MULTICONT
SIMPLEX
I. Table of Contents
1. General Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11-5
1.1 The Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.2 The MULTICONT System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.3 SIMPLEX Loss-in-Weight Feeders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.3.1 Fill Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
1.3.2 Gravimetric/Volumetric Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
1.3.3 Batching Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Technische
Redaktion BV2ED
Table of Contents
FH 399 GB/ I-1
SIMPLEX
MULTICONT
2.3.9 Service Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
2.4 Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
2.4.1 Display Parameters/Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
2.4.2 Enter Parameters / Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
2.4.3 Print Parameters/Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
2.4.4 MULTIKEY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
2.4.5 Default Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
2.4.6 Multi-Memory Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
2.5 Restoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
4. Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14-41
4.1 General Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.2 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4.3 List of Configuration Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
9941
Table of Contents
FH 399 GB/ I - 2
Technische
Redaktion BVED
MULTICONT
SIMPLEX
5. Parametrization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15-32
5.1 Parameter Designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.2 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
5.3 List of Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1C-1-2
9941
Technische
Redaktion BV2ED
Table of Contents
FH 399 GB/ I-3
SIMPLEX
MULTICONT
FDW 1202-01
Edition: 9941
9941
Table of Contents
FH 399 GB/ I - 4
Technische
Redaktion BVED
MULTICONT
SIMPLEX
1. General Comments
1.1 The Manual
The MULTICONT Loss-In-Weight Feeder Service
Manual FH 399 completes Operating Manual FH 398 by
information on commissioning, calibration, configuration
and parametrization.
Transmission to third parties and reproduction of this documentation are not permitted. SCHENCK PROCESS GmbH
reserves all rights of ownership and copy-
Technische
Redaktion BVED
General Comments
FH 399 GB/ 1 - 1
SIMPLEX
MULTICONT
9941
General Comments
FH 399 GB/ 1 - 2
Technische
Redaktion BVED
Transmission to third parties and reproduction of this documentation are not permitted. SCHENCK PROCESS GmbH
reserves all rights of ownership and copy-
MULTICONT
SIMPLEX
(B)
(C)
(D)
(E)
(F)
After settling time TBRUHE, the actual measuring and control period commences, that is to
say, gravimetric feeding.
(G)
9941
Transmission to third parties and reproduction of this documentation are not permitted. SCHENCK PROCESS GmbH
reserves all rights of ownership and copy-
Technische
Redaktion BVED
General Comments
FH 399 GB/ 1 - 3
SIMPLEX
MULTICONT
HMAX1
AMOUNT
HMIN1
HMIN2
BUFFER
9941
General Comments
FH 399 GB/ 1 - 4
Technische
Redaktion BVED
Transmission to third parties and reproduction of this documentation are not permitted. SCHENCK PROCESS GmbH
reserves all rights of ownership and copy-
MULTICONT
1.3.2 Gravimetric/Volumetric Mode
SIMPLEX
1.3.3 Batching Mode
(A)
(B)
(C)
(D)
9941
Transmission to third parties and reproduction of this documentation are not permitted. SCHENCK PROCESS GmbH
reserves all rights of ownership and copy-
Technische
Redaktion BVED
General Comments
FH 399 GB/ 1 - 5
MULTICONT
SIMPLEX
Functions
Mode 0 / Mode 1
Test Mode
Local Mode
DE / SE / TT
SE / TT
DE
START/STOP Feeder
DE / SE / TT
DE / SE / TT
DE
AE / SE / TT
.0 /SE / TT
AE / SE / TT
AE (control
magnitude)
DE / SE / TT
DE / SE / TT
(DE)
DE / SE / TT
DE / SE / TT
Mode-Independent
.0 / SE / TT
Volumetric Mode 1
DE
Volumetric Mode 2
.0 / .1
.0 / .1
DE / SE / TT
DE / SE / TT
DE / SE
DE
DAE Disturbance-AutoElimination
.0 / .1
.0 / .1
Feed Index
Batching Mode
Discharge Gate
DE = Digital Input; AE = Analog Input; SE = SE Bus (group control station); TT = Keyboard (machine control station) ; .0 =
OFF; .1 = ON; Pabs = Absolute feed rate setpoint; Prel = Relative feed rate setpoint (For details, see Chapter 4.)
9941
Technische
Redaktion BVED
SIMPLEX
MULTICONT
Sub-function. . . . . . . . . . . . . . . . . Display
Programming
BATCH MODE ON
BATCH MODE
OFF
BATCH INT.
REFILL MODE ON
START REFILLING
STOP REFILLING
REFILL MODE
OFF
DISCHARGE
MODE
DISCHARGE
STOP
FEED-INDEX
VOLUMETRIC
VOLUMETRISCH
SYNCHRONOUS
GRAVIMETRIC
DISPLAY CHECK
CALIBRATIONS
PROGRAMMING
RECOVER
Sub-function . . . . . . . . . . . . . . . . . Display
Calibrating Functions
Taring . . . . . . . . . . . . . . . . . . .
Tare supply bin . . . . . . . . . .
Check weight. . . . . . . . . . . . . .
Test Mode . . . . . . . . . . . . . . . .
Optimize DAE . . . . . . . . . . . . .
Adapt controller . . . . . . . . . . . .
Compensate control
magnitude . . . . . . . . . . . . . .
Enter time . . . . . . . . . . . . . . . .
TW: TARE
TF: SUPPLY BIN
CW: CHECK Q
TEST-MODE
OPTIM. DAE
CONTR. ADAPT.
Display parameters. . . . . . . . . .
Display configuration data . . . .
Enter parameters . . . . . . . . . . .
Configurate . . . . . . . . . . . . . . . .
Print parameters . . . . . . . . . . . .
Print configuration data. . . . . . .
Load parameters from
multi-memory module . . . . . . . .
Load configuration from
multi-memory module . . . . . . . .
Store parameters in
multi-memory module . . . . . . . .
Store configuration in
multi-memory module . . . . . . . .
Load default parameters from
EPROM . . . . . . . . . . . . . . . . . .
Load default configuration from
EPROM . . . . . . . . . . . . . . . . . .
Load parameters from
MULTIKEY . . . . . . . . . . . . . .
Load configuration from
Multikey . . . . . . . . . . . . . . . .
Store parameters in
MULTIKEY . . . . . . . . . . . . . .
Store configuration in
MULTIKEY . . . . . . . . . . . . . .
READ PARAM.
READ CONF.
ENTER PARAM.
ENTER CONF.
DUMP PARAM.
DUMP CONFIG.
PARAM. MMM-SE
CONFIG. MMM-SE
PARAM. SE-MMM
CONFIG. SE-MMM
LOAD INIT. PAR.
LOAD INIT. CONF.
PARAM. MK-SE
CONFIG. MK-SE
PARAM. SE-MK
CONFIG. SE-MK
YC: COMPENS.
SET TIME
Tab.2.2: Funktionsverteiler
9941
Technische
Redaktion BVED
MULTICONT
SIMPLEX
Sequence:
FUNCTION
PRESELECT
BATCH
P
H8
Zt = xxxx.xx kg
JP
I8
Zb xxx.xx kg
Zd xxx.xx kg
A
B
FUNCTION
ABORT BATCH
Sequence:
FUNCTION
SELECT REFILLING
FUNCTION
START REFILLING
FUNCTION
STOP REFILLING
FUNCTION
ABORT REFILLING
FUNC TION
ABORT BATCH
P
9941
Technische
Redaktion BVED
SIMPLEX
MULTICONT
Discharge continues operating in gravimetrical mode.
Message : MF 01
Message : MF 03
c) Either a) or b).
MF 01/03
Sequence:
FUNCTION
DISCHARGE MODE
P
A
FUNCTION
DISCHARGE STOP
Mode 1: P 06.11 = 0
If limit value hmin 1 is reached, a normal filling cycle is
initiated. This is when bin level monitoring starts. As may
be selected, (conditions a...c), missing material is
recognized and filling mode ignored.
Technische
Redaktion BVED
FUNCTION
VOLUMETRIC
VOLUM. SYNC.
FUNCTION
GRAVIMETRIC
P
P
MULTICONT
SIMPLEX
FUNCTION
FEED-INDEX
FUNCTION
DISPLAY CHECK
Call function.
NUMBER X
FEED-INDEX
NUMBER X
OK? Y=1, N=0
Acknowledge accordingly.
1P
Load data.
9941
Technische
Redaktion BVED
SIMPLEX
MULTICONT
2.3.1 Taring
STOP Feeder,
Program End:
STOP Feeder,
Program Sequence:
Program End:
FUNCTION
TF: SUPPLY BIN
Display in sub-function
distributor.
TF: xxxx %
Tare xxxx %
Running display.
The upper line shows
residual run time of program
[% total time], in the lower
line, the acquired tare [%
nominal fill weight FVNENN] is
displayed.
Abw. xxxx %
Tara xxxx %
Final display.
Display shows deviation from
previous value [% FVNENN]
and newly acquired tare N
[% FVNENN].
Display in sub-function
distributor.
Start program.
TW:
CALIB.ACTIVE
Running display.
Abw. x.xx%
Tara x.xx%
Final display.
Display shows deviations
from previous value and new
tare
value [% WZNENN].
P
N
P
N
Accept values.
Abort program. No values are
stored.
Store value.
Technische
Redaktion BVED
MULTICONT
SIMPLEX
STOP Feeder,
1P
Display in sub-function
distributor.
Start program.
CW:
FG:xx,xxkg
PLACE WEIGHT
YES=ENT
P
CW:xx.xx
KOR:x.xxxxx
P
O
9941
Acknowledge weight
application and restart
program.
Final display.
Display shows measured
weight CW and correction
factor KOR of range
correction.
Terminate program.
Correction factor is stored.
Abort program. Correction
factor is not acquired.
WZ SIMULATION
Y=1, N=0
Program End:
GA SIMULATION
Y=1, N=0
Technische
Redaktion BVED
SIMPLEX
MULTICONT
Prerequisites:
Program Sequence:
FUNCTION
OPTIM.DAE
Start program.
DAE:e-rel
0.xxxxx % wz0
Running display.
Display shows measuring
noise related to load cell
rated capacity.
VARIANCE:
x.xxxxx % wz0
Final display.
Display shows acquired
variance.
Display in sub-function
distributor.
P
N
Terminate program.
Value on display is stored.
Abort program.
Value on display is not stored.
This
program
serves
for
setting
of
the
Disturbance-Auto-Elimination (K 11.11) and can be
started no matter whether the DAE is ON or OFF.
Program End:
START Feeder,
No refilling.
Program End:
The acquired variance is stored as Parameter P 04.03.
Note:
P 01.02 Pnenn[i]
P 02.05 wz_filt
P 04.01 filter
Filter time,
P 05.02 bn[i]
Technische
Redaktion BVED
9941
MULTICONT
SIMPLEX
Program Sequence:
FUNCTION
CONTR.ADAPT.
Start program.
Exit sub-function distributor
after termination of program.
10%
500
Point 2
30%
1500
Point 3
50%
2500
Point 4
70%
3500
Point 5
90%
4500
Program End:
Acquired values are stored as parameters in Block P 05.
Note:
After termination of program, monitoring becomes active
as soon as compensation is ON. If in computation of
characteristic curve an error is detected in the
assignment of compensation point to feed rate, event
message CO 04 COMP PAR.NOT OK is output.
After approx. 10 min, program automatically aborts and
deletes result.
9941
Technische
Redaktion BVED
SIMPLEX
MULTICONT
Program Sequence:
Pt = xxxx. x kg
P xxxx.x kg
JP
GP
28
P
EAx.AAx[V]
ab
[%]
Start program.
frq
[Hz]
Enter number of
compensation point
corresponding to feed rate
set in accordance with table.
[V]
Control magnitude
Yf
[V]
ED
[h]
CY: XXXXX mV
I: XXX,X %
FUNCTION
YC: COMPENS.
NUMBER_
P
N
Display in sub-function
distributor.
Terminate program.
Values are stored.
Abort program.
No values are stored.
EAx_DE 000000
EAx_DA 000000
DAE
[%]
IF
[t/h]
avb
[%]
PG_F
[kg]
Fill weight
acquired by check weight
automatic
9941
Technische
Redaktion BVED
MULTICONT
SIMPLEX
PG_T
[HH.MM.SS]
PG_D
[DD.MM.JJ]
PG_Kor [%]
PG_Corr =
SetAct
100%
Act
2.4 Programming
With the aid of the programming functions, parameters
and configuration data can be entered, stored internally
or externally, or loaded.
P
00
01
Passakt
*
YES
46
P
P 00.01 Passakt
* YES
9941
Display in subfunction
distributor.
Select sub-function.
Display first parameter.
28
P
K 03.02 T_MAX1
DE -.NO W1
Technische
Redaktion BVED
Parameter
Block
Number
Symbol
No default value.
Current parameter value.
Configuration data are
displayed accordingly. For
details, see Chapter 4.
SIMPLEX
P
O
N
N
MULTICONT
2.4.4 MULTIKEY
Acquire next value.
Display next parameter.
Delete faulty value.
Abort entry by operating key
ESCAPE.
Operate ESCAPE again to
terminate parameter entry.
Sub-function distributor is left.
P
2.4.3 Print Parameters/Configuration
A commercial printer can be connected to the central
interface of the system unit with interconnecting cable
FSC 0006. (See Hardware Manual FH 369 E, pp. 13,
14.)
Printer setting:
FUNCTION
DUMP. PARAM.
FUNCTION
DUMP. CONF.
MK Code X
Yes=1, No=0
1P
Display in sub-function
distributor.
Call function. Configuration
data can be loaded only if
feeder is OFF. The attempt to
load data with running feeder
entails abort of program and
message CUT OFF is
output.
Display shows module code.
FUNCTION OK!!
OVERWRITE?
OK? Y=1, N=0
Technische
Redaktion BVED
NO CONNECTION
NO CODE
9941
MULTICONT
WRITE ERROR
READ ERROR
STATUS ERROR
QUANTITY ERROR
WR. LENGTH
CHECKSUM FAULT
WRONG TYPE
WRONG VERS
WRONG P, K
REFUSED
MK NOT PROG!
9941
Yes=1, No=0
Param. SE-MMM
WRONG REV
FUNCTION
PARAM. SE-MMM
SIMPLEX
Display in sub-function
distributor.
Acknowledge accordingly.
1P
Store data.
Error Messages:
CHECKSUM FAULT
WRITE ERROR
READ ERROR
Upper display
Lower display
:
: SY 09
Data lost
Restau. 0/1 ?
:
: SY 09
Data lost
Default values 0/1 ?
:
: SY 09
Data lost
Multikey 0/1 ?
Technische
Redaktion BVED
SIMPLEX
MULTICONT
2.5 Restoring
Function Restoring enables simultaneous loading of
configuration data and parameters stored in the
multi-memory module. Function can be started only in
the OFF state of feeder.
Error Messages:
SWITCH OFF
RECOVER
CHECKSUM FAULT
Program Sequence:
FUNCTION
RECOVER
Display in sub-function
distributor. Start function.
P
Yes=1, No=0_
RECOVER
1P
Acknowledge accordingly.
Load data.
At first parameters are
checked and loaded, then
configuration data. Errors
entail abort of function.
9941
Technische
Redaktion BVED
MULTICONT
SIMPLEX
3.3 Taring
After entry of rated data (see also feed index), feeder
tares. The automatic taring program (s. 3.1.1) serves for
electrical compensation of acquired tare.
3.1 Power ON
Before powering feeder, check mechanical installation
in accordance with manual and electrical connections in
accordance with circuit diagrams.
After power-up, the feeder data stored are loaded from
the E2PROM into the active store. This is when system
message SCHENCK MULTICONT is displayed. If
system is ready to operate the message effaces and the
current operating state is displayed. For clearing of event
messages, occurring e.g. due to a missing release
signal, see instructions in Chapter 6.
Feeder connection
Counter reset
Setpoint entry
9941
Technische
Redaktion BVED
SIMPLEX
MULTICONT
After controller setting, the Disturbance- AutoElimination is set by program (s.3.2.4). Switch feeder to
gravimetric mode, enter a mean value as feed rate
setpoint and start feeder. Then start program. When
program has run through and value is acquired, feeder
is ready to operate.
9941
Technische
Redaktion BVED
MULTICONT
SIMPLEX
4. Configuration
4.1 General Comments
The MULTICONT system is adapted to any users
requirements by configuration. From the scope of
available functions only those
required for the
application are activated. Analog inputs and outputs are
assigned to logical signals and data. The event
messages are grouped in different classes. Entry is via
function Configuration (s. 2.4.2). The values for source
type, source, and event class can be selected from the
admissible range by cursor operation.
The system is factory-configured in accordance with
specification. Modifications should exclusively be
effected by persons with comprehensive system
knowledge.
Section 4.2 Overview comprises a list of configuration
blocks complete with available signals and functions
facilitating location of individual data.
In Section 4.3 Index, all configuration data including
default values and setting ranges are listed. The
representation corresponds to the display of a machine
control station; additional symbols and block names
largely reduce the need for explanatory texts.
Symbol
Source Type
Source
Event Class
Range
: Settable source types / event classes
Reference: To parameters
To event messages
Note
: The note completes representation by
additional information.
Together with symbol, source type and event message,
the name of the signal describes the function. This name
is used in the alphabetic search list. The symbols beside
the names refer to the source type.
n
m
p
o
q
Input
Output
N/C contact
N/O contact
Flank-controlled
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 1
SIMPLEX
MULTICONT
Channel*
DE
(NE)
EA1 -EA3
ME1-ME3
-
DE1 - DE6
DE1 -DE6
YES / NO
DA
(NA)
EA1 -EA3
-
DA1 -DA7
AE
EA1 - EA3
ME1 -ME3
-
AE1
AE1
AA
EA1 -EA3
-
AA1 -AA2
WZ
EA1 - EA3
ME1 -ME3
-
WZ1
WZ1
GA
EA1 - EA3
ME1 -ME3
-
GA1
GA1
IM
EA1 EA3
-
IM1
TT
LB1 - LB2
SE
Digital Input,
DA
Digital Output,
AE
Analog Input,
AA
Analog Output,
WZ
GA
Speed Input,
IM
Pulse Output,
SE
SE Bus,
TT
IN
.0/.1
Not Active/Active.
IN
Source
ZBS
PLS
IPC
YES/NO
Logical YES/NO.
.1 (YES)
.0 (NO)
9941
Configuration
FH 399 GB/ 4 - 2
Technische
Redaktion BVED
MULTICONT
SIMPLEX
ALARM,
W1
WARNING 1,
W2
WARNING 2,
IG
IGNORE.
Example
K 00.00
DE (NE)
BSP
EA2.DE1
Range: DE (NE) / SE
NO
A / W1
See : P 00.00 beispiel
E 00 Example
Note : To signal Example K 00.00 BSP, a digital
input (N/O contact) is assigned as source type.
As source, digital input 1 of input/output unit 2
is determined. A missing signal is reported as
ALARM. As an alternative, source type SE bus
and event class Warning 1 can be assigned to
the signal. As sources, all active assemblies
with digital inputs, or interfaces, can be
configured via SE bus. To source type solely
logical state NO can be assigned.
If no source is assigned to the signal, -.NO
has to be configured as source, otherwise
event message Example would be
permanently available.
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 3
SIMPLEX
MULTICONT
4.2 Overview
Block K 00.
Hardware Configuration
Measurement Data
Acquisition Unit 1
Measurement Data
Acquisition Unit 2
Input/Output Unit 1
Input/Output Unit 2
Input/Output Unit 3
Machine Control Station 1
Machine Control Station 2
Batch Processor
SE Memory
Multikey
No SI Units
Block K 01.
Block K 02.
K 00.01 ME1_AKT
K 00.02
K 00.03
K 00.04
K 00.05
K 00.06
K 00.07
K 00.08
K 00.09
K 00.10
K 00.11
ME2_AKT
EA1_AKT
EA2_AKT
EA3_AKT
LB1_AKT
LB2_AKT
SE*_AKT
SE_MEM
MK_AKT
NON-SI
K 01.01
K 01.02
K 01.03
K 01.04
FHMIN2
BLOCKSC
T_DAE
DAE_AKT
K 01.05 WARTUNG
K 01.06 WZUEBER
Block K 04.
K 04.00 MATFL_O
K 04.01 TFIL_MA
Block K 05.
External Interlocking
>
>
>
>
>
<
<
>
<
<
<
<
K 05.01
K 05.02
K 05.03
K 05.04
K 05.05
K 05.06
K 05.07
K 05.08
K 05.09
K 05.10
K 05.11
K 05.12
Emergency Stop
Safety Disconnector
Release 1
Release 2
Release 3
No Release
Electrical Equipment Ready
Ready in Mode 0
Ready in Mode 1
Ready to Start in Mode 0
Ready to Start in Mode 1
No EMERGENCY STOP
NOTAUS
FREISCH
FREI_1
FREI_2
FREI_3
NO_FREI
EL_BER
M0_BER
M1_BER
M0_EBER
M1_EBER
NO_NOT
Safety Indications:
Electrical Equipment of Feeder
Block K 06.
< Drives OK
K 02.00
Power Failure
K 02.01
> Error: Feed Drive Overload K 02.02
> Error: Feed Drive Controller K 02.03
> Error: Agitator Overload
K 02.04
> Error: Auxiliary Drives
Overload
K 02.05
Cable Breakage/Short
Circuit
K 02.06
Setpoint Analog Input
Range > MIN
K 02.07
> Feed Drive Temperature Too
High
K 02.08
ANTR_OK
NETZAUS
MS_DOSA
REG_DOS
MS_RUER
MS_HILA
F_KABEL
>
>
>
>
>
>
>
<
FP_ANAL
Block K 03.
Fill Control START/STOP
Automatic Initial Filling
START/STOP
> Suppress Filling
LO_EIN
LO_VORW
LO_STAR
LO_STOP
LO_FKLA
LO_RWEI
LO_SCHN
LO_STEL
K 06.09 LO_AKT
DA_TEMP
Block K 07.
Configuration
FH 399 GB/ 4 - 4
K 04.02 TVOL_MA
K 04.03 IF_MIN
Fill Control
K 03.01 FIL_ST
K 03.02 FIL_AUT
K 03.03 NOFILL
Technische
Redaktion BVED
>
>
>
>
Start Feeder
Preselect Test Mode
START/STOP
Reset Totalizing Counter 1
Reset Totalizing Counter 2
Start Refilling
TM_EIN
TM_VORW
TM_I/O
TM_RES1
TM_RES2
TM_FSTA
9941
MULTICONT
> Stop Refilling
> Preselect Discharge Mode
< Test Mode Preselection
Active
Volumetric Mode 2
> Absolute Feed Rate
Setpoint
Block K 08.
Start Feeder
Preselect Mode 0
START/STOP
Reset Totalizing Counter 1
Reset Totalizing Counter 2
Start Refilling
Stop Refilling
Preselect Discharge Mode
Mode 0 Preselection Active
Volumetric Mode 2
> Absolute Feed Rate
Setpoint
Relative Feed Rate
Setpoint
Block K 09.
K 07.08 TM_AKT
K 07.09 TM_VOL2
K 07.10 TM_PABS
K 08.00
K 08.01
K 08.02
K 08.03
K 08.04
K 08.05
K 08.06
K 08.07
K 08.08
K 08.09
M0_EIN
M0_VORW
M0_IO
M0_1RES
M0_2RES
M0_FSTA
M0_FSTO
M0_LVOR
M0_AKT
M0_VOL2
K 08.10 M0_PABS
K 08.11 M0_PREL
Mode 1 Sources
Start Feeder
Preselect Mode 1
START/STOP
Reset Totalizing Counter 1
Reset Totalizing Counter 2
Start Refilling
Stop Refilling
Preselect Discharge Mode
Mode 1 Preselection Active
Volumetric Mode 2
> Absolute Setpoint
Relative Feed Rate
Setpoint
>
>
>
>
>
>
>
<
9941
K 07.06 TM_FSTO
K 07.07 TM_LVOR
Mode 0 Sources
>
>
>
>
>
>
>
<
Block K 10.
SIMPLEX
K 09.00
K 09.01
K 09.02
K 09.03
K 09.04
K 09.05
K 09.06
K 09.07
K 09.08
K 09.09
K 09.10
M1_EIN
M1_VORW
M1_IO
M1_1RES
M1_2RES
M1_FSTA
M1_FSTO
M1_LVOR
M1_AKT
M1_VOL2
M1_PABS
K 09.11 M1_PREL
K 10.00 EIN_DOS
K 10.01
K 10.02
K 10.03
K 10.04
K 10.05
K 10.06
K 10.07
K 10.08
STCLR
VOL1_EI
FIL_VOR
S_ALARM
S_WARN
RW_EIN
W_EIN
FM1_IA
<
>
>
<
<
<
<
<
<
<
<
Totalizing Counter 2
Bin Level, Load Cell Input
Number of Revolutions
Feed Unit Control
Magnitude
Actual Feed Rate 1
Actual Feed Rate 2
Bin Level
Setpoint
Number of Revolutions
Feed Amount
Message: Auxiliary
Drive started
Speed / Frequency Display
K 10.09 FM2_IA
K 10.10 QU_FGEW
K 10.11 QU_DREH
K 10.12
K 10.13
K 10.14
K 10.15
K 10.16
K 10.17
K 10.18
K 10.19 H_EIN
K 10.20 rin_frq
Block K 11.
Controller
K 11.01
K 11.02
K 11.03
K 11.04
K 11.05
K 11.06
K 11.10
K 11.11
K 11.14 NREG_IO
Limit Values
Block K 13.
K 12.01
K 12.02
K 12.03
K 12.04
K 12.05
K 12.06
K 12.07
K 12.08
K_PMIN
K_PMAX
K_BMIN1
K_BMIN2
K_BMAX1
K_BMAX2
K_NMIN
K_NMAX
Technische
Redaktion BVED
QU_NOTS
MERKREG
DA_REGA
NOTSOL
REG_ERR
PSOLNUL
AA_REGA
DAE.AKT
K 11.12 ST_KOMP
K 11.13 STINDEX
Block K 12.
<
<
<
<
<
<
<
<
STL_DOS
P_IST1
P_IST2
FGEW
P_SOLL
DREHZ
AA_HUB
K 13.01
K 13.02
K 13.03
K 13.04
K 13.05
WZ_MIN
WZ_MAX
GA_ERR
VERST_M
VORL_MIN
K 13.06
K 13.07
K 13.08
K 13.09
F_WZNEN
HMIN2_M
HMAX1_M
SIM_AKT
Configuration
FH 399 GB/ 4 - 5
SIMPLEX
Block K 14.
MULTICONT
Start Fill Device
K 18.04 FILOR_E
Fill Device Inactive
K 18.05 F_AUSFI
Message: Fill Device Active K 18.06 F_EINFI
>
>
<
<
K 14.01
K 14.02
K 14.03
K 14.04
K 14.05
K 14.06
K 14.07
K 14.08
K 14.09
Block K 15
Block K 16.
> Preselect Batching Mode 0
> Preselect Batching Mode 1
> Preselect Batching
Test Mode
> Abort Batch, Mode 0
> Abort Batch, Mode 1
> Abort Batch, Test Mode
< Pre-contact
< Main Contact
Not Dedicated
Batch Setpoint Mode 0
Batch Setpoint Mode 1
Batch Setpoint Test Mode
QU_Z1ST
QU_Z2ST
RUET_EI
VOL_AKT
mes_sys
I2_INV
INV_AKT
P_IST3
I3_Store
Not Active
Batching Mode
K 16.01 M0_BATQ
K 16.02 M1_BATQ
K 16.03
K 16.04
K 16.05
K 16.06
K 16.07
K 16.08
K 16.09
K 16.10
K 16.11
K 16.12
Block K 17.
TM_BATQ
M0_BATA
M1_BATA
TM_BATA
VORKON
HAUPTK
M0_PBAT
M1_PBAT
TM_PBAT
Block K 19.
Block K 20.
> Discharge Gate Open
< OPEN Discharge Gate
Discharge Gate Does
Not Open
Invert Limit Switch
>
>
<
<
<
Block K 18.
Fill Device Available
>: Error: Fill Device Overload
< Fill Device Active
Configuration
FH 399 GB/ 4 - 6
HIFIL_D
RMAUF_E
TRIAUS
ELKL_AU
F_ELKLA
BL_VORB
BLKL_ZU )
RMZU_BL
F_BLKLZ
TRIAUS
SAUGFIL
DRUCKFIL
ELKL_IN
BLKL_IN
Discharge Gate
K 20.01 RM_ATK
K 20.02 ATK_AUF
K 20.03 F_ATK
K 20.04 ATKL_IN
Fill Gate
Block K 21.
K 17.01
K 17.02
K 17.03
K 17.04
K 17.05
K 17.06
K 17.07
K 17.08
K 17.09
FKL_DA
FKL_RMZ
FKL_RMA
FKL_AUF
F_FKLAU
F_FKLZU
DA_FKLA
DA_FKLZ
>
<
<
<
<
QU_FGVB
FGVB
FVB_MIN
FVB_MAX
FILORVB
K 21.06 WZVB_MI
K 21.07 WZVB_MA
Fill Device
K 18.01 FILOR_D
K 18.02 MS_FILO
K 18.03 FILOR_R
Technische
Redaktion BVED
9941
MULTICONT
Block K 22.
SIMPLEX
Dead Time Element
TOT_VM0
Block K 23.
Zero Setting
K 23.01 QU_NUL
K 23.02 ERR_NUL
TOT_VM1
TOT_TM0
Block K 24.
TOT_TM1
TOT_VOR
TOT_INI
TOT_IM0
Pressure Compensation
K 24.01 D_QU
K 24.02 D_MIN
K 24.03 D_MAX
K 24.04 D_MEMIN
K 24.05 D_MEMAX
TOT_IM1
TOT_TI0
TOT_TI1
TOT_GEW
TOT_PON
TOT_ON
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 7
SIMPLEX
MULTICONT
Input/Output Unit 3
ME1_AKT
K 00.05
EA3_AKT
.1
.0
Range: .0 / .1
See : SY 01 ME1 DATA LINK
Range: .0 / .1
See : SY 05 EA3 DATA LINK
ME2_AKT
K 00.06
LB1_AKT
.0
.1
Range: .0 / .1
See : SY 02 ME2 DATA LINK
Range: .1
A / IG
See : SY 06 LBS DATA LINK
Note : Machine control station 1 cannot be
de-activated. Configure event message as
IG.
Input/Output Unit 1
Machine Control Station 2
K 00.03
EA1_AKT
K 00.07
.1
Range: .0/.1
See : SY 03 EA1 DATA LINK
LB2_AKT
.0
Range: .0 / .1
See : SY 07 LBS 2 DATA LINK
Input/Output Unit 2
K 00.04
Batch Processor
EA2_AKT
K 00.08
SE*_AKT
.0
.0
Range: .0 / .1
See : SY 04 EA2 DATA LINK
Range: .0 / .1
See : SY 08 SE* DATA LINK
Configuration
FH 399 GB/ 4 - 8
A / IG
Technische
Redaktion BVED
A
A / W2
9941
MULTICONT
SIMPLEX
SE Memory
No SI Units
K 00.09
SE_MEM
IN
See
A
: SY 09 MEMORY FAIL
Multikey
K 00.10
MK_AKT
K 00.11
NON-SI
.0
Range: .0 / .1
See : Chapter 5.1 Parameter Designation
Note : The SI units are converted into American units.
Upon system start, all parameters, counter
readings and setpoints are converted. The SE
bus message continues transmitting data in SI
units. A running batch is aborted.
.0
Range: .0 / .1
FHMIN2
IN
See:
K 01.03
IN
DAE Active
Feeder Blocked
IN
Range:
See : SC 02 FEEDER BLOCKED
P 05.28
Range:
A / W1 / W2
See: K 11.11 DAE_AKT
P 04.04 twach
SC 03 DAE TIME MONITORING
P 06.02 HMIN2
SC 01 BIN LEVEL < HMIN2"
K 01.02
T_DAE
BLOCKSC
IG
A / IG
K 01.04
IN
Range:
See : K 11.11 DAE_AKT
P 04.02 warfak
SC 04 DAE ACTIVE
DAE_AKT
W2
W1 / W2 / IG
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 9
SIMPLEX
MULTICONT
WARTUNG
IN
See
Standby
W1
standby
IN
IG
Range: IN
See : P 05.28, P 05.29, SC 07
: P 02.07 wartint
SC 05 MAINTENANCE INTERVAL
no
K 01.07
W1 / W2 / IG
K 01.06
DE
WZUEBER
-.NO
Range:
W1/A
See : SC 06 L/C OVERLOAD CONTACT
Latest measurement is used as long as signal
is available.
mo
no
Electrical OK
K 02.00
ANTR_OK
K 02.02
MS_DOSA
DA
DE
Range: DA (NA)
Range: DE (NE)
NO
See : WE 02 FEED DRIVE OVERLOAD
Power Failure
K 02.01
IN
Range: IN
See : WE 01 POWER DOWN
NETZAUS
A
A / IG
np
EA1.DE2
K 02.03
DE
REG_DOS
-.NO
Range: DE (NE)
YES / NO
See : WE 03 FEED DRIVE SCR FAIL
9941
Configuration
FH 399 GB/ 4 - 10
Technische
Redaktion BVED
MULTICONT
np
no
K 02.04
DE
SIMPLEX
MS_RUER
EA1.DE4
Range: DE (NE)
NO
A / W1 / W2 / IG
See : WE 04 AGITATOR OVERLOAD
np
K 02.08
DE
DA_TEMP
-.NO
Range: DE (NE)
NO
See : WE 08 FEED DRIVE TEMPERATURE
K 02.05
MS_HILA
DE
-.NO
W2
Range: DE (NE)
YES/NO A / W1 / W2 / IG
See : WE 05 ADD. DRIVE OVERLOAD
F_KABEL
IN
Range:
See : WE 06 CABLE SHORT OR INT.
Note : Only with NAMUR inputs.
Special case: IG
Contact connection possible.
Open : Level 1
Closed : Level 0
FP_ANAL
A
A/IG
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 11
SIMPLEX
MULTICONT
K 03. Fill Control
FIL_AUT
.0
: Block K 17.
Fill Gate
Block K 18.
Fill Device
Block K 19.
Auxiliary Fill Devices
Block P 06.
Fill Control
Note : With fill control extended by Blocks K 17 to
K 19, signal K 03.05 cannot be used.
FIL_ST
Range: .0
Note : If bin level FG has fallen below safety limit value
HMIN2, event message SC 01 configured as
ALARM triggers and feeder stops. For safety
reasons, no refilling is possible. Initial filling
requires to be effected.
If critical materials are fed, cut off automatic
initial filling. Preselect refilling mode (K 10.03)
before refilling is started.
With easy-to-feed materials, automatic initial
filling can be activated, enabling initial filling to
be started via contact by using command
START Filling.
Refilling is equally started if event message SC
01 Bin Level < HMIN2" is acknowledged for
the first time after power-up, or power failure.
no
Suppress Filling
K 03.03
.1
Range: .0 / .1
See : K 03.05 FIL_EIN
P 06.01 hmin1
Note : Cut off fill control, if no automatic fill devices are
provided (e.g. manual refilling).
If fill control is cut off, signal K 03.05 is output
when bin level falls below P 06.01. All other fill
control functions are inactive.
DE
NOFILL
EA2.DE3
Range: DE (NE)
YES / NO
Note : SE bus acts as source of equal priority,
independent of configuration.
no
9941
Configuration
FH 399 GB/ 4 - 12
Technische
Redaktion BVED
MULTICONT
mo
SIMPLEX
Discharge With Filling Error
START Refilling
K 03.05
FIL_EIN
DA
FILST_SPEZ
.0
EA1.DA3
Range: DA (NA)
Note : If auxiliary fill devices are activated, signal is
irrelevant.
If fill control is cut off, signal is output when bin
level has fallen below HMIN1.
mo
K 03.07
Range: .0
.0
: Normal filling.
.1
: If filling cycle
continues.
See
is
interrupted,
discharge
K 03.06
DA
FIL_AKT
EA1.DA6
Range: DA (NA)
mo
mo
Material Flow OK
K 04.00
DA
Range: DA (NA)
MATFL_O
-
K 04.01
DA
TFIL_MA
-
W1
Range: DA (NA)
A / W1 / W2
See : P 06.09 tfuell
MF 01 REFILLING TIME EXC
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 13
SIMPLEX
mo
MULTICONT
mo
K 04.02
TVOL_MA
DA
W1
Range:DA (NA)
A / W1 / W2
See : P 11.03 tvolum
MF 02 VOL. DISCHARGE TIME
K 04.03
IF_MIN
DA
W1
Range: DA (NA)
See : P 08.11 if_min
MF 03 If < MIN
W1 / W2 / IG
np
K 05.01
NOTAUS
DE
-.NO
Range: DE (NE)
NO
See : IL 01 EMERGENCY STOP
mp
no
Emergency Stop
DE
Range: DE (NE) / SE
no
EA1.DE1A
-.YES
K 05.05
FREI_3
FREI_1
EA1.DE6
YES / NO
No Release
K 05.06
DA
YES / NO
-.NO
Range: DE (NE) / SE
no
Release 1
YES / NO
Release 3
DE
K 05.03
DE
FREI_2
DE
FREISCH
Range: DE (NE)
NO
See : IL 02 LOCAL MAIN SWITCH
no
K 05.04
Safety Disconnector
K 05.02
Release 2
NO_FREI
-
Range: DA (NA)
See : IL 03 NO RELEASE
W2
W2
9941
Configuration
FH 399 GB/ 4 - 14
Technische
Redaktion BVED
MULTICONT
mo
SIMPLEX
mo
K 05.07
EL_BER
DA
mo
Ready in Mode 0
M0_BER
EA1.DA5
K 05.11
M1_EBER
DA
Range: DA (NA)
mo
M0_EBER
Range: DA (NA)
K 05.08
DA
K 05.10
DA
Range: DA (NA)
no
Range: DA (NA)
mo
Ready in Mode 1
K 05.09
DA
Range: DA (NA)
M1_BER
-
No EMERGENCY STOP
K 05.12
DA
NO_NOT
-
Range: DA (NA)
Message No EMERGENCY STOP = NO does not
efface until input signal EMERGENCY STOP is
inactive and event message IL 01 is acknowledged.
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 15
SIMPLEX
MULTICONT
K 06. Local Mode Sources
n oq
LO_EIN
IN
K 06.05
LO_FKLA
DE
ME2.DE4
Range: DE (NE)
no
n oq
K 06.01
LO_VORW
DE
ME2.DE1
n oq
K 06.02
LO_STAR
ME2.DE2
Range: DE (NE)
n oq
ME2.DE5
Range: DE (NE)
K 06.03
LO_STOP
YES / NO
K 06.07
LO_SCHN
-.NO
Range: DE (NE)
Range: DE (NE)
LO_RWEI
DE
YES / NO
DE
K 06.06
n oq
DE
Start Agitator
DE
Range: DE (NE)
YES / NO
Note : Contact precedes any other main mode.
If Local Mode is cut off, feeder automatically stops
and returns to its previous mode. After power failure
feeder is in Mode 0.
YES / NO
YES / NO
K 06.08
ME1.DE3
YES / NO
AE
LO_STEL
ME2.AE1
Range: AE
See : P 10.03 I_adan1
P 10.04 I_adbe1
Note : The drive signal is set in manual on local control
box and controls the discharge unit directly.
9941
Configuration
FH 399 GB/ 4 - 16
Technische
Redaktion BVED
MULTICONT
mo
SIMPLEX
K 06.09
LO_AKT
DA
Range: DA (NA)
Start Feeder
K 07.00
TM_EIN
IN
no
K 07.04
TT
TM_VORW
TT
LB1
n oq
TT
START/STOP
K 07.02
TM_I/O
TT
LB1
Start Refilling
TM_FSTA
LB1
n oq
no
YES / NO
K 07.05
Range: SE/TT
n oq
LB1
Range: DE (NE) / SE / TT
TM_RES2
Stop Refilling
K 07.06
TT
K 07.03
TT
TM_RES1
TM_FSTO
LB1
Range: DE (NE) / SE / TT
LB1
Range: DE (NE) / SE / TT
YES / NO
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 17
SIMPLEX
no
MULTICONT
Volumetric Mode 2
K 07.07
TM_LVOR
TT
Range: .0 / .1
Note : If configuration is active, feeder automatically
changes over from Test Mode to sub-mode
Volumetric Mode 2.
K 07.08
TM_AKT
DA
TM_VOL2
.0
LB1
Range: DE (NE) / SE / TT
mo
K 07.09
K 07.10
Range: DA (NA)
TM_PABS
TT
LB1
Range: AE / SE / TT
See : P 10.01 adan1
P 10.02 adbe1 [i]
n oq
Start Feeder
K 08.00
M0_EIN
IN
START/STOP
K 08.02
SE
M0_IO
ZBS
Range: DE (NE) / SE / TT
n oq
Preselect Mode 0
K 08.01
TT
M0_VORW
no
K 08.03
LB1
SE
Range: DE (NE) / SE / TT
M0_1RES
ZBS
Range: DE (NE) / SE / TT
YES / NO
9941
Configuration
FH 399 GB/ 4 - 18
Technische
Redaktion BVED
MULTICONT
no
SIMPLEX
mo
K 08.04
M0_2RES
SE
ZBS
Range: DE (NE) / SE / TT
n oq
M0_AKT
YES / NO
Volumetric Mode 2
Start Refilling
K 08.09
M0_FSTA
SE
ZBS
Stop Refilling
Range: .0 / .1
Note : If configuration is active, feeder automatically
changes over from Mode 0 to sub-mode
Volumetric Mode 2.
K 08.10
M0_FSTO
SE
M0_VOL2
.0
K 08.06
ZBS
M0_PABS
SE
ZBS
Range: AE / SE / TT
See : P 10.01 adan1
P 10.02 adbe1[i]
Range: DE (NE) / SE / TT
no
K 08.08
DA
K 08.05
n oq
K 08.07
SE
M0_LVOR
ZBS
M0_PREL
.0
Range: SE / TT / .0
Range: DE (NE) / SE / TT
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 19
SIMPLEX
MULTICONT
K 09. Mode 1 Sources
n oq
Start Feeder
K 09.00
M1_EIN
IN
M1_VORW
TT
LB1
Range: DE (NE) / SE / TT
n oq
n oq
TT
START/STOP
LB1
Range: DE (NE) / SE / TT
no
K 09.03
LB1
Range: DE (NE) / SE / TT
M1_1RES
LB1
Range: DE (NE) / SE / TT
M1_FSTO
K 09.07
TT
TT
Stop Refilling
Range: DE (NE) / SE / TT
M1_IO
TT
LB1
K 09.06
K 09.02
no
M1_FSTA
Preselect Mode 1
K 09.01
no
K 09.05
TT
n oq
Start Refilling
YES / NO
mo
K 09.08
DA
Reset Totalizing Counter 2
K 09.04
TT
M1_2RES
LB1
Range: DE (NE) / SE / TT
Configuration
FH 399 GB/ 4 - 20
YES / NO
Technische
Redaktion BVED
9941
MULTICONT
SIMPLEX
Volumetric Mode 2
Relative Setpoint
K 09.09
M1_VOL2
K 09.11
M1_PREL
.0
.0
Range: .0/.1
Note : If configuration is active, feeder automatically
changes over from Mode 1 to sub-mode
Volumetric Mode 2.
Range: SE / TT / .0
Absolute Setpoint
K 09.10
M1_PABS
TT
LB1
Range: AE / SE / TT
See : P 10.01 adan1
P 10.02 adbe1[i]
mo
Volumetric Mode 1
K 10.00
EIN_DOS
DA
EA2.DE4
Range: DE (NE)
YES / NO
Note : In this sub-mode feeder operates with filtered
control magnitude YF (see also Service
Values).
Independent of configuration, the SE bus has
equal priority.
K 10.01
DE
VOL1_EI
DE
EA1.DA1
Range: DA (NA)
no
K 10.02
STCLR
EA1.DE5
K 10.03
Range: DE (NE)
YES / NO
Note : Independent of configuration event messages
can be acknowledged both via machine control
station and SE bus.
TT
FIL_VOR
LB1
Range: SE / TT / .0
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 21
SIMPLEX
mo
MULTICONT
General Alarm
K 10.04
S_ALARM
DA
EA1.DA2
K 10.09
FM2_IA
IM
Range: DA (NA)
mo
Totalizing Counter 2
EA2.IM1
Range: IM
See : P 01.11 fm2dim
P 01.12 fm2puls
General Warning
K 10.05
S_WARN
DA
EA1.DA7
K 10.10
QU_FGEW
WZ
Range: DA (NA)
ME1.WZ1
Range: WZ
See : SY 10 qb WRONG UNIT
mo
Start Agitator
K 10.06
RW_EIN
EA1.DA4
Number of Revolutions
K 10.11
Range: DA (NA)
See : P 08.09 rwerk
mo
QU_DREH
GA
W_EIN
DA
Range: GA
See : SY 11 n WRONG UNIT
K 10.07
ME1.GA1
K 10.12
STL_DOS
Range: DA (NA)
AA
Totalizing Counter 1
K 10.08
IM
FM1_IA
EA1.AA1
Range: AA
See : P 05.02 bn[i]
P 05.06 go
P 05.07 gu
P 05.08 anh
EA1.IM1
Range: IM
See : P 01.09 fm1dim
P 01.10 fm1puls
9941
Configuration
FH 399 GB/ 4 - 22
Technische
Redaktion BVED
MULTICONT
K 10.13
AA
SIMPLEX
P_IST1
EA1.AA2
DREHZ
-
Range: AA
See : P 09.11 n_Anh
P 09.12 n_Ber[i]
K 10.14
K 10.17
AA
Range: AA
See : P 09.01 P1_Anh
P 09.02 P1_Ber[i]
Number of Revolutions
P_IST2
Feed Amount
K 10.18
AA
AA_HUB
AA
Range: AA
See : P 09.03 P2_Anh
P 09.04 P2_Ber[i]
m
AA
Range: AA
See : P 09.07 H_Anh
P 09.08 H_Ber[i]
mo
Bin Level
K 10.15
FGEW
EA2.AA2
K 10.19
H_EIN
DA
Range: AA
See : P 09.05 FG_Anh
P 09.06 FG_Ber[i]
Range: DA (NA)
K 10.20
Setpoint
K 10.16
AA
P_SOLL
-
Range: AA
See : P 09.09 PS_Anh
P 09.10 PS_Ber[i]
rin_frq
.0
Range: .0 / .1
See: P 01.15 frqnenn
.0
: Display speed in lower display field
.1
: Display vibro feeder frequency
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 23
SIMPLEX
MULTICONT
K 11. Controller
no
mo
K 11.01
QU_NOTS
DE
EA2.DE5
K 11.05
REG_ERR
DA
W1
Range: DE (NE) / SE
YES / NO
See : P 05.12 Emergency Setpoint Limit
Note : The emergency setpoint limit can be activated
externally enabling feed rate to be immediately
reduced in case of need.
Range: DA (NA)
W1 / W2 / IG
See: P 05.06 go
P 05.07 gu
CO 03 CONTROLLER OUT LIMIT
Controller Memory
Setpoint 0
K 11.02
MERKREG
K 11.06
PSOLNUL
.1
.1
Range: .0 / .1
Note : Applies to start-up operation. With memory
activated the control magnitude YF stored last
is used when feeder is started.
Range: .1
Note: For feeder OFF, setpoint can be set to 0 kg/h.
Enter new setpoint upon restart of feeder.
mo
Message: Deviation
K 11.03
DA_REGA
DA
Range: DA (NA)
See: P 05.09 diffmax
P 05.10 regtim
CO 01 DEVIATION
mo
W1
A / W1 / W2
K 11.10
DA
Range: AA
See : P 09.13 r_Anh
P 09.14 r_Ber
START/STOP DAE
NOTSOL
-
W1
Range: DA (NA)
W1 / W2 / IG / A
See: P 05.12 notsol
P 01.02 pnenn
CO 02 SETPOINT LIMITED
Configuration
FH 399 GB/ 4 - 24
AA_REGA
AA
K 11.04
Deviation
Technische
Redaktion BVED
K 11.11
DAE.AKT
.0
Range: .0 / .1
Note : Start DAE for feeding and cut off for controller
setting.
9941
MULTICONT
SIMPLEX
K 11.12
NREG_IO
ST_KOMP
.0
.0
Range: .0 / .1
See : P 05.14 - P 05.23
Note : This function serves for compensating the
non-linary behaviour of a vibro-feeder. Upon
commissioning, the control magnitudes for
different feed rates are acquired. These values
are stored as Parameters P 05.14 to P 05.23
and serve for computation of the feeder
characteristic curve used for compensation (s.
function Compensation) . During value
acquisition, compensation requires to be cut
off.
mo
Range: .0 / .1
See: P 05.30...
The special speed controller is active only if:
1.
K11.14 = .1
2.
3.
K 11.13
STINDEX
DA
Range: DA (NA)
See : P 05.27
Select operating ranges INDEX 1/2 of vibration
feeder.
mo
K 12.01
DA
9941
mo
Range: DA (NA)
See : P 08.01 pmin
LO 01 FEED RATE I LO
W2
A / W1 / W2 / IG
K 12.02
DA
K_PMAX
-
Range: DA (NA)
See : P 08.02 pmax
HI 01 FEED RATE I HI
Technische
Redaktion BVED
W2
A / W1 / W2 / IG
Configuration
FH 399 GB/ 4 - 25
SIMPLEX
mo
MULTICONT
mo
K 12.03
K_BMIN1
DA
W2
Range: DA (NA)
A / W1 / W2 / IG
See : P 08.03 bmin1
LO 02 BIN LEVEL < BMIN1"
mo
K 12.06
K_BMAX2
DA
K 12.07
K 12.04
K_NMIN
K_BMIN2
DA
DA
W2
Range: DA (NA)
A / W1 / W2 / IG
See : P 08.04 bmin2
LO 03 BIN LEVEL < BMIN2"
mo
Range: DA (NA)
See: P 08.06 bmax2
HI 03 BIN LEVEL > BMAX2"
no
Range: DA (NA)
See : P 08.07 nmin
LO 04 SPEED LO
mo
K 12.08
K 12.05
K_NMAX
K_BMAX1
DA
DA
W2
Range: DA (NA)
A / W1 / W2 / IG
See : P 08.05 bmax1
HI 02 BIN LEVEL > BMAX1"
Range: DA (NA)
See: P 08.08 nmax
HI 04 SPEED > nmax
@BLOCK 2 = K 13.02WZ_MAX
IN
IN
Range: IN
See : CA 01 LC OUT < MIN
Range: IN
See : CA 02 LC INP > MAX
9941
Configuration
FH 399 GB/ 4 - 26
Technische
Redaktion BVED
MULTICONT
SIMPLEX
PLL Overflow
K 13.03
IN
See
: K 10.11 QU_DREH
CA 03 PLL OVERFLOW
Note : Speed input overamplified.
K 13.08
HMAX1_M
IN
See
A
: CA 08 HMIN1 > HMAX1"
Simulator Active
Amplification MAX
K 13.04
K 13.09
VERST_M
IN
W1
Range: IN
See : CA 04 AMPLIFICATION MAX
SIM_AKT
IN
See
W2
: CA 09 SIMULATION ACTIVE
W1 / A
Preload < 5 %
K 13.05
VORL_MIN
IN
See
A
: CA 05 PRELOAD < 5%
F_WZNEN
IN
See
A
: CA 06 PREL + BUFF + FEED > NOM
HMIN2_M
A
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 27
SIMPLEX
MULTICONT
no
K 14.01
QU_Z1ST
DE
no
-.NO
Range: DE m(NE) / SE
YES / NO
: Controlling System
: Measuring System
Preset setpoint is output via controller bypass.
Controller does not operate.
K 14.02
QU_Z2ST
DE
-.NO
Range: DE (NE) / SE
K 14.06
YES / NO
I2_INV
.0
mo
Start Vibrator
K 14.03
RUET_EI
DA
See
: P 08.10 vibro
mo
Volumetric
K 14.04
VOL_AKT
DA
Range: .0 / .1
See: K 14.07 INV_AKT
.0
: Analog outputs K 10.13 and K 10.14 are
designed for output of positive feed rate.
Feed rates smaller than zero are limited to the
elevation.
.1
: Analog output 2 (K 10.14) is designed for
output of negative feed rates.
Internally, the sign of the feed rate to be output
is reversed.
If fill control is activated, estimated discharge is output
during filling.
EA2.DA7
Range: DA (NA)
Measuring System
K 14.05
mes_sys
mo
.0
K 14.07
Range: .0 / .1
DA
Range: DA(NA)
Configuration
FH 399 GB/ 4 - 28
Technische
Redaktion BVED
9941
MULTICONT
See:
SIMPLEX
n oq
K 14.06
K 14.09
DE
I3_Store
-.NO
K 14.08
AA
P_IST3
Range: DE(NE)
See: K 14.08 P_IST3
NO
Range: AA
See: P 09.15 P3_Anh
P 09.16 P3_BER
P 07.02 pdatau
K 14.09 I3_Store
Outputs feed rate amount. Value output can be stored
via input K 14.09.
K 15 Not Active
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 29
SIMPLEX
MULTICONT
K 16. Batching Mode
See:
Block P 12.
no
no
K 16.01
M0_BATQ
SE
ZBS
K 16.06
TT
no
LB1
K 16.02
TM_BATA
M1_BATQ
mo
Pre-contact
K 16.07
TT
VORKON
LB1
DA
no
Range: DA (NA)
Preselect Batching Test Mode
K 16.03
TM_BATQ
TT
LB1
DA
HAUPTK
-
Range: DA (NA)
Abort Batch, Mode 0
K 16.04
M0_BATA
SE
ZBS
Range: DE (NE) / SE / TT
no
Main Contact
K 16.08
no
mo
NO
K 16.05
TT
M1_BATA
LB1
Configuration
FH 399 GB/ 4 - 30
9941
Technische
Redaktion BVED
MULTICONT
SIMPLEX
Not Dedicated
K 16.09
K 16.11
M1_PBAT
TT
LB1
Range: SE / TT
SE
ZBS
K 16.12
TT
Range: SE / TT
TM_PBAT
LB1
Range: SE / TT
See:
no
K 17.03
DE
FKL_DA
Range: DE (NE)
FKL_RMA
ME1.DE2
YES / NO
.0
Range: .0 / .1
no
mo
Fill Gate Closed
K 17.02
DE
K 17.04
FKL_RMZ
ME1.DE3
Range: DE (NE)
DA
FKL_AUF
EA2.DA2
Range: DA (NA)
YES / NO
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 31
SIMPLEX
MULTICONT
mo
F_FKLAU
IN
Range: IN
See: WM 01 FILL GATE NOT OPEN
F_FKLZU
IN
Range: IN
See : WM 02 FILL GATE NOT CLOSED
K 17.08
DA_FKLA
DA
Range: DA (NA)
Prerequisite: K 17.01 = 1
mo
K 17.09
DA_FKLZ
DA
Range: DA (NA)
Prerequisite: K 17.01 = 1
Not Dedicated
K 17.07
K 18.02
DE
np
FILOR_D
MS_FILO
-.NO
W1
Range: DE (NE)
NO
A / W1 / W2
See: WM 03 FILL DEVICE OVERLOAD
.0
mo
Range: .0 / .1
K 18.03
DE
Range: DE (NE)
FILOR_R
-.NO
NO
9941
Configuration
FH 399 GB/ 4 - 32
Technische
Redaktion BVED
MULTICONT
SIMPLEX
K 18.04
FILOR_E
DA
K 18.05
F_AUSFI
IN
Range: DA (NA)
W1
Range: IN
A / W1 / W2
See: WM 04 FEEDBACK FILL DEVICE
F_EINFI
IN
Range: IN
A / W1 / W2
See : WM 05 FILL DEVICE ACTIVE
no
K 19.02
RMAUF_E
DE
ME1.DE4
Range: DE (NE)
n oq
K 19.03
DE
NO
Range: DE (NE)
TRIAUS
ME2.DE6
YES / NO
HIFIL_D
.0
Range: .0/.1
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 33
SIMPLEX
1)
Initiate Filling
a) Start Filling HMIN
P 06.01
IN
P 06.03
IN
K 14.04
DA
K 19.12
P 13.05
DA
K 19.11
DA
K 19.10
DA
a) OPEN
K 19.04
DA
b) Open
K 19.02
DE)
a) SHUT
K 19.07
DA
b) Closed
K 19.08
DE
DA
b) Closed
K 17.04
P 06.06
K 17.02
DE
c) Open
K 17.03
DE
K 19.06
P 13.01
P 13.02
DA
a) START
K 18.04
DA
b) Active
K 18.03
DE
K 03.06
DA
2)
Volumetric Mode
3)
Filter Cleaning
4)
5)
Vent Valve
6)
7)
MULTICONT
Ventilating Valve
Fill Gate
a) OPEN
8)
9)
Fill Device
P13.06 tvs
Start P06.09 tfuell
P13.04
tn2
P13.03
P06.06
tbruhe
Configuration
FH 399 GB/ 4 - 34
Technische
Redaktion BVED
MULTICONT
mo
K 19.04
DA
SIMPLEX
ELKL_AU
7)
8)
Supply Bin
Compressed
Air Filter
Weigh Hopper
W1
Range: IN
See : WM 06 VENTING
5)
6)
F_ELKLA
IN
EA2.DA3
Range: DA (NA)
3)
K 19.05
mo
K 19.06
BL_VORB
DA
EA2.DA4
Range: DA (NA)
mo
K 19.07
DA
BLKL_ZU
EA2.DA5
Range: DA (NA)
Supply Bin
Ventilation
Supply Bin
Fill Device
Supply Bin
Ventilation
Funnel
Blow-Out
Fill Device
HMAX 1
A / W1
Funnel
Blow-Out
Feed Amount
Weigh Hopper
Suction Filter
Vent
Valve
Feed Amount
HMIN1
Puffer
HMAX 1
Buffer
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 35
SIMPLEX
no
MULTICONT
K 19.08
RMZU_BL
DE
ME1.DE5
Range: DE (NE)
mo
K 19.11
SAUGFIL
DA
NO
Range: DA (NA)
mo
Ventilating Valve Does Not Close
K 19.09
W1
Range: IN
See : WM 07 VENTILATION
K 19.12
F_BLKLZ
IN
mo
mo
DA
DRUCKFIL
-
Range: DA (NA)
A / W1
K 19.10
TRIAUS
DA
EA2.DA6
Range: DA
no
K 20.01
DE
RM_ATK
-.NO
Range: .0 / DE (NE)
Note : .0 = No discharge gate provided.
Configuration
FH 399 GB/ 4 - 36
Technische
Redaktion BVED
9941
MULTICONT
mo
SIMPLEX
K 20.02
ATK_AUF
DA
Range: DA (NA)
mo
K 20.03
F_ATK
DA
Range: DA (NA)
See:
WM 08 DISCHARGE GATE
A
A / IG
K 21.02
FGVB
AA
Bin Level Source
K 21.01
WZ
QU_FGVB
-
Range: WZ / SE
See : SY 12 qvb WRONG UNIT
Range: AA
See : P 14.06 vbanh
P 14.07 vbdakor
mo
K 21.03
DA
FVB_MIN
-
Range: DA (NA)
See : P 16.01 vbmin
LO 05 SUPPLY BIN LO
W2
W1 / W2 / IG
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 37
SIMPLEX
mo
MULTICONT
Supply Bin Load Cell Input < MIN
K 21.04
FVB_MAX
DA
W2
Range: DA (NA)
See : P 16.02 vbmax
HI 05 SUPPLY BIN HI
mo
W1 / W2 / IG
K 21.06
WZVB_MI
IN
Range: IN
See : CA 10 LC SUPPLY BIN < MIN
A / W1
K 21.05
WZVB_MA
FILORVB
IN
DA
Range: IN
See : CA 11 LC SUPPLY BIN > MAX
Range: DA (NA)
See : P 16.03 vhmin
P 16.04 vhmax
A / W1
no
DE
Range: DE (NE) / SE
Preselect Dead
Time Element Setpoint M1
K 22.02
TOT_VM1
DE
-.NO
Range: DE (NE) / SE
no
Preselect Dead
Time Element Setpoint M0
K 22.01
no
TOT_VM0
YES / NO
K 22.03
-.NO
YES / NO
DE
Range: DE (NE) / SE
TOT_TM0
-.NO
YES / NO
9941
Configuration
FH 399 GB/ 4 - 38
Technische
Redaktion BVED
MULTICONT
no
SIMPLEX
no
K 22.04
Dead
Time Element START/STOP, Clock ON M1
TOT_TM1
DE
-.NO
Range: DE (NE) / SE
no
YES / NO
no
Dead
Time Element START/STOP Clock ON M0
TOT_VOR
-.NO
K 22.09
TOT_TI0
DE
Range: DE (NE) / SE
YES / NO
Note : Setpoint is assigned to dead time element.
n oq
-.NO
Range: DE (NE) / SE
Preassign Dead
Time Element Setpoint
DE
TOT_IM1
DE
YES / NO
K 22.05
K 22.08
-.NO
Range: DE (NE) / SE
YES / NO
no
Dead
Time Element START/STOP Clock ON M1
K 22.10
K 22.06
TOT_TI1
TOT_INI
DE
DE
-.NO
-.NO
Range: DE (NE) / SE
Range: DE (NE) / SE
no
Dead
Time Element START/STOP, Clock ON M0
K 22.07
DE
Range: DE (NE) / SE
YES / NO
YES / NO
TOT_IM0
-.NO
YES / NO
mo
K 22.11
DA
TOT_GEW
-
Range: DA (NA)
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 39
SIMPLEX
mo
MULTICONT
Dead Time
Element Setpoint Active
K 22.12
TOT_PON
DA
Range: DA (NA)
mo
Dead Time
Element START/STOP Active
K 22.13
TOT_ON
DA
Range: DA (NA)
n oq
mo
K 23.01
DE
QU_NUL
-.NO
K 23.02
DA
Range: DE (NE)
NO
See: K 23.02 ERR_NUL
P 19.01 erg_nul
P 19.02 gr-Nul
W1
Range: DA(NA)
See: K 23.01 QU_NUL
Event HI 09, Zero Setting Limit
P 19.01, P 19.02
W1 / IG
9941
Configuration
FH 399 GB/ 4 - 40
Technische
Redaktion BVED
MULTICONT
SIMPLEX
K 24. Pressure Compensation
K 24.03
D_MAX
DA
W2
Range: DA(NA)
See: HI 06 Measured Value Comp. > MAX
P 20.04 d_max
Load Cell Input (Pressure) < MIN
K 24.01
D_QU
WZ
Range: L/C
See: SY13 Wrong Unit
W1 / W2 / A / IG
mo
mo
D_MEMIN
IN
Range:
See:
CA12 Comp. Input < MIN
W1 / A
K 24.02
DA
K 24.05
D_MIN
Range: DA(NA)
See: LO 06 Measured Value Comp. < MIN
P 20.03 d_min
W2
D_MEMAX
IN
Range:
See: CA13 Comp. Input > MAX
W1 / A
9941
Technische
Redaktion BVED
Configuration
FH 399 GB/ 4 - 41
MULTICONT
SIMPLEX
5. Parametrization
5.1 Parameter Designation
Parameters complete configuration and serve for total
system definition. All rated data, calibration and
evaluation data as well as controller settings, limit
values, and standard interfaces are entered as
parameters. All functions required for parameter setting
can be accessed via the function distributor. The
operating functions are described in Chapter 2
Functions and Operating Modes.
For rated data, calibration and evaluation data, see
relevant data sheets.
Section 5.2 Overview comprises a list of all parameter
blocks which enables instantaneous survey and
facilitates location of individual parameters.
Name
Number
Symbol
Value
In Section 5.3 Index, all parameter blocks including
default values and eligible settings are listed.
The parameter units can be converted from the
international (SI) to the American system of units by
configuration (K 00.11 Nonsi).
Conversion
Intl. Units => American Units
g
=>
oz
1 oz
= 28.3703 g
kg
=>
lb
1 lb
= 0.4535925 kg
=>
1t
= 2000 lb
mm =>
inch
1 inch
= 25.4 mm
1f
= 0.3048 m
=>
Range: A...Z
9941
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 1
SIMPLEX
MULTICONT
5.2 Overview
Block P 00.
Dialog Behaviour
Password Active
Language
P 00.01 Passakt
P 00.02 spr
Block P 01.
Block P 03.
Tare (FD)
Tare (FG)
Range Correction
Block P 04.
P 03.04 b_vork[i]
Differentiator, Disturbance
Auto-Elimination (DAE)
Filter Time
Probability Factor
Variance
Monitoring Time
Blending Prolongation
P 04.01 filter
P 04.02 warfak
P 04.03 varianz
P 04.04 twach
P 04.05 TB_DAE
Block P 05.
P 01.03 bdim
P 01.04 hdim
P 01.05 hub[i]
P 01.06 puffer[i]
P 01.07 bnenn[i]
P 01.08 nnenn
P 01.09 fm1dim
P 01.10 fm1puls
P 01.11 fm2dim
P 01.12 fm2puls
P 01.13 if_dim
P 01.14 if_nenn
P 01.15 frqnenn
Parametrization
FH 399 GB/ 5 - 2
P 01.01 pdim
P 01.02 pnenn[i]
P 02.01 wz_nenn
P 02.02 wz_kenn
P 02.03 fmech
P 02.04 fgeber
P 02.05 wz_filt
P 02.06 pruef
P 02.07 wartint
P 02.08 mes_res
P 02.09 spczeit
P 02.10 xdfilter
P 02.11 spcanza
Calibrating Results
P 03.01 h_rest[i]
P 03.02 p_rest[i]
P 03.03 kor_ber
Technische
Redaktion BVED
Controller
Dynamic Factor
Setpoint Bypass
P Component KP
Setback Time TN
Lead Time TV
Upper Control Magnitude Limit
go
Lower Control Magnitude Limit
gu
Control Magnitude Elevation
ANH
Message: Threshold Deviation
Message: Deviation Monitoring
Time
Control Magnitude Filter GTAU
Emergency Setpoint Limit
Number of Compensation
Points
Control Magnitude YKomp1
Actual Feed Rate IKomp1
Control Magnitude YKomp2
Actual Feed Rate IKomp2
Control Magnitude YKomp3
Actual Feed Rate IKomp3
Control Magnitude YKomp4
Actual Feed Rate IKomp4
Control Magnitude YKomp5
Actual Feed Rate IKomp5
Max. Setpoint Increase
Max. Setpoint Change
Max. Increase in STOP State
Vibration Feeder Range
Anti-Blocking Time
Stand-By Limit
Speed Control P-Component
Speed Control Setback Time
Speed Reset
P 05.01 dynfak
P 05.02 bn[i]
P 05.03 kp[i]
P 05.04 tn[i]
P 05.05 tv[i]
P 05.06 go
P 05.07 gu
P 05.08anh
P 05.09 diffmax
P 05.10 regtim
P 05.11 gtau
P 05.12 notsol
P 05.13 komppkt
P 05.14 Y_1[i]
P 05.15 I_1[i]
P 05.16 Y_2[i]
P 05.17 I_2[i]
P 05.18 Y_3[i]
P 05.19 I_3[i]
P 05.20 Y_4[i]
P 05.21 I_4[I]
P 05.22 Y_5[i]
P 05.23 I_5[i]
P 05.24 delta+
P 05.25 deltaP 05.26 delta_f
P 05.27 STINDEX[i]
P 05.28 t_blksch
P 05.29 standby
P 05.30 Kp_n
P 05.31 tn_n
P 05.32 norm_n
9941
MULTICONT
Block P 06.
Fill Control
Block P 07.
Block P 08.
P 06.11
LEERSPEZ
P 07.01 plbtau
P 07.02 pdatau
P 07.03 psetau
P 07.04 htau
P 07.05 btau
P 07.06 ntau
P 07.07 etau
Block P 10.
P 09.07 H_Anh
P 09.08 H_Ber[i]
P 09.09 Ps_Anh
P 09.10 Ps_Ber.[i]
P 09.11 n_Anh.
P 09.12 n_Ber.
P 09.13 r_Anh.
P 09.14 r_Ber
P 09.15 P3_Anh
P 09.16 P3_BER
Block P 11.
P 10.01 adan1
P 10.02 adbe1[i]
P 10.03 I_adan1
P 10.04 I_adbe1
Preset Times
Afterflow Totalization
Start-Up Time
Volumetric Discharge Time
P 11.01 tnach
P 11.02 tanfahr
P 11.03 tvolum
Limit Values
9941
P 06.01 hmin1
P 06.02 hmin2
P 06.03 hmax[i]
P 06.04 te_puls
P 06.05 te_paus
P 06.06 tf_puls
P 06.07 tf_paus
P 06.08 tbruhe
P 06.09 tfuell
P 06.10 FIL_MODE
Block P 09.
SIMPLEX
P 08.01 pmin
P 08.02 pmax
P 08.03 bmin1
P 08.04 bmin2
P 08.05 bmax1[i]
P 08.06 bmax2[i]
P 08.07 nmin
P 08.08 nmax
P 08.09 rwerk[i]
P 08.10 vibro[i]
P 08.11 if_min
P 09.01 P1_Anh.
P 09.02 P1_Ber.[i]
P 09.03 P2_Anh.
P 09.04 P1_Ber.[i]
Block P 12.
Batching Mode
Block P 13.
P 12.01 pvor
P 12.02 vbat
P 12.03 hbat
P 12.04 hkadap
P 13.01 tv_puls
P 13.02 tv_paus
P 13.03 tn1
P 13.04 tn2
P 13.05 tfilter
P 13.06 tv_s
P 13.07 tklapp
P 09.05 FG_Anh.
P 09.06 FG_Ber[i]
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 3
SIMPLEX
MULTICONT
Block P 14.
Block P 15.
P 14.06 vbanh
P 14.07 vbdakor
Tare N
Range Correction KORFV
Pre-load Compensation
Block P 16.
P 15.01 vb_tara
P 15.02 vb_kor
P 15.03 vb_vork
Supply Bin Fill Control
P 16.01 vbmin
P 16.02 vbmax
P 16.03 vhmin
P 16.04 vhmax
Block P 17.
Dead Time
Dead Time
P 17.01 Totzeit
Block P 18.
Simulator
P 18.01 tsim_fu
Block P 19.
Zero Setting
P 14.01 vbdim
P 14.02 vbnenn
P 14.03 vwz_nen
P 14.04 vwz_ken
P 14.05 vb_filt
P 19.01 erg_nul
P 19.02 gr_nul
Pressure Compensation
P 20.01 d_nenn
P 20.02 d_norm
P 20.03 d_min
P 20.04 d_max
P 20.05 d_tara
P 20.06 d_vork
P 20.07 wztau
9941
Parametrization
FH 399 GB/ 5 - 4
Technische
Redaktion BVED
MULTICONT
SIMPLEX
Password Active
Language
P 00.01
Passakt
P 00.02
spr
ENGLISCH
Range : J=Yes/N=No
Note : 7274
P 01.03
bdim
.-kg/h
.-kg
P 01.02
pnenn[i]
P 01.04
hdim
1000.0 kg/h
.kg
Range: -.-g... - t
Note:
Maximum 7 digits can be displayed. For entry,
see P 01.01.
9941
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 5
SIMPLEX
MULTICONT
fm1dim
50.0 kg
kg
Range : 1 kg ... 100 000 kg
Note : Change feed amount only in OFF state of
feeder.
Range : .-g...-t
See
: K 10.08 FM1_IA
Note : Inclusive decimal point, up to 7 places with
maximum 3 after-comma places can be
displayed. Select format and units by
operating cursors UP and DOWN. One pulse
corresponds to the smallest digit on display.
fm1puls
puffer[i]
50 ms
20.0 kg
Range : 50 ms ... 250 ms
Range : 0 kg ... 100 000 kg
Change feed amount only in OFF state of
feeder.
bnenn[i]
P 01.11
fm2dim
kg
Note
nnenn
1500 rpm
Range : 300 rpm ... 5000 rpm.
Note : Display is in revolution per minute (rpm).
9941
Parametrization
FH 399 GB/ 5 - 6
Technische
Redaktion BVED
MULTICONT
SIMPLEX
fm2puls
P 01.14
if_nenn
50 ms
100000.0 kg/h
if_dim
frqnenn
t/h
50
wz_nenn
Lever Ratio
P 02.03
fmech
220.00 kg
FG = WZ
Load Cell Characteristic Value E
P 02.02
wz_kenn
2.850 mV/V
Range: 0.5 mv/V ... 9.999 mV/V
9941
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 7
SIMPLEX
MULTICONT
VS Characteristic Value
P 02.04
Measuring Reserve
fgeber
P 02.08
mes_res
30 I/U
wz_filt
1
Range : 0 / 1 / 2 / 3
Note : 0 = Smallest filter time.
Check Weight
P 02.06
pruef
SPC Time
30.000 kg
P 02.09
8h
spczeit
Range: 1...24h
Monitoring time of diagnosis and quality tool for:
Maintenance Interval
P 02.07
wartint
3000 h
9941
Parametrization
FH 399 GB/ 5 - 8
Technische
Redaktion BVED
MULTICONT
SIMPLEX
SPC Filter
SPC Number
P 02.10
xdfilter
P 02.11
spcanza
60s
Range: 1...600s
Range: 1...60
Note:
Tare (FG)
P 03.02
p_rest[i]
0.000 kg
Tare (FD)
h_rest[i]
Range Correction
0.000 kg
Range : 0.0 kg ... 100 kg
Note : Parameter mes_res
Use h_rest to extend measuring range to negative
input signals. The smallest value is 1 % of
WZNENN. The negative component does not
become active before taring program has elapsed.
With empty hopper and reduced tare
(contamination), excess of measuring range
(message Measuring Range Exceeded CA 01") can
thus be avoided. Measuring resolution limited,
values exceeding 10% of feed amount (P 1.5)
should be avoided.
P 03.03
NOTE:
If h_rest is entered in manual, select same value
for each feed index.
0.0 % WZ
kor_ber
1.00000
Range : 0.95 ... 1.25
Note : Result from weight check CW: CHECK Q.
b_vork[i]
9941
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 9
SIMPLEX
MULTICONT
Filter Time
Blending Prolongation
P 04.01
filter
P 04.05
4.0 s
0s
Range: 0 ... 10 s
Probability Factor
P 04.02
TB_DAE
warfak
5
Range : 2 ... 20
See
: K 01.04 DAE_AKT
Note : Probability factor + variance = Response
threshold of disturbance auto-elimination.
Variance
P 04.03
varianz
0.05000 % wz0
Range : 1E-5% ... 100 % WZNENN
Note : Acquired with setting program OPTIM. DAE.
Monitoring Time
P 04.04
twach
30 s
Range : 0.600 s
See
: K 01.03 T_DAE
Note : The monitoring time is the period a
disturbance has to be continuously above the
DAE response threshold to be output as event
message.
9941
Parametrization
FH 399 GB/ 5 - 10
Technische
Redaktion BVED
MULTICONT
SIMPLEX
P 05. Controller
Setback Time TN
dynfak
1.000
P 05.04
tn[i]
2.147 s
Lead Time TV
P 05.05
Setpoint Bypass
tv[i]
0.000 s
P 05.02
bn[i]
Range : 0 s ... 6000 s
5000 mV
Range : 0 mV ... 20 000 mV
Note : Active only in submode Volumetric Mode 2",
the setpoint bypass is to be set such that the
actual feed rate corresponds to the nominal
feed rate entered as setpoint. The parameter
value should be between 4.5 V and 6.5 V.
P Component KP
P 05.03
18.8 mV/%
Range : 0 ... 1000 mV/%
Note : KP = 0 = > I controller
kp[i]
go
10000 mV
Range : 0 mV ... 10 000 mV
See
: K 11.05 REG_ERR
CO 03 Controller Out Limit
Note : Enter
maximum
admissible
control
magnitude for setpoint 0 %. For setpoint
100 %, control magnitude is limited to 10 V.
9941
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 11
SIMPLEX
MULTICONT
P 05.10
regtim
0 mV
20.0 s
gtau
3.0 s
anh
0 mV
Range : 0 mV ... 10 000 mV
Note : This parameter serves for elevating the
control magnitude zero point and can equally
be selected as lower control magnitude limit.
notsol
0.0 kg/h
Message: Threshold Deviation
P 05.09
diffmax
3.0 % pn
komppkt
5
Range : 1 ... 5
See
: K 11.12 ST_KOMP
Note : Maximum 5 points can be entered for
definition of the vibro-feeder characteristic
curve. For each point, a feed rate setpoint
requires to be preset, actual feed rate and
control magnitude are stored.
9941
Parametrization
FH 399 GB/ 5 - 12
Technische
Redaktion BVED
MULTICONT
SIMPLEX
P 05.18
Y_3[i]
500 mV
2500 mV
P 05.19
I_3[i]
10.00 %
50 %
P 05.20
Y_2[i]
Y_4[i]
3500 mV
Range: 1 mV ... 10 000 mV
1500 mV
Range : 1 mV ... 10 000 mV
I_4[I]
70 %
Actual Feed Rate IKomp2
P 05.17
30.00 %
Range : 0.1 % ... 500 % PNENN
Y_5[i]
4500 mV
Range: 1 mV ... 10 000 mV
9941
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 13
SIMPLEX
MULTICONT
P 05.26
delta_f
90 %
1.0
STINDEX[i]
delta+
0
25.0 %
Range: 2.0 ... 100.0 % of PNENN
This parameter serves for limiting absolute or
percentage setpoint increases entered by keyboard
to preset difference delta+.
If higher values are entered, message VALUE TOO
HIGH is displayed for a short period of time. Only
admissable change delta+ is accepted.
Bigger changes can be realized by multiple entry.
The limitation is active in Volumetric and Gravimetric
Mode.
If absolute and percentage setpoint can be changed
via keyboard, the limitation acts on the setpoint
currently being changed.
Range : 0 / 1
See
: K 11.13
0 : Preselect INDEX 1 for vibration feeder
1 : Preselect INDEX 2 for vibration feeder.
Anti-Blocking Time
P 05.28
t_blksch
10 s
Range: 0 ... 1000 s
See:
K 01.07, Message SC 07
deltaP 05.29
standby
25.0 %
2%
Range: 2.0 ... 100.0 % of PNENN
Function corresponds analogously to Parameter
deltat. Message VALUE TOO LOW appears.
Parametrization
FH 399 GB/ 5 - 14
Technische
Redaktion BVED
MULTICONT
SIMPLEX
Speed Reset
P 05.30
Kp_n
P 05.32
norm_n
0.40
5,0
norm_n =
Speed Control Setback Time
P 05.31
tn_n
P05.02
n
in
mV
rpm
0.6 s
Range : 0.0 ... 6000.0 s
See
: K 11.14, P 05.32
In STOP state of feeder, I component is reset.
See
: Block K 03.
P 06.02
hmin1
10.0 % FD
Range : -2000 ... 100 % FD
Note : If bin level falls below HMIN1 during normal
operation, refilling is initiated. HMIN1 must
exceed HMIN2.
hmin2
-5,0 % FD
Range : -10.0 % ... 100.0 % FD
See
: K 01.01 FHMIN2
SC 01 Bin Level < HMIN2"
9941
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 15
SIMPLEX
MULTICONT
P 06.06
tf_puls
70.0 % FD
3s
P 06.07
tf_paus
0s
Range : 0 s ... 6000 s
Note : For continuous filling, set break time to 0 s.
SettlingTime
te_puls
P 06.08
tbruhe
3.0 s
5s
te_paus
P 06.09
tfuell
20 s
60 s
9941
Parametrization
FH 399 GB/ 5 - 16
Technische
Redaktion BVED
MULTICONT
SIMPLEX
FIL_MODE
0
Range : 0 / 1 / 2
See
: Operating Instructions
Active only if K 03.07 reads 1 (Discharge With Filling
Error). Set event classes K 04.01, K 04.03 to W1.
0
Discharge,
: although max. filling phase is
exceeded (P 06.09).
Discharge,
: although min. fill feed rate is
excceded down (P 08.11).
Discharge
: in addition to Case 0 or 1.
LEERSPEZ
.0
Range : .0 / .1
See
: P 06.11
0 Discharge
: up to max. hmin 2
1
Discharge
: even below hmin 2
9941
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 17
SIMPLEX
MULTICONT
P 07. Display and Output Filter
Number of Revolutions
plbtau
P 07.06
ntau
3.0 s
3.0 s
P 07.07
3.0 s
3.0 s
etau
psetau
3.0 s
Range: 0 s ... 600 s
Feed Amount
P 07.04
htau
3.0 s
Range: 0 s ... 600 s
Bin Level
P 07.05
btau
3.0 s
Range: 0 s ... 600 s
Parametrization
FH 399 GB/ 5 - 18
9941
Technische
Redaktion BVED
MULTICONT
SIMPLEX
P 08. Limit Values
P 08.05
bmax1[i]
5.0 % pn
95.0 % fg
pmax
95.0 % pn
P 08.06
100.0 % fg
bmax2[i]
bmin1
P 08.07
nmin
@BLOCK 3 = 5.0 % fg
3.0 % nn
Range : -10 % ... 300 % FGNENN
See
: K 12.03 K_BMIN1
LO 02 BIN LEVEL < BMIN1"
P 08.08
nmax
0.0 % fg
100.0 % nn
9941
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 19
SIMPLEX
MULTICONT
Agitator Threshold
P 08.09
rwerk[i]
P 08.11
if_min
30.0 % pn
00.0 % If0
Vibrator Threshold
P 08.10
vibro[i]
60 % pn
Range : 0 % ... 200 % PNENN
See
: K 14.03 RUET_EI
Start-up Conditions
1) Feeder ON.
2) Setpoint > vibro .
3) No clearance mode.
P 09.03
P2_Anh.
2.00 V
2.00 V
Range : 0 V ... 10 V
K 10.14 P_IST2
10.00 V
P 09.04
P1_Ber.[i]
10.00 V
Range: 0 V ... 10 V
9941
Parametrization
FH 399 GB/ 5 - 20
Technische
Redaktion BVED
MULTICONT
SIMPLEX
FG_Anh.
Setpoint, Range
P 09.10
Ps_Ber.[i]
2.00 V
10.00 V
Range : 0 kg = 0 V ... 10 V
See
: K 10.15 FGEW
P 09.11
n_Anh.
10.0 V
2.00 V
Speed, Range
H_Anh
P 09.12
n_Ber.
2.00 V
6.00 V
P 09.13
r_Anh.
10.00 V
5.00 V
Range : 0 % = 0 V ... 10 V
See
: K 11.10 AA_REGA
Deviation, Range
Ps_Anh
P 09.14
r_Ber
2.00 V
20.00 V
9941
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 21
SIMPLEX
MULTICONT
2.00 V
P3_BER
10.00 V
Range: 0.00...10.00 V
See:
P 09.16
for 0%I
Range: 0.00...100.00 V
for 100%I
K 14.08 P_IST3
P 10.03
I_adan1
2.00 V
0.00 V
Setpoint, Range
P 10.02
P 10.04
I_adbe1
10.00 V
5.00 V
9941
Parametrization
FH 399 GB/ 5 - 22
Technische
Redaktion BVED
MULTICONT
SIMPLEX
P 11. Preset Times
Afterflow Totalization
P 11.01
tnach
3.0 s
Range : 0.1 s ... 10 000 s
Note : For the set time, feed amount is acquired by
totalizing counter after cut-off of feeder.
Start-Up Time
P 11.02
tanfahr
2.0 s
Range : 0s ... 300 s
See
: K 04.02 TVOL_MA
MF 02 Vol. Discharge Time
Note : For the defined start-up time, feeder runs in
volumetric mode. As control magnitude either
a stored value or the bypass value can be
used. The smallest start-up time is approx.
2 filter (P4.1) independent of parameter.
Volumetric Discharge Time
P 11.03
tvolum
20.0 s
Range : 1 s ... 6000 s
Note : The discharge time serves for monitoring and
determines the duration of volumetric mode
until output of event message.
9941
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 23
SIMPLEX
MULTICONT
P 12. Batching Mode
See
Note
: P 01.09 fm1dim
: Batching counter display format = Format of
totalizing counter 1.
Residual Amount Main Contact
Feed Rate Pre-act Contact
P 12.03
P 12.01
hbat
pvor
0.0000 kg
50.0000 kg/h
Range : 0 kg ... 10000 kg
Range: 0 kg/h ... 10 000 kg/h
Adaptation Factor
Residual Amount Pre-Act Contact
P 12.04
P 12.02
hbatadap
vbat
0.0
10.0000 kg
Range: 0.0 ... 1.0
Range: 0 kg ... 10000 kg
Residual quantities P 12.02 and P 12.03 are
self-optimizing.
The two parameters are adapted by value
Batch Error P 12.04".
P 12.04
= 0
= 1
: No adaptation
: Full adaptation
9941
Parametrization
FH 399 GB/ 5 - 24
Technische
Redaktion BVED
MULTICONT
SIMPLEX
P 13. Auxiliary Fill Devices
P 13.05
tfilter
1.0 s
0s
Range: 1 s ... 60 s
Range : 0 s ... 60 s
See
: K 19.12 DRUCKFIL
Note : This parameter determines the pulse
intervals of filter cleaning during pre-suction
time. Pulse duration is permanently set.
tv_paus
P 13.06
tv_s
2.0 s
3.0 s
Range: 1 s ... 60 s
Range : 1 s ... 60 s
See
: K 19.12 DRUCKFIL
Note
Reaction Time tk
tn1
P 13.07
tklapp
6.0 s
3.0 s
Range: 1 s ... 60 s
tn2
2.0 s
Range: 1 s ... 60 s
9941
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 25
SIMPLEX
MULTICONT
P 14. Supply Bin, Rated Data and Calibration
P 14.05
vb_filt
-kg
Range : g / kg / t
Note : Display shows maximum 7 places, with up to
3 after-comma places. Select by operating
cursors UP/DOWN.
Value range: 0 / 1 / 2 / 3
P 14.06
vbanh
10000.0 kg
2.00 V
Range: 0 V ... 10 V
vwz_nen
30000 kg
P 14.07
10.0 V
vbdakor
vwz_ken
2.850 mV/V
Range: 0.5 mV/V ... 9.999 mV/V
9941
Parametrization
FH 399 GB/ 5 - 26
Technische
Redaktion BVED
MULTICONT
SIMPLEX
P 15. Supply Bin, Calibration Results
Pre-load Compensation
P 15.01
vb_tara
P 15.03
vb_vork
0.0 kg
0.0 % WZ
vb_kor
1.00000
Range: 0.5 ... 2
P 16.03
vhmin
5.0 % FV
10.0 % FV
P 16.04
95.0 % FV
90.0 % FV
vhmax
9941
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 27
SIMPLEX
MULTICONT
P 17. Dead Time
Dead Time
P 17.01
Totzeit
0.00 s
Range: 0 s ... 600 s
The dead time applies to all dead time elements.
P 18. Simulator
tsim_fu
15.0 s
Range : 0 s ... 300 s
Note : With simulator being switched on, parameter
determines time for refilling of feed amount.
9941
Parametrization
FH 399 GB/ 5 - 28
Technische
Redaktion BVED
MULTICONT
SIMPLEX
P 19. Zero Setting
P 19.02
gr_nul
0.00 kg
5.0 %
Range: -100000.00...+100000.00 kg
See:
See:
K 23.02 ERR_NUL
P 19.02 gr_nul
K 23.02 ERR_NUL
P 19.01 erg_nul
9941
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 29
SIMPLEX
MULTICONT
P 20. Pressure Compensation
Nenn
d_nenn
100.0
Range: 0.0...100.0 %
See:
2.85mV/V
E
if load cell input is used
Fo = Nominal load (pressure)
E = Sensitivity in mV/V
Service display KOMP%:
Nom = Fo
KOMP% = S%d_vork
S% =
i
100%
20mA
S% =
F 2.85mV/V
with converter
Smax
d_nenn
nenn
100%
Parametrization
FH 399 GB/ 5 - 30
9941
Technische
Redaktion BVED
MULTICONT
SIMPLEX
P 20.06
d_vork
0.000 kg/%
0.0%
Range: 0.0...100.0%
See:
See:
P 20.05 d_tara
Smin
in kg
d_vork
nenn
100%
P 20.03
d_min
0.0%
P 20.07
wztau
0.00s
Range: -100.0....100.0%
See:
(see Fig.)
K 24.02, Message LO 06
Range: 0.00...3.00s
Filter can be used to adapt weight channel time
behaviour to pressure channel.
d_max
105.0%
Range: -100.0...+200.0%
See:
(see Fig.)
K 24.03, Message HI 06
d_tara
0.0%
Range: 0.0...100.0%
9941
See:
P 20.02 d_norm
Technische
Redaktion BVED
Parametrization
FH 399 GB/ 5 - 31
SIMPLEX
MULTICONT
Calibration Suggestion:
Attention!
1.
2.
3.
4.
in %
in kg
5.
6.
7.
in %
in kg
d_norm =
FG(2)FG(1)
KOMP%(2)KOMP%(1)
in
kg
%
8.
9.
10.
9941
Parametrization
FH 399 GB/ 5 - 32
Technische
Redaktion BVED
MULTICONT
SIMPLEX
6. Event Messages
6.1 General
The MULTICONT system monitors the hardware as well
as the signals and parameters decisive for feeding
operation and operating safety. Malfunctions or
deviations from setpoints are reported as events. Event
classes and reactions are assigned per configuration.
6.1.1 Display
ALARM
Stop feeder,
ALARM
Warning 1
Display W1,
W1
Warning 2
Display W2,
W2
permanent.
IGNORE
Suppress display.
System Faults,
SC
WE
WM
MF
IL
Interlocking,
CO
Controller,
CA
Calibration,
HI
LO
9941
Technische
Redaktion BVED
Event Messages
FH 399 GB/ 6 - 1
SIMPLEX
MULTICONT
SY 08:
SE* DATA LINK
Batch processor.
K 00.08 SE_AKT
SY 09:
MEMORY FAIL
SE memory.
K 00.09 SE_MEM
(a)
SY 10:
qb WRONG UNIT
Bin configuration.
K 10.10 QU_FGEW
(b)
(c)
SY 11:
n WRONG UNIT
Speed transducer configura- K 10.11 QU_DREH
tion.
(d)
(e)
SY 12:
qvb WRONG UNIT
Supply bin configuration.
K 21.01 QU_FGVB
SY 13:
WRONG UNIT
Pressure compensation con- K 24.01 D_QU
figuration
SY 03:
EA 1 DATA LINK
Input/output unit EA1.
K 00.03 EA1
SC 02:
FEEDER BLOCKED
Drive blocked.
K 01.02 BLOCKSC
SY 04:
EA 2 DATA LINK
Input/output unit EA2.
K 00.04 EA2
SY 05:
EA 3 DATA LINK
Input/output unit EA3.
K 00.05 EA3
SY 06:
LBS 1 DATA LINK
Machine control station .
1K 00.06 LB1_AKT
SY 07:
LBS 2 DATA LINK
Machine control station 2.
K 00.07 LB2_AKT
SC 03:
DAE TIME LIMIT
Time monitoring
K 01.03 T_DAE
DAE System.
P 04.04 twach
The DAE System is active for time twach.
If message occurs frequently, check system for
disturbances. Try to remedy cause.
99
Event Messages
FH 399 GB/ 6 - 2
Technische
Redaktion BVED
MULTICONT
SC 04:
DAE ACTIVE
DAE System active.
SIMPLEX
K 01.04 DAE.AKT
P 04.02 warfak
P 04.03 varianz
Cause:
DAE System responds. Disturbances exceed set
response threshold.
WE 04:
AGITATOR OVERLOAD
Agitator motor protective
K02.04 MS_RUER
switch.
See WE 02.
WE 05:
ADD. DRIVE OVERLOAD
Auxiliary drive protective
K 02.05 MSHILA
motor switch.
SC 05:
MAINTENANCE
Maintenance interval
K 01.05 WARTUNG
reached.
P 02.07 wartint
See WE 02.
SC 06:
L/C Overload
Load cell is overloaded.
WE 06:
CABLE SHORT OR INT.
Cable breakage /short
K 02.06 F_KABEL
circuit.
K 01.06 WZUEBER
Stand-By
K 01.07 standby
WE 07:
ANALOGUE INPUT P
Analogue input.
K 02.07 FP_ANAL
K 07.10 TM_PABS
K 08.10 M0_PABS
K 09.10 M1_PABS
P 10.01 adan1
P 10.02 adbe1[i]
Analog input setpoint range exceeded down.
Signal at analog setpoint input is out of admissible
range. Check connection, cabling and setpoint
transducer.
WE 08:
FEED DRIVE TEMPERATURE
Feed drive temperature too K 02.08 DA_TEMP
high.
Motor protective switch has triggered.
9941
Technische
Redaktion BVED
Event Messages
FH 399 GB/ 6 - 3
SIMPLEX
MULTICONT
MF 01:
REFILLING TIME EXC
Refill time exceeded.
K 04.01 MATFL_O
P 06.09 tfuel.
Filling time was exceeded during feeding
operation. If refilling is initiated by signal or
menue, no message is output. Check bin level. In
case of overflow (flushing material) change time
conditions for refilling mode. Check auxiliary fill
units and control signals.
MF 02:
VOL. DISCHARGE TIME
Volumetric discharge time
K 04.02 TVOL_MA
exceeded.
P 11.03 tvolum
Volumetric discharge time during feeding was
exceeded. During discharge operation and
volumetric mode, selected by contact or menue,
no message is output. See MF 01.
MF 03
If < MIN
Fill feed rate < MIN.
K 04.03 IF_MIN
P 08.11 if_min
K 19.09 F BLKLZ
IL 01:
EMERGENCY STOP
Emergency stop.
K 05.01 NOTAUS
Emergency stop switch was operated.
WM 08:
DISCHARGE GATE
Discharge gate does not
K 20.03 A_ATK
open.
IL 02:
LOCAL MAIN SWITCH
Local main switch.
K 05.02 FREISCH
Local main switch signal not available.
IL 03:
NO RELEASE
Release 3.
K 05.06 NO_FREI
K 05.03 FREI_1
K 05.04 FREI_2
K 05.05 FREI_3
Event Messages
FH 399 GB/ 6 - 4
Technische
Redaktion BVED
MULTICONT
SIMPLEX
6.2.7 Controller CO
CO 01:
Deviation.
6.2.8 Calibration CA
DEVIATION
K 11.03 DA_REGA
P 05.08 diffmax
P 05.09 regtim
CA 01:
LC OUT < MIN
Load cell input underamplified.
K 13.01 WZ_MIN
CA02:
LC OUT > MAX
Load cell input overampliK 13.02 WZ_MAX
fied.
Input of load cell measured value transducer is
overamplified, measured value not reliable.
Check mechanical equipment, check bin for
overflow and impacts on bin.
CA 03:
PLL OVERFLOW
PLL overflow.
K 13.03 GA_ERR
Discharge unit speed transducer does not provide
usable signal. Check speed transducer and
cabling.
CA 04:
AMPLIFICATION MAX
MAX amplification.
K 13.04 VERST_M
Load cell measured value transducer operates
with maximum amplification factor ( approx. 3%
of load cell rated capacity). Check rated data
(upon commissioning). With rated data being
correct, measuring capability is not affected.
CA 05:
PRELOAD < 5%
Preload below 5%.
K 13.05 VORL_MI
Dead weight is below 5 % of load cell rated
capacity. Check mechanical equipment for
positive connection, check transit restraints and
rated data upon commissioning.
9941
Technische
Redaktion BVED
Event Messages
FH 399 GB/ 6 - 5
SIMPLEX
MULTICONT
CA 06:
PREL + BUFF + FEED > NOM.
Preload + buffer + amount
K 13.06 F_WZNEN
mes_res exceeds load cell
P 01.05 hub[i]
rated capacity.
P 01.06 puffer[i]
P 02.01 wz_nenn
P 02.08 mes_res
CA 13:
CA 08:
HMIN1 > HMAX1
HMIN1 exceeds HMAX1.
K 13.08 HMAX1_M
P 06.03 hmax[i]
See CA 07.
HI 02:
BIN LEVEL > BMAX1
Bin level exceeds BMAX1.
K 12.05 K_BMAX1
P 08.05 bmax1[i]
CA 09:
SIMULATION ACTIVE
Simulator active.
K 13.09 SIM_AKT
Load cell or speed signal simulator is active in
Test Mode.
CA 10:
LC SUPPLY BIN < Min
Supply bin load cell input
K 21.06 WZVB_MI
underamplified.
See CA 01.
HI 03:
BIN LEVEL > BMAX2
Bin level exceeds BMAX2.
K 12.06 K_BMAX2
P 08.06 bmax2[i]
Bin level exceeds limit value BMAX2.
HI 04:
SPEED HI
Speed exceeds NMAX.
CA 11:
LC SUPPLY BIN > Max
Supply bin load cell input
K 21.07 WZVB_MA
overamplified.
See CA 01.
CA 12:
K 12.08 K_NMAX
P 08.08 nmax
Event Messages
FH 399 GB/ 6 - 6
Technische
Redaktion BVED
MULTICONT
HI 06:
MEAS. VAL. COMP > MAX
Pressure > MAX
K 24.03 D_MAX
P 20.04 d_max
HI 09:
ZEROING LIMIT
Zero setting limit exceeded. K 23.02 ERR_NUL
P19.02 gr_nul
Refers to zeroing of bin level display via external
contact.
SIMPLEX
6.2.10 MIN Limit Values LO
LO 01:
FEDDRATE I LO
Feed rate below PMIN.
K 12.01 K_PMIN
P 08.01 pmin
Actual feed rate has fallen below set minimum
feed rate. Check feed rate setpoint, check
parameters.
LO 02:
BIN LEVEL < BMIN1
Bin level below BMIN1.
K 12.03 K_BMIN1
P 08.03 bmin1
Bin level has fallen below limit value BMIN 1.
LO 03:
BIN LEVEL < BMIN2
Bin level below BMIN2
K 12.05 K_BMIN2
P 08.04 bmin2
Bin level has fallen below limit value BMIN2.
LO 04:
SPEED LO
Speed below NMIN.
K 12.07 K_NMIN
P 08.07 nmin
9941
Technische
Redaktion BVED
Event Messages
FH 399 GB/ 6 - 7
MULTICONT
SIMPLEX
9941
K 16.05
K 16.06
K 16.04
K 09.10
K 07.10
K 08.10
K 10.01
K 11.01
M1_BATA
TM_BATA
M0_BATA
M1_PABS
TM_PABS
M0_PABS
STCLR
QU_NOTS
P 08.02
P 05.15
P 05.19
P 05.21
P 05.17
P 09.01
P 09.15
P 09.16
P 09.04
P 09.02
pmax
I_1[i]
I_3[i]
I_4[I]
I_2[i]
P1_Anh.
P3_Anh
P3_BER
P1_Ber.[i]
P1_Ber.[i]
P 07.02
K 14.08
K 10.14
K 10.13
P 09.03
P 07.03
P 07.01
pdatau
P_IST3
P_IST2
P_IST1
P2_Anh.
psetau
plbtau
P 08.01
P 05.23
P 12.04
P 11.01
P 08.09
K 13.04
K 14.07
P 05.28
pmin
I_5[i]
hkadap
tnach
rwerk[i]
VERST_M
INV_AKT
t_blksch
K 03.02 FIL_AUT
K 19.01 HIFIL_D
K 16.11
K 16.10
K 16.12
K 00.08
P 09.06
K 21.01
K 01.01
K 12.03
P 08.04
P 08.03
P 08.05
M1_PBAT
M0_PBAT
TM_PBAT
SE*_AKT
FG_Ber[i]
QU_FGVB
FHMIN2
K_BMIN1
bmin2
bmin1
bmax1[i]
P 08.06
K 10.15
K 21.04
K 21.03
K 10.10
K 21.02
K 12.04
K 12.06
K 12.05
P 04.05
P 01.06
bmax2[i]
FGEW
FVB_MAX
FVB_MIN
QU_FGEW
FGVB
K_BMIN2
K_BMAX2
K_BMAX1
TB_DAE
puffer[i]
K 02.06
P 02.06
K 19.12
K 19.11
K 19.07
P 05.18
F_KABEL
pruef
DRUCKFIL
SAUGFIL
BLKL_ZU
Y_3[i]
P 05.08
P 05.22
P 05.20
P 05.11
P 05.16
P 05.14
K 11.02
K 11.05
anh
Y_5[i]
Y_4[i]
gtau
Y_2[i]
Y_1[i]
MERKREG
REG_ERR
Technische
Redaktion BVED
SIMPLEX
MULTICONT
K 05.07
K 05.01
P 05.12
K 02.03
K 02.04
K 18.02
K 01.06
EL_BER
NOTAUS
notsol
REG_DOS
MS_RUER
MS_FILO
WZUEBER
K 02.05
K 02.02
P 07.04
MS_HILA
MS_DOSA
htau
P 01.04
hdim
P 01.01
P 09.07
P 09.09
P 12.01
P 06.03
P 06.02
P 06.01
P 09.08
K 10.18
K 12.01
K 12.02
pdim
H_Anh
Ps_Anh
pvor
hmax[i]
hmin2
hmin1
H_Ber[i]
AA_HUB
K_PMIN
K_PMAX
K 02.08
K 10.12
K 01.02
K 17.05
K 17.03
K 17.06
K 17.02
K 18.05
DA_TEMP
STL_DOS
BLOCKSC
F_FKLAU
FKL_RMA
F_FKLZU
FKL_RMZ
F_AUSFI
P 08.11
K 04.03
K 06.05
if_min
IF_MIN
LO_FKLA
P 01.13
K 17.09
K 03.01
K 17.01
K 18.03
K 17.08
K 18.01
if_dim
DA_FKLZ
FIL_ST
FKL_DA
FILOR_R
DA_FKLA
FILOR_D
MIN
K 20.01
RM_ATK
Technische
Redaktion BVED
P 06.10
P 13.05
P 04.01
FIL_MODE
tfilter
filter
P 09.05
FG_Anh.
P 01.03
P 07.05
bdim
btau
General Alarm
General Warning
K 10.04
K 10.05
S_ALARM
S_WARN
K 13.07
K 13.08
HMIN2_M
HMAX1_M
P 06.04
P 06.05
te_puls
te_paus
K 22.06
K 00.05
K 00.04
K 00.03
K 20.04
TOT_INI
EA3_AKT
EA2_AKT
EA1_AKT
ATKL_IN
K 19.14
K 19.13
BLKL_IN
ELKL_IN
P 00.02
P 05.05
P 02.03
spr
tv[i]
fmech
P 02.01
P 14.05
wz_nenn
vb_filt
P 02.02
P 14.04
P 02.05
K 13.02
wz_kenn
vwz_ken
wz_filt
WZ_MAX
K 24.05
D_MEMAX
K 13.06
P 14.03
K 13.01
F_WZNEN
vwz_nen
WZ_MIN
K 24.04
D_MEMIN
P 10.03
I_adan1
K 06.09
P 10.04
LO_AKT
I_adbe1
P 05.07
P 20.06
gu
d_vork
Language
Lead Time TV
Lever Ratio
Load Cell Rated Capacities
WZNENN
Load Cell Filter
Load Cell Characteristic Value
E
Load Cell Characteristic E
Load Cell Filter
LC Input > MAX
Load Cell Input (Pressure)
> MAX
Load > Load Cell Rated
Capacity
Load Cell Rated Capacities
LC Input < MIN
Load Cell Input (Pressure)
> MIN
Local Speed Setpoint, Zero
Point
Local Mode Preselection
Active
Local Speed Setpoint, Range
Lower Control Magnitude Limit
gu
Lower Full Scale Value
9941
MULTICONT
9941
SIMPLEX
K 00.06
K 00.07
K 16.08
K 01.05
P 02.07
K 04.00
P 05.25
P 05.26
P 05.24
P 06.09
P 07.07
LB1_AKT
LB2_AKT
HAUPTK
WARTUNG
wartint
MATFL_O
deltadelta_f
delta+
tfuell
etau
K 00.02 ME2_AKT
K 00.01
P 02.08
K 14.05
K 10.07
P 05.09
K 03.06
ME1_AKT
mes_res
mes_sys
W_EIN
diffmax
FIL_AKT
P 05.10
K 11.03
K 11.04
K 18.06
regtim
DA_REGA
NOTSOL
F_EINFI
K 10.19
K 09.08
K 08.08
P 04.04
H_EIN
M1_AKT
M0_AKT
twach
K 14.08
K 05.06
K 05.12
K 00.11
K 05.06
P 14.02
P 01.08
P 01.07
P 01.02
P 01.05
P 01.14
K 17.07
K 16.09
I2_INV
NO_FREI
NO_NOT
NON-SI
NO_FREI
vbnenn
nnenn
bnenn[i]
pnenn[i]
hub[i]
if_nenn
P 05.13
P 07.06
K 10.11
K 10.17
komppkt
ntau
QU_DREH
DREHZ
K 19.04
K 17.04
K 20.02
P 14.07
ELKL_AU
FKL_AUF
ATK_AUF
vbdakor
Output Normalization,
Zero Point
P 14.06 vbanh
P Component KP
Password Active
PLL Overflow
Power Failure
Pre-contact
Pre-assign Setpoint Dead
Time Element
Pre-suction Time tvs
Pre-load Compensation
Preload < 5 %
Preload Compensation (FG)
Preselect Discharge Mode
Preselect Mode 0
Preselect Local Mode
Preselect Dead
Time Element Setpoint M1
Preselect START/STOP Dead
Time Element M1
Preselect Refilling Mode
Preselect Dead
Time Element Setpoint M0
Preselect Test Mode
Preselect Batching Test Mode
Preselect Discharge Mode
Preselect Mode 1
Preselect Batching Mode 0
Preselect Batching Mode 1
Preselect Discharge Mode
Pressure Compensation Filter
Pressure Compensation Input
Pressure Compensation Range
Pressure > d-max
Pressure > d-max
Pressure < d-min
Pressure > d-min
Probability Factor
K 22.01
K 07.01
K 16.03
K 09.07
K 09.01
K 16.01
K 16.02
K 08.07
P 20.07
K 24.01
P 20.02
K 24.03
P 20.04
K 24.02
P 20.03
P 04.02
TOT_VM0
TM_VORW
TM_BATQ
M1_LVOR
M1_VORW
M0_BATQ
M1_BATQ
M0_LVOR
wztau
D_QU
d_norm
D_MAX
d_max
D_MIN
d_min
warfak
Range Correction
Range Correction KORFV
Reaction Time tk
Ready to Start in Mode 1
Ready in Mode 0
Ready in Mode 1
Ready to Start in Mode 0
Refill Time Exceeded
Refilling, Break Time
Refilling, Pulse Time
Relative Feed Rate Setpoint
Relative Feed Rate Setpoint
Release 1
Release 3
Release 2
P 03.03
P 15.02
P 13.07
K 05.11
K 05.08
K 05.09
K 05.10
K 04.01
P 06.07
P 06.06
K 08.11
K 09.11
K 05.03
K 05.05
K 05.04
kor_ber
vb_kor
tklapp
M1_EBER
M0_BER
M1_BER
M0_EBER
TFIL_MA
tf_paus
tf_puls
M0_PREL
M1_PREL
FREI_1
FREI_3
FREI_2
Technische
Redaktion BVED
P 05.03
P 00.01
K 13.03
K 02.01
K 16.07
kp[i]
Passakt
GA_ERR
NETZAUS
VORKON
K 22.05
P 13.06
P 15.03
K 13.05
P 03.04
K 07.07
K 08.01
K 06.01
TOT_VOR
tv_s
vb_vork
VORL_MIN
b_vork[i]
TM_LVOR
M0_VORW
LO_VORW
K 22.02 TOT_VM1
K 22.08 TOT_IM1
K 10.03 FIL_VOR
SIMPLEX
Reset Totalizing Counter 1
Reset Totalizing Counter 2
Reset Totalizing Counter 2
Reset Totalizing Counter 1
Reset Totalizing Counter 1
Reset Totalizing Counter 2
Residual Amount Pre-Act
Contact
Residual Amount Main Contact
Saftey Disconnector
SE Memory
Set Error to Zero
Set Error to Zero
Setback Time TN
Set Limit to Zero
Setpoint Bypass
Setpoint, Range
Setpoint, Range
Setpoint, Zero Point
Setpoint 0
Setpoint
Setpoint, Analog
Input Range < MIN
Set Result to Zero
SettlingTime
Simulated Refill Time
Simulator Active
SPC Time
SPC Number
SPC Filter
Speed, Limit Value MAX
Speed, Limit Value MIN
Speed, Zero Point
Speed Reset
Speed, Range
Speed > NMAX
Speed Control Setback Time
Speed / Frequency Display
Speed Control P-Component
Speed < NMIN
Stand-By Limit
START/STOP
START/STOP
START/STOP
Start Supply Bin Ventilation
Start Feed Screw
Start Local Funnel Blow-Out
Start Agitator
Start Fill Device
Start Feeder
Start-Up Time
Start Feeder
Start Feed Unit
Start Vibrator
MULTICONT
K 07.03
K 09.04
K 07.04
K 08.03
K 09.03
K 08.04
TM_RES1
M1_2RES
TM_RES2
M0_1RES
M1_1RES
M0_2RES
P 12.02
P 12.03
vbat
hbat
K 05.02
K 00.09
K 23.01
K 23.02
P 05.04
P 19.02
P 05.02
P 09.10
P 10.02
P 10.01
K 11.06
K 10.16
FREISCH
SE_MEM
QU_NUL
ERR_NUL
tn[i]
gr_nul
bn[i]
Ps_Ber.[i]
adbe1[i]
adan1
PSOLNUL
P_SOLL
K 02.07
P 19.01
P 06.08
P 18.01
K 13.09
P 02.09
P 02.11
P 02.10
P 08.08
P 08.07
P 09.11
P 05.32
P 09.12
K 12.08
P 05.31
K 10.20
P 05.30
K 12.07
P 05.29
K 07.02
K 09.02
K 08.02
K 19.06
K 06.07
K 19.03
K 06.06
K 18.04
K 09.00
P 11.02
K 08.00
K 06.02
K 14.03
FP_ANAL
erg_nul
tbruhe
tsim_fu
SIM_AKT
spczeit
spcanza
xdfilter
nmax
nmin
n_Anh.
norm_n
n_Ber.
K_NMAX
tn_n
rin_frq
Kp_n
K_NMIN
standby
TM_I/O
M1_IO
M0_IO
BL_VORB
LO_SCHN
TRIAUS
LO_RWEI
FILOR_E
M1_EIN
tanfahr
M0_EIN
LO_STAR
RUET_EI
Technische
Redaktion BVED
Start Refilling
Start Feeder
Start Agitator
Start Funnel Blow-out
Start Refilling
Start Supply Bin Fill Device
Start Refilling
Start Feed Drive
K 09.05
K 07.00
K 10.06
K 19.10
K 07.05
K 21.05
K 08.05
K 10.00
M1_FSTA
TM_EIN
RW_EIN
TRIAUS
TM_FSTA
FILORVB
M0_FSTA
EIN_DOS
START Refilling
START/STOP DAE
START/STOP Speed Controller
START Feed Unit
K 03.05
K 11.11
K 11.14
K 06.00
FIL_EIN
DAE.AKT
NREG_IO
LO_EIN
K 11.12
K 09.06
K 08.06
K 14.01
K 14.02
K 06.03
K 07.06
K 14.09
P 13.03
P 16.04
P 16.03
ST_KOMP
M1_FSTO
M0_FSTO
QU_Z1ST
QU_Z2ST
LO_STOP
TM_FSTO
I3_Store
tn1
vhmax
vhmin
P 13.01
tv_puls
P 13.02
tv_paus
K 21.07
WZVB_MA
K 21.06
P 16.02
P 16.01
K 03.03
WZVB_MI
vbmax
vbmin
NOFILL
P 03.02
P 15.01
P 03.01
K 07.08
p_rest[i]
vb_tara
h_rest[i]
TM_AKT
P 01.09
fm1dim
P 01.10
fm1puls
P 01.12
K 10.09
K 10.08
fm2puls
FM2_IA
FM1_IA
P 01.11
fm2dim
P 05.06
go
9941
MULTICONT
SIMPLEX
P 20.01 d_nenn
Variance
Vent Valve Open
Vent Valve Does Not Open
Ventilating Valve Does Not
Close
Ventilating Valve Shut
Ventilation Time tn2
Vibration Feeder Range
Vibration Feeder Range
Vibrator Threshold
Vibro Feed Rated Frequency
P 04.03 varianz
K 19.02 RMAUF_E
K 19.05 F_ELKLA
K 19.09
K 19.08
P 13.04
P 05.27
K 11.13
P 08.10
P 01.15
Volumetric Mode 2
Volumetric Discharge Time Exceeded
Volumetric Discharge Time
Volumetric Mode 2
Volumetric Mode 1
Volumetric
Volumetric Mode 2
VS Characteristic Value
F_BLKLZ
RMZU_BL
tn2
STINDEX[i]
STINDEX
Zero Ponit Pressure Compenvibro[i]
sation
frqnenn
K 08.09 M0_VOL2
K 04.02
P 11.03
K 09.09
K 10.02
K 14.04
K 07.09
P 02.04
TVOL_MA
tvolum
M1_VOL2
VOL1_EI
VOL_AKT
TM_VOL2
fgeber
P 20.05 d_tara
9941
Technische
Redaktion BVED
MULTICONT
SIMPLEX
NAME
NUMBER
CODE
DEFAULT VALUE
K 01.06
WZUEBER
-.NO
K 02.02
MS_DOSA
EA1.DE2
K 02.03
REG_DOS
-.NO
K 02.04
MS_RUER
EA1.DE4
K 02.05
MS_HILA
-.NO
W2
K 02.08
DA_TEMP
-.NO
Suppress Filling
K 03.03
NOFILL
EA2.DE3
EMERGENCY STOP
K 05.01
NOTAUS
-.NO
Safety Disconnector
K 05.02
FREISCH
EA1.DE1
Release 1
K 05.03
FREI_1
EA1.DE6
Release 2
K 05.04
FREI_2
-.YES
Release 3
K 05.05
FREI_3
-.NO
K 06.01
LO_VORW
ME2.DE1
K 06.02
LO_STAR
ME2.DE2
K 06.03
LO_STOP
ME2.DE3
K 06.05
LO_FKLA
ME2.DE4
Start Agitator
K 06.06
LO_RWEI
ME2.DE5
VALUE
SWITCH
o
p
p
p
p
o
o
p
p
o
o
o
oq
oq
oq
oq
9941
Technische
Redaktion BVED
List of Interfaces
FH 399 GB/ B - 1
SIMPLEX
MULTICONT
K 06.07
LO_SCHN
START/STOP
K 07.02
TM_I/0
LB1
K 07.03
TM_RES1
LB1
K 07.04
TM_RES2
LB1
Start Refilling
K 07.05
TM_FSTA
LB1
Stop Refilling
K 07.06
TM_FSTO
LB1
K 07.07
TM_LVOR
LB1
Preselect Mode 0
K 08.01
M0_VORW
LB1
START/STOP
K 08.02
MO_IO
ZBS
K 08.03
M0_1RES
ZBS
K 08.04
M0_2RES
ZBS
Start Refilling
K 08.05
M0_FSTA
ZBS
Stop Refilling
K 08.06
M0_FSTO
ZBS
K 08.07
M0_LVOR
ZBS
Preselect Mode 1
K 09.01
M1_VORW
LB1
START/STOP
K 09.02
M1_IO
LB1
K 09.03
M1_1RES
LB1
K 09.04
M1_2RES
LB1
Start Refilling
K 09.05
M1_FSTA
LB1
Stop Refilling
K 09.06
M1_FSTO
LB1
K 09.07
M1_LVOR
LB1
-.NO
oq
oq
o
oq
oq
o
oq
oq
o
o
oq
oq
o
oq
oq
o
o
oq
op
o
9941
List of Interfaces
FH 399 GB/ B - 2
Technische
Redaktion BVED
MULTICONT
SIMPLEX
Acknowledge Event
Message
K 10.01
STCLR
EA1.DE5
Volumetric Mode 1
K 10.02
VOL1_EI
EA2.DE4
Activate Emergency
Setpoint
K 11.01
QU_NOTS
EA2.DE5
K 11.13
STINDEX
Activate Emergency
Setpoint
K 11.01
QU_NOTS
EA2.DE5
K 11.13
STINDEX
K 14.01
QU_Z1ST
-.NO
K 14.02
QU_Z2ST
-.NO
K 14.09
I3_Store
-.NO
K 16.01
M0_BATQ
ZBS
K 16.02
M1_BATQ
LB1
K 16.03
TM_BATQ
K 16.04
M0_BATA
ZBS
K 16.05
M1_BATA
LB1
K 16.06
TM_BATA
LB1
K 17.02
FKL_RMZ
ME1.DE3
K 17.03
FKL-RMA
ME1.DE2
K 18.02
MS_FILO
-.NO
K 18.03
FILOR_R
-.NO
K 19.02
RMAUF_E
ME1.DE4
LB1
W1
o
o
o
o
o
o
o
o
oq
o
o
o
o
o
o
op
op
p
o
op
9941
Technische
Redaktion BVED
List of Interfaces
FH 399 GB/ B - 3
SIMPLEX
MULTICONT
K 19.03
TRIAUS
ME2.DE6
K 19.08
RMZU_BL
ME1.DE5
K 20.01
RM_ATK
.0
K 22.01
TOT_VM0
K 22.02
TOT_VM1
K 22.03
TOT_TM0
K 22.04
TOT_TM1
K 22.05
TOT_VOR
K 22.06
TOT_INI
K 22.07
TOT_IM0
K 22.08
K 22.09
K 22.10
K 23.01
-.NO
-.NO
-.NO
-.NO
-.NO
-.NO
-.NO
-.NO
-.NO
TOT_M1
TOT_TI0
TOT_TI1
-.NO
QU_NUL
oq
op
op
o
o
o
o
o
oq
o
-.NO
o
oq
9941
List of Interfaces
FH 399 GB/ B - 4
Technische
Redaktion BVED
MULTICONT
SIMPLEX
NAME
NUMBER
CODE
DEFAULT VALUE
Drives OK
K 02.00
ANTR_OK
Start Refilling
K 03.05
FIL_EIN
EA1.DA3
K 03.06
FIL_AKT
EA1.DA6
Material Flow OK
K 04.00
MATFL_O
K 04.01
TFIL_MA
W1
Volumetric Discharge
Time Exceeded
K 04.02
TVOL_MA
W1
K 04.03
IF_MIN
No Release
K 05.06
NO_FREI
K 05.07
EL_BER
Ready in Mode 0
K 05.08
M0_BER
EA1.DA5
Ready in Mode 1
K 05.09
M1_BER
K 05.10
M0_EBER
K 05.11
M1_EBER
No EMERGENCY STOP
K 05.12
NO_NOT
K 06.09
LO_AKT
K 07.08
TM_AKT
Mode 0 Preselection
Active
K 08.08
M0_AKT
W1
W2
VALUE
SWITCH
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
9941
Technische
Redaktion BVED
List of Interfaces
FH 399 GB/ B - 5
SIMPLEX
MULTICONT
NAME
NUMBER
CODE
DEFAULT VALUE
Mode 1 Preselection
Active
K 09.09
M1_AKT
K 10.00
EIN_DOS
EA1.DA1
General Alarm
K 10.04
S_ALARM
EA1.DA2
General Warning
K 10.05
S_WARN
EA1.DA7
Start Agitator
K 10.06
RW_EIN
EA1.DA4
Message: Feeder ON
K 10.07
W_EIN
K 10.19
H_EIN
Message: Deviation
K 11.03
DA_REGA
W1
K 11.04
NOTSOL
W1
K 11.05
REG_ERR
W1
K 12.01
K_PMIN
W2
K 12.02
K_PMAX
W2
K12.03
K_BMIN1
W2
K 12.04
K_BMIN2
W2
K 12.05
K_BMAX1
W2
K 12.06
K_BMAX2
W2
K 12.07
K_NMIN
W2
K 12.08
K_NMAX
W2
Start Vibrator
K 14.03
RUET_EI
Volumetric
K 14.04
VOL_AKT
EA2.DA7
VALUE
SWITCH
o
o
p
p
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
9941
List of Interfaces
FH 399 GB/ B - 6
Technische
Redaktion BVED
MULTICONT
SIMPLEX
NAME
NUMBER
CODE
DEFAULT VALUE
K 14.07
INV_AKT
Pre-act Contact
K 16.07
VORKON
Main Contact
K 16.08
HAUPTK
K 17.04
FKL_AUF
EA2.DA2
K 17.08
DA_FKLA
K 17.09
DA_FKLZ
K 18.04
FILOR_E
K 19.04
ELKL_AU
EA2.DA3
K 19.06
BL_VORB
EA2.DA4
K 19.07
BLKL_ZU
EA2.DA5
K 19.10
TRIAUS
EA2.DA6
K 19.11
SAUGFIL
K 19.12
DRUCKFIL
K 20.02
ATK_AUF
K 20.03
F_ATK
K 21.03
FVB_MIN
W2
Start Supply
K 21.04
FVB_MAX
W2
K 21.05
FILORVB
K 22.11
TOT_GEW
VALUE
SWITCH
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
9941
Technische
Redaktion BVED
List of Interfaces
FH 399 GB/ B - 7
SIMPLEX
MULTICONT
NAME
NUMBER
CODE
DEFAULT VALUE
K 22.12
TOT_PON
K 22.13
TOT_ON
K 23.02
ERR_NUL
K 24.02
D_MIN
K 24.03
D_MAX
VALUE
SWITCH
o
o
o
o
o
NAME
NUMBER
CODE
DEFAULT VALUE
Drive Signal
K 06.08
LO_STEL
ME2.AE1
Absolute Setpoint
K 07.10
TM_PABS
LB1
Absolute Setpoint
K 08.10
M0_PABS
ZBS
Absolute Setpoint
K 09.10
M1_PABS
LB1
K 10.10
QU_FGGEW
ME1.WZ1
Number of Revolutions
K 10.11
QU_DREH
ME1.GA1
K 21.01
QU_FGVB
K 24.01
D_QU
VALUE
NAME
NUMBER
CODE
DEFAULT VALUE
Totalizing Counter 1
K 10.08
FM1_IA
EA1.IM1
Totalizing Counter 2
K 10.09
FM2_IA
EA2.IM1
K 10.12
STL_DOS
EA1.AA1
VALUE
9941
List of Interfaces
FH 399 GB/ B - 8
Technische
Redaktion BVED
MULTICONT
SIMPLEX
NAME
NUMBER
CODE
DEFAULT VALUE
K 10.13
P_IST1
EA1.AA2
K 10.14
P_IST2
Bin Level
K 10.15
FGEW
EA2.AA2
Setpoint
K 10.16
P_SOLL
Number of Revolutions
K 10.17
DREHZ
Feed Amount
K 10.18
AA_HUB
Deviation
K 11.10
AA_REGA
K 14.08
P_IST3
K 21.02
FGVB
VALUE
9941
Technische
Redaktion BVED
List of Interfaces
FH 399 GB/ B - 9
MULTICONT
SIMPLEX
Annex C:
As from Version FDW 1202-01
New Configurators:
K 02.06
K 03.02
K 03.07
Cable Breakage
Automatic Initial Filling
Spezial Fllsteuerung
Fixed to A
Fixed to .0
Fixed to .0
K 07.05
K 08.05
K 09.05
Start Filling
Start Filling
Start Filling
No automatic
initial filling
possible
K 11.06
K 12.06
K 12.07
K 12.08
K 13.01
K 13.02
K 15. ...
K 17.05
K 17.06
K 23.01
K 24.01
Compensation
Fixed to .1
Fixed to A
Fixed to A
Fixed to A
Fixed to A
Fixed to A
Not possible
Fixed to A
Fixed to A
Fiexed to
DE -.NO
Fixed WZ
P 01.14
Max.
999999.9
P 05.24
P 05.25
Max. 100.0%
Max. 100.0%
P 05.26
P 06.02
P 06.04
P 06.05
P 08.08
P 08.11
P 09.06
Max. 10.0
Max. 100.0
Max. 4.0s
Min. 0.0 s
Max. 130 %
Max. 200.0%
Max. 100.0
P 13.07
P 14.07
Max. 10.0s
Max. 100.0 V
K 01.06
K 01.07
K 02.08
K 03.07
K 05.12
K 10.19
K 10.20
K 11.13
K 11.14
K 17.08
K 17.09
New Parameters:
P 01.15
frqnenn
FG_Ber
H_Ber
9941
Technische
Redaktion BVED
Annex C
FH 399 GB/ C - 1
SIMPLEX
MULTICONT
Operation:
After operation of HELP key, the most significant event
message is displayed in plain language.
b_vork [i]
h_rest[i]
P 08.05
P 08.06
P 08.09
P 08.10
bmax1[i]
bmax2[i]
rwerk[i]
vibro[i]
Providing negative
measuring range
Now with feed index
Now with feed index
Now with feed index
Now with feed index
Local Mode:
Solely alarms of Group WE (Electrical Equipment of
Feeder) entail cut-off. If Local Mode is aborted, feeder
returns to its previous mode of operation and cuts off
automatically.
F_KABEL
Contact connection to
Namur inputs possible.
K 06. 05
K 06.06
K 06.07
K 19.03
LO_FKLA
LO_RWEI
LO_SCHN
TRIAUS
Now edge-controlled
Now edge-controlled
Now edge-controlled
Now edge-controlled
delta+
Setpoint entry of
increase, or decrease, separately limited.
Additional source
for counter reset
Extended by alarm
In addition, all configurators for digital inputs and outputs cater for inversion of switching levels.
K 17.07, K 19.13, K 19.14, K 20.04 are thus omitted.
9941
Annex C
FH 399 GB/ C - 2
Technische
Redaktion BVED
MULTICONT
SIMPLEX
Annex D:
Special Hints
DISPLAY
FILL
WEIGHT
ALARM CA 02
FEED
AMOUNT
bmax
AMOUNT
*
mes_res
hmax
AMOUNT
+
hmin1
0
hmin2
BUFFER
+
0
h_rest
ALARM CA 01
MEASUREMENT
TERMINATED
2. Alarm :
Load cell amplifier underamplified, or overamplified.
Use parameters h_rest and mes_res to extend
measuring range up or down. Frequent cut-off can
thus be avoided.
mes_res
h_rest
is preset in kg.
Value is active only after taring. A value
of approx. 5% of BUFFER is recommended.
MAX =
8. Monitoring Unit.
This circuitry monitors the relation between
armature voltage and feed rate setpoint and requires
to be thoroughly adjusted.
a) Preselect feeder nominal feed rate.
b) On limit switch -A13/49-8 a voltage V(SET) of
approx. 8 V should come up. Jot V(SET) value.
Effect corrections with parameter PS_BER.
9941
Technische
Redaktion BVED
Annex D
FH 399 GB/ D - 1
SIMPLEX
MULTICONT
9. Controller in Multicont.
P 2.5 Load cell filter
: 1 (Default)
P 4.1 Filter time differentiator: 4 ... 8 s
P 5.1 Dynfak
: 0.7 ... 0.9
P 5.2 Setpoint bypass
: 4.5 ... 6.5 V
Thoroughly adjust speed control circuit and call
function REGLEROPT.
Do not fail to call function REGLEROPT after having
changed one of the above parameters.
Dynfak must not exceed nor equal 1. With pulverized
coal feeders, the resulting PI controller entails inadmissibly high control magnitude variations.
10. Pressures
Hopper blow out
: Recommended 1 bar
Surge bin ventilation: Recommended 0.8 bar
The maximum setting value at both pressure
reducers is 2 bar.
9941
Annex D
FH 399 GB/ D - 2
Technische
Redaktion BVED