TECHNICAL SPECIFICATION FOR 11 KV, 4 PANEL,HT-VCB INDOOR SWITCH BOARD

INSTRUMENTATION LIMITED, PALAKKAD


Annexure 1 to Enquiry No:ILP/IP/2/261 015/37/T0241 DT 28/10/2013

Instrumentation Limited
Kanjikode West,
Palakkad 678 623
Kerala

TECHNICAL SPECIFICATION
FOR
11 KV,4 PANEL,HT-VCB
INDOOR SWITCH BOARD
AT
INSTRUMENTATION LIMITED,
KANJIKODE WEST, PALAKKAD

TECHNICAL SPECIFICATION FOR 11 KV, FOUR PANEL, HT-VCB


INDOOR SWITCH BOARD

TECHNICAL SPECIFICATION FOR 11 KV, 4 PANEL,HT-VCB INDOOR SWITCH BOARD


INSTRUMENTATION LIMITED, PALAKKAD
Annexure 1 to Enquiry No:ILP/IP/2/261 015/37/T0241 DT 28/10/2013

-----------------------------------------------------------------------------------------------------------INSTALLATION
SYSTEM
FAULT LEVEL
FINISH

:
:
:
:

INDOOR
11 KV 3PH 50HZ
350 MVA
Dark Admirology Grey.

Totally enclosed, free standing, sheet steel clad, cubicle pattern Four Panel HT Switch Board complete
with 1 No.1200A VCB and 3 Nos. 630A Load Break Switch, PVC sleeved Aluminium bus bars and
each complying to IS 342 T and comprising the following specifications given below :
3 Nos TP Vacuum / 1200A/630A Circuit Breaker, horizontal draw-out type & Horizontal isolation,
rated current 1200A/630A, fitted with :
1 No. Manually spring charged closing mechanism with manual release.
1 ,,
Set of Mechanical Close / Trip knob
1 ,,
Mechanical spring Charged / Free indicator.
1 ,,
Mechanical ON / OFF indicator
1 ,,
Close / Trip control switch.
1 ,,
110V DC Shunt Trip (source thro PT & RB)
1 ,,
Operation counter
1 ,,
Rectifier Bridge, 110V AC to 110V DC
1 ,,
Set of space heaters with thermostat,
1 ,,
White lamp with push button for on demand trip circuit healthy indication
1 ,,
Set of Red / Green indicating lamps for Circuit Breaker On / Off indication,
3 Nos Resin Cast twin core Current Transformers of ratio 300/150/5-5A class 5P10
class 0.5 accuracy, 15VA / 15 VA burden for protection and metering.
1 No 3 Ph. Resin cast, draw-out type Potential Transformer ratio 11KV/110V class 1
accuracy 100VA burden / phase complete with HT and LT fuses connected to
incoming side,
1 No 144 sq mm flush mounting MISC Ammeter scaled suitably
1 ,,
3 way and off rotary type selector switch for Ammeter,
1 ,,
144 sq mm flush mounting MISC Voltmeter scaled suitably,
1 ,,
3 way and off rotary type selector switch for Voltmeter,
1 ,,
Tri-vector meter
1 ,,
TP IDMT non-directional shunt tripping relay, two poles arranged for Over
current protection with settings 50-200% and one pole arranged for Earth
fault protection with settings 20-80%,
1 ,,
Master Trip relay.
1 ,,
Unit cable box, Provision for connecting 3 core 150sqmm XLPE Cable.

HT VACUUM CIRCUIT BREAKER


Scope
2

TECHNICAL SPECIFICATION FOR 11 KV, 4 PANEL,HT-VCB INDOOR SWITCH BOARD


INSTRUMENTATION LIMITED, PALAKKAD
Annexure 1 to Enquiry No:ILP/IP/2/261 015/37/T0241 DT 28/10/2013

Testing and commissioning integrated cubicle type floor mounted free standing extensible on either
side sheet steel enclosed front operated, indoor type HT switch board operated by vacuum type circuit
breaker as per specifications
System : 11KV, 3 Phase 50 Hz earthed system
Fault Level

: 350 MVA

Installation

: Indoor

Standards :
Unless otherwise stated, HT switch board shall conform to following relevant Indian standard with
latest amendment and latest Indian electricity rules and regulation.
a)
IS 3427 : AC metal enclosed switch gear and control gear above 1 KV up to including 52 KV
b)
IS 2147 : Degree of Protection provided by enclosure for low voltage switch gear and control
gear
c)
IS 375 : Switch gear bus bar main connection and auxiliary wiring etc.
d)
IS 2705 : Current transformer general requirement
e)
IS 3156 : Voltage transformer general requirement
f)
IS 3231 : Electrical relay for power system protection
g)
IS 1248 : Direct acting indicating analogue electrical measuring instrument and their accessories part 1 general requirement
h)
IS 722 : AC Electricity meters part 1 general requirement and test.

Construction Details
MS Sheet Steel enclosure is made out of 14 gauge thick and shall be folded and welded. Thickness of
door is 2 mm, rear and front with surface mounting hinges in each compartment. The switchgear shall
be with louvers for ventilation and shall provide a degree of protection IP 44. All louvers shall how
screens and filters.
Circuit breaker carriage shall be fitted with positive guide so as to ensure proper alignment.
Switchgear cubicle shall be provided with top sheet metal plate 3 mm thick, cubicle with bottom entry
shall be fixed with removable plates for fixing XLPE cable terminating kit and glands. Switch gear
shall be provided with painted legend indicating switchgear designation, rating and duty of each relay,
instrument switch, fuse and other devices shall be provided with separate legend.
Safety, interlocks and features switchgear shall be provided with following interlocks. Operation on
circuit breaker shall not be possible unless it is fully onto working position withdrawn to service
position (Isolated from supply) or fully drawn out. The breaker shall be earthed before the main
circuit breaker controls are plugged in the stationary contacts. Positive earthling of circuit breaker
frames truck shall be maintained in the connected position.
For safe transportation of circuit breaker eye bolts are provided where applicable. Caution line
terminals shall be provided at all points where terminals are likely to remain live and isolation should
be possible only at remote end.
3

TECHNICAL SPECIFICATION FOR 11 KV, 4 PANEL,HT-VCB INDOOR SWITCH BOARD


INSTRUMENTATION LIMITED, PALAKKAD
Annexure 1 to Enquiry No:ILP/IP/2/261 015/37/T0241 DT 28/10/2013

Bus bar System


Bus bar are fabricated from Electrolyte grade Aluminium E91 as per IS 5082 and the current density
shall not exceed 0.8A/sqmm. Bus bar shall not be accessible after opening bus bar channel door. A
separate wire mesh cover shall be provided bus bar and channel door, bus bar supports are moulded
from thermosetting fibres glass reinforced polyester material having high impact and tensile strength
high tracking index and properties of high temperature withstand and fire retardance. It has to support
dynamic stress conforming IS 2544. Bus bar shall be suitably colour coded for phase indication.

VCB (Vacuum Circuit Breaker)


11 KV 3 phase 50 Hz 350 MVA circuit breaker dust and vermin proof totally enclosed in sheet steel
housing fully inter locked horizontal draw out un-door truck type with trip free spring losing
mechanism with mechanical On-Off indicators earthling terminals automatic safety shutters, complete
with auxiliary contacts, resign cast CTs of suitable ratio and accuracy class for metering and also
protection. Bus bar compartment have suitable capacity non Hygroscopic and high dielectric strength
SMC/FRP bus bar supports with suitable sleeves. Metering compartment with 144x144mm flush type
ammeter with suitable selector switch, combined overload and earth fault protective relays with IDMT
relays characteristic, shunt/series trip coil under voltage release, indication lamps cable entry boxes
including all inter connections providing fire/heat resistant coatings for metering, bus bar CB Truck
enclosures and painting with approved synthetic enamel paint complete panel as per IS 2516 & IS
3427 with latest amendment complete as required. The spring closing mechanism will be manual.