SYSTEM
G.P.M.

ALL VERTICAL
(483) MODELS

3/4

ALL 2-STAGE
(485) MODELS

1-1/4

490 MODELS

3/4

250
500
750
1000
1250
1500
2000
2500
3000
3500
4000

VALVE
INLET
SIZE - B

3/4

4-1/2

(114)

5-1/2
(140)

NOTES:
1. Dimensions are in inches (mm) and may
vary 1/4 (6).
2. Accessories shown are shipped loose for
field installtion.
3. Casing relief valve is to be adjusted to
appropriate pressure upon field installtion
4. Casing relief valve is furnished on electric
motor driven units only.
5. Two stage pumps require both vent taps
piped to air release valve.
6. Suction guage range is 30-0-150 PSI for
suction pressures up to 75 PSI, or 30-0300 PSI for suction pressures over 75 PSI.
7. Discharge gauge range is 0-300-PSI for
pumps with rated discharge pressures up
to 150 PSI, or 0-600 PSI for pumps with
rated discharge pressures over 150 PSI.

FLOAT OPERATED AIR RELEASE VALVE


SYSTEM
OPERATING
PRESSURE
UP TO 175 P.S.I.
OVER 175 P.S.I.

5-7/8 (149) 3-3/4 (95)


6-11/16 (170) 5-5/8 (143)

Section 916 Page 206


Date September 2013

AURORA FIRE PUMPS


AUTOMATIC AIR RELEASE VALVE

Supersedes Section 916 Page 206


Dated June 2002
5-1/8 (130)

1/2 NPT" OUTLET

6-5/16
(160)

HYDR8AC
(VAL-MATIC VM-22.7)
OR APPROVED EQUAL USED
WITH HORIZONTAL FIRE PUMPS
WORKING PRESSURE UP TO 300 PSI
(FM APPROVED)
1/2" NPT INLET

9-1/2 (241)
2" NPT OUTLET

12
(305)

HYDR8AD
(VAL-MATIC #102)
USED WITH VERTICAL TURBINE FIRE PUMPS
WORKING PRESSURE UP TO 300 PSI

2" NPT INTLET

NOTES:
1. All dimensions are in inches (mm) and may vary 1/4 (6).

AIR RELEASE VALVE


SERIES NO. 15A
STANDARD MATERIALS OF CONSTRUCTION

PART NAME

MATERIAL

BODY

CAST IRON ASTM A126, CLASS B

COVER

CAST IRON ASTM A126, CLASS B

LEVER FRAME

STAINLESS STEEL T316, ASTM A240

SEAT

STAINLESS STEEL T316, ASTM A276

FLOAT

STAINLESS STEEL T316, ASTM A240

GASKET

COMPRESSED NON-ASBESTOS FIBER

COVER BOLT

ALLOY STEEL SAE, GRADE 5

10

FLOAT ARM

STAINLESS STEEL T316, ASTM A240

11

ORIFICE BUTTON

VITON

12

PIVOT PIN

STAINLESS STEEL T316, ASTM A479

13

PIN RETAINER

STAINLESS STEEL PH 15-7 MO

14

PIPE PLUG

STEEL

17

FLOAT RETAINER

STAINLESS STEEL T316, ASTM F879

21

LOCATOR

STAINLESS STEEL T316, ASTM F593

34

LOCK WASHER

STAINLESS STEEL T316, ASTM A240

PART NO.

NOTE: ALL SPECIFICATIONS AS


LAST REVISED.

Revised 1-29-03

MATERIALS OF CONSTRUCTION

DATE

2/23/87

DRWG. NO.

VALVE AND MANUFACTURING CORP.

VM-15A-M

Bulletin 1500

AIR VALVES
PROVIDING
SYSTEM
EFFICIENCY
AND
PROTECTION
NSF/ANSI 61
Certified

TABLE OF CONTENTS
UNDERSTANDING AIR VALVES
Air and Its Impact on a Water and Wastewater System pp. 3-7
Features and Benefits pp. 8-9

AIR VALVE APPLICATIONS


Look to Val-Matic for Solutions p. 10
Applications, Functions, Purpose and Features p. 11

TECHNICAL DATA

Air Release Valves pp. 12-13

Air/Vacuum Valves pp. 14-15

Combination Air Valves pp. 16-19

Surge-Suppression Air Valves pp. 20-21

Well Service Air Valves pp. 22-23

Vacuum Breaker Valves pp. 24-25

Vacuum Priming Valves p. 26

Air Valve Sizing Software p. 27


2

AIR

&
Its Impact on a Water and Wastewater System

ne of the most misunderstood aspects of the


Water & Wastewater industry is the presence
of air in a pipeline and its impact on operations. Many operational problems, especially at the time
of initial start-up, including broken pumps, valves and
pipe, as well as faulty instrumentation readings, are
blamed on inadequate thrust blocking, improper pipeline
bedding, etc. In reality, many of these problems are not
caused by improper installation of the line, but by failure
to de-aerate the line. Properly de-aerating your pipeline
will safeguard it from air-related problems, however if no
steps are taken to accomplish this, you should be ready for
trouble.

Vertical Pump
Well Service
Air Valve
Check Valve

FLOW

Water Level

SOURCES OF AIR
Air in a pressurized, operating pipeline comes from three
primary sources. First, prior to start-up, the line is not
empty - it is full of air. To entirely fill a pipeline with fluid,
it is necessary to eliminate this air. As the line fills, much
of this air will be pushed downstream to be released
through hydrants, faucets, etc. but a large amount will
become trapped at system high points (Figure 1). This
phenomenon will occur because air is lighter than water

Figure 2
Air entering through mechanical equipment

AIR BUBBLES RISE


TO HIGHT POINT
INCREASING IN SIZE

FL

AIR COLLECTS AT HIGH POINT

OW

Figure 1
Air in pipeline collects at high points

and therefore, will collect at the high points. This air will
continuously be added to by the second and third sources
as the system continues operation.
Source number two is the water itself. Water contains
approximately 2% air by volume. During system operation, the entrained air will continuously separate out of the
water and once again accumulate at system high points.
To illustrate the potential massive amount of air this 2%
represents, consider the following: A 1000 ft. length of
pipe could contain a pocket of air 20 ft. long if all the air
accumulated in one location. Or a one mile length of pipe
could contain a 100 ft. pocket of air. This would be true
regardless of the diameter of the pipe.

The third source of air is that which enters through


mechanical equipment (Figure 2). This includes air being
forced into the system by pumps as well as air being
drawn in through packing, valves, etc. under vacuum conditions. As one can see, a pressurized pipeline is never
without air and typically the volume is substantial.

IMPACT OF AIR ON SYSTEM


Now that we have identified the air sources, let us consider
their impact on the system. Two problems are apparent.
The pocket(s) of air accumulating at a high point(s) can
result in a line restriction (Figure 3). Like any restriction, the
AIR BUBBLES
RISE TO HIGH POINT
INCREASING IN SIZE

FL

AIR COLLECTS AT HIGH POINT

OW

RESTRICTED FLOW
INCREASED VELOCITY
INCREASED HEAD LOSS

Figure 3
Air pockets can lead to line restriction

Air in a pressurized pipeline is a serious concern. Obviously, its removal will result in a more
efficient, cost effective operation and potentially avoid more serious problems.

pocket(s) of air increases headloss, extends pumping


cycles and increases energy consumption. The presence of
air can also promote corrosion of pipe and fittings. As air
continues to accumulate at system high points, the fluid
velocity increases as the fluid is forced through a smaller
and smaller opening.

can and often will, lead to a high pressure surge (water


hammer). Serious damage to valves, fittings, gaskets, or
even breakage of the line can occur. This is the most
serious of the possible consequences of air being allowed
to accumulate in system high points.

HISTORICAL SOLUTIONS

W
LO

Figure 4
Air pockets can lead to total flow stoppage

As the pocket(s) grows, one of two phenomena will occur.


The first possibility is a total flow stoppage (Figure 4). If system dynamics are such that the air cannot be continuously
removed by the increased fluid velocity and pushed downstream, then this could happen. As the pocket(s) continues to accumulate air, a pressure drop higher than pump
capacity can develop and stop all flow.

As we can see, air in a pressurized pipeline is a serious


concern. Obviously, its removal will result in a more efficient, cost effective operation and potentially avoid more
serious problems. In the early 1900's, engineers and water
works personnel started developing an understanding of
the problems associated with air and the search for a solution began. Some depended on standpipes, believing that a
large portion of the air would be expelled through them.
Hydrant

The second, and more likely occurrence, is that the


increased velocity will cause all, or part of, the pocket to
suddenly dislodge and be pushed downstream (Figure 5).
The sudden and rapid change in fluid velocity when the
pocket dislodges and is then stopped by another high point,
Air Pocket

FL

OW

Butterfly Valve

Distribution Line

Figure 6
Opening a hydrant may not eliminate air pockets

FL

OW

Part of air pocket breaks


away, creating surge

Figure 5
Air pockets can lead to surges in the line

Many began placing gate or ball valves at system high points


to manually bleed off accumulated air. Unfortunately, it has
proved impossible to predict when it is time to bleed the air.
This proved impractical, especially on larger systems. Open
fire hydrants (Figure 6) are frequently used under the
assumption that all air in the pipeline will be released.
Unfortunately, hydrants are generally connected to the side
of the pipe, leaving air trapped at the top and at system
high points. It should be noted that there are still municipalities using these methods.

An added benefit of an Air/Vacuum Valve is its ability to provide pipeline vacuum protection. If a
negative pressure develops, the valve will open, admitting air into the line, reducing the potential for
surges related to column separation and possible pipeline collapse.
AIR EXHAUST

THE AIR VALVE SOLUTION


Today, most municipalities utilize Automatic Air Valves.
They are available in many different designs and
configurations for a wide range of applications. Their
function is to automatically release and admit air without
operator assistance. Today, countless Air Valves are
performing this task around the globe on a daily basis.
Air Valves are available in three basic configurations
(Figure 7): Air Release Valves, Air/Vacuum Valves and
Combination Air Valves. Correct sizing and location of all
three types are critical. Every high point greater than one
pipe diameter where the pipeline converts from a positive
grade to a negative grade requires an air valve. Even minimal high points with small air pockets can cause serious
surge problems and reduce line efficiency. In addition, it
is recommended that air valves be installed every half
mile or 2500 feet on straight horizontal runs (AWWA
M51). Air Valve Sizing Software is available, see page 27.

WATER LEVEL
WATER LEVEL

AIR ENTERING
VALVE

CLOSED
POSITION

OPEN
POSITION

Figure 8
Air Release Valve in Operation

by water, raising the float and closing the valve orifice. As


air accumulates, the valve will continue to cycle in this
manner to remove collected air.

AIR/VACUUM VALVES
Air/Vacuum Valves (Figure 9), sometimes referred to as
"large orifice" valves, are used to exhaust large quantities
of air upon system start-up, as well as allowing air to reenter the line upon system shut down or system failure.
As water enters the valve, the float will rise, closing the discharge port. The valve will remain closed until system
pressure drops to near zero psi. It will not open to release
any accumulation of air while the system is under pressure.

Air Release Valve

AIR EXHAUSTING

Combination
Air Valve

OPEN
Air exhausted during
pipeline fill

Air/Vacuum Valve
Figure 7

WATER LEVEL

Basic Air Valve configurations

AIR RELEASE VALVES


An Air Release Valve (Figure 8), sometimes referred to as
a "small orifice" valve, will continuously release accumulated air during system operation. As air from the pipeline
enters the valve, it displaces the water, allowing the float
to drop. The air is then released into the atmosphere
through a small orifice. As the air is vented it is replaced

CLOSED
Pipeline under
pressure

AIR INTAKE

OPEN
Air enters during
pipeline draining
Figure 9
Air/Vacuum Valve Operation

Air Release Valves


Installation Dimensions
WATER AIR RELEASE VALVES
Inlet
Size

Outlet
Size

Model
Number

CWP
PSI

Orifice Size

1/2 NPT
3/4 NPT
1 NPT
1 NPT
1/2 - 3/4 NPT
1/2 NPT
1/2 - 1 NPT
3/4 - 1 NPT
3/4 - 1 NPT
1 NPT
1 NPT
2 NPT
1 NPT
2 NPT
2 NPT
2 NPT
3 NPT
2 NPT
3 NPT
2 NPT
2 NPT
6 125lb Flg

1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1 NPT
1 NPT
1 NPT
1 NPT
1 NPT
1 NPT
1 NPT
1 NPT

15A*
15A.2*
15A.3*
22.3*
22.4*
22.7*
22.9*
25.5*
25.6*
38*
38HP*
38.2*
38.5*
38.6*
45*
45HP*
45.2*
45.5*
45.6*
50*
50HP*
61*

175
175
175
175
175
300
300
150
300
150
500
150
300
300
150
400
150
300
300
500
1000
150

1/16
1/16
1/16
3/32
3/32
1/16
1/16
1/8
3/32
3/16
1/8
3/16
5/32
5/32
23/64
3/16
23/64
7/32
7/32
7/32
1/8
1

*NSF/ANSI 61 Certified

Dimensions
A
4 3/4
4 3/4
4 3/4
5 1/8
5 1/8
5 1/8
5 1/8
6 1/8
6 1/8
7
7
7
7
7
9 1/2
9 1/2
9 1/2
9 1/2
9 1/2
10 7/8
10 7/8
18 3/4

B
5 1/4
5 1/4
5 1/4
6
6
6
6
7
7
10
10
10
10
10
12 1/4
12 1/4
12 1/4
12 1/4
12 1/4
13
13
22

15A - 50HP
Air Release Valve

61
Air Release Valve

UL Listed/FM Approved

WASTEWATER AIR RELEASE VALVES


Inlet
Size

Outlet
Size

Model
Number

CWP
PSI

Orifice Size

2 NPT
3 NPT
2 NPT
3 NPT
2 NPT
3 NPT
2 NPT
3 NPT
4 NPT

1/2 NPT
1/2 NPT
1/2 NPT
1/2 NPT
1 NPT
1 NPT
1 NPT
1 NPT
1 NPT

48A
48A.2
48A.4
48A.5
49A
49A.2
49A.4
49A.5
49A.6

150
150
75
75
150
150
75
75
75

3/16
3/16
5/16
5/16
7/16
7/16
1/2
1/2
1/2

Dimensions
A
7
7
7
7
9 1/2
9 1/2
9 1/2
9 1/2
9 1/2

B
15 5/16
15 5/16
15 5/16
15 5/16
17 9/16
17 9/16
17 9/16
17 9/16
17 9/16

48A - 49A.6
Wastewater Air
Release Valves

13

Make the change to QUALITY!

Specify V

Val-Matics quality of design and meticulous workmanship has set


the standards by which all others are measured. Quality design
features such as Type 316 stainless steel trim as standard on Air
Release, Air/Vacuum and Combination Air Valves...combined
resilient/metal to metal seating for Silent Check Valves...stabilized components that provide extended life of the Dual Disc
Check Valves...high strength and wear resistant aluminum bronze
trim as standard for Tilted Disc Check valves...unrestricted full
flow area through Swing-Flex Check Valves...heavy duty stainless
steel screened inlet on Sure Seal Foot Valves...a Cam-Centric
Plug Valve with more requested features than any other eccentric

Copyright 2008 Val-Matic Valve & Mfg. Corp.


ISO 9001:2000 certified company

Val-Matic is totally committed to providing the highest quality


valves and outstanding service to our customers. Complete customer satisfaction is our goal.

VAL-MATIC VALVE AND MANUFACTURING CORP.


905 RIVERSIDE DRIVE ELMHURST, I L 60126
630-941-7600 FAX: 630-941-8042
www.valmatic.com
valves@valmatic.com

1500-4/08

plug valve, and the American-BFV Butterfly Valve that provides


a field replaceable seat without the need for special tools. These
features coupled with our attention to detail put Val-Matic valves
in a class by themselves. The VaultSafe family of products included the FloodSafe Inflow Preventer, FrostSafe two-way
damper and the VentSafe vent pipe security cage.

Section 916 Page 205


Date September 2013

AURORA FIRE PUMPS


OPTION 79 - MAIN RELIEF VALVE
OPTION 80 - WASTE CONE

Supersedes Section 916 Page 205


Dated April 2012

"A" MAIN RELIEF VALVE INLET SIZE

"A" MAIN RELIEF VALVE INLET SIZE

WASTE CONE

WASTE CONE

"X" 125# ANSI FLANGE


RELIEF VALVE OUTLET

"X" 125# ANSI FLANGE


RELIEF VALVE OUTLET

Spring-Operated Main Relief Valve


125# INLET FLANGE
250# INLET FLANGE

Pilot-Operated Main Relief Valve


125# INLET FLANGE
250# INLET FLANGE

Enclosed Waste Cone

Enclosed Waste Cone

PUMP
RATING
G.P.M.

250
500

750

3000
3500
4000
4500
5000

125#
250#

1000
1250
1500
2000
2500

INLET
FLANGE
RATING

125#
250#

125#
250#

SPRING-OPERATED
MAIN RELIEF VALVE
B
C
D

5-7/8
(149)

21-1/4
(540)

6-1/8
(155)

6-7/16
(163)

22-5/8
(575)

6-5/8
(168)

8-1/2
(216)

36
(914)

9-3/8
(238)

125#
Not Available
250#

125#
Not Available
250#

NOTES:
1. All dimensions are in inches (mm) and may vary
1/4 (6).
2. Valves are available with inlet flange ratings of 125# or
250#. All waste cones have 125# flange ratings.
3. Dimensions for conventional relief valves are not affected
by flange rating.

PILOT OPERATED
WASTE CONE
MAIN RELIEF VALVE
E
F
G
X
Y

6
(152)
6
(152)

14-7/8
(378)
15-1/4
(387)

7-5/8 16-15/16
(194)
(430)
7-15/16 17-1/4
(202)
(438)

4
(102)
4-3/8
(111)
5-1/16
(129)
5-3/8
(137)

10
(254)
10
(254)

19-7/8
(505)
20-3/8
(518)

6
(152)
6-1/2
(195)

12-3/4
(324)
12-3/4
(324)
12-3/4
(324)
12-3/4
(324)

22-7/8
(581)
22-7/8
(581)
22-7/8
(581)
22-7/8
(581)

8
(203)
8-1/2
(216)
8
(203)
8-1/2
(216)

11
(279)

11
(279)
11-1/2
(292)

8
8
10

14
(356)
11-1/2
(292)

12

12
(305)

14

22-1/4
(565)

4. Relief valve discharge is intended to be piped to waste.


Refer to factory if discharge is to be piped to a line where
back pressure is present.
5. Maximum operating pressure for valves rated for 125# is
175 PSI.
6. Maximum operating pressure for valves rated for 250# is
300 PSI.

50B-4KG1 Globe
2050B-4KG1 Angle

MODEL

Fire Protection Pressure Relief Valve


E

OF

U N D E R W RIT

CANADA

BLLED BY
LA

ULC
LAB

O R AT O

RI

U.L. Listed / U.L.C. Listed


Factory Mutual Approved
Fast Opening to Maintain Steady Line Pressure
Accommodates Wide Range of Flow Rates
Closes Gradually for Surge-Free Operation
Adjustable Pressure Settings, Not Affected by
Pressure At Valve Discharge
The Cla-Val Model 50B-4KG1 Globe / 2050B-4KG1 Angle
Pressure Relief Valve is designed specifically to automatically relieve excess pressure in fire protection pumping systems. Pilot controlled, it maintains constant system pressure at the pump discharge within very close limits as
demands change. The 50B-4KG1 and 2050B-4KG1 can be
supplied with optional internal and external epoxy coating of
the main valve wetted surfaces.

U.L. Listed...............Sizes 3" thru 10"


F.M. Approved.........Sizes 3" thru 10"
U.L.C. Listed............Sizes 2 thru 10

2050B-4KG1 (Angle)

Typical Application

KOModel 2050B-4KG1
Pressure Relief Valve
(Angle Pattern)

Operation Sequence
At pump start, Cla-Val Relief Valve modulates to relieve
excess pump capacity, maintaining positive system pressure at the pump discharge.
When fire demand slows or ceases, Cla-Val Model
50B-4KG1 opens, diverting entire pump output to discharge, allowing fire pump to be stopped without causing
surging in the lines.

Fire Pump

Check Valve

(Please note that if the Model 50B-4KG1 is to be used on


a continuous duty basis to maintain fire-system pressure,
suitable back pressure must be provided on the valve to
prevent cavitation damage. Consult the factory for details.)

"Fluid Control at It's Best"


To Fire
Protection System

Specifications

Dimensions
B

Sizes Globe: 2" - 10 flanged


Angle: 2" - 10" flanged

End Details 150 and 300 ANSI B16.42


Pressure Ratings class - 175 psi Max.

= U.L., F.M. sizes

class - 300 psi Max


Water, to 180F Max.
Model 50B-4KG1 Globe

Materials Main Valve Body & Cover

Model 2050B-4KG1 Angle

Ductile Iron ASTM A-536


Naval Bronze ASTM B61
Other Material Available
Standard Main Valve Trim:
Bronze Seat, Teflon Coated
Stainless Steel Stem, Dura-Kleen Stem
Standard Pilot Control System:
Cast Bronze with
Stainless Steel trim

Adjustment Range Available in the following relief


pressure ranges:
20-200 psi (150 Class)
100-300 psi (300 Class)

We recommend providing adequate space around valve for maintenance work.


Valve Size

Optional Protective epoxy resin coating


of wetted surfaces of main
valve cast iron components
(UL listed HNFX EX2855)

The Fire Pump Pressure Relief Valve shall modulate to relieve excess
pressure in a fire protection system. It shall maintain constant pressure
in the system regardless of demand changes. It shall be pilot controlled
and back pressure shall not affect its set point. It shall be actuated by
line pressure through a pilot control system and open fast in order to
maintain steady system pressure as system demand decreases. It shall
close gradually to control surges and shall re-seat drip-tight within 5% of
its pressure setting. The main valve shall be of the hydraulically-operated, pilot-controlled, diaphragm-type, globe or angle valve. It shall have
a single, removable, teflon-coated seat, a grooved stem guided at both
ends, and a resilient disc with a rectangular cross section, being contained on 3 1/2 sides. No external packing glands shall be permitted and
the diaphragm shall not be used as a seating surface. The pilot control
shall be a direct-acting, adjustable, spring-loaded, diaphragm-type valve
designed for modulating service to permit flow when controlling pressure
exceeds spring setting. This valve shall be UL Listed and Factory Mutual
approved. It shall be the Model 50B-4KG1 (globe) or Model 2050B4KG1 (angle) Pressure Relief Valve as manufactured by Cla-Val Newport
Beach, California.
*Special Note:
The Model 50B-4KG1 Pressure Relief Valve is available with 300# ANSI
inlet flange and 150# ANSI outlet flange. This valve is used on higher
pressure systems where 300# flange connections are required, and
allows for adapting of a discharge cone (generally supplied with 150#
flange) to accommodate "atmospheric break" at relief valve discharge.
This relief valve, with 300# / 150# flanges is available on special order,
and is UNDERWRITERS LABORATORIES LISTED AND FACTORY
MUTUAL APPROVED.

Seawater Service Option

Sizes

Globe: 2" - 10" flanged


Angle: 2" - 10" flanged
Consult factory for materials and flange ratings.

2-1/2

9.38

11.00

12.50

---

---

---

---

A 150 Flanged

9.38

11.00

12.00

15.00

20.00

25.38

29.75

300 Flaanged

10.00

11.62

13.25

15.62

21.00

26.38

31.12

12.88

15.31

20.56

25.88

30.44

(inches)

300 X 150

Purchase Specifications

Specifications

Threaded Ends

3.31

4.00

4.56

5.75

7.88

10.00

11.81

12.00

12.25

12.50

13.00

14.31

16.31

18.00

1.50

1.69

2.66

3.19

4.31

5.31

9.25

Threaded Ends

4.75

5.50

6.25

---

---

---

---

E 150 Flanged

4.75

5.50

6.00

7.50

10.00

12.75

14.88

300 Flanged

15.56

5.00

5.88

6.38

7.88

10.50

13.25

Threaded Ends

3.25

4.00

4.50

---

---

---

---

F 150 Flanged

3.25

4.00

4.00

5.00

6.00

8.00

8.62

300 Flanged

3.50

4.31

4.38

5.31

6.50

8.50

9.31

6.00

6.69

7.75

7.88

8.50

9.75

13.25
250

G&H
Valve Size

50

65

80

100

150

200

Threaded Ends

238

279

318

---

---

---

---

A 150 Flanged

234

279

305

381

508

645

756

300 Flaanged

254

295

337

397

533

670

790

300 X 150

---

---

327

389

522

657

773

84

102

116

146

200

254

300

305

311

1318

330

363

414

457

38

43

65

81

109

135

235

Threaded Ends

121

140

159

---

---

---

---

E 150 Flanged

121

140

152

191

254

324

378

300 Flanged

395

((mm)

127

149

162

200

267

337

Threaded Ends

83

102

114

---

---

---

---

F 150 Flanged

83

102

102

127

152

203

219

89

109

111

135

165

216

236

152

170

197

200

216

248

337

300 Flanged
G&H

Valve Capacity
Valve Sizes in Inches:

2" 2 1/2" 3"

4"

6"

8"

10"

NFPA 20 Maximum
Recommended GPM 208 300

CLA-VAL
CLA-VAL CANADA

CLA-VAL EUROPE

CLA-VAL UK

4687 Christie Drive


Beamsville, Ontario
Canada L0R 1B4
Phone: 905-563-4963
Fax:
905-563-4040
E-Mail: sales@cla-val.ca

Chemin des Msanges 1


CH-1032 Romanel/
Lausanne, Switzerland
Phone: 41-21-643-15-55
Fax:
41-21-643-15-50
E-Mail: cla-val@cla-val.ch

Dainton House, Goods Station Road


GB - Tunbridge Wells
Kent TN1 2 DH England
Phone: 44-1892-514-400
Fax:
44-1892-543-423
E-Mail: info@cla-val.co.uk

Copyright CLA-VAL 2012 Printed in USA Specifications subject to change without notice.

500 1000 2500 5000 11000

Represented By:

PO Box 1325 Newport Beach CA 92659-0325 Phone: 949-722-4800


Fax: 949-548-5441 Web Site: cla-val.com E-mail: claval@cla-val.com

E-50B-4KG1/2050B-4KGLl (R-5/2012)

10

Section 916 Page 210


Date September 2013

AURORA FIRE PUMPS


OPTION 91 - FLOW METERING SYSTEM

Supersedes Section 916 Page 210


Dated June 2002

NOTES:
1. Accuracy is approximately 1%.
2. Flow meter is Gerand Model K Venturi type rated for 500 PSI
with butt-weld or grooved connections and for 275 PSI with
Class 150 flanged connections.
3. Proper operation requires that minimum distances of straight
pipe runs be maintained both upstream and downstream
from flowmeter. Refer to manufacturers instructions before
attempting installation.
4. Meter range is 50% to 200% of nominal rated flow. Dial is direct
reading in G.P.M. for the specified range.

GERAND VENTURI FLOW METERS


NOMINAL
BUTT-WELD
GROOVED
CLASS 150 FLANGES
FLOW RATE PIPE OPTION A
AURORA
OPTION A
AURORA
OPTION
B
AURORA
G.P.M.
SIZE NUMBER DIM. PART NUMBER NUMBER DIM. PART NUMBER NUMBER DIM. PART NUMBER
100
2.5
91MP
3
366-0377-649
91LN
4
366-0337-649
91PL
9.5
366-0244-649
150
3
91MR
3.5
366-0378-649
91LP
4.38 366-0338-649
91PM
9
366-0245-649
200
3
91MT
3.5
366-0379-649
91LR
4.38 366-0339-649
91PN
9
366-0246-649
4
91MW
3.5
366-0380-649
91LT
5
366-0340-649
91PP
9.5
366-0247-649
250
4
91NA
3.5
366-0381-649
91M
3.75 366-0154-649
91PR
9.5
366-0248-649
5
91ND
5
366-0384-649
91MB
5
366-0343-649
91RA
12
366-0251-649
300
4
91NB
3.5
366-0382-649
91LW
3.75 366-0341-649
91PT
9.5
366-0249-649
450
4
91NC
3.5
366-0383-649
91MA
3.75 366-0342-649
91PW
9.5
366-0250-649
5
91NE
5
366-0385-649
91MC
5
366-0344-649
91RB
12
366-0252-649
500
5
91NF
5
366-0386-649
91N
5
366-0155-649
91RC
12
366-0253-649
6
91NH
6
366-0388-649
91ME
6
366-0346-649
91RE
13
366-0255-649
750
5
91NG
5
366-0387-649
91MD
5
366-0345-649
91RD
12
366-0254-649
6
91NJ
6
366-0389-649
91P
6
366-0156-649
91RF
13
366-0256-649
1000
6
91NK
6
366-0390-649
91R
6
366-0157-649
91RG
13
366-0257-649
8
91NP
7
366-0392-649
91MF
7
366-0347-649
91RJ
15
366-0359-649
1250
6
91NL
6
366-0391-649
91T
6
366-0158-649
91RH
13
366-0258-649
8
91NR
7
366-0393-649
91MG
7
366-0348-649
91RK
15
366-0360-649
1500
8
91NT
7
366-0394-649
91W
7
366-0159-649
91RL
15
366-0361-649
10
91PC
8
366-0398-649
91MH
8
366-0349-649
91RR
16
366-0355-649
2000
8
91NW
7
366-0395-649
91AA
7
366-0160-649
91RM
15
366-0362-649
10
91PD
8
366-0399-649
91MJ
8
366-0350-649
91RT
16
366-0366-649
2500
8
91PA
7
366-0396-649
91AB
7
366-0161-649
91RN
15
366-0363-649
10
91PE
8
366-0400-649
91MK
8
366-0351-649
91RW
16
366-0367-649
3000
8
91PB
7
366-0397-649
91AC
7
366-0162-649
91RP
15
366-0364-649
10
91PF
8
366-0401-649
91ML
8
366-0352-649
91TA
16
366-0368-649
3500
10
91PG
8
366-0402-649
91AD
8
366-0163-649
91TB
16
366-0369-649
12
91PJ
12
366-0406-649
91MM
12
366-0355-649
91TD
21
366-0373-649
4000
10
91PH
8
366-0403-649
91AE
8
366-0164-649
91TC
16
366-0370-649
12
91PK
12
366-0407-649
91MN
12
366-0356-649
91TE
21
366-0374-649

Section 916 Page


Date July 2012

AURORA FIRE PUMPS


DIESEL ENGINE MUFFLERS

261

Supersedes Section 916 Page 261


Dated August 2011

A DIA.

MUFFLER INLET & OUTLET


SIZE 150# ANSI FLANGE
ENGINE MODEL
CATERPILLAR
3406C
3412C*, 3508C, C18*
CLARKE FIRE PROTECTION
JU4H-UF10, -UF12, -UF14, -UF20, -UF22, -UF24,
-UFAB26, -UFAEA0, -UFAEE8, -UFAEF2, -UFADJ2,
-UFADJ8
JU4R-UF09, -UF11, -UF13, -UF19, -UF21, -UF23,
-UFAEA9, -UFAEE7, -UFAEF1
JU4H-UF30, -UF32, -UF34, -UF40, -UF42, -UF 50,
-UF52, -UF54, -UF58, -UFADJG, -UFADP0, -UFADR0,
-UFADW8, -UFADY8, -UFAD5G
JU4R-UF40, -UF49, UF51 -UF53
JU6H-UF30, -UF32, -UF34, -UF 50, -UF52, -UF54,
-UF58, -UF60, -UF62, -UF62, -UF68, -UF84,
-UFAAPG, -UFAAQ8, -UFAARG, -UFAAS0,-UFAB76,
-UFABL0, -UFABL8, -UFD0, -UFD2, -UFG8, -UFM0,
-UFM2, -UFM8, -UFAD58, -UFAD88, -UFADM0,
-UFADM8, -UFADN0, -UFADNG, -UFADP8
DP6H SERIES
JW6H-UF30, -UF40, UF48
DS0H SERIES*
DR8H SERIES*
JW6H-UF50, -UF58, -UF60, -UF8, -UFAAM8,
-UFAA80, -UFADD0, -UFADB0, -UFADF0, -UFADJO,
-FAD70, -UFAD80
JU6H-UFAD98, -UFADP0, -UFADQ0, -UFADR0,
-UFADR8, -UFADS0, -UFADS8, -FADT0, -UFADW8
-UFADX8
DQ6H SERIES
DT2H SERIES*
JX6H SERIES
CUMMINS
CFP5E, CFP59, CFP7E Series
CFP83 Series
CFP9E Series
CFP11E Series
CFP15E Series
CFP23E Series
CFP30E Series
DEUTZ
DFP4-2011 Series
DFP4-2012 Series
DFP6 Series

COMMERCIAL GRADE
A
B
WGT

RESIDENTIAL GRADE
A
B
WGT

6" FLANGED
8" FLANGED

12
18

42
49

35
110

12
18

54
61

43
124

16
20

73
75

131
220

3" NPT

36

19

42

21

10

42

42

4" FLANGED

10

36

24

10

46

29

12

55

68

5" FLANGED

10

42

27

10

54

34

14

61

92

5" FLANGED

10

42

27

10

54

34

14

61

92

6" FLANGED

12

42

35

12

54

43

16

73

131

8" FLANGED

18

49

110

18

61

124

20

75

220

4" NPT, FLANGED


4" NPT, FLANGED
5" NPT, FLANGED
5" NPT, FLANGED
6" FLANGED
8" NPT, FLANGED
10" NPT, FLANGED

10
10
10
10
12
18
22

36
36
42
42
42
49
64

24
24
27
27
35
110
205

10
10
10
10
12
18
22

46
46
54
54
54
61
75

29
29
34
34
43
124
220

12
12
14
14
16
20
28

55
55
61
61
73
75
99

68
68
92
92
131
220
360

3" NPT
4" FLANGED
6" FLANGED

8
10
12

36
36
42

19
24
35

8
10
12

42
46
54

21
29
43

10
12
16

42
55
73

42
68
131

MUFFLER
INLET & OUTLET

CRITICAL GRADE
B
WGT

Section 916 Page


Date July 2012

262

AURORA FIRE PUMPS


EXHAUST FLEX CONNECTORS

Supersedes Section 916 Page 262


Dated August 2011

ENGINE MODEL
CATERPILLAR
3406C
3412C*, 3508C, C18*
CLARKE FIRE PROTECTION
JU4H-UF10, -UF12, -UF14, -UF20, -UF22,
-UF24, -UFAB26, -UFAEA0, -UFAEE8, -UFAEF2,
-UFADJ2, -UFADJ8
JU4R-UF09, -UF11, -UF13, -UF19, -UF21,
-UF23, -UFAEA9, -UFAEE7, -UFAEF1
JU4H-UF30, -UF32, -UF34, -UF40, -UF42, -UF
50, -UF52, -UF54, -UF58, -UFADJG, -UFADP0,
-UFADR0, -UFADW8, -UFADY8, -UFAD5G
JU4R-UF40, -UF49, UF51 -UF53
JU6H-UF30, -UF32, -UF34, -UF 50, -UF52,
-UF54, -UF58, -UF60, -UF62, -UF62, -UF68,
-UF84, -UFAAPG, -UFAAQ8, -UFAARG,
-UFAAS0,-UFAB76, -UFABL0, -UFABL8,
-UFD0, -UFD2, -UFG8, -UFM0, -UFM2, -UFM8,
-UFAD58, -UFAD88, -UFADM0, -UFADM8,
-UFADN0, -UFADNG, -UFADP8
DP6H SERIES
JW6H-UF30, -UF40, UF48
DS0H SERIES*
DR8H SERIES*
JW6H-UF50, -UF58, -UF60, -UF8, -UFAAM8,
-UFAA80, -UFADD0, -UFADB0, -UFADF0,
-UFADJO, -FAD70, -UFAD80
JU6H-UFAD98, -UFADP0, -UFADQ0, -UFADR0,
-UFADR8, -UFADS0, -UFADS8, -FADT0,
-UFADW8 -UFADX8
DQ6H SERIES
DT2H SERIES*
JX6H SERIES
CUMMINS
CFP5E, CFP59, CFP7E Series
CFP83 Series
CFP9E Series
CFP11E Series
CFP15E Series
CFP23E Series
CFP30E Series
DEUTZ
DFP4-2011 Series
DFP4-2012 Series
DFP6 Series

MUFFLER
CONNECTION
SIZE

FLEX
CONNECTOR
STYLE

6" FLANGED
8" FLANGED

B
B

3" NPT

4 FLANGED

ANSI FLANGE
BY AURORA
FLEX CONNECTOR
BY DIESEL ENGINE
MANUFACTURER
STYLE A

FLANGE TO FIT
DIESEL ENGINE
EXHAUST OUTLET
5 FLANGED

STYLE B*

5" FLANGE

6" FLANGED

8" FLANGED

3" NPT, FLANGED, CUFF


4" NPT, FLANGED, CUFF
4" NPT, FLANGED, CUFF
5" NPT, FLANGED, CUFF
6" FLANGED
6" FLANGED
6" FLANGED

A, B
A, B
A, B
A,B
B
B
B

3" NPT
4" FLANGED
6" FLANGED

A
B
B

*FLANGED FLEX CONNECTOR PROVIDED BY DIESEL


ENGINE MANUFACTURER. NO ADDITIONAL FLEX
CONNECTOR OR ADAPTOR FITTING IS REQUIRED OR
PROVIDED BY AURORA.

Section 916 Page


Date June 2010

AURORA FIRE PUMPS

256

SINGLE WALL FUEL TANKS WITH FITTINGS

Supersedes Section 916 Page 256


Dated April 2009
19

11

17

DIESEL FUEL TANKS:


1. Tanks are constructed and labeled in accordance with UL-142.
2. Fittings shown are consistent with N.F.P.A. 30 and UL-142.
3. Tank to be pitched toward drain 1/4 per foot with outlet on the same elevation
as engine fuel pump. Means of elevating tank (by others) may be required.
4. Usable tank volume is total capacity less 5% for sump and 5% for expansion.

16
15

10

18

21

20
21
5

6"

"A" DIA.

12
22
14
L
13

2" NPT CPLGS. FOR


CUST. FURN. LEGS

4
B

FUEL SUPPLY
14

FUEL RETURN

NOMINAL
USABLE
TANK SIZE
VOLUME
IN GALLONS IN GALLONS
119
105

24 (609)

61 (1548)

6 (152)

6 (152)

6 (152)

19 (482)

37 (939)

14 (355)

3 (76)

187

165

30 (761)

61 (1548)

6 (152)

6 (152)

6 (152)

19 (482)

37 (939)

16 (406)

3 (76)

300

270

38 (964)

61 (1548)

6 (152)

6 (152)

6 (152)

19 (482)

37 (939)

23 (584)

3-3/4 (95)

359

320

36 (914)

73 (1853)

6 (152)

6 (152)

6 (152)

31 (787) 44 (1117)

23 (584)

3-3/4 (95)

572

515

48 (1218)

73 (1853)

6 (152)

6 (152)

6 (152)

31 (787) 44 (1117)

30 (761)

4-3/4 (121)

849

766

64 (1626)

61 (1548)

6 (152)

6 (152)

6 (152)

19 (482) 44 (1117)

30 (761)

4-3/4 (121)

1100

993

64 (1626)

79 (2007)

6 (152)

6 (152)

6 (152)

37 (940) 44 (1117)

30 (761)

4-3/4 (121)

ITEM NO.
20

COMPONENTS FURNISHED BY OTHERS


QTY. REQD
DESCRIPTION
1
Z Diameter Piping for Vent

21

1/2 Tubing and Fittings or


1/2 Black Pipe

22

3/4 Tubing and Fittings or


3/4 Black Pipe

NOTES
1. All dimensions are in inches and may vary 1/4.
2. Components shown are shipped loose for field assembly.
3. Illustration is for component identification only. Actual installation must meet
local codes and all applicable standards.
4. Item 10 may consist of a combination of fittings.
5. Refer to Section 916 page 259 for details of Aurora-furnished components.
6. Items 11 & 17 not required for 515 gallon tanks.

COMPONENTS FURNISHED BY AURORA PUMP


ITEM NO.
QTY. REQD
DESCRIPTION
1
1
2 NPT Lockable Fuel Cap
2
1
2 Screened Tank Vent
3
1
Fuel Gauge 1-1/2 NPT
4
1
1 NPT Drain Plug
5
1
2 NPT Pipe Plug
7
1
1/2 Tee
8
1
1/2 Close Nipple
9
1
2 Fuel Fill Pipe
10
1
Z x Z x 2 Tee
11
1
Z Coupling
12
1
3/4 NPT Lockable Fuel Valve
13
1
3/4 Close Nipple
14
2
Fuel Hoses for Supply & Return
(Furnished by Engine Mfr.)

15
16
17
18
19

1
1
1
1
1

2 Street Elbow
Z x Z x 2 Tee
Z Close Nipple
2 x 6 Nipple
Z Emergency Vent

AURORA FIRE PUMPS


FITTINGS FOR DIESEL FUEL TANKS
T NKS
TA

Section 916 Page 259


Date April 2009
Supersedes Section 916 Page 259
Dated November 2000

NOTES
1. All dimensions are in inches and may vary 1/4".
2. Components shown are shipped loose for field assembly.
3. Illustration is for component identification only. Actual installation must meet
local codes and all applicable standards.
4. Refer to Section 916 pages 255 through 258 for the location and applicability
of each component shown above

AURORA MODEL 481 & 485 PUMPS


DIESEL BATTERIES, RACKS, & CABLES

Section 916 Page


Date June 2002

251

Supersedes Section 916 Page 251


Dated July 2001

POS

NOTES:

11
(279)

1. Dimensions are in inches (mm) and may vary 1/4" (6).


2. Batteries are 12 volt, lead-acid type D-8D, approximately
95 Ibs. each, dry.
3. Batteries are shipped dry. Electrolyte (approx.19 quarts
per battery) must be procured locally.
4. Refer to Section 916 page 252 for exact number of
batteries & cables to be furnished based on the
diesel engine manufacturer and model used.
5. Battery racks are fabricated steel, approximately
20 Ibs. each.
6. Each rack holds 2 batteries. Racks are not to be stacked.

NEG
POS

11
(279)
NEG

20.75
(527)

BATTERY

16.25
(419)
5.5 (140)
20.5
(521)

NOTES:
1. All cables are SAE J55BA type SGT with
tensile attachment of 700-800 lbs.
2. Positive & negative cables 60" (1524) long are
2/0 gauge; positive & negative cables 80"
(2032) long are 3/0 gauge.
3. Terminal clamps have steel reinforced
inserts.
4. Not all cable types are required for every
engine. Refer to Section 916 page 252 for
cable applicability.

BATTERY
RACK

23.5
(597)

POSITIVE CABLE

NEGATIVE CABLE

INTERCONNECTING
CABLE

60" or 80"
(1524 or 2032)
17/32 DIA. HOLE (TYPICAL)
60" or 80"
(1524 or 2032)

12"
(305)

Section 916 Page 252


Date October 2006

AURORA MODEL 481 & 485 PUMPS


DIESEL BATTERY CABLE DIAGRAMS

Supersedes Section 916 Page 252


Dated June 2002

12 VOLT SYSTEM
POS

REQUIRED COMPONENTS

ENGINE APPLICABILITY

12V
NEG
POS

12V

(1)
(2)
(2)
(2)

BATTERY RACK
BATTERIES
POSITIVE CABLES
NEGATIVE CABLES

NEG

CUMMINS:
ALL CFP MODELS
CLARKE:
ALL JU4H MODELS
ALL JU64 MODELS
ALL JW6H MODELS
EDWARDS:
ALL MODELS

NOTES:
1. Clarke VMFP, JU4H & JU6H Engines require cable sets of different lengths. On these engine models, a 2/0 guage
postive and negative cable set 60 (1524 mm) long, and a 3/0 guage positive and negativecable set 80 (2032 mm) long
are furnished.
2. Refer to Section 916, Page 251 for details of batteries, racks and cables.

POS

NEG

POS

24V

24 VOLT SYSTEM
REQUIRED COMPONENTS
(2)
(4)
(2)
(2)
(2)

NEG

POS

NEG
POS

NEG

24V

BATTERY RACKS
BATTERIES
POSITIVE CABLES
NEGATIVE CABLES
INTERCONNECTING
CABLES

ENGINE APPLICABILITY
CLARKE:
ALL JX6H MODELS
CATERPILLAR:
ALL MODELS

Project:
Customer:
Engineer:
Pump Manufacturer:






 
  !  

Contents:



  
 


 

  

NOTE: The drawings included in this package are for controllers covered under our standard
offering. Actual AS BUILT drawings may differ from what is shown in this package

-XO\2012

Submittal Data Sheet


GPD Diesel Fire Pump Controller

Built to NFPA 20 (latest edition)


Standard,
Listings,
Approvals and
Certifications

Enclosure

Underwriters Laboratory (UL)


FM Global
New York City
Optional
CE Mark
Protection Rating
Standard: NEMA 2 (IP31)
Optional
NEMA 12
NEMA 3
NEMA 3R
NEMA 4
Accessories
Bottom entry gland plate
Wall mounting lugs
Keylock handle
AC
DC

General

Grounding system
Battery chargers

UL218 - Fire pump controllers


CSA C22.2 No. 14 Industrial Control Equipment
Class 1321/1323
Accepted for use in the City of New York by the Department of Buildings
Various EN, IEC & CEE directives and standards

NEMA 4X-304 sst painted


NEMA 4X-304 sst brushed finish
NEMA 4X-316 sst painted
NEMA 4X-316 sst brushed finish
Paint Specifications
Red RAL3002
Powder coating
Glossy textured finish
120V/1ph/60hz
208V to 240V/1ph/50-60hz
12VDC
24VDC
Negative
Two independent fully automatic
10A continuous charge
500mA trickle charge

Electrical
Readings

Battery 1 & Battery 2 voltage


Battery 1 & Battery 2 charging amperage
Charging mode

Pressure
Readings

Continuous system pressure display


Cut-in and Cut-out pressure settings

Pressure and
Event
Recorder

Pressure
Sensing

july 2012

IP54
IP55
IP65
IP66

Pressure readings with date stamp


Event recording with date stamp
Under regular maintained operation, events can be stored in memory for up to 5 years
Data viewable on operator interface display screen
Downloadble by USB port to external memory device
Pressure transducer and run test solenoid valve assembly for fresh water application
Pressure sensing connection 1/2 Female NPT
Drain connection 3/8
Rated for 0-500PSI working pressure (calibrated at 0-300psi)
Externally mounted with protective cover

Submittal Data Sheet


GPD Diesel Fire Pump Controller

Audible Alarm

4 alarm bell - 85 dB at 10ft. (3m)

Visual and
Audible Alarms

Visual only
Engine run
Periodic test
Main switch in AUTO
Main switch in HAND
Pump room temperature (F or C)
Visual and Audible
Overspeed
Battery #1 & battery #2 failure
Low oil pressure
Charger #1 & charger #2 failure
High engine temperature
AC Power available
Fail to start
Low pump room temperature
High fuel level
System overpressure

Remote Alarm
Contacts

SPDT-8A-250V.AC
Engine run (2)
Common controller trouble
Charger #1 and/or #2 failure
Pressure line failure
Common engine trouble
Battery #1 and/or #2 failure
Overspeed
High engine temperature
Fail to start
DC Failure
Fail when running
Low oil pressure
Fuel injection malfunction* Loss of continuity (starter) #1 and/or #2
ECM selector switch in alternate position**
Common pump room alarm
Low fuel level
Low suction pressure
Water reservoir low
High Fuel level
Low pump room temperature
Water reservoir empty
Fuel tank leak
High pump room temperature
AC failure
H-O-A selector switch in AUTO
H-O-A selector switch in OFF or HAND

ViZi Touch
Operator
Interface

Cranking cycle
Main switch in OFF

Low fuel level


Water reservoir low
Fuel tank leak
Fail when running

Embedded microcomputer with software PLC logic


4.2 color touch screen (HMI technology)
Upgradable software
Expandable storage
Multi-language

* Applicable to electronic engines only.


** Applicable to electronic engines only. Alarms when ECM selector switch on the engine is in alternate mode.

july 2012

Submittal Data Sheet


GPD Diesel Fire Pump Controller

HAND-OFF-AUTO
Behind lockable and breakable cover
Start on pressure drop
Remote start signal from automatic device
Crank 1 and Crank 2 start pushbuttons
Run test pushbutton
Deluge valve start
Remote start from manual device
6 consecutive cycle attempts
3 X 15s crank from battery 1 or 2 alternatively
15s rest in between each crank attempt
Manual with Stop pushbutton
Automatic after expiration of minimum run timer ***
Minimum run timer ***(off delay)
Field Adjustable & Visual Countdown Sequential start timer (on delay)
Periodic test timer
Pressure
Non-pressure
Visual Indication
Automatic
Non-automatic

Selector Switch
Automatic Start

Manual Start

Operation

Crank Cycle
Stopping
Timers
Actuation
Mode

*** Automatic shutdown shall be approved by the AHJ.

Alarm &
Shutdown
Schedule

High Coolant
Low Oil Pressure
Overspeed

Automatic Start

Manual Start Or Remote Start

Run Test or Periodic test

Alarm only
Alarm only
Shutdown

Alarm only
Alarm Only
Shutdown

Shutdown
Shutdown
Shutdown

Wall Mount

Floor Mount

Dimensions in inches (mm)

Approx. Shipping Weight in


Lbs (kg)

27-5/8"h x 23-3/4"w x 9"d


(700 x 600 x228 )

120 (55)

july 2012

Dimensions in inches (mm)

50"h x 23-3/4"w x 9"d


(1220 x 600 x 228)

Approx. Shipping Weight in


Lbs (kg)
145 (67)

Submittal Data Sheet


GPD Diesel Fire Pump Controller

A1
A2
A3
A4
A5
A6
A7
A8
A9
A11
A12
Ax
B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B11
B12
B13
Bx
C5
C6
C7
C8
C9
C13

Periodic test alarm contact (Form C-SPDT)


Overspeed alarm contact (Form C-SPDT)
Low oil pressure alarm contact (Form C-SPDT)
High coolant temperature alarm contact
(Form C-SPDT)
Failure to start alarm contacts alarm contact
(Form C-SPDT)
Battery 1 & 2 failure alarm contact
(2 x Form C-SPDT)
Charger 1 & 2 failure alarm contact
(2 x Form C-SPDT)
AC failure alarm contact (Form C-SPDT)
System overpressure alarm contact
(For engines with PLD) (Form C-SPDT)
Extra controller trouble alarm contact
(Form C-SPDT)
Extra engine trouble alarm contact
(Form C-SPDT)
Additional engine alarm contact alarm contact
(Form C-SPDT) (specify function)
Low fuel level alarm contact (Form C-SPDT)
Water reservoir level low alarm contact
(Form C-SPDT)
Water reservoir empty alarm contact
(Form C-SPDT)
Low pump room temperature alarm contact
(Form C-SPDT)
High fuel level alarm contact (Form C-SPDT)
Low system (discharge) pressure alarm contact
(Form C-SPDT)
Low suction pressure alarm contact
(Form C-SPDT)
Pump on demand alarm contact (Form C-SPDT)
Fuel tank leak alarm contact (Form C-SPDT)
Main relief valve open alarm contact
(Form C-SPDT)
Flow meter loop valve open alarm contact
(Form C-SPDT)
Water reservoir level high alarm contact
(Form C-SPDT)
High pump room temperature alarm contact
(Form C-SPDT)
Additional pump room alarm contact
(Form C-SPDT) (specify function)
CE Mark with factory certificate
Nickel Cadmium battery chargers
Engine block heater circuit (same voltage as
battery charger primary)
Foam pump application w/o pressure transducer
and run test solenoid valve
Non pressure actuated controller w/o pressure
transducer and run test solenoid valve
Louver activation circuit (battery power specific)

C14
C15
C16
C17
C19
D4
D6
D7A
D7B
D8A
D8B
D9A
D9B
D9C
D11

D11A
D12
D17
D18
D19
D25
D25A
D25B
D25C
D25D
D26
D26A
D27
D28
D29
D30
D31
D32
D32A
D33

Delayed automatic start on AC power failure


(factory set at 15 minutes)
Low zone pump control function
Medium zone pump control function
High zone pump control function
Lockout/interlock circuit from equipment installed
inside the pump room
Pressure transducer and run test solenoid valve
for fresh water rated for 0-500 PSI (for calibration
purposes only)
Pressure transducer and run test solenoid valve
for sea water rated for 0-500 PSI
Low fuel level float switch supplied as separate
item (1.1/4)
Low fuel level float switch supplied as separate
item (1.1/2)
High fuel level float switch supplied as separate
item (1.1/4)
High fuel level float switch supplied as separate
item (1.1/2)
Anti-condensation heater & thermostat
Anti-condensation heater & humidistat
Anti-condensation heater & thermostat &
humidistat
Low suction pressure transducer for fresh water
rated for 0-300PSI with visual indication and alarm
contact
Low suction pressure transducer for sea water
rated for 0-300PSI with visual indication and alarm
contact
Tropicalization
French labeling
Spanish labeling
Other languages
Mounting stand
Mounting stand SST- 304 painted
Mounting stand SST- 304 brushed finish
Mounting stand SST- 316 painted
Mounting stand SST- 316 brushed finish
Combined low and high fuel level float switch
(1- 1/4)
Combined low and high fuel level float switch
(1-1/2)
Fuel level probe (1-1/4) Level indication
Field programmable I/O board - 8 input / 5 output
Field programmable I/O board - 8 input / 10 output
Redundant pressure transducer for fresh water
rated for 0-500PSI (calibrated at 0-300PSI)
Redundant pressure transducer for sea water
rated for 0-500PSI (calibrated at 0-300PSI)
Modbus RTU provision
Modbus TCP/IP provision
Window kit for operator interface

Note: Options chosen from this page are not electrically


represented on the wiring schematics in this submittal
package.

july 2012

Submittal Data Sheet


GPD Diesel Fire Pump Controller

ViZiTouch Operator Interface


3

7
8

10

1
12

11

13

1 - Power LED
2 - Color touch screen
3 - Alarm LED
4 - HOME page button
5 - ALARM page button
6 - CONFIGURATION page button
7 - HISTORY page button

july 2012

14

8 - USB port
9 - CRANK 1 button
10 - CRANK 2 button
11 - Contextual navigation pad
12 - STOP button
13 - RUN TEST button
14- HELP button

qwertyuiopasdfghjklzxcvbnmqwertyui
opasdfghjklzxcvbnmqwertyuiopasdfgh
jklzxcvbnmqwertyuiopasdfghjklzxcvb
JOCKEY PUMP
nmqwertyuiopasdfghjklzxcvbnmqwer
SparePartListBook
Aurora
Vertical Multistage In-Line
ControllerModel:GPD
Model : PVM 10 - 14
tyuiopasdfghjklzxcvbnmqwertyuiopas
dfghjklzxcvbnmqwertyuiopasdfghjklzx
cvbnmqwertyuiopasdfghjklzxcvbnmq
wertyuiopasdfghjklzxcvbnmqwertyuio
pasdfghjklzxcvbnmqwertyuiopasdfghj
klzxcvbnmqwertyuiopasdfghjklzxcvbn
mqwertyuiopasdfghjklzxcvbnmqwerty
uiopasdfghjklzxcvbnmqwertyuiopasdf
ghjklzxcvbnmqwertyuiopasdfghjklzxc
vbnmqwertyuiopasdfghjklzxcvbnmrty
uiopasdfghjklzxcvbnmqwertyuiopasdf
ghjklzxcvbnmqwertyuiopasdfghjklzxc

PERTAMINABALIKPAPANDEPOTPANGKALANBUN,
DEPOTPULANGPISAU,DPPUJUWATA
COAL
FIRED POWER STATION,BABELAN

Preparedby:PT.RodaNurmala

AURORA
PVM(X) SERIES

Certified to
NSF/ANSI 61 & 372

PVMX1
through
PVMX33 Only

VERTICAL MULTISTAGE PUMPS


60Hz Catalog

w w w.AuroraPump.com

Customer
:
Project name : Default
Item number
Service
Quantity
Quote number

: 012
:
:1
: 259241

Pump Performance Datasheet


Encompass 2.0 - 15.1.1.0

Size
Stages
Based on curve number
Date last saved

Operating Conditions

: PVM(X)10-14
: 14
: PVM(X)10-14-50Hz
: 13 May 2015 2:10 AM

Liquid

Flow, rated
Differential head / pressure, rated (requested)
Differential head / pressure, rated (actual)
Suction pressure, rated / max
NPSH available, rated
Frequency
Performance

: 12.00 m3/h
: 100.0 m
: 101.1 m
: 0.00 / 0.00 psi.g
: Ample
: 50 Hz

Speed, rated
Impeller diameter, rated
Impeller diameter, maximum
Impeller diameter, minimum
Efficiency
NPSH required / margin required
nq (imp. eye flow) / S (imp. eye flow)
Minimum Continuous Stable Flow
Head, maximum, rated diameter
Head rise to shutoff
Flow, best eff. point (BEP)
Flow ratio (rated / BEP)
Diameter ratio (rated / max)
Head ratio (rated dia / max dia)
Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-2010]
Selection status

: 2,915 rpm
: PVM(I/X)10-14
: PVM(I/X)10-14
: PVM(I/X)10-14
: 65.77 %
: - / 0.00 ft
: N/A Metric units
: 4.73 m3/h
: 147.3 m
: 41.62 %
: 10.37 m3/h
: 115.67 %
: 100.00 %
: 100.00 %
: 1.00 / 1.00 / 1.00 / 1.00
: Acceptable

Liquid type
Additional liquid description
Solids diameter, max
Solids concentration, by volume
Temperature, max
Fluid density, rated / max
Viscosity, rated
Vapor pressure, rated
Material

: Water
:
: 0.00 in
: 0.00 %
: 68.00 deg F
: 0.999 / 0.999 SG
: 1.00 cP
: 0.34 psi.a

Material selected
Pressure Data

: Not specified

Maximum working pressure


Maximum allowable working pressure
Maximum allowable suction pressure
Hydrostatic test pressure
Driver & Power Data

: 209.0 psi.g
: N/A
: N/A
: N/A

Driver sizing specification


Margin over specification
Service factor
Power, hydraulic
Power, rated
Power, maximum, rated diameter
Minimum recommended motor rating

: Rated power
: 0.00 %
: 1.15 (used)
: 4.42 hp
: 6.72 hp
: 6.73 hp
: 10.00 hp / 7.46 kW (Fixed)

8
Power

Power - hp

6
4
2
0
200

Minimum Continuous Stable Flow


Preferred operating region

180
160

49

140

56

61

64

PVM(I/X)10-14

66

67

Head - m

120

67

66
64

100
80
60
40
20
0

7
8
Flow - m3/h

PT RODA NURMALA
,

10

11

12

13

14

PHONE: FAX:

15

Encompass 2.0 - 15.1.1.0

General Arrangement Drawing


Pump Data
Model

PVM(X)10-14

Stages

14

Flow

53

Head

328

Rotation

Right

Liquid Type

Water

Suc/Disch Size

2.5

Actual Pressure

47.28 psi.g

Ambient Temperature

68.00 deg F

Max Ambient Temperature

32.00 deg F

Liquid Temperature

68.00 deg F

Liquid Temp Rating

68.00 deg F

Connection Suc/Disch

250

Motor Data
Power

10.00 hp

Phase

Hertz

50 Hz

Volts

190/380

RPM

2,915 rpm

Frame Size

254TCZ

Efficiency Rating

premium

Enclosure

TEFC

Pump Material Data


Pump Material

stainless steel

Elastomer

EPDM

Estimated Weights

31.30

20.03

12.94

3.75

55.08

12.94

Pump

404.9 lb

Total

404.9 lb

Additional Options
Certification Correct

NOTES:
All dimensions are in inches.
Dimensions shown may vary 1/4" (6mm) due to normal manufacturing tolerances.
Not for construction, installation, or application purposes unless certified.
Measurements represent the largest number possible for each model using standard efficiency motors.

Customer
Customer Quote # 259241
Job Name

Default

Market

Quote Item #

012

Quote Date

21 Feb 2013

PVM(X)
VERTICAL MULTISTAGE CENTRIFUGAL PUMPS
PUMP CONSTRUCTION
POS.

NAME

MATERIAL

PVM 1, 3, 5, 10, 15, 20

PVMX 1, 3, 5, 10, 15, 20

36

Pump Head

Cast Iron

EN-GJL-200 ; ASTM 25B

EN-GJS-450-10 ; ASTM
65-45-12

56

Pump Head Cover

Stainless Steel

1.4401 ; AISI 316

18

Impeller

Stainless Steel

1.4301 ; AISI 304

1.4401 ; AISI 316

37

Shaft

Stainless Steel

1.4057 ; AISI 431

1.4401 ; AISI 316

48

Outer Sleeve

Stainless Steel

1.4301 ; AISI 304

1.4401 ; AISI 316

82

O-Ring for Outer


Sleeve

EPDM

12

Chamber

Stainless Steel

1.4301 ; AISI 304

1.4401 ; AISI 316

24

Neck Ring

PTFE

59

Base

Cast Iron

EN-GJL-200 ; ASTM 25B

Stainless Steel

1.4401 ; AISI 316

62

Base Plate

Cast Iron

EN-GJL-200 ; ASTM 25B

44

Coupling

Fe-Cu-C

SINT C11 ; MPIF FC0525

SINT C11 ; MPIF FC0525

57

Mechanical Seal

Cartridge Type

PVM 1, 3, 5, 10, 15, 20

PVMX 1, 3, 5, 10, 15, 20

Model

JP

Jockey Pump Controller


Standard Features:
Solid state controls with digital iPD+
operator interface
All adjustments on door front
Visual indicators
Manual motor run
Automatic motor run
System pressure
Automatic mode
Off mode
Motor overload
Pump start counter
Elapsed time meter (hours / non-resettable)
Timers
Minimum run period timer
Sequential start timer
Operators
OFF-AUTO pushbutton
Start and stop pushbuttons
NEMA 2 enclosure
Pressure transducer
Fuseless magnetic motor starter
The model JP jockey pump controllers are specifically
designed to control jockey pumps in order to
maintain the desired water pressure in fire pump
serviced systems. A jockey pump installation prevents
unnecessary starting of the fire pump due to small leaks
in the sprinkler system piping.
The model JP jockey pump controller is supplied with the
front door mounted, solid state controls with digital iPD+
operator interface. The iPD+ allows the user to set and adjust
all parameters required such as start and stop pressures,
ON or OFF timers and units of measure (psi, bar, kPA, feet of
head, meter of head) without having to open the controller
door. The iPD+ also continuously displays the system
pressure and the start and stop pressure settings. LED visual
indications include manual motor run, automatic motor
run, system pressure above stop pressure setting, system
pressure in-between start and stop pressure setting and
system pressure below start pressure setting.

Full voltage across the line starter


Solid State Controls with Digital
Operator Interface

The standard power circuit consists of a horsepower


rated disconnect switch, a thermo-magnetic motor
protector and a motor contactor for across the line
full voltage starting. Consult factory for other types of
motor protection or starting methods available.
Individual models are specific to the voltage available
on site:
JP1: 120 V / Hp (kW) / single phase / 60Hz
JP2: 220 to 240 V / Hp (kW) / single phase / 50 or 60Hz
JP3: 208 to 600 V / Hp (kW) / three phase / 50 or 60Hz
N.Y.C.
APPROVED
2015-2016

Model

JP

Operator Interface
6

9
6

1 - High luminosity four digit digital display


2 - System status diagnostic LEDs for:
i. Green: system pressure at or above cut-out
value
ii. Yellow: system pressure between cut-in
and cut-out
iii. Red: system pressure at or below cut-in value
3 - Motor run LEDs (manual start or automatic start)
4 - Start and stop pushbuttons
5 - Navigation keypad

6 - OFF-AUTO position pushbutton and visual


indication (LED)
7 - Horsepower rated door interlocked rotary
type disconnect switch
8 - Fuseless magnetic motor starter with
thermo-magnetic motor protector and
horsepower rated contactor
9 - Pressure transducer with 0-600psi
range and 316 stainless steel construction

HOW TO ORDER: JPx -


V / HP / Ph / Hz
Ex.: JP3 - 208 /
2 / 3 / 60

Americas
Tornatech Inc.
Head Office

USA Sales
Representatives

7075, Pl. Robert-Joncas


Suite # 132
Montreal, Canada
H4M 2Z2
Tel.: + 1 514 334 0523
+ 1 800 363 8448
Fax: + 1 514 334 5448

Toll Free: + 1 800 363-8448


Cincinnati, Ohio
Cell: + 1 513 307 6766
Birmingham, Alabama
Cell: + 1 205 902 9331

Latin America
Sales Representative

Europe

Middle East

Asia

Tornatech S.P.R.L.

Tornatech FZE

Tornatech Pte Ltd.

Avenue Sabin 3
1300 Wavre
Belgium
Tel.: + 32 (0) 10 84 40 01
Fax: + 32 (0) 10 24 75 05

Warehouse RA08CC04
Jebel Ali North
PO Box 18435
Dubai,
United Arab Emirates
Tel.: + 971 (0)4 887 0615
Fax.: + 971 (0)4 887 0604

3 Soon Lee Street #05-33


Pioneer Junction
Singapore 627606
Tel.: + 65 6795 8114

+ 65 6795 7823
Fax: + 65 6795 3201

Tel.: + 1 514 334 0523


Cell: + 1 514 945 4067
JP-BRO-002/E Rev.9

March 2015 Printed in Canada

tornatech.com

Project:
Customer:
(QJLQHHU
3XPS0DQXIDFWXUHU

Technical Data Submittal Document


Model JP3
Across the Line Start
Jockey Pump Controller

Contents:
'DWD6KHHWV
'LPHQVLRQDO'DWD
:LULQJ6FKHPDWLFV
)LHOG&RQQHFWLRQV

1RWH7KHGUDZLQJVLQFOXGHGLQWKLVSDFNDJHDUHIRUFRQWUROOHUVFRYHUHGXQGHURXUVWDQGDUGRIIHULQJ

$FWXDO$6%8,/7GUDZLQJVPD\GLIIHUIURPZKDWLVVKRZQLQWKLVSDFNDJH

March 2015

Technical Data
Model JP3 Jockey Pump Controller

6WDUWLQJ0HWKRG Full Voltage


Across the line (Direct on line)
7\SLFDO9ROWDJH$SSOLHGDW6WDUW100%
Inrush Current:[QRUPDOORDGFXUUHQW
6WDUWLQJ7RUTXH100%
Motor Type: Across the line (Direct on line)
1RRI&RQWDFWRUV1 at 100% of horsepower
0LQDPSDFLW\RIPRWRUFRQGXFWRUVDW[RI)XOOORDG&XUUHQW )/&
Underwriters Laboratory (UL) UL508A - Industrial Pump Controllers
/LVWLQJ

CSA

CSA C22.2 No. 14 Industrial Control Equipment

New York City

Accepted for use in the City of New York by the Department of Buildings

Optional

CE Mark

Various EN, IEC & CEE directives and standards

3URWHFWLRQ5DWLQJ

Standard: NEMA 2 (IP31)

Enclosure

Optional
NEMA 12
NEMA 3
NEMA 3R
NEMA 4
Accessories
:DOOPRXQWLQJOXJV [

March 2015

NEMA 4X-304 sst painted


1(0$;VVWEUXVKHGQLVK
NEMA 4X-316 sst painted
1(0$;VVWEUXVKHGQLVK
3DLQW6SHFLFDWLRQV
5HG5$/
3RZGHUFRDWLQJ
*ORVV\WH[WXUHGQLVK

Technical Data
Model JP3 Jockey Pump Controller

)XVHOHVV0RWRU
Starter

0DLQGLVFRQQHFWURWDU\W\SHGRRULQWHUORFNHG
7KHUPRPDJQHWLFPRWRUSURWHFWRU
&RQWDFWRU

Control Circuit

9$&

iPD+ Operator
,QWHUIDFH

6ROLGVWDWHFRQWUROV
$OODGMXVWPHQWVRQGRRUIURQW
1DYLJDWLRQSXVKEXWWRQV

3UHVVXUH6HQVLQJ

3UHVVXUHWUDQVGXFHUIRUIUHVKZDWHUDSSOLFDWLRQVWDLQOHVVVWHHOFRQVWUXFWLRQ
5DWHGIRUSVLZRUNLQJSUHVVXUH
3UHVVXUHVHQVLQJOLQHFRQQHFWLRQ0DOH137

Visual Indications

0DQXDOPRWRUVWDUWUXQ/('
$XWRPDWLFPRWRUVWDUWUXQ/('
0RWRURYHUORDG
3UHVVXUHUHDGLQJ
6WDUWSUHVVXUH
6WRSSUHVVXUH
6\VWHPSUHVVXUH
6\VWHPSUHVVXUHGLDJQRVWLF/('V
*UHHQV\VWHPSUHVVXUHDWRUDERYHVWRSSUHVVXUH
<HOORZV\VWHPSUHVVXUHEHWZHHQVWDUWDQGVWRSSUHVVXUH
5HGV\VWHPSUHVVXUHDWRUEHORZVWDUWSUHVVXUH
$872PRGH
2))PRGH

Timers

0LQLPXPUXQWLPHU RIIGHOD\
'HOD\VWDUWWLPHU RQGHOD\
9LVXDOFRXQWGRZQ

Counters

3XPSVWDUWFRXQWHU
(ODSVHGWLPHUPHWHU KRXUVQRQUHVHWWDEOH

Operators

2))$872SXVKEXWWRQ
6WDUWDQG6WRSSXVKEXWWRQ

Operation

March 2015

Automatic Start

Start on pressure drop

Manual Start

Start pushbutton

Stopping

Stop pushbutton

7LPHUV

)LHOGDGMXVWDEOH 
visual countdown

0LQLPXPUXQWLPHU RIIGHOD\
'HOD\VWDUWWLPHU RQGHOD\

Technical Data
Model JP3 Jockey Pump Controller
A5

Motor run alarm contact

L01

2WKHUODQJXDJHDQG(QJOLVK ELOLQJXDO

A6

Loss of power alarm contact

L02

French

A7

2YHUORDGRUVKRUWFLUFXLWDODUPFRQWDFW

L03

Spanish

D12

&(0DUNFZH[WHUQDOO\PRXQWHGZHWWHGSDUWV

L04

*HUPDQ

D13A

([WHUQDOO\PRXQWHGZHWWHGSDUWV

L05

Italian

D14

([SRUWSDFNLQJIRUFRQWUROOHU

L06

Polish

D18

Audible alarm

L07

Romanian

D19

Anti-condensation heater and thermostat

L08

Hungarian

D20

Anti-condensation heater and humidistat

L09

Slovak

D21

7URSLFDOL]DWLRQ

L10

Croatian

D22

3KDVHUHYHUVDOIDLOXUHSLORWOLJKWDQGDODUPFRQWDFW

L11

&]HFK

D23

Controller power healthy pilot light and alarm contact

L12

Portuguese

D24

Pump failure via current sensing relay with pilot light and dry
alarm contact

L13

Dutch

L14

Russian

L15

7XUNLVK

L16

Swedish

L17

Bulgarian

L18

7KDL

L19

Indonesian

L20

Slovenian

D25

/RZ]RQHSXPSFRQWUROIXQFWLRQ

D26

0LG]RQHSXPSFRQWUROIXQFWLRQ

D27

+LJK]RQHSXPSFRQWUROIXQFWLRQ

D28

Selector switch in auto alarm contacts

D29

Selector switch in off alarm contacts

D30

Motor heater circuit

D32

Service entrance rated - 100kA short circuit withstand rating:


9SK KSPD[
9SK KSPD[
99K] KSPD[
99K] KSPD[
99K]K] KSPD[
99K] KSPD[

D33

Service entrance rated - 65kA short circuit withstand rating:


9SK KSPD[
9SK KSPD[
99K] KSKSPD[
99K] KSPD[
99K]K] KSKSPD[
99K] KSKSPD[

D34

Service entrance rated - 42kA short circuit withstand rating:


9K] KSPD[

1RWH2SWLRQVFKRVHQIURPWKLVSDJHDUHQRWHOHFWULFDOO\UHSUHVHQWHGRQWKHZLULQJVFKHPDWLFVLQWKLVVXEPLWWDOSDFNDJH

March 2015

Technical Data
Model JP3 Jockey Pump Controller
iPD+2SHUDWRU,QWHUIDFH

HAND

AUTO

5
8

1 - Power on LED
2 - System status LED
3 - Digital display
4 - Hand start LED
67$57SXVKEXWWRQ

March 2015

6723SXVKEXWWRQ
7 - Auto start LED
8 - Navigation keypad
212))SXVKEXWWRQ

PER QUOTE DRAWING No.

Jockey Pump Controller


Across the Line / 3 Phase

Dimension

Built to the latest edition of the UL 508A & CSA C22.2 No.14

0
1
2

DD/MM/YY

DESCRIPTION

REV.

Model:JP3

8
NYC
Dpt of Building
Approved

First Issue
Dimension Table and Notes
IPD+ R221B

04/07/14
17/10/14
23/01/14

Drawing No.

FU1
B

JP3-DI500 /E

DS
B

XTR1

D
F

1L1

3L2

5L3

2T1

4T2

6T3

Underwriters
Laboratories Inc.
LISTED
ENCLOSED INDUSTRIAL CONTROL PANEL
No. AC-XXX

NYC

Main Disconnect
ON

G
Y

OFF

HAND

AUTO

G
D

DS

OL1

C1

PT1
DANGER
Rating
Label

Sensing Line
Connection

Standard Internal Layout

"[9] x4

1/4 " M.NPT

Dimension*
Maximum Motor Horsepower
200-208V
3HP
5HP
10HP
20HP
25HP

220-240V
3HP
5HP
10HP
20HP
30HP

380-416V
7.5HP
10HP
20HP
40HP
50HP

440-480V
7.5HP
10HP
20HP
50HP
60HP

575-600V
10HP
15HP
25HP
50HP
60HP

Dimension Enclosure
AXBXC

Dimension Door
DXE
10- "X12- "
10- "X12- "
10- "X12- "

Dimension Anchor
FXG

TBD

TBD

TBD

A
H

Notes:
- Standard NEMA: NEMA 2
- Standard Paint : Textured Red RAL 3002.
- All Dimensions are in Inches [Millimeters]
- Use Watertight Conduit and Connector Only.
- Protect Equipment Against Drilling Chips.
- Door Swing Equal to Door Width
0

- Drawing for information only.


Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.
-*Dimension may change depending on option required. Consult Factory for exact
dimensions.
2

I
Projection

Jockey Pump Controller


Across the Line / 3 Phase
A

L2

0
1
2

Built to the latest edition of the UL 508A & CSA C22.2 No.14

PT1

L3

8
NYC
Dpt of Building
Approved

DD/MM/YY

DESCRIPTION

REV.

Model:JP3

Wiring schematic
L1

PER QUOTE DRAWING No.

First Issue
Remove Dimension Table
IPD+ R221B

04/07/14
17/10/14
23/01/14

Drawing No.

JP3-WS500 /E

Pressure Sensor
Type 0-100mV

G
DS

5 S

B W G R

OL1

FU1

A1

XTR1
H2

A2

7
9

X1 3

IN1

J5
G

AUTO

J9

J21

IN2
H1

HAND

PsInPsOutPsOut+
PsIn+

RESET

Red

White

Green

Black

OUTPUT ON

X2

J8

1
J19
A1
A2
A1
A2

"IPD+"

OUT1
OUT2

F5

24Vdc

J2

J3

J1
24Vac

24Vac

A2 A1
22 8

3 1

A1

C1

A2

OL1

H
C1

G
T1 T2 T3

P1
0

- Drawing for information only.


Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.
1

PER QUOTE DRAWING No.

Jockey Pump Controller


Across the Line / 3 Phase

Line and Motor Terminal Size

Built to the latest edition of the UL 508A & CSA C22.2 No.14

0
1
2

DD/MM/YY

DESCRIPTION

REV.

Model:JP3

8
NYC
Dpt of Building
Approved

First Issue
Remove Dimension Table
IPD+ R221B

04/07/14
17/10/14
23/01/14

Drawing No.

Power Connections and Motor Connections

JP3-TD500 /E

3 Phases
Incoming Power

Bonding Ground

L1 L2 L3
DS

C1
T1 T2 T3

Line Terminals (L1,L2,L3,GND)


Maximum Motor Horsepower

200-208V
7.5HP
10HP
15HP

220-240V
10HP
10HP
15HP

380-416V
15HP
20HP
25HP

440-480V
20HP
25HP
30HP

575-600V
15HP
25HP
40HP

Wire Size Copper Only

Torque

Wire Size Ground Copper Only

#14 AWG - #8 AWG


#12 AWG - #4 AWG
#4 AWG - #1/0 AWG

1.8 Nm
1.8 Nm
5.65 Nm

#14 AWG - #2 AWG


#14 AWG - #2 AWG
#6 AWG - #2 AWG

Motor Terminals (T1,T2,T3,GND)

Maximum Motor Horsepower

200-208V
3HP
5HP
10HP
20HP
25HP

220-240V
3HP
5HP
10HP
20HP
30HP

380-416V
7.5HP
10HP
20HP
40HP
50HP

440-480V
7.5HP
10HP
20HP
50HP
60HP

575-600V
10HP
15HP
25HP
50HP
60HP

Wire Size Copper Only

Torque

Wire Size Ground Copper Only

#14 AWG - #10 AWG


#14 AWG - #8 AWG
#14 AWG - #6 AWG
#10 AWG - #3 AWG
#10 AWG - #2 AWG

1.7 Nm
1.7 Nm
2.25 Nm
5 Nm
11.3 Nm

#14 AWG - #2 AWG


#14 AWG - #2 AWG
#12 AWG - #2 AWG
#12 AWG - #2 AWG
#12 AWG - #2 AWG