LARSEN & TOUBRO LIMITED

ECC Division - GES


PROJECT:

TITLE:

SIDRA MEDICAL AND RESEARCH CENTER,QATAR


HOSPITAL BUILDING - DESIGN OF SECOND FLOOR BEAMS &
SLABS

DOCUMENT NO

DATE

1861B-CS-05-00320

01/07/09

DESIGNED

CHECKED

RVR / UMA

CSR/MDS

2.0 BEAM SLAB DESIGN


(AT SECOND FLOOR LEVEL IN TOWER BLOCK OF HOSPITAL BUILDING)

SHEET

LARSEN & TOUBRO LIMITED


ECC Division - GES
PROJECT:

TITLE:

SIDRA MEDICAL & RESEARCH CENTER, DOHA


HOSPITAL BUILDING - DESIGN OF SECOND FLOOR BEAMS &
SLABS

DOCUMENT NO

DATE

1861B-CS-05-00320

1/7/09

DESIGNED CHECKED

SHEET

RVR / UMA

CSR/MDS

DESIGN OF BEAM SLABS


In this section the design of slab for beam slab portion of part -3 is presented. This portion consist of
oneway slabs and twoway slabs supported by main beams and secondary beams. Slab thickness
considered is 200 mm. Analysis and design carried out as per BS 8110.
Unit weight of the concrete
Loads Considered
Superimposed Dead load
Live load

3
25 kN/m

=
=

2
5.5 kN/m
2
4 kN/m

LARSEN & TOUBRO LIMITED


ECC Division - GES
PROJECT:

TITLE:

DOCUMENT NO

SIDRA MEDICAL & RESEARCH CENTER, DOHA

1861B-CS-05-00320

HOSPITAL BUILDING - DESIGN OF SECOND FLOOR BEAMS &


SLABS

DESIGNED CHECKED
RVR/UMA

DATE
1/7/09

SHEET

CSR/MDS

Design of slab panels S7,S8 AND S10,S11


The design moments & shear forces are arrived based on clause 3.5.2.4 of BS 8110 Part 1 provisions
by considering 1m wide strip of the one way slab.
Loads are as follows.
Slab thickness
Self weight
Super imposed dead load
(a) Total Dead load (DL)
(b) Live load (LL)

=
=
=
=
=

200
5
5.5
10.5
4

=
=

2
21.1 kN/m
2
14.5 kN/m

Design factored load (Fu) =1.4DL+1.6LL


Load for serviceability condition, (Fs) =DL+LL

Moment and Shear coefificients (Table 3.12, pg 37) of BS8110

S7

S8

-0.086

0.075

0.063

5.2m

L18= 5.2m

-0.063

L19=

(a) Moment coefficients

0.46

L19=

S7

S8

0.6

5.2m

L18= 5.2m

(b) Shear coefficients

0.5

mm
kN/m2
kN/m2
kN/m2
kN/m2

LARSEN & TOUBRO LIMITED


ECC Division - GES
PROJECT:

TITLE:

DOCUMENT NO

SIDRA MEDICAL & RESEARCH CENTER, DOHA

1861B-CS-05-00320

HOSPITAL BUILDING - DESIGN OF SECOND FLOOR BEAMS &


SLABS

DESIGNED CHECKED
RVR/UMA

Bending moment and shear force diagram


(a) Strength case
Bending moment = (FuxL) x L x moment coefficient
-35.4

-48

35.4
42.2
(a) Bending Moment(kN-m)
Shear Force = (FuxL) x shear coefficient
50.12

65.4

54.48

65.376
(b) Shear Force(kN)
(b) Seviceability case
Bending moment = (FsxL) x L x moment coefficient
-33

-24.4

29.0
24.4
(a) Bending Moment(kN-m)
Design for Flexure
Slab section is designed for maximum moment from the above calculation.
2
Grade of Concrete, fcu
=
40 N/mm
2
Yield Strength of Steel, fy
=
420 N/mm
Cover to reinforcement
Slab thickness, D
(a) Top Reinforcement (main bars)
Maximum Hogging moment
Effective depth, d
Breadth, b

30 mm

200 mm

=
=
=

48.4 kN-m
162 mm

1000 mm

CSR/MDS

DATE
1/7/09

SHEET

LARSEN & TOUBRO LIMITED


ECC Division - GES
PROJECT:

DOCUMENT NO

SIDRA MEDICAL & RESEARCH CENTER, DOHA

TITLE:

1861B-CS-05-00320
DESIGNED CHECKED

HOSPITAL BUILDING - DESIGN OF SECOND FLOOR BEAMS &


SLABS

K = (Mu / fcub * d

2)

Z = Min[0.95d, d{0.5 + sqrt(0.25-K/0.9)}]


Area of Steel required, (Mu/(0.87fy*z)

=
=
=

Req%Pt
Min. Ast required (0.13%)
Ast provided
16

Provide

=
=
150

mm dia bar at

=
=
=

Z = Min[0.95d, d{0.5 + sqrt(0.25-K/0.9)}]


Area of Steel required, (Mu/(0.87fy*z)

=
=
=

Req%Pt
Min. Ast required (0.13%)
Ast provided
16

=
=

mm dia bar at

150

0.05

RVR/UMA

1/7/09

SHEET

CSR/MDS

<K'(0.156)

153.2 mm
2
864 mm
0.53 %
2
211 mm
2
1340 mm

mm C/C as Top reinforcement (main bars)

(b) Bottom Reinforcement (main bars)


Maximum Sagging moment
Effective depth, d
Breadth, b
K = (Mu / fcub * d2 )

Provide

DATE

42.2 kN-m

162 mm
1000 mm
0.04 <K'(0.156)
153.9 mm
2
750 mm
0.46 %
2
211 mm
2
1340 mm

mm C/C as Bottom reinforcement (main bars)

(c) Secondary reinforcement


Minimum reinforcement shall be provided both top and bottom secondary reinforcemet
Min Percentage of Ast
=
0.13 %
mm2
Ast min
=
211
mm2
Ast provided
=
524
Provide

10

mm dia bar at

150 mm C/C on as secondary bars both at top and bottom

Check for Shear


(using Table 3.8, pg 30 BS8110 part1)

Allowableshearstressinconcrete
1/3

vc = 0.79[100As/(bvd)]

1/4

(400/d) /m

(multiplication factor for concrete grade > 25 = (fcu/25)1/3 )

1340 , bv =
Maximum shear, v = Vu/bd
(where, As =

(Vu =

1000

65 kN, b=1000, d=

d=

162

vc =

2
0.87 N/mm

v =

2
0.40 N/mm
< vc Hence Safe

, m = 1.25)

162 )

Check for deflection (Cl 3.4.6.3 of BS8110 part 1)


Basic span/effective depth ratio from table 3.9

26

Modification factors
(a) For Tension reinforcement (Using Table 3.10 of the code)

LARSEN & TOUBRO LIMITED


ECC Division - GES
PROJECT:

TITLE:

DOCUMENT NO

SIDRA MEDICAL & RESEARCH CENTER, DOHA

1861B-CS-05-00320

HOSPITAL BUILDING - DESIGN OF SECOND FLOOR BEAMS &


SLABS

DESIGNED CHECKED
RVR/UMA

DATE
1/7/09

SHEET

CSR/MDS

Design service stress, fs = 2fyAs req/(3As prov b)


=

Mu/bd2

131
where,

N/mm2
As req
As prov
b

=
=
=

2
750 mm
2
1340 mm
1.2 for 20%redistribution

1.61

Modification factor = 0.55 + (477-fs) / [120(0.9+Mu/bd2] < 2.0


=

1.70

< 2.0

(b) For Compression reinforcement (Using Table 3.11 of the code)

2
As`prov
100As`prov/bd = 0.83
=
1340 mm
Modification factor = 1 + (100As`prov/bd) / (3+ 100As`prov/bd) < 1.5

= 1.22 < 1.5


Allowable span/effective depth ratio = 26 x 1.7 x 1.22
=
53.8
Actual ratio = 5.164 x 1000 / 162
=
31.9
Check for crack width
Crack width is calculated and and attached seperately

Hence safe against deflection

LARSEN & TOUBRO LIMITED


ECC Division - GES
PROJECT:

TITLE:

DOCUMENT NO

SIDRA MEDICAL & RESEARCH CENTER, DOHA

1861B-CS-05-00320
DESIGNED CHECKED

HOSPITAL BUILDING - DESIGN OF SECOND FLOOR BEAMS &


SLABS

RVR/UMA

DATE
1/7/09

SHEET

CSR/MDS

Design of slab panels S12,S13,S14


The design moments & shear forces are arrived based on clause 3.5.2.4 of BS 8110 Part 1 provisions
by considering 1m wide strip of the one way slab.
Loads are as follows.
Slab thickness
Self weight
Super imposed dead load
(a) Total Dead load (DL)
(b) Live load (LL)
Design factored load (Fu) =1.4DL+1.6LL
Load for serviceability condition, (Fs) =DL+LL

=
=
=
=
=

200
5
5.5
10.5
4

mm
kN/m2
kN/m2
kN/m2
kN/m2

=
=

2
21.1 kN/m
2
14.5 kN/m

Moment and Shear coefificients (Table 3.12, pg 37)

S14

-0.063

0.063

S13

-0.086

0.063

S12

-0.04

0.075

L21= 3.2m

L22= 2.78m

L23= 2.90m

(a) Moment coefficients

S14

L21=

3.2m

0.5

S13

L22= 2.78m

(b) Shear coefficients

0.6

S12

0.46

L23= 2.90m

LARSEN & TOUBRO LIMITED


ECC Division - GES
PROJECT:

TITLE:

DOCUMENT NO

SIDRA MEDICAL & RESEARCH CENTER, DOHA

1861B-CS-05-00320
DESIGNED CHECKED

HOSPITAL BUILDING - DESIGN OF SECOND FLOOR BEAMS &


SLABS

RVR/UMA

Bending moment and shear force diagram


(a) Strength case
Bending moment = (FuxL) x L x moment coefficient
-13.41

-51

-15.3

-7.1

10.24
13.4
(a) Bending Moment(kN-m)

13.3

Shear Force = (FuxL) x shear coefficient


54.92

29.28

36.7

33.51
(b) Shear Force(kN)

28

35.13

(b) Seviceability case


Bending moment = (FsxL) x L x moment coefficient
-35

-10.5

-9.21

9.2

7.03
(a) Bending Moment(kN-m)

-4.9

9.1

Design for Flexure


Slab section is designed for maximum moment from the above calculation.
2
Grade of Concrete, fcu
=
40 N/mm
2
Yield Strength of Steel, fy
=
420 N/mm
Cover to reinforcement
Slab thickness, D
(a) Top Reinforcement (main bars)
Maximum Hogging moment
Effective depth, d
Breadth, b

30 mm

200 mm

=
=
=

50.5 kN-m
162 mm

1000 mm

CSR/MDS

DATE
1/7/09

SHEET

LARSEN & TOUBRO LIMITED


ECC Division - GES
PROJECT:

DOCUMENT NO

SIDRA MEDICAL & RESEARCH CENTER, DOHA

TITLE:

1861B-CS-05-00320
DESIGNED CHECKED

HOSPITAL BUILDING - DESIGN OF SECOND FLOOR BEAMS &


SLABS

K = (Mu / fcub * d

2)

Z = Min[0.95d, d{0.5 + sqrt(0.25-K/0.9)}]


Area of Steel required, (Mu/(0.87fy*z)

=
=
=

Req%Pt
Min. Ast required (0.13%)
Ast provided
16

Provide

=
=
150

mm dia bar at

=
=
=

Z = Min[0.95d, d{0.5 + sqrt(0.25-K/0.9)}]


Area of Steel required, (Mu/(0.87fy*z)

=
=
=

Req%Pt
Min. Ast required (0.13%)
Ast provided
16

=
=

mm dia bar at

150

0.05

RVR/UMA

1/7/09

SHEET

CSR/MDS

<K'(0.156)

152.8 mm
2
905 mm
0.56 %
2
211 mm
2
1340 mm

mm C/C as Top reinforcement (main bars)

(b) Bottom Reinforcement (main bars)


Maximum Sagging moment
Effective depth, d
Breadth, b
K = (Mu / fcub * d2 )

Provide

DATE

13.4 kN-m

162 mm
1000 mm
0.01 <K'(0.156)
153.9 mm
2
238 mm
0.15 %
2
211 mm
2
1340 mm

mm C/C as Bottom reinforcement (main bars)

(c) Secondary reinforcement


Minimum reinforcement shall be provided both top and bottom secondary reinforcemet
Min Percentage of Ast
=
0.13 %
mm2
Ast min
=
211
mm2
Ast provided
=
524
Provide

10

mm dia bar at

150 mm C/C on as secondary bars both at top and bottom

Check for Shear


(using Table 3.8, pg 30 BS8110 part1)

Allowableshearstressinconcrete
1/3

vc = 0.79[100As/(bvd)]

1/4

(400/d) /m

(multiplication factor for concrete grade > 25 = (fcu/25)1/3 )

1340 , bv =
Maximum shear, v = Vu/bd
(where, As =

(Vu =

1000

55 kN, b=1000, d=

d=

162

vc =

2
0.87 N/mm

v =

2
0.34 N/mm
< vc Hence Safe

, m = 1.25)

162 )

Check for deflection (Cl 3.4.6.3 of BS8110 part 1)


Basic span/effective depth ratio from table 3.9

26

Modification factors
(a) For Tension reinforcement (Using Table 3.10 of the code)

LARSEN & TOUBRO LIMITED


ECC Division - GES
PROJECT:

TITLE:

DOCUMENT NO

SIDRA MEDICAL & RESEARCH CENTER, DOHA

1861B-CS-05-00320

HOSPITAL BUILDING - DESIGN OF SECOND FLOOR BEAMS &


SLABS

DESIGNED CHECKED
RVR/UMA

DATE
1/7/09

SHEET

CSR/MDS

Design service stress, fs = 2fyAs req/(3As prov b)


=

Mu/bd2

42
where,

N/mm2
As req
As prov
b

=
=
=

2
238 mm
2
1340 mm
1.2 for 20%redistribution

0.51

Modification factor = 0.55 + (477-fs) / [120(0.9+Mu/bd2] < 2.0


=

3.12

< 2.0

(b) For Compression reinforcement (Using Table 3.11 of the code)

2
As`prov
100As`prov/bd = 0.83
1340 mm
=
Modification factor = 1 + (100As`prov/bd) / (3+ 100As`prov/bd) < 1.5

= 1.22 < 1.5


Allowable span/effective depth ratio = 26 x 2 x 1.22
=
Actual ratio = 3.176 x 1000 / 162
=
Check for crack width
Crack width is calculated and and attached seperately

63.2
19.6

Hence safe against deflection

LARSEN & TOUBRO LIMITED


ECC Division - GES
PROJECT:

TITLE:

DOCUMENT NO

SIDRA MEDICAL & RESEARCH CENTER, DOHA

DATE

1861B-CS-05-00320

HOSPITAL BUILDING - DESIGN OF SECOND FLOOR BEAMS &


SLABS

DESIGNED CHECKED
RVR / UMA

1/7/09

SHEET

CSR/MDS

Design of slab panel S15


The design moments & shear force are arrived by taking the slab as a cantilever slab
considering 1m wide strip of the one way slab.
Design loads are as follows.
Slab thickness
=
250 mm
2
Self weight
=
6.25 kN/m
2
Super imposed dead load
=
5.5 kN/m
Curtain wall load
(a) Total Dead load (DL)
(b) Live load (LL)

=
=
=

5 kN/m
16.75 kN/m
4 kN/m

=
=

29.85 kN/m
20.75 kN/m

Clear span, L
Effective Span
Maximum Support moment, Mu = FuL2/2
Maximum Shear force, Vu = FuL

=
=
=
=

1.517
1.84
51
55

Moment under serviceability condition, Mu = FsL2/2

35 kN-m

=
=

2
40 N/mm
2
420 N/mm

per meter width


per meter width

Design factored load (Fu) =1.4DL+1.6LL


Load for serviceability condition, (Fs) =DL+LL

m
m
kN-m
kN

Design for Flexure


Slab section is designed for maximum moment.
Grade of Concrete, fcu
Yield Strength of Steel, fy
Cover to reinforcement
Slab thickness, D
(a) Top Reinforcement (main bars)
Maximum Hogging moment
Effective depth, d
Breadth, b
K = (Mu / fcub * d2 )

mm dia bar at

250 mm

=
=
=

Min. Ast required (0.13%)


Ast provided
16

Req%Pt

Provide

30 mm

=
=
=

Z = Min[0.95d, d{0.5 + sqrt(0.25-K/0.9)}]


Area of Steel required, (Mu/(0.87fy*z)

(b) Bottom reinforcement

=
=
150

51 kN-m

212 mm
1000 mm
0.03 <K'(0.156)
201 mm
2
687 mm
0.32 %
2
276 mm
2
1340 mm

mm C/C as Top reinforcement (main bars)

LARSEN & TOUBRO LIMITED


ECC Division - GES
PROJECT:

DOCUMENT NO

SIDRA MEDICAL & RESEARCH CENTER, DOHA

1861B-CS-05-00320
DESIGNED CHECKED

HOSPITAL BUILDING - DESIGN OF SECOND FLOOR BEAMS &


SLABS

TITLE:

Min Percentage of Ast


Ast min
Ast provided
Provide

16

=
=

mm dia bar at

0.13
276
1340

RVR / UMA

DATE

1/7/09

SHEET

CSR/MDS

mm2
mm2

150 mm C/C on as Bottom reinforcement (main bars)

(c) Secondary reinforcement


Minimum reinforcement shall be provided both top and bottom secondary reinforcemet
Min Percentage of Ast
=
0.13 %
mm2
Ast min
=
276
mm2
Ast provided
=
524
Provide

10

mm dia bar at

150 mm C/C on as secondary bars both at top and bottom

Check for Shear


(using Table 3.8, pg 30 BS8110 part1)

Allowableshearstressinconcrete
1/3

vc = 0.79[100As/(bvd)]

1/4

(400/d) /m

(multiplication factor for concrete grade > 25 = (fcu/25)1/3 )


(where, As = 1340 , bv =
Maximum shear, v = Vu/bd

( u=
(V

1000

55 kN, b=1000,
b 1000, d=
d

212

d=

vc =

2
0.74 N/mm

v =

2
0.26 N/mm
< vc Hence Safe

, m = 1.25)

212 )

Check for deflection (Cl 3.4.6.3 of BS8110 part 1)


Basic span/effective depth ratio from table 3.9

(for cantilever condition)

Modification factors
(a) For Tension reinforcement (Using Table 3.10 of the code)
Design service stress, fs = 2fyAs req/(3As prov b)
=

Mu/bd2

143
where,

N/mm2
As req
As prov
b

=
=
=

1.12

Modification factor = 0.55 + (477-fs) / [120(0.9+Mu/bd2] < 2.0


=

1.92

< 2.0

(b) For Compression reinforcement (Using Table 3.11 of the code)


2
100As`prov/bd = 0.63
As`prov
1340 mm
=
Modification factor = 1 + (100As`prov/bd) / (3+ 100As`prov/bd) < 1.5
= 1.17 < 1.5
Allowable span/effective depth ratio = 7 x 1.92 x 1.17
=
15.8

2
687 mm
2
1340 mm
1

LARSEN & TOUBRO LIMITED


ECC Division - GES
PROJECT:

TITLE:

DOCUMENT NO

SIDRA MEDICAL & RESEARCH CENTER, DOHA

1861B-CS-05-00320

HOSPITAL BUILDING - DESIGN OF SECOND FLOOR BEAMS &


SLABS

Actual ratio = 1.84 x 1000 / 212

Check for crack width


Crack width is calculated and and attached seperately.

8.7

DESIGNED CHECKED
RVR / UMA

DATE

1/7/09

SHEET

CSR/MDS

Hence safe against deflection

LARSEN & TOUBRO LIMITED


ECC Division EDRC
PROJECT :

SIDRA MEDICAL AND RESEARCH CENTER,QATAR

DOCUMENT NO.

DATE

HOSPITAL BUILDING - DESIGN OF SECOND FLOOR BEAMS & SLABS

1861B-CS-05-00320
DESIGNED
CHECKED
RVR / UMA CSR / MDS

1/7/2009
TITLE :

As per BS 8110 : Part 1 : 1997


30 mm
40 N/mm2
420 N/mm2

Clear cover :

Grade of conc:
Grade of steel:

OF

DESIGN OF TWO WAY SLAB NAMED AS S1, S2, S3, S4 & S5

SLAB

Depth

Clear Span (m)

Eff. Span ( m )

Span

ID

short

long

short

long

Ratio

( mm)

lx

ly

lx

ly

ly/lx

S1, S5

200

4.392

5.796

5.092

6.496

1.28

5.500

5.000

4.000

S2,S4

200

4.528

6.830

5.228

7.530

1.44

5.500

5.000

S3

200

5
5.062
062

5
5.780
780

5
5.562
562

6
6.480
480

1
1.17
17

5 500
5.500

5
5.000
000

Designed By

PAGE

Un fact. Load in kN/m2


Dead

S. W.

Boundary conditions/Type

Eff. Depth
(mm)

Moment coefficients

Fac. B. M. ( kN-m )

short span

long span

short span

long span

-ve

+ve

-ve

+ve

K'

K=Mu/bd2fcu

As

Ast req. in mm2

spacing of bars ( mm )

spacing of bars ( mm )

short span

long span

short span ong spahort spa long span

As,
min

short span

long span

-ve

mm2

-ve

+ve

-ve

+ve Support

+ve

-ve

+ve

fs

mm2

N/mm2

mf

Slab

l/d

dreqd

Id

long

-ve

+ve

-ve

+ve

21.100 One long edge discontinuous

162

146

0.061

0.046

0.037

0.028

33.12

25.05

20.24

15.32 0.156

0.032 0.024

0.024

445

399

302

260

589

445

399

302

Y- 16 @

150

Y- 16 @ 150 Y- 16 @

150 Y- 16 @

150

1.00

1340

93

2.00

26

4.000

21.100 Interior panel

162

146

0.051

0.038

0.032

0.024

29.53

22.04

18.45

13.84 0.156

0.028 0.021

0.022

359

333

250

260

481

359

333

260

Y- 16 @

150

Y- 16 @ 150 Y- 16 @

150 Y- 16 @

150

1.00

1340

75

2.00

26

100.5

S2,S4

4
4.000
000

I t i panell
21
21.100
100 Interior

162

146

0 040
0.040

0
0.031
031

0
0.032
032

0
0.024
024

26
26.27
27

19
19.98
98

20
20.89
89

15
15.67
67 0
0.156
156

0
0.025
025 0
0.019
019 0
0.024
024

325

377

283

260

428

325

377

283

Y
Y- 16 @

150

Y
Y- 16 @ 150 Y
Y- 16 @

150 Y
Y- 16 @

150

1
1.00
00

1340

68

2
2.00
00

26

107
107.0
0

S3

Total

-ve

As
Prov.

short

Live

+ve

Check for Deflection

Span

Support

Span

mm

97.9 S1, S5

Checked By

LARSEN & TOUBRO LIMITED


ECC Division - GES
PROJECT:

TITLE:

SIDRA MEDICAL AND RESEARCH CENTER,QATAR


Hospital Building - Crack width calculation

Calculation for crack width

DOCUMENT NO

DATE

1861B-CS-05-00320

1/7/09

DESIGNED

CHECKED

RVR/UMA

CSR/MDS

(For slab panal - S7)

Moment due to service load

= 33.3

Width of slab (b)

= 1000 mm

Overall depth of slab (h)


Area of steel provided (As)

= 200 mm
mm2
= 1340

Clear cover to tension steel provided (c)


Diameter of bar provided on the tension face ()

= 30 mm

Effective depth of slab (d) =


Spacing of steel (s)

kNm

= 16 mm
200-30-16/2

= 162 mm
= 150
mm c/c

As per BS8110-2:1985 Design Surface Crack Width


Wcr = 3acrm/(1+2(acr-Cmin)/(h-x))
Where

x
fs

= depth of neutral axis.


= the tensile stress in the reinforcement.
= M(d
M(d-x)/I
)/I
= Strain at the level considered, calculated ignoring

= 61.6
=

175

mm
N/mm2

the stiffening of the concrete in the tension zone.

1 = (h-x)fs/Es(d-x)

0.00121

= average steel strain at the level considered,


1 - b(h-x)(a-x)/(3EsAs(d-x))

0.00097

= distance from the compression face to the point at


which crack width is being calculated, and

= 200 mm

Actual crack width:

acr

= distance from the point considered to the surface


of the nearest longitudinal bar

W cr

= Crack width
Allowable crack width

= 76.1

mm

= 0.133 mm
=

0.300 mm

HENCE SAFE

SHEET

LARSEN & TOUBRO LIMITED


ECC Division - GES
PROJECT:

TITLE:

SIDRA MEDICAL AND RESEARCH CENTER,QATAR


Hospital Building - Crack width calculation

Calculation for crack width

DOCUMENT NO

DATE

1861B-CS-05-00320

1/7/09

DESIGNED

CHECKED

RVR/UMA

CSR/MDS

(For slab panal - S15)

Moment due to service load

= 35.1

Width of slab (b)

= 1000 mm

Overall depth of slab (h)


Area of steel provided (As)

= 250 mm
mm2
= 1340

Clear cover to tension steel provided (c)


Diameter of bar provided on the tension face ()

= 30 mm

Effective depth of slab (d) =


Spacing of steel (s)

kNm

= 16 mm
250-30-16/2

= 212 mm
= 150
mm c/c

As per BS8110-2:1985 Design Surface Crack Width


Wcr = 3acrm/(1+2(acr-Cmin)/(h-x))
Where

x
fs

= depth of neutral axis.


= the tensile stress in the reinforcement.
= M(d
M(d-x)/I
)/I
= Strain at the level considered, calculated ignoring

= 72.6
=

140

mm
N/mm2

the stiffening of the concrete in the tension zone.

1 = (h-x)fs/Es(d-x)

0.00089

= average steel strain at the level considered,


1 - b(h-x)(a-x)/(3EsAs(d-x))

0.00061

= distance from the compression face to the point at


which crack width is being calculated, and

= 250 mm

Actual crack width:

acr

= distance from the point considered to the surface


of the nearest longitudinal bar

W cr

= Crack width
Allowable crack width

= 76.1

mm

= 0.091 mm
=

0.300 mm

HENCE SAFE

SHEET

LARSEN & TOUBRO LIMITED


ECC Division - GES
PROJECT:

TITLE:

SIDRA MEDICAL AND RESEARCH CENTER,QATAR


Hospital Building - Crack width calculation

Calculation for crack width

DOCUMENT NO

DATE

1861B-CS-05-00320

1/7/09

DESIGNED

CHECKED

RVR/UMA

CSR/MDS

(For slab panal - S14)

Moment due to service load

= 35.1

Width of slab (b)

= 1000 mm

Overall depth of slab (h)


Area of steel provided (As)

= 200 mm
mm2
= 1340

Clear cover to tension steel provided (c)


Diameter of bar provided on the tension face ()

= 30 mm

Effective depth of slab (d) =


Spacing of steel (s)

kNm

= 16 mm
200-30-16/2

= 162 mm
= 150
mm c/c

As per BS8110-2:1985 Design Surface Crack Width


Wcr = 3acrm/(1+2(acr-Cmin)/(h-x))
Where

x
fs

= depth of neutral axis.


= the tensile stress in the reinforcement.
= M(d
M(d-x)/I
)/I
= Strain at the level considered, calculated ignoring

= 61.6
=

185

mm
N/mm2

the stiffening of the concrete in the tension zone.

1 = (h-x)fs/Es(d-x)

0.00128

= average steel strain at the level considered,


1 - b(h-x)(a-x)/(3EsAs(d-x))

0.00104

= distance from the compression face to the point at


which crack width is being calculated, and

= 200 mm

Actual crack width:

acr

= distance from the point considered to the surface


of the nearest longitudinal bar

W cr

= Crack width
Allowable crack width

= 76.1

mm

= 0.142 mm
=

0.300 mm

HENCE SAFE