Chapter 4: Load Tracing

4.1 Load Tracing


During the initial stages of a project, the designer makes assumptions regarding
the way loads (forces) are transferred through the structure to the foundation
(ground).
These loads (forces) travel along load paths.

The analysis method is known as load tracing.

Definition: Load tracing involves the systematic process of determining loads and
support reactions of individual structural members and how these loads are
transferred to other structural elements.
Simple determinate structures are analyzed using the following.
Free-body diagrams (FBDs).

Basic equations of equilibrium.

The process starts at the top (with the uppermost roof element), tracing the
loads down through the structure to the foundation.

Load Paths
The economy and efficiency of the structure is improved by the following.
Minimizing the load path to the foundation.

Involving fewer structural elements.

Using the unique and inherent strengths of the materials (e.g. tension in steel,
compression in concrete)

Tributary Area
Loads uniformly distributed over an area of roof or floor are assigned to individual
members (rafters, joists, beams, girders) based on the concept of tributary area.
This concept typically considers the tributary area that a member must support
as being halfway between the adjacent similar members.
Consider the wood floor framing
system shown at the right with a
uniform load over the entire deck
area of 50 psf.
Each beam has a span length of 16.

4.1

Beams A and D
Tributary width for edge Beam A = half the distance between A and B.
The tributary width for edge Beam A = 2.

Similarly, the tributary width for edge Beam D = 2.

Beams B and C
Tributary width for interior Beam B = half the distance between A and B plus half
the distance between B and C.
Tributary width for interior Beam B = 2 + 2 = 4

Similarly, the tributary width for interior Beam C = 4.

Beam load = distributed load (psf) times the tributary width.


The load on Beams A and D:
wA = wD = 50 psf x 2 = 100 lb/ft

The load on Beams B and C:


wB = wC = 50 psf x 4 = 200 lb/ft

Framing Design Criteria: Direction of Span


Architectural character
Exposed structural framing can contribute to the architectural expression of
buildings.

Differences in the depth of the structural elements can help define individual
structural bays of a building (e.g. short/shallow joists loading long/deep beams).

Structural efficiency and economy


Considerations for structural efficiency and economy should include the following.
The appropriateness of materials (e.g. wood, steel, concrete) selected for the
structural system.

The span capacity and intermediate supports.

The availability of material and skilled labor locally.

Standard sections and repetitive spacing of uniform members are generally


more economical.
4.2

Mechanical and electrical system requirements


The location and direction of mechanical systems should be coordinated with the
intended structural system.
Layering the structural system provides space for ducts and pipes to cross
structural members, eliminating the need to cut openings in the beams.

Flush or butt framing saves space in situations where it is desirable or


necessary to limit floor-to-floor dimensions.

Openings for stairs and vertical penetrations


Most framing systems accommodate openings.
It is generally economical to make openings parallel to the principal spanning
direction.

If openings are not parallel, additional headers and connections create point
loads on members that would otherwise be designed for light, uniform loads,
increasing their size.

Construction and Load Paths: Pitched Roof Systems


Figures 4.8 to 4.11 (pp. 200 - 201 of the textbook) illustrate the construction and
load paths of typical pitched roof systems.
Single-level framing
Construction: Single-level framing construction is a common roof system for
residential structures.
- The single-level framing system
consists of sheathing (plywood, other
structural panels, or boards), roof
rafters, ridge board, and ceiling
joists.
-

The roof rafters, ridge board, and


ceiling joists combine to form a simple
truss spanning between bearing walls.

Load path
- Loads on the roof are initially supported by the sheathing.
-

The sheathing transfers the loads to


the roof rafters.

The roof rafters transfer the loads


to the ceiling joists and to the bearing
walls that support the trusses.
4.3

Double-level framing
Construction: Double-level framing construction is another common roof framing
system.
- The double-level framing system consists
of decking or sheathing (plywood, other
structural panels, or boards), rafter
beams, and a ridge beam.

The rafter beams are supported at one


end by the ridge beam (usually at the
peak of the roof) and supported at the
other end by a bearing wall or by a
header beam.

The ridge beam is supported at each end by a column or by a bearing wall.

Load path
- Loads on the roof are initially supported by the decking or sheathing.
-

The decking or sheathing transfers the loads to the rafter beams.

The rafter beams transfer the loads


to the ridge beam at one end and to a
bearing wall or header beam at the
other end.

The ridge beam transfers the loads to the supporting column or bearing wall.

Notice that each level of the structural framing spans in a perpendicular direction
to the next layer.
The sheathing is perpendicular to rafters.

The rafters are perpendicular to ridge beam and bearing walls.

Three-level framing
Construction: A third method makes use of heavier roof beams (rather than
roof rafters or rafter beams).
- The three-level framing system
consists of decking, purlins, roof
beams, and a ridge beam.
-

The center-to-center spacing between


the roof beams ranges from 4 to 12
(compared to 16 to 24 for roof
rafters or rafter beams).
4.4

The ridge beam is supported at each end by a column or by a bearing wall.

The purlins, spaced 1-6 to 4-0 on centers, are installed between the roof
beams and support the decking.

The roof beams are supported by the ridge beam at one end (generally at
the peak of the roof) and supported by a bearing wall or header beam at the
other end.

Load path
- Loads on the roof are initially supported by the decking.
-

The decking transfers the load to the purlins.

The purlins transfer the loads to the


roof beams as concentrated loads.

The roof beams transmit the loads to the


ridge beam at one end and a bearing wall
or header beam at the other.

Columns or wall framing support the ends of the ridge beam.

Load Paths: Wall Systems


Figures 4.12 to 4.17 (pp. 202 - 203 of the textbook) illustrate the load paths for
various types of loads acting on typical wall systems.
Bearing wall
A bearing wall is a vertical support system that transmits compressive forces
through the wall plane and to the foundation.
Bearing wall systems can be constructed with masonry, cast-in-place concrete,
pre-cast concrete panels, or studs (wood or light-gauge metal framing).
Load Paths

Uniform distribution

Uniform compressive forces acting along the length of the wall result in a
relatively uniform distribution of force.
Roof or floor joists (in typical light-wood framing) are closely spaced at 16 or
24 on center.

This regular, close spacing is assumed as a uniformly distributed load along the
top of the wall.

If there are no openings to disrupt the load path from the top to the bottom of
the wall, a uniform load will result on top of the footing.
4.5

Non-uniform distribution

Concentrated loads develop at the top of a wall when beams are spaced at wide
intervals.
The effect of the concentrated load
spreads out as it moves down the wall.
- Depending on the wall material, the
area of influence of the concentrated
load is generally defined by an angle
of 45 or 60.

The resulting footing load will be nonuniform with the largest forces directly
under the applied load.

Disruptions in the structural continuity of the wall (e.g. a large window or door
opening) result in a non-uniform distribution of the compressive forces on the
footing.

Arching action over an opening

Openings in walls redirect the loads to either side of the opening.


The natural stiffness of a concrete wall under compression produces an arching
action that contributes to the lateral distribution of the loads.

Openings in a stud wall

Stud walls (wood and metal) are generally idealized as monolithic walls (except for
openings) when loaded uniformly from above.
Openings require the use of headers (beams) that redirect the loads to either
side of the opening.

Concentrated loads from the header reactions must be supported by a buildup


of studs resembling a column.

Concentrated loads pilasters

In special cases where the concentrated loads are very large, walls may need to be
reinforced with pilasters directly under the beam.
Pilasters are essentially columns and carry the large concentrated loads directly
to the footing.

The walls between the pilasters are now considered as non-bearing walls except
for carrying their own weight.

4.6

Example Problems - Load Tracing


Problems 4.1 and 4.2
These homework problems will be worked together in class using the homework
problem worksheet available from the website.

4.7

Load Paths: Roof and Floor Systems


Figures 4.18 to 4.23 (pp. 204 - 205 of the textbook) illustrate the load paths for
common roof and floor systems.
One-level framing
Construction:
Pre-cast
hollow-core
concrete planks or heavy timber-plank
decking is used to span closely spaced
bearing walls or beams.
- This is not a common framing system.

Spacing of the supports (the distance between the bearing walls) is based on
the span capability of the concrete planks or timber decking.

Load path
- Loads acting on the concrete planks or
timber-plank decking are transmitted
directly to the bearing walls.

Two-level framing
Construction: Two-level framing is a very common type of floor system.
- The two-level framing consists of decking with closely spaced beams (called
joists) to support the deck.

The decking is laid perpendicular to the


beam (joist) framing.

Efficient structural sections of wood or


steel beams (joists) allow relatively long
spans between bearing walls.

Lighter deck materials such as plywood


panels can be used to span between the
closely spaced beams (joists).

Span (distances) between bearing walls and beams affect the size and
spacing of the joists.

Load path
- Loads on the decking are transmitted to
beams (joists).
-

The beams transmit loads to the bearing


walls.

4.8

Notice, again, that each level of structural framing spans in a perpendicular


direction to the next layer.
The decking is perpendicular to the beams/joists, and the beams/joists are
perpendicular to the bearing walls.
Three-level framing
Construction: This type of construction is used for buildings requiring large
open floor areas.
- The three-level framing consists of
decking or sheathing, joists, beams,
and girders, trusses, columns, or
bearing walls.

Floor space is free of bearing walls


and with a minimum number of
columns.

Construction typically relies on the


long span capacity of joists supported
by trusses or girders.

The spacing of the primary structure and the layering of the secondary
structural members establish regular bays that subdivide the space.

Load path
- Loads on the decking or sheathing are supported by the joists.
-

The decking transfers the loads to


the joists.

The joists transfer the loads to the


beams.

The beams transfer the loads to


girders or trusses.

The girders or trusses transfer the loads to columns or bearing walls.

Each level of framing is arranged perpendicular to the level directly above it.

4.9

Example Problems - Load Tracing


Problems 4.3 and 4,.4
These homework problems will be worked together in class using the homework
problem worksheet available from the website.

4.10

Load Paths: Foundation Systems


Figures 4.24 to 4.29 (pp. 206 - 207 of the textbook) illustrate common foundation
systems.
The foundation system for a particular structure or building depends on the
following.
The use and size of the structure.

Subsurface soil (geology) conditions at the site.


- A geologist or soils engineer will likely be part of the project team.

The cost of the foundation system to be used.

A large building with heavy loads can often be supported on relatively inexpensive
shallow footings if the subsurface soils are dense and stable.
A large building constructed at a site with soft soils, compressive clay soil, or
poorly graded soils (e.g. beach sand or sugar sand) may require expensive
foundations or soil stabilization.
One such stabilization technique might be over-excavation and refill with
borrow material (such as stone) and the use of geo-textiles (geo-grids).
- This technique requires the removal, hauling, and dumping of poor materials.
-

This technique requires the purchase, hauling, spreading and compaction of


borrow materials.

This technique requires the purchase, handling, and placing of the geotextile materials.

Chemical stabilization (using lime or cement) may provide a remedy for shallow
foundations.

Pile or caisson foundations may be necessary in areas where poor soils are
present for significant depths below the ground surface.

Foundations are generally divided into two major categories: shallow foundations
and deep foundations.
Shallow foundations
Shallow foundations essentially obtain their support on soil or rock.
- Soils with moderate to high soil-bearing capacities can provide adequate
support for most construction.
-

Rock located just below the bottom of the structure can provide support in
direct bearing.
4.11

Rock located just below the structure may offer challenges and increase the
costs of extending underground utilities.

Vertical loads are transmitted from walls or columns to a footing.


- The footing then distributes the load over a large enough area so that the
allowable load-carrying capacity of the soil is not exceeded and settlement
(including differential settlement) is minimized.

Shallow foundations are of three basic types.


1. Spread footings support an individual column.
The spread footing is usually square or circular in plan.

The spread footing is generally simple and


economical for moderate to high soil-bearing
capacities.
- The footings are generally shallow.
-

Simple wood framed forms are used.

Pedestals and footings are reinforced


with little to no steel.

The purpose of this footing is to distribute


the load over a large area of soil.

2. Wall footings (continuous strip footings) support bearing walls.


Continuous strip footings are one of the most common types of footings used
to support a bearing wall.
- For example, a continuous strip footing is
commonly used to support a concrete
block foundation wall for a typical
residential structure.

Continuous strip footings usually support


uniform bearing wall loads.

The continuous strip footing is simple and


economical for moderate to high soil-bearing
capacities.
- The footings are generally shallow.
-

Simple wood framed forms or metal forms are used.

Pedestals and footings are reinforced with little to no steel.

The wall footing width remains constant throughout its length if no large
concentrated loads occur.
4.12

3. Mat or raft foundations cover the entire plan area of the building.
Mat foundations are used when soil
bearing is relatively low or where
loads are heavy in relation to soilbearing capacities.

This foundation type is essentially one


large footing under the entire building
and the load is distributed over the
entire mat.

A mat foundation is referred to as a raft foundation when it is placed deep


enough in the soil that the soil removed during excavation equals most or all
of the buildings weight.

Deep foundations
Deep foundations are generally piles, piers, or caissons installed in a variety of
ways.
The function of a deep foundation is to carry building loads beneath a layer of
unsatisfactory soil to a satisfactory bearing stratum.

Building loads are distributed to the soil in contact with the surface area of the
pile through skin friction (friction piles), in direct end-bearing (bearing piles) at
the bottom of the pile on a sound stratum of earth or rock, or a combination of
skin friction and direct bearing.

Deep foundations are of three basic types.


1. Pile foundations are the most common deep-foundation system.
Piles are driven into the earth by pile-driving hammers powered with drop
hammers, compressed air, or diesel engines.

Friction piles: Timber piles are


normally used as friction piles;
however, timber piles can rot if the
water table fluctuates.

Bearing piles: Concrete and steel piles


are generally used as bearing piles.
- A combination of steel and
concrete is used when bearing piles
must be driven to great depths to
reach suitable bearing.

4.13

Hollow steel casings are driven into the ground to a predetermined


bearing point, reinforcing steel (cages) may be placed within the casing,
and then the casings are filled with concrete.
As each hollow steel casing section (typically 20 long) is driven into
the ground, additional sections are welded to the end and then driven.

2. Pile caps are used when individual building columns are supported by more than a
single pile.
The thick reinforced concrete cap that is
poured on top of a pile group distributes
the column load to all the piles in the
group.

3. Grade beams are used to transfer the loads from a building wall to a group of
piles.
Piles or piers supporting bearing walls
are generally spaced at regular
intervals and are connected with a
continuous reinforced concrete grade
beam.

4.14

Example Problems - Load Tracing


Problems 4.5 and 4.6
These homework problems will be worked together in class using the homework
problem worksheet available from the website.

4.15

4.2

Lateral Stability Load Tracing


Geometric stability refers to a configuration property that preserves the
geometry of a structure.
Geometric stability is achieved by the way the structural elements are
strategically arranged.

Geometric stability is achieved by the way the structural elements interact to


resist loads.

All building structures require a bracing system.


A bracing system provides the stability for the entire structure.

The type and location of the bracing system directly affects the organizational
plan of the building and its final appearance.

The primary concerns in the design of any structure include the following.
To provide sufficient stability to resist collapse.

To prevent excessive deformation (deflection and racking), which may result in


the cracking of brittle surfaces and glass.

To be adequately stiffened against gravity-induced loads.

To be stable against horizontal forces (e.g. wind and seismic forces) coming
from two perpendicular directions.

The use of horizontal diaphragms (i.e. roof and floor planes) is the most common
system to resist lateral loads in wood-frame buildings.
The roof sheathing can be designed economically to serve as both a verticalload and lateral-load carrying element.
Ways to achieve stability
There are several ways of achieving stability and counteracting the racking of the
frame under vertical and/or horizontal loading.
Each solution has architectural implications.

The selection of the bracing system must be made for reasons beyond being the
most efficient structurally.
- The most efficient systems may interfere with openings (such as doors,
windows, and internal passages).

Figures 4.37 to 4.42, 4.44, 4.46 - 4.48 (pp. 234 - 237 of the textbook) illustrate
common ways of achieving stability.

4.16

Diagonal Truss Member


A simple way of providing lateral stability is to introduce a simple diagonal member
connecting two diagonally opposite corners.
In effect, a truss is created, and stability is
achieved through triangulation.
- If a single diagonal member is used, it must
be capable of resisting both tension and
compression forces, since lateral loads are
assumed to occur in either direction.
-

The members need to be sized similarly to truss members in compression.


Members subjected to compression have a tendency to buckle.

X-Bracing Members
Another strategy involves the use of two cross-bracing members with smaller
cross-sectional areas.
These X-braces are also known as diagonal
tension counters (discussed in Section 3.3).
- Only one counter is effective in resisting
the directional lateral load.

Knee-Bracing
A commonly used arrangement in carports and elevated wood decks is knee-bracing.
This stiffening method triangulates the beam-column connection to provide a
degree of rigidity at the joint.
- The larger the knee-braces are, the more
effective their ability to control racking.
-

Bracing is usually placed as close to 45 as


possible but will sometimes range between
30 and 60.

Knee-braces develop tension and compression


forces (like truss members) depending on the
lateral force direction.

Some movement will still occur because of the pin connections at the base of
the columns.
4.17

Gusset Plates
Large gusset plates at each beam-column connection can also provide the required
rigidity to stabilize the frame.
Some movement will occur because of the pin
connections at the base of the columns.

Modifying the base into a more rigid connection


can add to the rigidity of the frame.
- Rigid connections induce bending moments in
the beams and columns.

Rigid Base Condition


Columns placed at some depth into the ground and set in concrete can provide a
rigid base condition.
Resistance to lateral loads comes through the
columns acting as large vertical cantilevers.
The horizontal beam transfers loads between
the columns.

Combination Knee-Brace and Rigid Column Base


Knee-braces may be used in conjunction with rigid column bases.
All connections of the frame are rigid.

The lateral loads are resisted through the


bending resistance offered by the beam and
columns.

The lateral displacements are less than the


three previous examples (i.e. knee bracing,
gusset plates, and rigid base).

Rigid Beam/Column Joints


Connections may be made so that the beam and column form a rigid type of
connection.
Steel-framed structures: The connections
may be made using bolts, welds, and
stiffener plates in specific arrangements.

4.18

Concrete structures: A rigid connection may


be formed using reinforcing steel and
monolithically cast beams and columns.

Knee-Braced Structure with Roof Truss


A truss supported on two pin-connected columns is unstable.
Knee-braces provide stability for
the truss to develop resistance to
racking.

Shear walls
Many residential and small- to mid-scale commercial buildings depend on the walls
(bearing and non-bearing) of the structure to develop the necessary resistance to
lateral forces.
This type of lateral restraint, referred
to as a shearwall, depends on the vertical
cantilever capacity of the wall.

Commonly used materials for shear walls


are concrete, concrete blocks, bricks,
and wood sheathing products such as
plywood, oriented strand board (OSB),
and wafer boards.

4.19

Example Problems Lateral Stability


Problem 4.9 (p. 249)
Given: The frame with the lateral
load shown.
Find: The reaction forces at A and
B, and all other member forces.
Assume Ax = Bx
Solution
Find the reactions at the supports.
FBD: Entire frame
MA = 0 = - 1200 (16) + By (14)
14 By = 1200 (16) = 19,200
By = + 1371.4 lb
By = 1371.4 lb

MB = 0 = - 1200 (16) - Ay (14)


14 Ay = - 1200 (16) = - 19,200
Ay = - 1371.4 lb
Ay = 1371.4 lb
Fx = 0 = Ax + Bx + 1200 (Assume Ax = Bx)
0 = Bx + Bx + 1200
2 Bx = - 1200
Bx = - 600
Ax = Bx = 600 lb
Find the forces acting on members AHG and FH.
FBD: Member AHG
MG = 0 = - 600 (16) + (1/ 2 ) HF (4)
0 = - 600 (16) + 2.828 HF
2.828 HF = 600 (16) = 9600
HF = + 3394.6 lb
HF = 3394.6 lb (T)

4.20

Fx = 0 = Gx + (1/ 2 ) HF 600 + 1200


0 = Gx + 0.707 (3394.6) 600 + 1200
Gx = - 2400 + 600 1200 = - 3000
Gx = 3000 lb on AHG
Fy = 0 = Gy + (1/ 2 ) HF - 1371.4
0 = Gy + 0.707 (3394.6) 1371.4
Gy = - 2400 + 1371.4 = - 1028.6
Gy = 1028.6 lb on AHG
Find the forces acting on members BCD and CE.
FBD: Member BCD
MD = 0 = - 600 (16) - (1/ 2 ) CE (4)
0 = - 600 (16) 2.828 CE
2.828 CE = - 600 (16) = - 9600
CE = - 3394.6
CE = 3394.6 lb (C)
Fx = 0 = Dx - (1/ 2 ) CE 600
0 = Dx 0.707 (- 3394.6) 600
Dx = 0.707 (- 3394.6) + 600
Dx = - 2400 + 600 = - 1800
Dx = 1800 lb on BCD
Fy = 0 = Dy + (1/ 2 ) CE + 1371.4
0 = Dy + 0.707 (- 3394.6) + 1371.4
Dy = - 0.707 (- 3394.6) - 1371.4
Dy = + 2400 1371.4 = + 1028.6 lb
Dy = 1028.6 lb on BCD

4.21

Multiple bays
The previous discussion of frame stability from lateral loads was limited to singlebay (panel) frames; however, most buildings contain multiple bays in the horizontal
and vertical directions.
The principles that apply to single-bay frames also hold true for multiple-bay
frame structures.

Often only one panel needs to be braced for the entire frame to be stabilized.
- It is rarely necessary for every panel to be braced to achieve stability.

Figure 4.50 (p. 238 of the textbook) illustrates the following common ways of
achieving stability in structures with multiple horizontal bays.
Shear walls, diagonal tension counters, and diagonal truss brace.
Multistory and Multi-bay Structures
Multistory and multi-bay structures also use the same bracing principles as
previously discussed with some modifications.
As the structures become taller, only certain types of bracing systems and
materials of construction remain practical from a structural and/or economic
standpoint.
- For example, knee-braces, although appropriate for smaller one- or twostory structures, are not nearly as effective for larger structures.
The horizontal force component within the knee-brace acts on the column
and produces a significant bending moment, which requires a larger
column size.

Larger diagonal braces that go across an entire panel from opposite diagonal
points are found to be much more effective structurally.
- Bracing techniques are generally limited to the exterior wall planes of the
building to permit more flexibility for interior spaces.
-

Diagonals, X-bracing, and K-trussing on multistory frames essentially form


vertical cantilever trusses that transmit lateral loads to the foundation.

Reinforced concrete (or masonry) and braced steel framing used for stairwells
and elevators are often used as part of the lateral force strategy.

Bracing systems must be provided at each story level.

Combinations of bracing, shear wall, and/or rigid frames are used in many buildings.
Larger multi-story buildings contain utility/service cores, which include
elevators, stairs, ducts, and plumbing chases.

4.22

These utility cores are strategically placed to meet functional and structural
criteria.

Because these cores are generally solid to meet fireproofing requirements,


they can often function as excellent lateral resisting elements, in isolation or
as part of a larger overall strategy.

Figure 4.51 (p. 239 of the textbook) illustrates the following common ways of
achieving stability in multistory structures.
X-bracing, eccentric braced frame, K-trussing, shear walls, and rigid frame.
Three-Dimensional Frames
Buildings are three-dimensional frameworks, as indicated in Figure 4.53 (p. 240 of
the textbook).
Each planar frame represents just one of several (or many) frames that
constitute the structure.

A fundamental requirement of geometric stability for a three-dimensional


structure is its ability to resist loads from three orthogonal directions (i.e.
vertically and both directions horizontally).

A three-dimensional frame can be stabilized by use of bracing elements or


shear walls in a limited number of panels in the vertical and horizontal planes.
- In multistory structures, these bracing systems must be provided at each
and every story level.

The exterior walls of a building transfer the wind forces to the roof and floors,
which in turn direct them to the lateral load resisting system (e.g. shear walls or
braced frames).
In wood-framed buildings or buildings with wood roof and floor systems, the
roof and floor sheathing is designed to connect to the supporting framing
members to function as horizontal diaphragms capable of transferring lateral
loads to the lateral load resisting system.

In buildings with concrete roof and floor slabs, the slabs are designed to
function as diaphragms.

If the wood sheathing or reinforced concrete slab is designed to function as a


horizontal diaphragm for lateral forces in one direction, it probably can be
designed to function as a diaphragm for forces applied in the other direction.

4.23

If the roof or floor sheathing is too light or flexible and unable to carry the
diaphragm forces, the horizontal framework must be designed with bracing
similar to braced walls or shear walls.
- Horizontal bracing may consist of tension counters, trusses, or stiff panels
in strategic locations (ref. Figure 4.53, p. 240 of the textbook).

Bracing Configurations
Once the roof plane (or floors) has been configured to function as a diaphragm, a
minimum requirement for stabilizing the roof is three braced (or shear) walls that
are neither all parallel nor concurrent to a common point.
The arrangement of the walls is crucial in resisting loads from multiple
directions.
- More than three braced (or shear) walls are usually provided increasing the
structural stiffness of the framework in resisting lateral displacements.

Braced (or shear) walls are located strategically throughout the structure to
minimize the potential of torsional displacements and moments.
- A common solution is to have two shear walls parallel to one another (a
reasonable distance apart) and a third wall (or perhaps more) perpendicular
to the other two.
-

Figure 4.54 (p. 241 of the textbook) illustrates various shear wall
arrangements some stable and others unstable.

Multistory Structures
In multistory structures, lateral loads (from wind and earthquake forces) are
distributed to each of the roof and floor (diaphragm) levels.
At any given floor level, there must be an adequate number of braced (shear)
walls to transfer the cumulative lateral forces from the diaphragms above.
- Each story level is similar to the simple structures examined previously, in
which the diaphragm load was transferred from the upper level (roof) to the
lower level (ground).
Multistory structures are generally braced with a minimum of four braced planes
per story, with each wall being positioned to minimize torsional moments and
displacements.
Although it is often desirable to position the braced walls in the same position
at each floor level, it is not always necessary.
- The transfer of shear through any one level may be examined as an isolated
problem.

4.24

Example Problems - Lateral Stability/Diaphragms and Shear walls


Problems 4.11 and 4.12
These homework problems will be worked together in class using the homework
problem worksheet available from the website.