Académique Documents
Professionnel Documents
Culture Documents
February, 2004
1.
2.
3.
4.
Page 2 of 6
6.
The ASHRAE 110 test tracer gas ejector occupies far less
space than the equipment and apparatus typically found in
actual laboratory fume hoods.
7.
Challenges to Containment
As stated, the laws of physics do not allow fumes to
flow from an area of lower static pressure to an area
of higher static pressure. Why then can fumes flow
out from a fume hood interior that is (presumably) at
a lower static pressure as evidenced by a proper
face velocity? Note that room air currents (like any
airflow) have a lower static pressure than room air
that is essentially at rest. And, as a room air current
passes an open sash, the pressure difference
between the fume hood interior and the static
pressure at the periphery of the air current can be
considerably less than the pressure difference
between the fume hood interior and room air that is
essentially at rest.
Figure 2 illustrates the relationship between the
static pressure (lower value) and the total pressure
(higher value) of an air current. The higher value of
total pressure is always in the direction of travel
while the lower static pressure is always
perpendicular to the direction of travel. As the
velocity of an air current increases even more, its
total pressure also increases while its static pressure
becomes even lower. Thus, as higher velocity air
currents pass crosswise to an open fume hood sash,
the reduced static pressure difference between the
fume hood interior and the periphery of the air
current creates a tendency for fumes to flow out from
the hood interior. This is especially true if air currents
within the fume hood travel toward the sash
8.
9.
The total fume hood open area consists of the sash opening
plus all additional openings, including the airfoil slot and the
bypass opening.
AIR CURRENT
TOTAL
PRESSURE
(HIGHER)
STATIC
PRESSURE
(LOWER)
T
S
Figure 2. Static Pressure is Lower for Air in Motion.
The safety standards advise that periodic retesting to verify fume hood containment should
still be done on an annual basis, or whenever
changes are made to the ventilation system.
Using the above sampling approach could reduce
the time and expense of testing in new facilities. 12
For example, if a facility had 100 laboratory rooms
and each room had two fume hoods of the same
size and type, the containment testing could possibly
be conducted on only two sample groups having 10
fume hoods per group. Then rather than 200
separate fume hood containment tests, perhaps only
20 fume hood tests would suffice.
Designer Responsibility
Conclusion
VAV Advantage
VAV fume hoods will typically allow greater flexibility
in establishing the necessary average face velocity
for a particular fume hood due to the diversity factor
associated with VAV systems. 14 In other words if a
particular fume hood requires a higher than
anticipated average face velocity, it can usually be
attained without adding to the overall exhaust
system capacity. Also, the fume hood working height
for vertical sash fume hoods can usually be
restricted to 18 inches 15 by implementing a sash
stop. This reduces the sash opening to about 65% of
the normal full open sash height. As a result, the
average face velocity could then be increased by up
to 35% if necessary, based upon the exhaust airflow
rate for a fully open sash.
13. Fume hood design airflow should be based upon either the
owners stated face velocity requirements or the fume hood
manufacturers as manufactured (AM) test data.
14. Fume hoods that have their sashes closed enable the
exhaust air capacity (and the room makeup air) to be used
where more airflow is needed.
15. A typical maximum fume hood vertical sash opening is at
least 28 inches.
Siemens Industry, Inc.
Document No. 149-989
Page 5 of 6
Product or company names mentioned herein may be the trademarks of their respective owners. 2009 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
USA