Académique Documents
Professionnel Documents
Culture Documents
VTC 2013
Learning outcome
suggest solutions to improve power line disturbances
in the electrical systems
Learning contents
Common power electronics related power line disturbances,
Voltage spikes, Chopped voltage waveform, Harmonics,
Electromagnetic Interference.
Harmonics Filter
Conclusion
Common Power Disturbances
Voltage Sags
One of the most common power frequency disturbances is voltage sag. By
definition, voltage sag is an event that can last from half of a cycle to several
seconds.
Voltage Sags due to motor starting or Arc furnace.
Voltage sags typically are due to starting on large loads, such as an electric
motor or an arc furnace. Induction motors draw starting currents ranging
between 600 and 800% of their nominal full load currents.
The current starts at the high value and tapers off to the normal running
current in about 2 to 8 sec.
Figure below contains the waveform of the starting current of a 50-hp
induction motor with a rated full-load current of 60 A at 460 VAC.
Conclusion
Common Power Disturbances
Waveform of Starting current
Zs
M
Other loads
Vsag = 77%.
Hence, the voltage at the bus during motor starting = 77% x
11kV =8.47kV.
loads and to the motor itself. One profound effect of motor starting is
voltage dip.
that is
Reduction of terminal voltage by using an auto-transformer.
Reduce of terminal voltage by using a star-delta switch.
By using the Variable Frequency Drive (VFD) to control the motor.
equipment.
Install equipment protection device
Constant voltage transformer
Voltage Dip Proof Inverter
contactor hold-in circuit
U/V
Chiller
Relay
Precaution
Voltage Dip
U/V
Chiller
Relay
Voltage Dip
Proofing Inverter
(DPI)
$6000/kVA
Constant Voltage
Transformer
(CVT)
$5000/kVA
(UPS)
$7000/kVA
(Constant-voltage transformers)
CVTs are especially attractive for constant, low power device.
CVTs are excited high on their saturation curves, thereby providing an output
Coil lock
Literally any device that is
controlled by energizing an ac
coil, when powered through a
Coil-Lock unit will continue
to operate as intended
through these power
disturbances.
Not only does the Coil-Lock
protect the coil circuits from
voltage sags, but also has the
ability to protect coils from
lightning and switching
induced transients just like a
surge suppressor.
Coil lock
The figure shows the typical
Conclusion
Static Uninterruptible Power Source System
Static uninterruptible power sources (UPSs) are devices that maintain power
to the loads during loss of normal power for a duration that is a function of
the individual UPS system.
All UPS units have an input rectifier to convert the AC voltage into DC
voltage, a battery system to provide power to loads during loss of normal
power, and an inverter which converts the DC voltage of the battery to an AC
voltage suitable for the load being supplied.
Static UPS systems may be broadly classified into offline and online
units.
Conclusion
Static Uninterruptible Power Source System
In the offline units, the loads are normally supplied from the primary electrical
source directly.
The primary electrical source may be utility power or an in-house generator. If
the primary power source fails, the power to the loads is switched to the
batteries and the inverter. The switching is accomplished within half of a cycle
in most UPS units, thereby allowing critical loads to continue to receive power.
During power transfer from the normal power to the batteries, the loads might
be subjected to transients. Once the loads are transferred to the batteries,
the length of time for which the loads would continue to receive power
depends on the capacity of the batteries and the amount of load.
UPS units usually can supply power for 15 to 30 min, at which time the
batteries become depleted to a level insufficient to supply the loads, and the
UPS unit shuts down.
Conclusion
Harmonics
What is harmonics ?
Multiples of the fundamental frequency of any
periodical waveform are called Harmonics.
50Hz (Fundamental Frequency)
+
150Hz (Third Harmonic)
+
250Hz (Fifth Harmonic)
Harmonic distortion
Harmonics vs Transients
Harmonics are associated with the continuing operation
Harmonic Distortion
Harmonic distortion is caused by non-linear devices in the power
system.
What is harmonic ?
For power networks, 50 Hz (60 Hz) is the
Triplen Harmonics
Triplen harmonics are the odd multiples of the third harmonic
(h=3,9,15,21)
Two typical problems are overloading the neutral and telephone interfence.
Third-harmonics components are three times the third-harmonic-phase
currents because they naturally coincide in phase and time.
In the wye-delta transformer, the triplen harmonics current remain trapped in
the delta side when the system is operated in balanced load condition.
Measuring the current on the delta side of a transformer will not show the
triplens and not give a true idea of the heating the transformer is being subject
to.
Although fed by a delta-delta connection, the third harmonics show up in the
large magnitudes in the line current when the furnace is operating in an
imbalanced state.
Harmonics classification
Order
Group
Effects
n=1
Fundamental
active power
heating
heating &
motor
problems
heating &
neutral
problems
n = 3n
0 sequence
Sequences Phasor
R
Positive Seq.
B
Negative Seq.
Zero Seq.
Source of Harmonics
Harmonic Currents flowing
through the system impedance
results in Harmonic Voltage
Distortion at load
Normal load
VL(t)
VS(t)
Cable
Harmonic
current
Supply
Side
Load Side
Dirty Load
Mode
Funda. Current
THD-F (%)
Dominating Harmonics
On
0.54A
110%
3rd
58%
UPS #1
UPS #2
Magnetic ballast w/cap
Print
Idle
Send
Print
Idle
Copy
Idle
Server
PC
On
0.34A
0.11
0.16A
3.74A
0.11A
5.56A
0.35A
40A
4.3A
0.21A
113%
160%
120%
6%
98%
26%
106%
35%
130%
30%
3rd
3rd
3rd
3rd
3rd
3rd
5th
3rd
3rd
3rd
55%
52%
87%
5%
54%
20%
42%
25%
89%
18%
Electronic ballast #1
On
0.19A
34%
3rd
26%
Electronic ballast #2
On
0.23A
10%
3rd
9%
Sodium Lamp
On
0.24A
64%
7th
44%
On
0.1A
136%
3rd
49%
On
Run
8.5A
39A
5%
36%
5th
5th
4.8%
28%
Photocopier
not constant.
For example, Speed increase, percentage of harmonics also
increase.
Blown fuses
Capacitor overload
Capacitor problems
Due to its lower impedance, capacitors are even more
susceptible to higher order
harmonics. If not designed for harmonic duty, a capacitor
may fail pretty soon
losses.
Eddy-current losses. This component of transformer losses
increase with the square of the frequency of the current causing
the eddy currents.
Core losses
Active
Filter
Active filters
Active filters are relatively new types of devices for
eliminating harmonics. They are based on sophisticated
power electronics and are much more expensive than passive
filters. However, they have the distinct advantage that they
do not resonate with the system.
Active filters
The basic idea is to replace the portion of the since wave that
is missing in the current in a nonlinear load.
An electronic control monitors the line voltage and/or
current, switching the power electronics very precisely to
track the load current or voltage and force it to be sinusoidal.
L
VLL
Shunt Filter
Harmonic
Source
For the filter to be tuned at the fifth harmonic, the capacitive reactance
To determine the amount of current that the filter will have to handle,
capacitor is
Vc1=Xc1Ic1=(238.05)(60.386) =14373.9V
Vc5=Xc5Ic5=(47.61)(10)=476.1V
The peak voltage across the capacitor is
Vp=2 (Vc1+Vc5) = 2 (14373.9+476.1)
Based on applicable capacitor standards, capacitors should
be capable of withstanding 120% of rated voltage.
Thus, the capacitor should be capable of withstanding
1.2Vp=1.2x(14850) = 17820V.
2
(
)
I
h
%THD =
h=2
I1
I 2 + I3 + I 4 + ...
100% =
100%
I1
For Voltage
h=2
THD =
V1
Rms
= V1 x 1+ THD
h max
h=1
THD can provide a good idea of how much extra heat will be realized
Operational Limit
Harmonic Current
Distortion
1.At 380V/220V
Total odd harmonic distortion:
I < 30A
20%
30A<=I<300A
15%
300A<=I<600A
12%
600A<=I<1500A
8%
I >= 1500A
5%
total even harmonic distortion:
25% of the odd harmonic
limits
Other Non-linear
Equipment with size I in
Ampere
Operational Limit
Harmonic Voltage
Distortion
At 132kV or above
odd harmonic distortion
total harmonic distortion
1%
1.5%
At 66kV or 33kV
odd harmonic distortion
total harmonic distortion
2%
3%
At 11kV
odd harmonic distortion
total harmonic distortion
3%
4%