Académique Documents
Professionnel Documents
Culture Documents
1200
120180
2400
120 + 0
(120 + 0)
240 + 0
1 2 = 0
= 1 + 2
= 1 2
= (83.330) (83.33120) = 83.33240
= 83.33 120
Phase Rotation
The phase angle shift of 120 is a function of the
actual rotational angle shift of the three pairs of
windings.
1
0
Perhaps the greatest advantage of the connected source is its fault tolerance. It is
possible for one of the windings in a - connected
three phase source to fail open without affecting
load voltage or current!
1
1
1
2
1
3
+ + = 0 =
=
= 3
=
A balanced - system is one in which both the
balanced source and balanced load are connected.
= 0
1
4
1
5
where:
0.95 to unity
0.5 to 0.9
as low as 0.4
1
6
4. Pipe earthing
5. Plate earthing
Earthing of a Power System
Earthing of neutrals of all industrial power
systems is always preferable. Earthing is
necessary as it offers many advantages:
1. Persistent arcing ground is eliminated.
2. Over voltage due to restriking is minimized.
3. The ground faults can be located an isolated
immediately.
4. Steady state voltage stress to earth is
reduced.
5. Sensitive protective apparatus can be used.
6. The maintenance expenditure is reduced.
7. Better safety is ensured.
8. Service reliability is improved.
9. Earthing
provides
improved
lightning
protection. The earthing of systems should be
done at the neutral of the supply transformers
and generators. If the supply transformers
and generators are delta connected, separate
earthing transformers may be used.
Examples:
1. If Vab = 400 V in a balanced Y connected
three phase generator, find the phase
voltages, assuming the phase sequence is: a.
abc
b. acb
2. Given that the line voltages of a three phase
circuit are
= 4200
= 420 120
= 420120
Find the phase voltages Van, Vbn and Vcn.
3. A balanced Y connected load with a phase
impedance of 16+j9 is connected to a
balanced three phase source with a line
voltage of 220 V. Calculate the line current IL.
4. A balanced Y Y four wire system has phase
voltages
= 1200
= 120 120
= 120120
1
7
1
8
1
9
2
0
+ 1( + + )
+ 2( + + + +
+ ) = 0
Phase Currents:
= 1 3
= 2 3
= 3
Line Currents:
=
=
=
- System
= , = , =
Phase Currents: = 1 3, = 2 3, = 3
Line Currents:
=
=
=
- Y System
2
1
+ ) = 0
Phase/Line Currents: = 1, = 2 1; = 2
= + +
Load Voltages:
=
=
=
2
2
2
3
difference of and .
3. Three wattmeter method used to measure
power drawn by a 3 phase, 4 wire system.
1 = cos
2 = cos
3 = cos
= 1 + 2 + 3
Watts Ratio Curve
The power factor for a balanced load can be obtained
from the wattmeter readings using a simple curve
called the watts ratio curve.
= 1 + 2
3. If pf = 0.5, only one wattmeter gives reading
and the other will not read = 1
2
4
= 230 0
= 60
= 230 120
= 30 + 50
= 230 240
= 80
Determine the reading of the two wattmeters
properly connected using line c as the
common point.
Determine the reading of the two
wattmeters properly connected using line b
as the common point. Determine the
reading of the two wattmeters properly
connected using line a as the common
point.
6. The power input to a 50 hp, 480 V, 3 phase
motor running at full load is measured by 2
watt meters which indicates 25.4 kW and
17.2 kW respectively. What is the operating
power factor and line current?
7. Two watt meters are connected to measure
the input power to a balanced three-phase
load. If the wattmeter readings are 9.3kW
and 5.4kW determine (a) the total output
power, and (b) the load power factor.
8. 8kW is found by the two wattmeter method
to be the power input to a 3 phase motor.
Determine the reading of each wattmeter if
the power factor of the system is 0.85.
9. When the two wattmeter method is used to
measure the input power of a balanced load,
the readings on the watt meters are 7.5kW
and 2.5kW, the connections to one of the
coils on the meter reading 2.5kW having to
be reversed. Determine (a) the total input
power, and (b) the load power factor.
10. Three similar coils, each having a resistance
of 4 and an inductive reactance of 3.46
are connected (a) in star and (b) in delta
across a 400V, 3 phase supply. Calculate
for
each
connection the
readings
on
each of two
watt
meters
connected to
measure the
power by the
2
5
Operator A
- is one which when multiplied to a vector,
rotates through a 120 in the counter
clockwise direction.
Let:
= 1120
2 = 1240
3 = 1360 = 1
Positive Sequence Component
=
=
=
=
2
6
= 0 + 21 + 32
Adding them up,
+ + 2 = 0(1 + + 2) + 31 + 2(1
+ 2 + 4)
= /( + + )
Also, Ib2 = AIa2 and Ic2 = A2Ia2 In matrix
notation:
2
7
1 = 1
2 = 2
and, as expected, the sequences are
independent. If the neutral point is not grounded
in (a) I0 = 0 but E0 = I1Z2 + I2Z1 so that there is a
zero sequence voltage, representing a neutral
voltage shift, created by positive and negative
sequence current flowing through the
unbalanced load. The previous equations also
hold for unsymmetrical series line impedances,
as shown in (b), where E0, E1 and E2 are
components of Ea, Eb and Ec, the voltage drops
across the impedances in the three phases.
Mutual Impedances between phases can also be
resolved into components. Consider Zmbc of (a),
as reference, then
1
= ( + 2 + )
3
2
8
and
0 = 0 + 1 + 2 1
= 0 + 1 + 2
2 = 0 + 1 + 2 Note,
however, that Y0 is not the reciprocal of Z0, Y1 is
not the reciprocal of Z1, and Y2 is not the
reciprocal of Z2, unless Za = Zb = Zc; in other
words, the components of admittance are not
reciprocals of the corresponding components of
impedance unless the three impedances (and
admittances) under considerations are equal.
Star Delta Conversion Equations
2
9
3
0
3
1
0
+
0
+
0 + = 0
Since
Since 0 = 0 = 0 and = 30
Since
Therefore,
= +
b. Synchronous Machines is designed with
symmetrical windings and it induces emfs of
positive sequence only. The positive sequence
generator impedance is the value found when
positive sequence current flows due to an imposed
positive sequence set of voltages. Neglecting
armature resistance, the positive sequence
impedance of the machine is
(Sub transient)
(Transient)
= (Steady state value) With
the flow of negative sequence currents in the
stator, the net flux in the air gap rotates at opposite
direction to that of the rotor. Therefore, the net flux
rotates twice the synchronous speed to the rotor.
3
2
c.
3
3
3
4
7.
Draw the zero sequence network of the
sample power system.
2. Draw the positive sequence network of the power
system.
3
5
Normally, transmission
lines implies
the
bulk transfer of power by high voltage
links between main load centers. On the other
hand, distribution system is mainly responsible
for the conveyance of thos power to the
consumers by means of lower voltage
networks.
Electric
power is generated in the range
of 11 kV to 25 kV, which is increase by
stepped up transformers ot the main
transmission voltage. At
sub
stations, the connection between
various
components are made, for example, lines and
transformers
and
switching
of
these
components is carried out. Transmission level
voltages are in the range of 66 kV to 400 kV (or
higher). Large amounts of power are transmitted
from the generating stations to the load centers
at 220 kV or higher.
The power supply network can be divided int two
parts, transmission and distribution systems. The
transmission system may be dividided into
primary and secondary distribution system. Most
of the distribution networks operate radially for
less short circuit current and better protective
coordination.
10.
Draw the zero sequence network of the sample
power network.
Generation,
Transmission and
Distribution
systems are the
main components
of
an electric
power system.
Generating
stations and
distribution
systems are
connected through
transmission lines.
Electrical Engineering Department | Engr. Gerard Francesco DG. Apolinario
3
6
3
7
3
8
3
9
Examples:
1. A single phase transformer is rated 20 kVA,
480/120 V, 60 Hz. The equivalent leakage
impedance of the transformer referred to the
120 V winding, denoted by winding 2, is 2
= 0.052578.13 . Using the transformer
ratings as the base values, determine the
per unit leakage impedance referred to
winding 2 and referred to winding 1.
2. A single phase two winding transformer is
rated 25 kVA, 1100/440 volts, 50 Hz. The
equivalent leakage impedance of the
transformer referred to the low voltage side
is 0.06 < 78 . Using transformer rating as
base values, determine the per unit
leakage impedance referred to low voltage
winding and referred to high voltage
winding.
3. The figure shows single line diagram of a
single phase circuit. Using the base values
of 3 kVA and 230 V, draw the per unit
circuit diagram and determine the per unit
impedances and per unit source voltage.
Also calculate the load current both in per
unit and in Amperes.
4
0
[1]
Alexander, Charles K. and Sadiku,
Michael N.O. (2013). Fundamentals of Electric
Circuits pp. 503 554. McGraw Hill Higher
Education.
[2]
Bird, John (2007). Electrical and
Electronic Principles and Technology pp. 311
326. Elsevier. [3] Boylestad, Robert L. (2007).
Introductory Circuit Analysis pp. 1029 1066.
Pearson Prentice Hall.
[4]Glover, J. Duncan, Sarma, Mulukutla S. and
Overbye, Thomas (2012). Power System:
Analysis & Design pp. 1 158. CENGAGE
Learning.
[5]Hobson, J.E. and Whitehead, D.L.
Symmetrical Components [PDF Document].
Retrieved
from
https://www.scribd.com/doc/63947448/Sym
metricalComponents
[6]Lucas, J.R. (2001). Three Phase Theory &
Symmetrical
Components [PDF Document]. Retrieved from
http://www.elect.mrt.ac.lk/EE201_3phase_sym
_comp.pdf [7] Nahvi, Mahmood and Edminister,
Joseph (2003). Schaums Outlines: Electric
Circuits pp. 248 272. McGraw Hill Higher
Education.
4
1
4
2