LCD-80
Installation Manual
Document 15037
9/9/02
Rev:
PN 15037:D2
D2
ECN 02-339
PN 15037:D2 9/9/02
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can
be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit
and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting
cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is
read and understood.
CAUTION - System Reaccepting Test after Software
Changes. To ensure proper system operation, this
product must be tested in accordance with NFPA 72
Chapter 7 after any programming operation or change in
site-specific software. Reaccepting testing is required
after any change, addition or deletion of system components, or after any modification, repair or adjustment to
system hardware or wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be
100% tested. In addition, to ensure that other operations
are not inadvertently affected, at least 10% of initiating
devices that are not directly affected by the change, up
to a maximum of 50 devices, must also be tested and
proper system operation verified.
This system meets NFPA requirements for operation at
0-49 C/32-120 F and at a relative humidity of 85% RH
- 93% per ULC - (non-condensing) at 30 C/86 F. However, the useful life of the system's standby batteries
and the electronic components may be adversely
affected by extreme temperature ranges and humidity.
Therefore, it is recommended that this system and all
peripherals be installed in an environment with a nominal room temperature of 15-27 C/60-80 F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate
more than a 10% I.R. drop from the specified device
voltage.
FCC Warning
WARNING: This equipment generates, uses, and
can radiate radio frequency energy and if not
installed and used in accordance with the instruction
manual, may cause interference to radio communications. It has been tested and found to comply with
the limits for class A computing device pursuant to
Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against
such interference when operated in a commercial
environment. Operation of this equipment in a residential area is likely to cause interference, in which
case the user will be required to correct the interference at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of
the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables
aux appareils numeriques de la classe A prescrites
dans le Reglement sur le brouillage radioelectrique
edicte par le ministere des Communications du
Canada.
Acclimate Plus, HARSH, NOTIFIRENET, ONYX, and VeriFire are trademarks, and FlashScan and
VIEW are registered trademarks of NOTIFIER. NION and UniNet are trademarks of NIS. NIS and Notifier
Integrated Systems are trademarks and NOTIFIER is a registered trademark of FireLite Alarms, Inc. Echelon
is a registered trademark and LonWorks is a trademark of Echelon Corporation. ARCNET is a registered trademark of Datapoint Corporation. Microsoft and Windows are registered trademarks of the Microsoft Corporation.
LEXAN is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
PN 15037:D2 9/9/02
Notes
PN 15037:D2 9/9/02
Table of Contents
Section 1 Product Overview: LCD-80 Liquid Crystal Display ............................7
1.1 Common Features ........................................................................7
1.2 ACS Mode ...................................................................................7
1.3 TERMINAL Mode ......................................................................8
Section 2 The LCD-80 and ACS Mode ................................................................11
2.1
2.2
2.3
2.4
2.5
2.6
PN 15037:D2 9/9/02
Notes
PN 15037:D2 9/9/02
PN 15037:D2 9/9/02
PN 15037:D2 9/9/02
PK-1 Programming
Key connector
When the key is
inserted, the LCD-80
enters program
mode. When the key
is removed, the
LCD-80 automatically
returns to normal
operations.
AKS-1 Keyswitch
connector
For connection of
an optional
AKS- 1
keyswitch. When
the two pins on
this interface are
shorted, all six
keys on the
membrane panel
will be ignored by
the LCD-80.
Terminal Connections
To provide 24 VDC
operating power, EIA-485
or EIA-232 connections to
the LCD-80. These
connections must be
power-limited.
PN 15037:D2 9/9/02
Notes
10
PN 15037:D2 9/9/02
FACP
to
PRN
to
PRN
to
PRN
LCD80-CAB4-ACSmode.cdr
PN 15037:D2 9/9/02
11
P2
P1
4
3
2
1
-EIA-485 In
-EIA-485 Out
+EIA-485 In
+EIA-485 Out
7
6
5
4
3
2
1
12
PN 15037:D2 9/9/02
Size of
display
labels
Max
LCD-80s
per
system*
Max
LCD-80s
per
AFP-200
32
DIP Switch
EIA-485
addresses
Number
of
points
OFF
OFF
one
64
40 characters
OFF
ON
two
128
40 characters
16
ON
OFF
two
128
20 characters
16
ON
ON
four
255
20 characters
* Max LCD-80s per system doesn't restrict the number of LCD-80s that can be set for
Receive Only (subject to system power supply limitations). A maximum of four
LCD-80s can be powered by the AFP-200. Other equipment (ACS, LDM, etc.) that
assumes addresses on the EIA-485 circuit will reduce the maximum number of
LCD-80s that can be used in the system.
Most
Significant
Digit
(SW3)
Least
Significant
Digit
(SW2)
PN 15037:D2 9/9/02
13
DIP SW3-1
DIP SW3-2
Rotary SW2
Start Address
OFF
OFF
n/a
OFF
OFF
01-09
01-09
ON
OFF
0-09
19-19
OFF
ON
0-09
20-29
ON
ON
0-02
30-32
ON
ON
03-09
n/a
Set SW2 to 1
14
PN 15037:D2 9/9/02
EIA-485
(-)
(+)
To EIA-485
terminals on
CPU
Cabinet
Terminating
Resistor
PN 15037:D2 9/9/02
15
AFP-200
TB5-1
TB5-2
EIA-485 (+)
EIA-485 (-)
AFP-300, AFP-400,
AFC-600
EIA-485 (+)
EIA-485 (-)
NCA
EIA-485 (+)
EIA-485 (-)
NFS-640
TB-13 (+)
TB-13 (-)
EIA-485 (+)
EIA-485 (-)
TB2-1
TB2-2
EIA-485 (-)
EIA-485(+)
AM2020/AFP1010
(SIB2048, SIB2048A,
SIBNET)
P5-1
P5-2
P5-3
P5-4
P5-5
P5-6
EIA-485 Common
Earth Ground Chassis
EIA-485 Loop 1(+)
EIA-485 Loop 1(-)
EIA-485 Loop 2(+)
EIA-485 Loop 2(-)
16
PN 15037:D2 9/9/02
P2
P1
4
3
2
1
7
6
5
4
3
2
1
PRN
See Section 2.3 Printer
Configuration for setup.
PN 15037:D2 9/9/02
17
FONT:
HS DRAFT
LPI:
6 CPI
ESC CHARACTER:
ESC
BIDIRECTIONAL COPY:
ON
CG-TAB:
GRAPHIC
COUNTRY:
E-USA ASCII
AUTO CR:
OFF
LANGUAGE:
ENGLISH
AUTO TEAR:
1S
COLOR OPTION:
NOT INSTALLED
FORMLEN:
LINES:
6 LPI=60
STANDARD:
EXECUTIVE 10.5"
CPI:
10 CPI
SKIP:
0.5"
EMULATE:
EPSON
I/O:
BUFFER:
36K
SERIAL:
BAUD:
600
FORMAT:
PROTOCOL:
XON/XOFF
CHARACTER SET:
STANDARD
S1.ZERO
ON
AUTO LF:
OFF
MENLOCK:
ALL
PAPER:
BIN 1:
18
12/72"
BIN 2:
12/72"
SINGLE:
12/72"
PUSH TRA:
12/72"
PULL TRA:
12/72"
PAP ROLL:
12/72"
PAPOPT:
NO
PN 15037:D2 9/9/02
PN 15037:D2 9/9/02
19
P1
7
6
5
4
3
2
1
24 VDC (+)
Common (-)
MPS-24A
TB3-3
TB3-4
MPS-24B
TB2-1
TB2-2
AFP-200
TB1-3
TB1-4
AFP-300,
AFP-400, MPS-6
TB2-1
TB2-2
APS-6R
TB2 +
TB2 -
FCPS-24
TB4 +
TB4 -
NCA
NFS-640
TB7 Nonresettable
24VDC +
TB7 Nonresettable
24VDC -
20
PN 15037:D2 9/9/02
GLOBAL
Acknowledge
SILENCE
RESET
PN 15037:D2 9/9/02
21
22
PN 15037:D2 9/9/02
1
2
3
4
01234567890123456789
<<<<<<<<<<<<<<CUSTOM
MESSAGE 1>>>>>>>>>>>
<<CUSTOM MESSAGE 2>>
HH: MMA MM/DD/YY
Where:
CUSTOM MESSAGE 1 is a 40-character user-defined
message.
CUSTOM MESSAGE 2 is a 20-character user-defined
message with a default of ALL SYSTEMS NORMAL. [note:
> means space]
HH:MMA MM/DD/YY is time and date in hours, minutes,
AM/PM, month, day and year. If the European DIP switch option
is selected, this format is changed to 24-hour, with different day/
month placement:
HH:MM DD/MM/YY
As an example, the following normal message could be provided:
ROSEWOOD HOSPITAL
NORTH HALL FLOOR 3
ALL SYSTEMS NORMAL
11:15P 12/25/00
PN 15037:D2 9/9/02
23
1
2
3
4
01234567890123456789
<<<<ALARMBANNER>>>>
<<<<<<<<CUSTOMPOINT
LABEL>>>>>>>>>>>>>>>
XXALARM YYTROUBLES
24
PN 15037:D2 9/9/02
01234567890123456789
<FIRST POINT LABEL>>
<<LAST POINT LABEL>>
XXALARM YYTROUBLES
1
2
3
4
01234567890123456789
<<TROUBLE BANNER>>>>
<<<<<<<<CUSTOM POINT
LABEL>>>>>>>>>>>>>>>
XXALARM YYTROUBLES
Where the TROUBLE BANNER is a user programmable 20character field with a default value of TROUBLE IN SYSTEM.
The 20-character option changes the custom point labels used in
trouble reporting to a format similar to the 20 character alarm
messages described above.
Supervisory Message: If supervisory condition occurs, it is reported to
the LCD-80 as both an alarm and a trouble from the same point
(custom labels must be used to distinguish supervisories). The LCD80 cannot distinguish the difference between supervisory and trouble
conditions. The system programmer must differentiate supervisory
conditions from trouble conditions when entering custom labels for
the appropriate points.
PN 15037:D2 9/9/02
25
1
2
3
4
01234567890123456789
<<<<<<<<<<<<<<<<COMM
FAILMESSAGE>>>>>>>>
<<<<<<<<<<>>>>>>>>>>
HH:MMAMM/DD/YY
26
PN 15037:D2 9/9/02
6. When the SILENCE key is pressed the LCD-80 will print the following message:
<<<SILENCE BANNER>>>
(line 2 blank)
(line 3 blank)
HH:MM MM/DD/YY
Where the SILENCE BANNER is a user-programmable 20character field with a default value of: SIGNAL SILENCE.
7. When the RESET key is pressed the LCD-80 will print the following message:
<<<<RESET BANNER>>>>
(line 2 blank)
(line 3 blank)
HH:MM MM/DD/YY
Where the RESET BANNER is a user-programmable 20character field with a default value of: SYSTEM RESET.
PN 15037:D2 9/9/02
27
first eight points on an LCD-80 set for address 01 are used for the
following functions:
LCD-80
Point
Point Indication
Switch Function
none
Acknowledge
none
Signal Silence
none
Reset
none
none
none
none
none
AC Fail
none
28
PN 15037:D2 9/9/02
P2
P1
4
3
2
1
EIA-232 TX
7
6
5
4
3
2
1
EIA-232
Reference
EIA-232 RX
LCD-80
PN 15037:D2 9/9/02
29
and
Press
Press
Press
30
PN 15037:D2 9/9/02
P2
P1
4
3
2
1
EIA-232 TX
7
6
5
4
3
2
1
EIA-232
Reference
EIA-232 RX
LCD-80
Female DB-9 connector for connection
to PC serial port (illustrated from pin
side to show wire connections)
DB-25
DB-9*
PN 15037:D2 9/9/02
31
PC Communications
software used to
program the LCD-80
must be used in direct
connect or terminal
mode and set for the
following options:
2400 Baud.
7 Data Bits.
1 Stop Bits.
Even Parity.
XON/XOFF.
Note: If ProComm Plus
is being used as the
communications
software to program the
LCD-80, the Terminal
Emulation must be set
for TVI925.
Characters
40
FIRE ALARM
SYSTEM ANUNCIATOR
20
40
COMMUNICATIONS FAIL
20
20
TROUBLE IN SYSTEM
20
RETURN TO NORMAL
20
ACKNOWLEDGE
20
SIGNAL SILENCE
20
SYSTEM RESET
32
PN 15037:D2 9/9/02
fire and security panel, the FIRE in default messages 1 and 4 must
be removed.
To restore default messages:
If in Program Mode, remove the Programming Key.
Insert the Programming Key.
Within several seconds after inserting the Programming Key,
push in and hold in the DISPLAY STEP switch until the LCD-80
displays the following message:
TRANSFER DEFAULT
CUSTOM MESSAGES
TO NONVOLATILERAM
PN 15037:D2 9/9/02
33
Text cannot be immediately entered since the cursor starts at the end
of the message. The LCD-80 programmer must edit the message using
the backspace key, then enter a new message.
Once the message has been edited, press ENTER to store the message.
The screen will return to the display, READY FOR
PROGRAMMING.
These custom messages have various character widths and are
displayed under different conditions present within the fire alarm
system.
Message
Number
7
8
9
34
PN 15037:D2 9/9/02
The label may be changed by backspacing over the existing label and
typing a new one.
LCD-80 set for 20-character labels:
ENTER 1 to 128 FOR CUSTOM POINT LABEL (40
CHARACTERS):
where 1-128 represent zones in the control panel.
Note:
AFP-200 uses Zones 1 to 99 only.
Once a point number has been entered, the LCD-80 screen will
display either the custom zone message (illustrated below) or the last
stored point message.
ZONE 005
(A01P05)
PN 15037:D2 9/9/02
35
36
PN 15037:D2 9/9/02
Fire Alarm
Control Panel
Terminal
Mode
EIA-485
24 VDC
EIA-232
Printer Port
Notes:
EIA-485 circuits have a maximum of 6000 feet between units.
Up to 32 LCD-80s may be used on the EIA-485 circuit (3.2 amps
regulated power max required - consult control panels battery
calculations. Note: When powered by the AFP-200, a maximum
of four LCD-80s may be connected to this circuit.
Between each LCD-80 are four wires: A twisted-shielded pair for
data communications and an open pair for 24 VDC power. The
return circuit only requires two wires for data communication.
The EIA-485 interface used in Terminal Mode should not be
confused with the EIA-485 circuit used in ACS Mode
(annunciator interface). With AM2020/AFP1010, the CCM-1
Convertor Module converts the EIA-232 Terminal Interface from
the SIB-2048 into the EIA-485 standard required by the LCD-80.
A separate EIA-485 circuit for powering ACS or LDM Series
annunciators can be taken off of the SIB-2048 Serial Interface
PN 15037:D2 9/9/02
37
38
PN 15037:D2 9/9/02
LCD80-board.tif
P2
4
3
2
1
+
+
EIA-485 In
EIA-485 Out
EIA-485 In
EIA-485 Out
7
6
5
4
3
2
1
No connection
No connection
System Common Out
System Common In
+24 Volts Out
+24 Volts In
No connection
PN 15037:D2 9/9/02
39
Printer Operation
The LCD-80 does not support a remote printer when operating in
Terminal Mode.
Pending Display
*Acknowledge
Contrast Adjust
*Silence
Local Silence/
Lamp Test
*Reset
40
PN 15037:D2 9/9/02
Acknowledge/Step Switch
When the ACK/STEP switch is pressed on the front panel, the LCD80 sends an Acknowledge command to the control panel, emulating a
CRT terminal.
Silence Switch
When the SILENCE switch is pressed on the front panel, the LCD-80
sends a Signal Silence command to the control panel, emulating the
CRT terminal.
System Reset Switch
When the System Reset switch is pressed on the front panel, the LCD80 sends a Reset command to the control panel, emulating the CRT
terminal.
Pending Display
The LCD-80 will keep a count of alarms in the system (number of
alarm messages, minus alarm clear messages, since the last ALL
SYSTEMS NORMAL message). When this key is pressed the alarm
count is displayed in place of the time/date for 10 seconds. AM2020/
AFP1010 Note: This feature requires Revision 5 software or greater.
Contrast Adjust
Repeatedly press this switch until the displays contrast is acceptable.
Local Silence/Lamp Test Switch
If the backlit LCD display has been turned off due to a trouble
condition in the system, pressing this switch will illuminate the
display for 60 seconds. This switch also silences the local piezo.
While it is held down, all segments on the display will be turned on
and the piezo will sound.
PN 15037:D2 9/9/02
41
42
PN 15037:D2 9/9/02
P2
R-120 resistors are required
across In and Out circuits on
each LCD-80.
See notes in the preceding
text.
Refer to Appendix A for shield
termination instructions.
4
3
2
1
First LCD-80
(set DIP Switch
SW3-1 and SW3-2
Off on all LCD-80s
except last one)
P2
4
3
2
1
Last LCD-80
(must set DIP Switch
SW3-1 and SW3-2
ON)
EIA-485
Return
EIA-485
Out
TwistedShielded Pairs
EIA-485
Out (-)
Return (-)
Out (+)
Return (+)
Cabinet
PN 15037:D2 9/9/02
43
AFP-200
DIA
(AM2020/
AFP1010)
NFS-640
AFP-300,
AFP-400,
AFC-600
TB5-2
TB1-4
TB12
TB3-4
P3-3
TB5-4
TB1-3
TB12
TB3-2
OUT(+)
P3-2
TB5-1
TB1-2
TB12
TB3-3
RET (+)
P3-1
TB5-3
TB1-1
TB12
TB3-1
EIA-485
Connections
on LCD-80
CCM-1
(AM2020/
AFP1010)
OUT(-)
P3-4
RET (-)
44
PN 15037:D2 9/9/02
PN 15037:D2 9/9/02
45
and 4. AM2020/AFP1010 Note: For the first LCD-80 on the loop, let
the shield coming in from the CCM-1 or DIA float.
When the EIA-485 shield is in conduit: At each respective LCD-80
enclosure (except the first on the loop), terminate the shield coming in
from the previous LCD-80 at system common. Let the shield going
out to next LCD-80 shield float (no connection). Shield termination
between LCD-80s can only occur at the receiving endthe end
connected to LCD-80 P1 Terminals 2 and 4. AM2020/AFP1010 Note:
For the first LCD-80 on the loop, let the shield coming in from the
CCM-1 or DIA float.
46
PN 15037:D2 9/9/02
8 CPU points
8 unusable
AIM-200 points
48 points mapped to
the next six modules
installed.
Annunciator Address 2
Intelligent Detectors, addressed 1-64, on the AIM-200 installed next
to the CPU-5000.
PN 15037:D2 9/9/02
47
Annunciator Address 3
Addressable Modules, addressed 1-64, on the AIM-200 installed next
to the CPU-5000.
Annunciator Address 4
Intelligent Detectors, addressed 65-96, followed by Addressable
Modules, addressed 65-96, on the AIM-200 installed next to the CPU5000.
The System 5000 Programming Manual, Document 15584, provides
programming instructions for this option. Refer to program choice
AIM(256).
Note: AIM-200 detector and module addresses 97, 98 and 99 may be
used, but cannot be point-annunciated.
Annunciator
Address
AIM-200 Points
LCD-80 Points
01
1-64
02
65-128
03
129-192
04
65-96 detectors
65-96 modules
193-224
225-256
48
PN 15037:D2 9/9/02
Notes
PN 15037:D2 9/9/02
49
Notes
50
PN 15037:D2 9/9/02
Limited Warranty
NOTIFIER warrants its products to be free from defects in materials
and workmanship for eighteen (18) months from the date of
manufacture, under normal use and service. Products are date
stamped at time of manufacture. The sole and exclusive obligation of
NOTIFIER is to repair or replace, at its option, free of charge for
parts and labor, any part which is defective in materials or
workmanship under normal use and service. For products not under
NOTIFIER manufacturing date-stamp control, the warranty is
eighteen (18) months from date of original purchase by NOTIFIERs
distributor unless the installation instructions or catalog sets forth a
shorter period, in which case the shorter period shall apply. This
warranty is void if the product is altered, repaired or serviced by
anyone other than NOTIFIER or its authorized distributors or if there
is a failure to maintain the products and systems in which they
operate in a proper and workable manner. In case of defect, secure a
Return Material Authorization form from our customer service
department. Return product, transportation prepaid, to NOTIFIER,
12 Clintonville Road, Northford, Connecticut 06472-1653.
This writing constitutes the only warranty made by NOTIFIER with
respect to its products. NOTIFIER does not represent that its
products will prevent any loss by fire or otherwise, or that its products
will in all cases provide the protection for which they are installed or
intended. Buyer acknowledges that NOTIFIER is not an insurer and
assumes no risk for loss or damages or the cost of any
inconvenience, transportation, damage, misuse, abuse, accident or
similar incident.
NOTIFIER GIVES NO WARRANTY, EXPRESSED OR IMPLIED,
OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR
PURPOSE, OR OTHERWISE WHICH EXTEND BEYOND THE
DESCRIPTION ON THE FACE HEREOF. UNDER NO
CIRCUMSTANCES SHALL NOTIFIER BE LIABLE FOR ANY LOSS
OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR
CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY
TO USE NOTIFIER PRODUCTS. FURTHERMORE, NOTIFIER
SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH
WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF,
PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS
PRODUCTS.
This warranty replaces all previous warranties and is the only
warranty made by NOTIFIER. No increase or alteration, written or
verbal, of the obligation of this warranty is authorized.
NOTIFIER is a registered trademark.
Warn-NS-10-2001.fm
World Headquarters
12 Clintonville Road
Northford, CT 06472-1653 USA
203-484-7161
fax 203-484-7118
www.notifier.com
NOTIFIER is a
company.
TIME
SELECT
GLOBAL
ACKNOWLEDGE
GLOBAL
ACKNOWLEDGE
TIME SET
SILENCE
CONTRAST
ADJUST
SILENCE
RESET
HOLD FOR
LAMP TEST
RESET
CONTRAST ADJ.
DISPLAY STEP
Local Acknowledge
HOLD FOR
LAMP TEST
ACS Mode
Label (left)
ACS Mode
Label (right)
Terminal Mode
Label (left)
Terminal Mode
Label (right)