DEPARTAMENTO DE HUANUCO
MEMORIA DE CALCULO DE
INSTALACIONES ELECTRICAS
Proyecto:
RECUPERACION Y MEJORAMIENTO DEL COLISEO KOTOSH
Propietario:
GOBIERNO REGIONAL DE HUANUCO
Proyectista:
Ing. OSCAR QUIROZ ZUIGA
CIP N 72931
Fecha:
Agosto del 2014
ESTUDIO DE CARGA
1.
* ALUMBRADO
LUM. LED SM480 LED30S/840: 40 W
LUM. LED BCS680 LED48/840: 43 W
LUM. LED SM120V LED25S/830: 31
LUM. LED BWG201 1xLED700/840: 24 W
LUM. LED BBS490 LLED4000: 23 W
LUM. LED BY460P LED100S/740: 102 W
LUZ DE EMERGENCIA 24LED: 48 W
* TOMACORRIENTE
USO GENERAL
* CARGAS ESPECIALES
EXTRACTOR DE AIRE INDUSTRIAL: 1/8 HP
AIRE ACONDICIONADO
ELECTROBOMBA 1 HP
ELECTROBOMBA 3 HP
RESERVA (20%)
TOTAL
Pot.
Cantidad Unitaria
(W)
68
60
77
50
13
102
46
0
0
138
0
0
1
1
2
2
40
43
31
24
23
102
48
172.5
93
5000
746
2238
Pot.
Instalada
(kW)
f.d.
Maxima
Demanda
(kW)
2.72
2.58
2.39
1.20
0.30
10.40
2.21
0.00
0.00
23.81
0.00
0.00
0.09
5.00
1.49
4.48
1.00
1.00
1.00
1.00
1.00
1.00
1.00
2.72
2.58
2.39
1.20
0.30
10.40
2.21
1.00
23.81
0.80
0.80
0.80
0.80
0.07
4.00
1.19
3.58
10.89
1.00
10.89
67.56
65.34
M.D. = 60,78 KW
1.2
Mxima Demanda
MD
65,34
Factor Potencia
Cos
0,90
PT
MD
Cos
72.60 KVA
1.3
Mxima Demanda
MD =
65,34
Factor Potencia
Cos=
0,90
PGE
MD
75%
Cos
54.45 KVA
Para esta carga se seleccionara un Grupo Electrgeno Trifsico de 50 KVA, con una
relacin de salida de 0,22 KV - 60 Hz.
IN
PTOT
3 V Cos
Donde:
IN
PTOT
Cos
IN
65,34
3 220 0,90
IN = 190,53 A
Id = 238,16 A
Para este valor de corriente se debe encontrar un conductor que admita esta
capacidad, que de acuerdo al Cdigo Nacional de Electricidad, escogemos lo
siguiente:
95
90
Tipo de Conductor
N2XH
Fc1
0,92
Fc2
0,95
Fc3
0,93
Ft = 0.81
Ic
Ft
Donde:
I
Ic
=
=
Corriente de Servicio
Capacidad de Conduccin Limitado por Ft.
CUADRO N1
I
(A)
95
330
Ic
(A)
268
Para nuestro caso, debemos constatar que nuestra cada de tensin no sobrepase
el 2,5 % de la tensin de servicio (220 V), es decir 5,50 V, segn lo establecido en
el Cdigo Nacional de Electricidad. Para calcular la cada de tensin del
alimentador principal, utilizaremos la siguiente formula:
3 IN r L
S
Donde:
V
IN
3 214,98 0,0179 36
95
V = 2,27 V
En resumen
Suma
Longitud
Caida
Caida
Caida
de
Tensin
Tensin
Tensin
Conductor
(%)
(V)
(V)
(m)
FASES
M.D.
(A)
(mm2)
LLEGADA A TDG
TDG A ST-1
TDG A ST-2
TDG A ST-3
TDG A ST-4
TDG A ST-5
TDG A ST-6
TDG A ST-7
TDG A ST-8
TDG A ST-9
TDG A ST-10
TDG A ST-11
TDG A ST-12
3
2
2
3
2
2
2
3
3
2
3
3
2
65.34
3.42
4.39
6.35
3.98
3.20
2.24
6.12
17.80
2.10
6.86
5.64
3.25
0.90
0.90
0.90
0.90
0.90
0.90
0.90
0.90
0.90
0.90
0.90
0.90
0.90
238.16
21.59
27.71
23.15
25.13
20.20
14.14
22.31
64.88
13.26
25.00
20.56
20.52
95
16
6
10
10
4
6
10
16
4
16
10
10
36.00
65.00
15.00
31.00
41.00
11.00
31.00
31.00
23.00
28.00
45.00
49.00
45.00
2.52
2.45
1.93
2.00
2.87
1.55
2.04
1.93
2.60
2.59
1.96
2.81
2.58
2.52
4.97
4.45
4.52
5.39
4.07
4.56
4.45
5.12
5.11
4.48
5.33
5.10
1.15
2.26
2.02
2.05
2.45
1.85
2.07
2.02
2.33
2.32
2.04
2.42
2.32
3
2
2
3
2
2
2
3
3
2
3
3
2
TDG A ST-12
TDG A ST-12
2
3
1.19
3.58
0.90
0.90
7.51
13.05
10
16
45.00
45.00
0.94
1.02
5.39
5.47
2.45
2.49
2 x 15
3 x 20
TABLERO
(Kw)
220V, 3
ITM
x
x
x
x
x
x
x
x
x
x
x
x
x
tub.
105
40
40
55
40
25
40
55
55
25
55
55
40
250
25
32
25
32
25
20
32
80
20
32
25
25
40
55
CAIDA DE TENSION:
Max_Caida
Tension
2.50%
220 V
Fuente: C.N.E. Seccion 050 - 102
Tension
Caida
Tension
5.50 V
2.1 OBJETIVOS
Para los diferentes niveles de actividad se hace necesario adoptar una serie de
requisitos que debe reunir la iluminacin que conciernen tanto al plano de
iluminacin horizontal (situado a nivel de terreno), y los planos verticales donde se
pueden localizar objetos verticales (jugadores, rbitros, etc.).
En la Tabla
Para los diferentes tipos de deportes se dan en la Tabla VIII los niveles de
iluminacin nominal horizontal recomendados. El nivel de iluminacin nominal
horizontal Eh es el valor medio recomendado de la iluminacin sobre el campo
deportivo. A fin de que la iluminacin nominal para las condiciones promedio de
operacin
El nivel de iluminacin medio no debe ser menor que 0.8 veces la iluminacin
nominal. El plano de medida para la iluminacin nominal debe estar a 1 m sobre
el campo deportivo. Para cada tipo de deporte se dan los valores de iluminacin
nominal horizontal para entrenamiento y competencia. Los mayores valores para
las competencias toman en consideracin tambin las exigencias de visibilidad de
11
Columna 3: Uniformidad.
En la Tabla VII se dan los limites para la uniformidad puntual del nivel de
iluminacin horizontal Gh = Eh min / Eh , sobre los campos deportivos.
Las propiedades de
Columna 5: Observaciones
12
Tabla VII
ILUMINACION RECOMENDADA PARA LOCALES DEPORTIVOS
13
En resumen
14
15
TABLA DE ILUMINANCIAS
PARA AMBIENTES AL INTERIOR
16
TABLA DE ILUMINANCIAS
PARA AMBIENTES AL INTERIOR
En resumen
18