ii - The closed circuit gas cycle coupled with low gas velocity
gives quite operation as there is no exhaust top atmosphere as
in air blast breakers .
iii - The closed gas circuit keeps the interior dry so that there is
no moisture problem .
iv - The arc extinguish properties of SF6 gas result in very short
arcing times .
v - There is no carbon deposits so that insulation break-down is
eliminated .
vi - Electrical clearances can be reduced due to the insulating
properties of the gas .
vii - As the circuit breaker is totally enclosed and sealed from
atmosphere , it is suitable for use in mines or petroleum
industries where explosion hazard exists .
Meanwhile . Figure (10.1) shows the types of circuit
breakers . Fig. (10.2) shows the breaking operation principles ,
and fig. (10.3) shows the method of removing the heat produced
by the electric arc .