Vous êtes sur la page 1sur 3

DAMPERS/SPACERS

VIBRATION DAMPER
4R STOCKBRIDGE

TD-1

Fargo 4-R vibration dampers effectively prevent fatigue damage to conductor and static wires caused by windinduced aeolian vibration.
The 4-R concept improves on the design of the basic Stockbridge damper, significantly increasing the efficiency
of converting wind-induced energy into heat. The improved design employs unequal weights on messengers of
unequal length. This config- uration doubles the number of resonant peaks from two generated by the old-style
Stockbridge damper to four in the improved Fargo 4-R. These additional resonant peaks create an envelope of dynamic response that protects the conductor through the en- tire range of dangerous vibration frequencies.
To assure maximum performance, Fargo utilizes a sophisticated computer simulation whose development has been
verified by decades of testing and field measurements. This computer model identifies the optimum damper placement on the span.
FARGO 4-R VIBRATION DAMPER SYSTEM PROVIDES YOU...

Maximum Protection From WindInduced Conductor Bending Strain

Comprehensive Application Program


For Optimum Performance

The four-resonant peaks include two separate cantilever


response modes and two separate rotational response modes
of the weight and messenger cable. These peaks also provide
maximum energy dissipation to reduce strain over the entire
spectrum of dangerous wind velocities

Provides precise selection and placement through our proprietary computer simulation

Wide frequency response range optimizes protection of


your system
Large 19 strand wire and tight strand lay dissipate energy
more efficiently
Press fit permanent weight attachment technique assures
long-term performance
Contoured surfaces prevent corona discharge

Computer program based on a mathematical model verified by decades of laboratory testing and field vibration
measurements
Precisely identifies the vibration performance characteristics of transmission lines
Determines dangerous frequencies for existing or proposed
spans
Identifies the frequency range requiring damper protection
Identifies proper damper placement for required energy
dissipation
Optimizes placement based on tension and span length
Vibration analysis, with damper size and placement recommendation, provided on request. Contact your Hubbell
Power Systems sales representative for details.

ANDERSON HUBBELL POWER SYSTEMS

FARGO

MAY 2014

DAMPERS/SPACERS
VIBRATION DAMPER
4R STOCKBRIDGE

ALUMINUM

607

TD-2

Fargo 4-R vibration dampers effectively prevent fatigue


damage to conductor and static wires caused by windinduced aeolian vibration.

Messenger Cable: Materials and stranding are selected to obtain the best energy
absorption characteristics. The galvanized
steel messenger is manufactured to rigid
engineering standards.

Weights: Uniquely shaped so that the resonant


peaks are effectively distributed over the desired
frequency range. All weights are given a corrosion-resistant finish and have smooth surfaces
and rounded edges to eliminate possible corona
discharge.

Clamp: The bolted clamp permits easy installation on a wide range of conductor sizes.
Minimum distortion of conductor strands is
controlled by careful anvil and keeper design.

Damper
Catalog
Number (1)

Bare Conductor/Cable
Diameter Range (2)
in. (mm)

607048

0.250 - 0.438
(6.35 - 11.1)
0.439 - 0.858
(11.2 - 21.9)

607051011
6070512

6071012

0.859 - 1.130
(21.8 - 28.7)

6071018

6071513

1.131 - 1.425
(28.7 - 36.2)

6071523

6072014

1.426 - 1.821
(36.2 - 46.3)

6072025

Conductor/Cable Dia. Clamp


Over Armor
Bolt
Rods Range (2)
Torque
in. (mm)
ft-lb
-

20

0.524 - 0.865
(13.3 - 22.0)
0.710 - 1.170
(18.0 - 29.7)

25

25

1.170 - 1.755
(29.7 - 44.6)

40

25

25

1.640 - 2.300
(41.7 - 58.4)

40

40

1.940 - 2.560
(49.3 - 65.0)

40

Dimensions - inches (mm)


A

Weight
Each
lb (kg)

11.1
(282)
16.1
(409)
16.1
(409)
20.0
(508)
20.0
(508)
21.9
(556)
21.9
(556)
24.0
(610)
24.0
(610)

2.38
(60)
2.69
(68)
2.91
(74)
2.91
(74)
3.20
(81)
3.78
(96)
4.20
(107)
5.92
(150)
6.30
(160)

1.75
(44)
1.75
(44)
2.26
(57)
2.26
(57)
2.26
(57)
2.82
(72)
2.82
(72)
3.54
(90)
3.54
(90)

2.8
(1.3)
4.8
(2.2)
5.0
(2.3)
9.0
(4.1)
9.4
(4.3)
15.7
(7.1)
16.0
(7.3)
22.0
(10)
22.5
(10.2)

Std Pkg
Qty
10
6
6
6
6
4
3
3
3

(1) To specify Torque Head/Break Away bolt option, add suffix O to catalog number.
(2) Recommended conductor/cable size range limits. Physical clamp range may be slightly larger.

MAY 2014

ANDERSON HUBBELL POWER SYSTEMS

FARGO

39

FARGO 4-R DAMPER


PLACEMENT AT CONDUCTOR SPAN ENDS

TD-3

1. Typical transmission line conductor/cable span lengths can be protected from Aeolian vibration damage with 1
or 2 dampers per span per wire. Longer spans may require 3 to 4 damper per span per wire.
2. When dampers are required at deadend structure span ends, conservative standard practice is to install a
2-damper pair.
3. Hubbell dampers have aluminum clamping bolts and may be direct mounted on ACSS as well as AAC, AAAC,
ACAR & ACSR conductors.
4. Detailed damper recommendations including quantity required and specific spacings, based on span conditions,
are available via the Select 4-R damper application online at www.HPSApps\Damper
5. Detailed installation installations are packed in each box of dampers supplied.

ANDERSON HUBBELL POWER SYSTEMS

40

FARGO

MAY 2014

Vous aimerez peut-être aussi