Académique Documents
Professionnel Documents
Culture Documents
UniGear ZS3.2
Air-insulated medium voltage switchgear
1
1.1
1.2
1.3
1.3.1
1.3.2
Summary
General
Standards and specifications
Service conditions
Normal service conditions
Special service conditions
3
3
3
3
3
3
2
2.1
2.2
2.3
Technical data
Electrical data
Resistance to internal arc faults
Dimensions and weights
4
4
4
4
3.1
3.2
3.3
3.4
3.5
3.5.1
3.5.2
3.5.3
3.5.4
4
4.1
4.2
4.3
4.4
15
15
15
15
15
5
5.1
5.2
5.3
5.4
5.5
5.6
5.7
17
17
17
18
19
19
19
19
6
6.1
6.1.1
6.1.2
6.2
6.2.1
6.2.2
6.2.3
28
28
28
28
28
28
29
29
6
6
6
7
8
8
9
9
9
6.3
6.3.1
6.3.2
Test procedures
Testing the off-circuit condition
Testing for in-phase condition
29
29
30
7
7.1
7.2
7.3
7.3.1
7.3.2
7.4
34
34
34
35
35
35
35
7.4.2
7.5
7.5.1
7.6
7.6.1
7.6.2
Maintenance
General
Inspection and servicing
Repair
Switchgear surface
Replacement of components
Tests on withdrawable parts with
circuit-breakers of VD4 or HD4
Checking the auxiliary switch
settings on withdrawable parts
Testing of interlock conditions
Tests on the switchgear panel
Auxiliary switch setting on the earthing switch
Spare parts, auxiliary materials and lubricants
Spare parts
Auxiliary materials and lubricants
39
7.4.1
35
36
37
37
37
37
37
1 Summary
1.1 General
The metal-enclosed, three-pole air-insulated switchgear
panels without disconnectors of UniGear ZS3.2 series are factory-assembled, type-tested indoor panels for a rated voltage
of 36/40.5 kV. They are designed as withdrawable module
type panels, and fitted with a single busbar system. The withdrawable parts are fitted with vacuum circuit-breakers.
Details of the technical design and configuration of individual
switchgears, such as the technical data, detailed equipment
lists for the individual panels and comprehensive circuit documentation, etc., can be found in the relevant order documents.
1.2 Standards and specifications
UniGear ZS3.2 switchgear panels comply with the standards
and specifications for factory-assembled and type tested
high voltage switchgears to IEC publications 62271-200 and
62271-100. In addition, in accordance with IEC 60529, the
switchgear panels have degrees of protection
IP 4X for the enclosure and
IP 2X for the partitions.
The corresponding IEC publications, the national or local safety at work regulations and the safety regulations for production materials are to be followed during erection and operation
of these systems. Above and beyond this, the order-related
data from ABB Xiamen Switchgear Co., Ltd. are to be taken
into account.
1.3 Service conditions
1.3.1 Normal service conditions
The switchgears are fundamentally designed for the normal
service conditions for indoor switchgears IEC publication
62271-1. The following limit values, among others, apply:
Ambient temperature:
Maximum
Maximum 24 h average
Minimum (according to
minus 15 indoor class)
Humidity
Highest average value measured
over 24 hours
Relative humidity
95 %
90 %
Remark:
With indoor installation, it is assumed that the humidity within
the enclosure can reach high values, but that there is normally
no condensation on the installed equipment. Condensation
can be prevented by appropriate configuration of the station
building or switchgear room.
The maximum site altitude is 1000 m above sea level.
1.3.2 Special service conditions
According to IEC 62271-100, the manufacturer and user may
agree on special service conditions which deviate from the
normal service conditions. The manufacturer must be consulted in advance about each special service conditions.
Examples are as follows:
+40 C
+35 C
-15 C
2 Technical data
2.1 Electrical data
Standard:
IEC/Chinese GB
Russian GOST
36/40.5
Rated voltage
kV
kV
70/95
kV
170/185
Rated frequency
Hz
190
50
kA
63, 80
kA
25, 31.5
Current of circuit-breaker
Rated short-time current 4 s 1)
kA
25, 31.5
Auxiliary voltage
1) Take the short-circuit withstand capability of the instrument transformers into account separately.
2) Special DC voltages on request.
3) Up to 3150 A at 40C and 2500 A at 55C with forced ventilation.
47
2400
1200
55
Figure 2/2
R(L1)
Y(L2)
2350
2400
B(L3)
Service
Position
Test
Position
450
30
2500
35
A
B
C
D
Circuit-breaker compartment
Low-voltage compartment
Busbar compartment
Cable connection compartment
Circuit-breaker compartment
Busbar compartment
The front and rear doors of the switchgear panels and the
cover plates of the end panels are thoroughly cleaned, treated
to prevent corrosion, and then painted with a high-quality twocoat stoved enamel system in colour RAL7035 (or special
colours as agreed) which are notable after stoving for their
particular insensitivity to impacts and corrosion.
3.3 Compartments in the switchgear panels
Circuit-breaker compartment
(Figures 3/6, 3/9 to 3/13)
The circuit-breaker compartment A fitted with the necessary
guide rails accommodates the withdrawable part 50, which
can be moved between the service position and the test/disconnected position.
06 Switchgear panel structure and equipment installed | UniGear ZS3.2 air-insulated medium voltage switchgear
At the top of the left hand duct, an entry for control cables is
reserved with the free-cut rubber sealing which will keep the protection class IP4X for the whole encloser of the switchgear panel.
3.4 Interlocks/protection against maloperation
(Figures 3/6, 3/10 to 3/12, 6/1 to 6/8)
A series of interlocks are provided to prevent fundamentally
hazardous situations and maloperation, thus protecting both
personnel and the switchgear itself. The interlocks which are
normally individually effective are as follows:
UniGear ZS3.2 air-insulated medium voltage switchgear | Switchgear panel structure and equipment installed 07
08 Switchgear panel structure and equipment installed | UniGear ZS3.2 air-insulated medium voltage switchgear
Advantages
Low residual voltage
Long protection distance
High energy input capacity
Stable U-I characteristics even after multiple strokes
Proof against ageing
Explosion and shatter-resistant design
Pollution resistant and UV-stable
Housing resistant to rough handling
Maintenance free
Stable against shock and vibration
High mechanical resistance
UniGear ZS3.2 air-insulated medium voltage switchgear | Switchgear panel structure and equipment installed 09
14
14.1
14.2
52
54
54.4
54.5
54.6
10 Switchgear panel structure and equipment installed | UniGear ZS3.2 air-insulated medium voltage switchgear
3.1
29
Y(L2)
30.1
1.2
29.1
30
50.2
14, 14.1
6
B(L3)
20.2
50
3.2
30.2
52
HEATING PLATE
23
16
51
9.1
21
17.2
35.2
D
10, 10.1, 10.2
19
10.3
17
A
B
C
D
1
1.1
1.2
3
3.1
3.2
5
6
9.1
10
10.1
10.2
10.3
14
14.1
16
Circuit-breaker compartment
Low-voltage compartment
Busbar compartment
Cable compartment
Enclosure
Pressure relief plate
Control wiring duct
Busbar
Tee-off conductor, busbar side
Tee-off conductor, cable side
Insulated separating plate
Earthing switch
Current transformer
Control wiring plug connector
Control wiring socket
Control wiring plug
Interlocking arm for wiring plug
Earthing switch operation mechanism
Hexagonal shaft
Cable sealing ends
17
17.2
19
20.1
20.2
21
23
28
29
30
30.1
30.2
35.1
35.2
50
50.2
51
52
UniGear ZS3.2 air-insulated medium voltage switchgear | Switchgear panel structure and equipment installed 11
Figure 3/8
30.1
35.3
35.1
35.2
43.1
44
30.2
19.1
30.1
30.2
Figure 3/10
50
50.2
19.1
35.1
35.2
Earthing rail
Hinged shutter system, above
Hinged shutter system, below
35.3
43.1
44
14
14.1
14.2
51
10
12 Switchgear panel structure and equipment installed | UniGear ZS3.2 air-insulated medium voltage switchgear
Figure 3/11
10.1
10.2
10.3
Control
10.1
10.2
10.3
Figure 3/13
Figure 3/14
20.1
25.1
20.2
20.1
20.2
25.1
Spout, above
Spout, below
Contact pin, ...1600 A
UniGear ZS3.2 air-insulated medium voltage switchgear | Switchgear panel structure and equipment installed 13
Figure 3/16
50.2
57.1
57.8
57.2
50.1
50.8
Figure 3/17
50.2
9.2
50
50.3
50.4
9.2
50
50.2
50.3
50.4
Voltage transformer
Frame of the withdrawable part
Front partition plate
Pin (for opening the shutter)
Guide cam
14 Switchgear panel structure and equipment installed | UniGear ZS3.2 air-insulated medium voltage switchgear
50.1
50.2
50.8
57.1
57.2
57.3
57.8
Earthing contact
Front partition plate
Wheel
Upper contact arm
Lower contact arm
Contact system
Embedded pole
crane
Fit lifting ropes of appropriate load capacity with shackles (opening width 30 mm, fastening bore diameter 30 mm)
Maintain an angle of 60 from the horizonta for the ropes leading to the crane hook. The use of a crane cross beam is urgently
recommended
Lifting tackles must never catch on the breaker poles or the part
of the operating mechanism! It is to be ensured that the breaker
do not suffer impacts or other injurious physical stresses during
handling
Only handle the modules by crane with bolted on transport
brackets (see BA 483/02E), suitable lifting ropes and crane har ness
Take care not to allow the modules to tip, as the centre of
gravity is high
When transporting modules by forklift, they must be fastened to
pallets and secured to the lift truck column
When moving the withdrawable part only use the sliding handles
51.2 (e.g. for racking in/out the withdrawable part into/out of the
switchgear panel or for the transport of the truck in the switchgear room). Do not bring any force on the front partition plate
50.2 of the truck
Take care that the catch pins 51.1 on the inter-lock yoke 51 are
engaged with the guiding rails 51.3 in the switchgear when moving-in with-draw able part into the panel
Note:
Do not walk on the roof of the panels (rupture points in pressure
relief devices)!
Place the foundation frame precisely in the specified position on the concrete floor in accordance with the installation
drawing
UniGear ZS3.2 air-insulated medium voltage switchgear | Assembly of the switchgear at site 17
kV
36/40.5
Panel type
UniGear ZS3.2
Panel equipment
Withdrawable
Panel width
mm
1200
mm
2000
mm
1500
Assembly openings:
in ceilings:
Width:
mm
1400
Length:
mm
2800
mm
1400
mm
2600
in doors:
Width:
Height:
2)
Panel weight
kg
Ceiling load
kg/m 2
1100 to 2000
1000
1) Determined by VDE 0101 and the data for maximum panel width.
2) Applies to low voltage compartments of standard height. Add 200 mm for top mounted low voltage compartments and customized low voltage compartments.
1)2)
(Nm)
Lubricant
Thread
Without
M5
2.5
M6
10
M8
25
M 10
50
M 12
86
200
M 20
M8
15
Copper or sheet to
M 10
50
epoxy materials
M 12
70
M 16
110
M 10
90
120
M 20
to voltage transfomer
Oil or grease
170
M 16
3)
20
1) The rated tightening torques for fasteners without lubrication are based on a
coefficient of friction for the thread of 0.14 (the actual values are subject to an
unavoidable, partly not inconsiderable, spread).
2) Rated tightening torques for fasteners with lubrication in accordance with DIN 43 673.
3) Thread and head contact surface lubricated.
Consult the detailed technical documentation for any tightening torques which deviate from the general table (e.g. for
contact systems or switch terminals).
18 Assembly of the switchgear at site | UniGear ZS3.2 air-insulated medium voltage switchgear
Install bushings 29
Note:
(Upper) busbar system:
Insert bushing 29 (phase B/L3) for the lower busbar into
bushing plate 28 from the right in contrast to the procedure
for the other two bushings
Release floor cover and open the control cable duct on the
left hand side
Cut the required holes in floor cover 17 if not already preparedinsert the cover and fasten it
Insert the control cables into the left-hand side control wiring
ducts 1.2
UniGear ZS3.2 air-insulated medium voltage switchgear | Assembly of the switchgear at site 19
C1
C1
33
60
300
2000
(1600)
A
B
C1
C2
E
33
1000
300
33
600
430
30
C2
60
1600
1685
50
C2
M12(4X)
35
480
(130)
C1
1340
665
105
50 300
1000
50
(360)
50
2565
panel
260
(360)
200
940
(280) (280)
220
940
(280) (280)
30
1500
60
300
1200
600
1200
Operator aisle
Inspection aisle
Opening for power cables
Opening for control cables(instead of individual openings, continuous openings or drilled holes are possible)
Points for fixing the switchgear panel on the floor frame
20 Assembly of the switchgear at site | UniGear ZS3.2 air-insulated medium voltage switchgear
(1600)
Ceiling
2565
2000
>4000
1500
Circuit breaker
2400
(820)
1000
35
(130)
(78)
(130)
50
200
5
10
1732
1)
1
2
3
8
300
14
2085
650
Minimum dimensions
Operator aisle
Inspection aisle
Opening for control cables (instead of individual openings, continuous
openings or drilled holes are possible)
5 Openings for power cables
7 Panel type UniGear ZS3.2 ...31.5 kA
8
9
10
11
12
14
11
12
Power cables
Projecting of floor frame: 5-12 mm above finished floor level
Conductor to main earthing bar
Screen 50 mm to 60 mm
Hight of the cable cellar, to be determined by the client
Guiding ramp, optional (recommended for circuit-breaker insertion)
UniGear ZS3.2 air-insulated medium voltage switchgear | Assembly of the switchgear at site 21
Figure 5/5
1.5
1.11
28
(1.9)
1.10
1.3
1.3
1.5
(1.9)
1.10
1.11
28
Figure 5/6
Figure 5/7
3.11
3.1
20.1
22 Assembly of the switchgear at site | UniGear ZS3.2 air-insulated medium voltage switchgear
Figure 5/8: Bushings with busbar mountings for busbar system with double
D-profile, tee-off ...1600 A.
Figure 5/9: Bushings with busbar mountings for busbar system with double
D-profile, tee-off ...2000 A to 3150 A.
Figure 5/8
3
3.1
25.5
28
29
29.2
84
Figure 5/9
Busbar
Tee-off conductor, busbar side
Sealing ring
Bushing plate
Busbar bushing
Busbar mounting for double conductor
Partitioning
UniGear ZS3.2 air-insulated medium voltage switchgear | Assembly of the switchgear at site 23
8.3
8.4,8.5,8.6
8.7
8.3
8.7
8.3
8.4
8.5
8.6
8.7
24 Assembly of the switchgear at site | UniGear ZS3.2 air-insulated medium voltage switchgear
29.2
29.4
29.3
3.12
a) Detail of a busbar bushing, sectional view. Always check that there is proper contact
between the metal tube in the bushing and the busbar via the contact spring.
3.12 Busbar section (length)
29.1 Busbar mounting for single conductor
29.2 Busbar mounting for double conductor
29.3 Contact spring
29.4 Metal tube
Caution:
The contact arm springs 29.3 or 8.3 must be
inserted during the installation of the busbars.
These contact springs prevent damages by glow
discharges inside the bushings on Live busbars.
UniGear ZS3.2 air-insulated medium voltage switchgear | Assembly of the switchgear at site 25
3
3.1
3.5
3.6
29
58
58.5
163
164
165
Busbar
Tee-off conductor
Spacer plate, 15 mm
Spacer plate, 10 mm
Busbar bushing
Insulation cover
Lid of cover
M10 socket head bolt
M10 nut
10 mm dished washer
a) Arrangement for tee-off current up to 1600 A and 1600 A or 3150 A busbar current.
Figure 5/16
During assembly, cut out the insulation cover and lid to fit cross-section of the feeder or busbar.
3
3.1
3.5
3.6
58
58.5
163
164
165
Busbar
Tee-off conductor
Spacer plate, 15 mm
Spacer plate, 10 mm
Insulation cover
Lid of cover
M10 socket head bolt
M10 nut
10 mm dished washer
26 Assembly of the switchgear at site | UniGear ZS3.2 air-insulated medium voltage switchgear
Figure 5/17: Insulating covers for busbars | Figure 5/18: Guiding ramp for
circuit-breaker insertion, optional. The rail on the guiding ramp
must be in line with the guiding rail in the UniGear ZS3.2 panel
Figure 5/17
58.5
Figure 5/18
UniGear ZS3.2 air-insulated medium voltage switchgear | Assembly of the switchgear at site 27
Check the general condition of the switchgear for detrimental circumstances of all kinds
Perform a visual examination of the switching devices, withdrawable parts, isolating contacts, insulating parts, etc
Instruct the local operators in the fundamental details of regular handling of the switchgear
power cables
auxiliary cables
Remove any existing earthing and short-circuiting connections in the critical switching area
Manual withdrawal from the service position into the test/disconnected position:
Turn the lever clockwise through approx. 180 until the stop
is reached to close the earthing switch, or anti-clockwise
until the stop is reached to open the earthing switch
Observe the mechanical/electrical switch position indicator
Remove operating lever 122. Slide 14.2 remains open if the
earthing switch is in the closed position
Insertion from the removed position into the test/ disconnected position:
When the switchgear is in operation, observe all the operating data and condition indications in the secondary area and
watch for any irregulatities
A distinction must be made between the low impedance system and the high impedance system. For further details, see
draft standard IEC 61243 Part 5.
Note:
The only permissible indicators are those which satisfy
the requirements of the IEC standards and correspond to the technical design of the indication system
in the relevant switchgear!
Note:
The measuring point sockets must on no account be short-circuited, except for voltage tests on the installation (e.g. at
power frequency voltage and/or impulse voltage).
Testing for the off-circuit condition is effected using a plugin
indicator at the corresponding socket pairs located among the
controls on the panels.
Use of the indicator:
Always follow the details given in the instructions for the particular indicator for your switchgear system.
Interface testing:
Perform an interface test as a functional test on all coupling
components, e.g. with interface tester KSP
After commissioning of the system, check all posi-tion indicators and displays for irregularities.
Note:
For voltage testing at power frequency and/or impulse voltage:
Only short-circuit the sockets for the capacitive voltage indicator on the relevant panel for the duration of the test
Always follow the details given in the instructions for the particular indicator for your switchgear system.
6.3.2 Testing of in-phase condition
Testing of the in-phase condition, e.g. when there is more
than one incoming feeder, can be carried out with a suitable
phase comparator coupled to the measuring point sockets of
the capacitive voltage indication system (if fitted).
Caution:
Operate truck slowly, be careful overturning Caused
by inertia of fast movement!
Test procedure:
Figure 6/1: Withdrawable part with circuit-breaker, VD4, operating mechanism side
Figure 6/2: Charging the spring energy storage mechanism manually by moving the inserted lever up and down
Figure 6/1
Figure 6/2
51.1
51.2
51
52
54.1
55.8
55.6
128
50.4
50.4
50.6
50.7
51
51.1
51.2
50.7
Guide cam
Front cover plate, right hand side
Front coverplate, left hand side
nterlock yoke
Catch pin spring loaded
Sliding handle
52
54.1
55.4
55.5
55.6
55.7
Spindle
Link rod
Switch position indicator
Operating cycle counter
Socket for charging lever
Rating plate
Figure 6/3: Fitting the hand cranck (against spring-loaded intermediate plate)
to move the truck inside the panel clockwise towards the service
position, and anti-clockwise from the service position towards the
test/disconnected position.
Figure 6/4: Manual operation of the circuit-breaker, by turning the double bit
key approx. 15 clockwise (ON), or approx. 15 anti-clockwise (OFF)
Figure 6/5: Interlock yoke with sliding handles which will be moved inwards to
release the circuit-breaker part for withdraw from the panel
Figure 6/6: Withdrawable part in service position, interlock yoke engaged, control
wiring pluged-in and engaged.
Figure 6/4
Figure 6/3
146
52.1
52
54
52
Spindle
52.1 Square spigot
146 Hand cranck
Figure 6/5
Figure 6/6
51.3
10.4
145
10.5
54
51
51
10
10.1
10.2
51.2
51.4
51.1
51
51.1
51.2
51.4
Interlock yoke
Catch pin, spring loaded
Sliding handle
Blocking shaft (interlocking circuit-breaker and earthing switch)
10
10.1
10.2
10.4
10.5
51
51.3
54
128
145
146
122
Figure 6/8
122
128
145
146
Figure 6/9
14.3
14.1
14.4
14.2
14.5
Figure 6/10: Active part of the earthing switch, EK6 mounted in the cable connection
compartment shown in open position
Figure 6/11: Earthing switch, EK6 mounted in the cable connection compartment
shown in closed position
Figure 6/12: Bevel gear mechanism and earthing switch, EK6 in open position
Figure 6/10
6.1
6.3
6.4
6.7
6.6
14.1
6.10
5
5
6.1
6.3
6.4
6.6
Figure 6/11
58
6.10
6.4
14.1
6.2
6.4
6.5
6.2
6.10
14.1
58
6.5
Figure 6/12
6.1
6.5
6.7
6.6
6.8
14.1
6.1
6.5
6.6
6.7
6.8
14.1
Bearing bracket
Earthing conductor
Bevel gear mechanism (not belonging to the earthing switch)
Operating shaft
Driver lever
Hexagonal shaft
7 Maintenance
7.1 General
Maintenance serves to preserve trouble-free operation and
achieve the longest possible working life of the switchgear. In
accordance with DIN 31 051, it comprises the following closely related activities:
Inspection: Determination of the actual condition
Servicing: Measures to preserve the specified condition
Repair:
Measures to restore the specified condition
Note:
When carrying out all maintenance work, the regulations in the
country of installation must be strictly complied with.
with the relevant safety regulations to DIN VDE/IEC, and secure it against reconnection.
The inspection may become necessary at shorter intervals
under unusual service conditions (including advers climatic
conditions) and/or particularly injurious environmental influences (e.g. heavy pollution and aggressive atmosphere).
The inspection should include but not be limited to the following:
Servicing
Basic servicing activities, and those which may be found necessary during inspections, include the following:
bon tetrachloride!
Should external discharges occur as a result of condensation, application of a thin silicone film on the surface
concerned is often effective as a temporary remedy. It is
advisable to request advice from the ABB after-sales service
department on permanent solutions to such unusual problems
Check that the bolt connections at the contact points in the
busbar system and the earth connections are tight, and that
the isolating contact system functions correctly
Regrease the contact points and mechanism of the withdrawable part insertion system as necessary, or, when lubrication is inadequate or missing, thoroughly clean the areas
concerned and regrease with Isoflex Topas NB52 lubricant
Slide the two inner annular tension springs 57.6 facing the
breaker pole to a position beside the two outer annular
tension springs, thus releasing contact system 57.7, and
remove the contact sys tem from isolating contact arm
57.1/57.2
7.3 Repair
7.3.1 Switchgear surface
Carefully remove any white rust on chromium plated functional parts and rust on phosphatized parts with a wire
brush or Scotch Sprite, and clean with a dry cloth. Then
evenly grease the parts (with Isoflex Topas NB52)
Note:
The set installation position of isolating contact arms
57.1/57.2 must not be changed by the improper use of force.
Replacement of the contact pins:
(Figure 3/13, 3/17 and 3/18)
After any required replacement of contact pins 25.1/25.2,
these are to be retightened using socket head screws:
7 Maintenance
In the inspection and test operation, the withdrawable part is
to be moved with the crank fitted.
1. Settings in the area of the test/disconnected position
Auxiliary switch 10.4 (S8) must then operate when the hand
crank still has 60 of turn to reach the stop.
Slowly insert the withdrawable part from the test/disconnected position towards the service position until auxiliary
switch 10.4 (S8) just operates
In this position, it must still just be possible to move the ONOFF operating shaft 54. For this test, the function of the
blocking magnet must be deactivated manually.
This condition ensures that the electrical interlock becomes
active before the mechanical interlock in the motion sequence
involved.
2. Settings in the area of the service position
Auxiliary switch 10.5 (S9) must then operate when the hand
crank has a remaining angle of 60 to turn up to the stop.
7.4.2 Testing of interlock conditions
(Figures 6/1 to 6/9)
1. The withdrawable part must only be movable from the test/
disconnected position into the ser vice position when the
circuit-breaker is open and the earthing switch is open.
Check the following conditions individually:
With the earthing switch closed, insertion of the withdrawable part towards the service position must be blocked
after only two clockwise turns of the crank
The enable conditions for the movement into the test/disconnected position apply accor-dingly, in this case established by auxiliary switch 10.4 (S8)
With the withdrawable part in the test/ disconnected position, it must be possible to press slide 14.2 in front of the
earthing switch drive shaft 14.1 downwards to the opening
position. The earthing switch can then be operated
Standard colour
RAL 7035
1-kg-box
1 Spray tin
Part no.
(order ref.)
GCE0007249P0100
GCE0007707P0100
GCEA901002P0102
GCE0007706P0100
GCEA901006P0102
GCE9014060R0103
GCE0007895P0100
7 Maintenance
Figure 7/1: Contact system sample for 2000 A to 3150 A | Figure 7/2: Sliding
the contact system onto the auxiliary arbour with the rear end first,
schematic representation here for 1600 A | Figure 7/3: Contact shift
on auxiliary arbour for 2000 A to 3150 A
Figure 7/4: Sliding of the contact system from the auxiliary arbour onto the
contact arm and engaging it here
Figure 7/1
Figure 7/2
1
1>
2>
57.3
127
127.1
Figure 7/3
130.1
57.13
57.6
57.7
130
130.1
127.1
Figure 7/4
130
57.13
57.6
57.7
127
57.3
UniGear ZS3.2 air-insulated medium voltage switchgear | Product quality and environmental protection 39
G.
Contact us