EMPIRE COOLING SOLUTIONS PRIVATE LIMITED

JOB :
NMDC -KUMAARASAMI IRON ORE PROJECT
Location :
BELLARY - DONIMALAI
AREA :
SUBSTATION - 1
Unit in Ft. :
W
Length
Area
Height
Size :
2220
16.4
Clean Room Class :
UC
Filtration : not required
Pressure Gradient :
1.5 mm WG Above At.Pr.
Lighting Load :
Watts
Occupancy :
10 Nos.
Equipment Load :
0 HP
CFM / Person :
5
Correction Factor :
12
Coil By Pass Factor. :
0.12 4 Row Deep Coil.
Fresh Air Changes/Hr.:
1
Room Air Changes/Hr.:
0 CFM
Area In
Sun Gain / Temp.
'U'Factor
Sq.ft.
In Deg. F
Glass W
0
158
0.56
Glass E
0
11
0.56
Glass N
0
39
0.56
Glass S
0
11
0.56
Glass NW
0
148
0.56
Glass SW
0
66
0.56
Glass NE
0
11
0.56
Glass SE
0
11
0.56
Eq.Temp.
Diff. :
Wall W
24
0.34
Wall E
30
0.34
Wall N
16
0.34
Wall S
28
0.34
Wall NW
949.03
18
0.34
Wall SW
0
26
0.34
Wall NE
210.9
22
0.34
Wall SE
0
30
0.34
Roof Exposed
0
47
0.12
Roof SHA
0
20
0.40
All Glass
0
31.6
1.13
Partition
1194.36
26.6
0.43
PartitionGl.
0
26.6
0.80
Ceiling
26.6
0.43
Floor
26.6
0.43
Out.Air
607
31.6
0.12 B.F.
1.08
People
10
No. X
255 Gain/Person.
HP
0
No. X
2545 Gain/HP
Lights
0
Watts X
1.25 X
3.40
Appliance
98,975
Watts X
3.40
Product Load
ROOM SENSIBLE HEAT SUBTOTAL :
Safety Factor :
10.0%
Fan HP :
0.000
Fan KW :
0.00
ROOM SENSIBLE HEAT :

Volume
36408

SUMMER
DB deg.F
Out Side
105
Room
73.4
T :
31.6
VENTILATION:
10 People
2220 Sq.ft.

Sun Time 16 Hours


4.00pm Date :03/09/2012
%RH
DP
GR/LB

WB deg.F
77

28
55
XXX

XXX

16.4 HT.

Sensible Heat Factor ( SHF ) :


398856 Room Sensible Heat
403136 Room Total Heat
Apparatus Dew Point. :( A.D.P.)

Heat
Btu / Hr.
0
0
0
0
0
0
0
0

Dehumidified Rise = (1-B.F.)


0.88
Dehumidified CFM =

398856
1.08

x
x

Gr/Lb :
5 CFM/Per.
1
Select :

50
607
607

0.99

Indicated =
Selected =

55
52

(RM.TEMP-A.D.P.)
21.4
R.S.H.
18.83

96
64
32

Deh. Rise

Dehum. CFM =
Supply Air CFM =
0
0
Coil By Pass CFM =
0
CFM / Sq.ft. =
0
Sq.ft. / TR =
5808 ROOM LATENT GAIN :
0 Infiltration
32 gr/lb
0.68
1578 Out.Air
607
32
0.12 B.F.
0.68
0 People
10 NO. X
245 Gain/Person
0 Steam
Lb/Hr. X
1080
0 Vap.Trans.
0
0.01
32
gr/lb
0 Permeation Load
0
0.1
32
0.06
13661
ROOM LATENT HEAT SUBTOTAL:
0
Safety Factor :
10%
0
ROOM LATENT HEAT :
0
ROOM TOTAL HEAT :
2485 Out Side Air Heat : x
T x
(1 - B.F.) x Factor = BTU / Hr.
2550 Sensible
606.8
31.6
T
0.88
1.08
0 Latent
606.8
32 gr/lb
0.88
0.68
0
GRAND TOTAL HEAT SUBTOTAL :
336515
Safety Factor :
0
0 Roof Sun
32
0
362597
0
36260 Roof SHA
8
0
0 Ceiling
26.6
0
0
GRAND TOTAL HEAT :
398856
LOAD TR :
SUMMARY

SUPPLY AIR CFM


Load TR
TR SELECTED
MACHINE SELECTED
20 % Safety Factor Considered

19610.85 Equals to

49.03 TR

36.08
44.00
22 TR X 2 Nos Working + 22 TR X 1 No Stand By

18.83

19610.85
19610.85
0
9
62
0
1584
2450
0
0
0
4034
245
4279
403136
18224
11619
432979
0
0
0
0
0
432979
36.08

EMPIRE COOLING SOLUTIONS PRIVATE LIMITED


JOB :
NMDC -KUMAARASAMI IRON ORE PROJECT
Location :
BELLARY - DONIMALAI
AREA :
SUBSTATION - 1
Unit in Ft. :
W
Length
Area
Height
Size :
2220
16.4
Clean Room Class :
UC
Filtration : not required
Pressure Gradient :
1.5 mm WG Above At.Pr.
Lighting Load :
Watts
Occupancy :
5 Nos.
Equipment Load :
0 HP
CFM / Person :
5
Correction Factor :
12
Coil By Pass Factor. :
0.12 4 Row Deep Coil.
Fresh Air Changes/Hr.:
1
Room Air Changes/Hr.:
0 CFM
Area In
Sun Gain / Temp.
'U'Factor
Sq.ft.
In Deg. F
Glass W
0
158
0.56
Glass E
0
11
0.56
Glass N
0
39
0.56
Glass S
0
11
0.56
Glass NW
0
148
0.56
Glass SW
0
66
0.56
Glass NE
0
11
0.56
Glass SE
0
11
0.56
Eq.Temp.
Diff. :
Wall W
24
0.34
Wall E
30
0.34
Wall N
16
0.34
Wall S
28
0.34
Wall NW
949.03
18
0.34
Wall SW
0
26
0.34
Wall NE
210.9
22
0.34
Wall SE
0
30
0.34
Roof Exposed
0
47
0.12
Roof SHA
0
20
0.40
All Glass
0
20.6
1.13
Partition
1194.36
15.6
0.43
PartitionGl.
0
15.6
0.80
Ceiling
15.6
0.43
Floor
15.6
0.43
Out.Air
607
20.6
0.12 B.F.
1.08
People
5
No. X
255 Gain/Person.
HP
0
No. X
2545 Gain/HP
Lights
0
Watts X
1.25 X
3.40
Appliance
98,975
Watts X
3.40
Product Load
ROOM SENSIBLE HEAT SUBTOTAL :
Safety Factor :
10.0%
Fan HP :
0.000
Fan KW :
0.00
ROOM SENSIBLE HEAT :

Volume
36408

MONSOON
DB deg.F
Out Side
94
Room
73.4
T :
20.6
VENTILATION:
5 People
2220 Sq.ft.

Sun Time 16 Hours


4.00pm Date :03/09/2012
%RH
DP
GR/LB

WB deg.F
78

50
55
XXX

XXX

16.4 HT.

Sensible Heat Factor ( SHF ) :


390288 Room Sensible Heat
394408 Room Total Heat
Apparatus Dew Point. :( A.D.P.)

Heat
Btu / Hr.
0
0
0
0
0
0
0
0

Dehumidified Rise = (1-B.F.)


0.88
Dehumidified CFM =

390288
1.08

x
x

Gr/Lb :
5 CFM/Per.
1
Select :

25
607
607

0.99

Indicated =
Selected =

55
52

(RM.TEMP-A.D.P.)
21.4
R.S.H.
18.83

120
64
56

Deh. Rise

Dehum. CFM =
Supply Air CFM =
0
0
Coil By Pass CFM =
0
CFM / Sq.ft. =
0
Sq.ft. / TR =
5808 ROOM LATENT GAIN :
0 Infiltration
56 gr/lb
0.68
1578 Out.Air
607
56
0.12 B.F.
0.68
0 People
5 NO. X
245 Gain/Person
0 Steam
Lb/Hr. X
1080
0 Vap.Trans.
0
0.01
56
gr/lb
0 Permeation Load
0
0.1
56
0.06
8012
ROOM LATENT HEAT SUBTOTAL:
0
Safety Factor :
10%
0
ROOM LATENT HEAT :
0
ROOM TOTAL HEAT :
1620 Out Side Air Heat : x
T x
(1 - B.F.) x Factor = BTU / Hr.
1275 Sensible
606.8
20.6
T
0.88
1.08
0 Latent
606.8
56 gr/lb
0.88
0.68
0
GRAND TOTAL HEAT SUBTOTAL :
336515
Safety Factor :
0
0 Roof Sun
32
0
354807
0
35481 Roof SHA
8
0
0 Ceiling
15.6
0
0
GRAND TOTAL HEAT :
390288
LOAD TR :
SUMMARY

SUPPLY AIR CFM


Load TR
TR SELECTED
MACHINE SELECTED
20 % Safety Factor Considered

19189.56 Equals to

47.97 TR

35.55
44.00
22 TR X 2 Nos Working + 22 TR X 1 No Stand By

18.83

19189.56
19189.56
0
9
62
0
2773
1225
0
0
0
3998
123
4120
394408
11880
20334
426623
0
0
0
0
0
426623
35.55

EMPIRE COOLING SOLUTIONS PRIVATE LIMITED


JOB :
NMDC -KUMAARASAMI IRON ORE PROJECT
Location :
BELLARY - DONIMALAI
AREA :
SUBSTATION - 2
Unit in Ft. :
W
Length
Area
Height
Size :
1700
16.4
Clean Room Class :
UC
Filtration : not required
Pressure Gradient :
1.5 mm WG Above At.Pr.
Lighting Load :
Watts
Occupancy :
5 Nos.
Equipment Load :
0 HP
CFM / Person :
5
Correction Factor :
12
Coil By Pass Factor. :
0.12 4 Row Deep Coil.
Fresh Air Changes/Hr.:
1
Room Air Changes/Hr.:
0 CFM
Area In
Sun Gain / Temp.
'U'Factor
Sq.ft.
In Deg. F
Glass W
0
158
0.56
Glass E
0
11
0.56
Glass N
0
39
0.56
Glass S
0
11
0.56
Glass NW
0
148
0.56
Glass SW
0
66
0.56
Glass NE
0
11
0.56
Glass SE
0
11
0.56
Eq.Temp.
Diff. :
Wall W
421.79
24
0.34
Wall E
30
0.34
Wall N
0
16
0.34
Wall S
342.71
28
0.34
Wall NW
0
18
0.34
Wall SW
0
26
0.34
Wall NE
0
22
0.34
Wall SE
0
30
0.34
Roof Exposed
0
47
0.12
Roof SHA
0
20
0.40
All Glass
0
31.6
1.13
Partition
1672.1
26.6
0.43
PartitionGl.
0
26.6
0.80
Ceiling
26.6
0.43
Floor
26.6
0.43
Out.Air
465
31.6
0.12 B.F.
1.08
People
5
No. X
255 Gain/Person.
HP
0
No. X
2545 Gain/HP
Lights
0
Watts X
1.25 X
3.40
Appliance
45,808
Watts X
3.40
Product Load
ROOM SENSIBLE HEAT SUBTOTAL :
Safety Factor :
10.0%
Fan HP :
0.000
Fan KW :
0.00
ROOM SENSIBLE HEAT :

Volume
27880

SUMMER
DB deg.F
Out Side
105
Room
73.4
T :
31.6
VENTILATION:
5 People
1700 Sq.ft.

Sun Time 16 Hours


4.00pm Date :03/09/2012
%RH
DP
GR/LB

WB deg.F
77

28
55
XXX

XXX

16.4 HT.

Sensible Heat Factor ( SHF ) :


203231 Room Sensible Heat
205791 Room Total Heat
Apparatus Dew Point. :( A.D.P.)

Heat
Btu / Hr.
0
0
0
0
0
0
0
0

Dehumidified Rise = (1-B.F.)


0.88
Dehumidified CFM =

203231
1.08

x
x

Gr/Lb :
5 CFM/Per.
1
Select :

25
465
465

0.99

Indicated =
Selected =

55
52

(RM.TEMP-A.D.P.)
21.4
R.S.H.
18.83

96
64
32

Deh. Rise

Dehum. CFM =
Supply Air CFM =
3442
0
Coil By Pass CFM =
0
CFM / Sq.ft. =
3263
Sq.ft. / TR =
0 ROOM LATENT GAIN :
0 Infiltration
32 gr/lb
0.68
0 Out.Air
465
32
0.12 B.F.
0.68
0 People
5 NO. X
245 Gain/Person
0 Steam
Lb/Hr. X
1080
0 Vap.Trans.
0
0.01
32
gr/lb
0 Permeation Load
0
0.1
32
0.06
19126
ROOM LATENT HEAT SUBTOTAL:
0
Safety Factor :
10%
0
ROOM LATENT HEAT :
0
ROOM TOTAL HEAT :
1903 Out Side Air Heat : x
T x
(1 - B.F.) x Factor = BTU / Hr.
1275 Sensible
464.67
31.6
T
0.88
1.08
0 Latent
464.67
32 gr/lb
0.88
0.68
0
GRAND TOTAL HEAT SUBTOTAL :
155747
Safety Factor :
0
0 Roof Sun
32
0
184755
0
18476 Roof SHA
8
0
0 Ceiling
26.6
0
0
GRAND TOTAL HEAT :
203231
LOAD TR :
SUMMARY

SUPPLY AIR CFM


Load TR
TR SELECTED
MACHINE SELECTED
20 % Safety Factor Considered

9992.38 Equals to

24.98 TR

19.05
22.00
11 TR X 2 Nos Working + 11 TR X 1 No Stand By

18.83

9992.38
9992.38
0
6
89
0
1213
1225
0
0
0
2438
123
2561
205791
13955
8898
228644
0
0
0
0
0
228644
19.05

EMPIRE COOLING SOLUTIONS PRIVATE LIMITED


JOB :
NMDC -KUMAARASAMI IRON ORE PROJECT
Location :
BELLARY - DONIMALAI
AREA :
SUBSTATION - 2
Unit in Ft. :
W
Length
Area
Height
Size :
1700
16.4
Clean Room Class :
UC
Filtration : not required
Pressure Gradient :
1.5 mm WG Above At.Pr.
Lighting Load :
Watts
Occupancy :
5 Nos.
Equipment Load :
0 HP
CFM / Person :
5
Correction Factor :
12
Coil By Pass Factor. :
0.12 4 Row Deep Coil.
Fresh Air Changes/Hr.:
1
Room Air Changes/Hr.:
0 CFM
Area In
Sun Gain / Temp.
'U'Factor
Sq.ft.
In Deg. F
Glass W
0
158
0.56
Glass E
0
11
0.56
Glass N
0
39
0.56
Glass S
0
11
0.56
Glass NW
0
148
0.56
Glass SW
0
66
0.56
Glass NE
0
11
0.56
Glass SE
0
11
0.56
Eq.Temp.
Diff. :
Wall W
421.79
24
0.34
Wall E
30
0.34
Wall N
16
0.34
Wall S
342.71
28
0.34
Wall NW
0
18
0.34
Wall SW
0
26
0.34
Wall NE
0
22
0.34
Wall SE
0
30
0.34
Roof Exposed
0
47
0.12
Roof SHA
0
20
0.40
All Glass
0
20.6
1.13
Partition
1672.1
15.6
0.43
PartitionGl.
0
15.6
0.80
Ceiling
15.6
0.43
Floor
15.6
0.43
Out.Air
465
20.6
0.12 B.F.
1.08
People
5
No. X
255 Gain/Person.
HP
0
No. X
2545 Gain/HP
Lights
0
Watts X
1.25 X
3.40
Appliance
45,808
Watts X
3.40
Product Load
ROOM SENSIBLE HEAT SUBTOTAL :
Safety Factor :
10.0%
Fan HP :
0.000
Fan KW :
0.00
ROOM SENSIBLE HEAT :

Volume
27880

MONSOON
DB deg.F
Out Side
94
Room
73.4
T :
20.6
VENTILATION:
5 People
1700 Sq.ft.

Sun Time 16 Hours


4.00pm Date :03/09/2012
%RH
DP
GR/LB

WB deg.F
78

50
55
XXX

XXX

16.4 HT.

Sensible Heat Factor ( SHF ) :


193802 Room Sensible Heat
197273 Room Total Heat
Apparatus Dew Point. :( A.D.P.)

Heat
Btu / Hr.
0
0
0
0
0
0
0
0

Dehumidified Rise = (1-B.F.)


0.88
Dehumidified CFM =

193802
1.08

x
x

Gr/Lb :
5 CFM/Per.
1
Select :

25
465
465

0.98

Indicated =
Selected =

55
52

(RM.TEMP-A.D.P.)
21.4
R.S.H.
18.83

120
64
56

Deh. Rise

Dehum. CFM =
Supply Air CFM =
3442
0
Coil By Pass CFM =
0
CFM / Sq.ft. =
3263
Sq.ft. / TR =
0 ROOM LATENT GAIN :
0 Infiltration
56 gr/lb
0.68
0 Out.Air
465
56
0.12 B.F.
0.68
0 People
5 NO. X
245 Gain/Person
0 Steam
Lb/Hr. X
1080
0 Vap.Trans.
0
0.01
56
gr/lb
0 Permeation Load
0
0.1
56
0.06
11216
ROOM LATENT HEAT SUBTOTAL:
0
Safety Factor :
10%
0
ROOM LATENT HEAT :
0
ROOM TOTAL HEAT :
1241 Out Side Air Heat : x
T x
(1 - B.F.) x Factor = BTU / Hr.
1275 Sensible
464.67
20.6
T
0.88
1.08
0 Latent
464.67
56 gr/lb
0.88
0.68
0
GRAND TOTAL HEAT SUBTOTAL :
155747
Safety Factor :
0
0 Roof Sun
32
0
176184
0
17618 Roof SHA
8
0
0 Ceiling
15.6
0
0
GRAND TOTAL HEAT :
193802
LOAD TR :
SUMMARY

SUPPLY AIR CFM


Load TR
TR SELECTED
MACHINE SELECTED
20 % Safety Factor Considered

9528.79 Equals to

23.82 TR

18.50
22.00
11 TR X 2 Nos Working + 11 TR X 1 No Stand By

18.83

9528.79
9528.79
0
6
92
0
2123
1225
0
0
0
3348
123
3471
197273
9097
15571
221941
0
0
0
0
0
221941
18.50