You can add a device to a project in which part of the station has already been
parameterized, as described in item 3.3. First find the device in the New devices
subnet after opening the System Configurator and then integrate it into an existing
subnet by dragging it with the mouse device.
IP-address Scheme Think about a logical structure within your substation, for example, every device in
substation 1 has IP-address 172.16.1.x, reserve an IP-address range for the Ethernet
switches, for example, 1-10, so the 1st switch in every substation has address
172.16.x.1, for the 1st SIPROTEC ring reserve 11-40, for a second 41-70, etc.; so you
know that 172.16.3.16 is the IP-address of the 6th SIPROTEC device in the 3rd
substation.
Also reserve an IP-address range for your devices in the control center room, etc.
Such kind of logical scheme makes your life much easier in case of maintenance or
fault clearance.
NTP clock server The NTP servers are integrated as 'Other IEC 61850 communicators' via an ICD File
which is included in the DIGSI4 CD. 2 NTP servers are supported. The primary server
Gateway address This is the IP address of the gateway. It is required whenever an address outside the
LAN of the station is to be accessed. It can only be set via DIGSI.
DHCP DHCP is used to avoid having to set the above parameters individually. If DHCP is
activated, the settings are provided by a DHCP server in the network. The only
exceptions are the MAC address and multicast addresses. This function requires that
a DHCP server be accessible in the network.
SNMP V2 This protocol has been implemented in order to have access to information in a
network in which other units, such as external switches, are administered as well. On
the basis of this protocol, the accessible information can be invoked with any MIB
browser. The MIB descriptions required for this are available in the internetworking at
http://www.siprotec.com or http://www.siprotec.de. In particular, the statuses of the 2
lines are readable via SNMP using a MIB browser. This protocol is implemented in all
modules. For more details please refer to Chapter 6.5.
NOTE
To be able to work with DHCP, this feature must be activated in the device. It is
activated in the as-delivered condition of the device. The IP addresses, subnet mask,
and gateway are then set to zero.
Integration Into Networks
SIPROTEC 4 EN100-Module - Manual IEC 61850 4-3