Datasheet

IDM 96
Multimeter

Multimeter for three or single phase mains with 56


electrical measured variables. The instrument has
harmonic measurement up to 63th order, THD for
current and voltage and waveform capture. All
parameters can be configured through keyboard or
software, which one follows the instrument. The
software allows view all variables, harmonics
spectrum and waveform.

Characteristics
Three LED displays
Waveform capture in the Modbus buffer for all three phases (current and voltage)
Free included configuration and monitoring software with the instrument
THD measurement for current and voltage. Harmonics (up to 63th )
measurements, which can be viewed through software in form of table or
histogram
Easy configuration through keyboard or software
Universal three phase connection, balanced and unbalanced load, or single phase.
Plugable serial communication RS 485 (optional) protocol Modbus RTU
Universal auxiliary supply 85...265VAC/90...300VDC
Protection degree IP50 (housing) and IP20 (connectors)
Accuracy class 0,5%

Technical data

Construction and mounting

Input

Housing

Plastic anti-flame UL94-VO.

Fastening

Pair of clamps

Protection degree

IP50 housing
IP20 connectors

Weight

~ 0,45 kg

Voltage (Vn)
Current (In)

0500VAC phase-phase
1A , 5A

Signal limit

U = 10120%
I = 10...120%

Consumption

Input signal voltage:


Input signal voltage:

2mA.
0,2VA.

Climatic conditions

Nominal
frequency

50; 60 Hz 10%
Permanent: 1,5 x Un ; 2 x In
Short time: 4 x U/1s; 50 x I/1s
Maximum: 250A /1s

Overload

Operating temperature

-20...+60C

Display temperature

-20...+55C

Storage temperature

-40...+80C
75%

Auxiliary supply

85 265VAC/90300VDC
Consumption ~ 6VA

Relative humidity

Communication

Serial RS485 Protocol Modbus RTU

Connections diagrams Input signal

Influence variables
Error limit

0,5%
I = 10%...100%;
U = 10%...100%
U = 10120%
I = 10...120%

Input:
Frequency:
Additional error input 1,2xI
or 1,2xU
Linearity deviation

0,2%
0,2%
(included in the error limit)
0,2%/10 K;
Nominal Temperature 25C

Temperature error
Auxiliary supply

85 265VAC/90300VDC

Connections diagrams Auxiliary supply and


RS 485

Electrical Tests
Test voltage

2,5kV/1 min 60 Hz between all


circuits

Mechanical tests
Impact

Acceleration 30g duration 11ms

Vibration

Acceleration 2g frequency 5..150Hz

Variables
Variable
Voltage L1 and Neutral
Voltage L2 and Neutral
Voltage L3 and Neutral
Voltage L1 and L2
Voltage L2 and L3
Voltage L3 and L1
Current I1
Current I2
Current I3
Active power P1
Active power P2
Active power P3
Total Active Power PT
Reactive power Q1
Reactive power Q2
Reactive power Q3
Total Reactive Power QT
Apparent power Q1
Apparent power Q2
Apparent power Q3
Total Apparent Power QT
Power Factor 1
Power Factor 2
Power Factor 3
Power Factor T
Frequency
Current demand 1
Current demand 2
Current demand 3
Active Power Demand
Reactive Power Demand
Apparent Power Demand
Cos Phi 1
Cos Phi 2
Cos Phi 3
Cos Phi T
THD Voltage 1
THD Voltage 2
THD Voltage 3
THD Current I1
THD Current I2
THD Current I3

Dimensional (mm)

Access
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus
Display/Modbus

Active Energy Consumed


Reactive Energy Consumed
Active Energy Supplied
Reactive Energy Supplied
Angle Phi 1
Angle Phi 2
Angle Phi 3
Angle Phi T
Voltage angle 1
Voltage angle 2
Voltage angle 3
Current angle 1
Current angle 2
Current angle 3

Display/Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus
Modbus

Caution
Be sure that all connected voltage and current are
compatible with the technical specification and if the
connection are in accordance with the connections
diagrams.

Mounting Instructions
The installation must regard the climatic conditions. It is
important verify the vibration, dust, temperature and
humidity, which must be in the specified limit. The
mechanical fastening in the panel door is done through a
pair of clamps, which is included with the instrument. The
connection of the input voltage, auxiliary supply and RS 485
should be done though pin terminal. The connections of the
input current should be done though lug terminal.

User guide
Verify the connection diagrams and user manual to
configure the instrument. Configure the PT ratio and the CT
primary, connection, and communication (address, baud
rate and byte are according to the local installation.

Product specification
IDM-96
Nominal frequency
50 Hz
60Hz
Connection (Universal)
Single phase/ Three phase
Current signal
1A
5A
Voltage signal
0500Vca (phase-phase)
Auxiliary Supply
85265VAC / 90300VDC
Interface
With RS485
Without RS485
Additional information
Standard configuration:
Default configuration, class 0,5%.
Special configuration
Inform a special configuration

Example:
Frequency:60Hz
Input current: 5A
Input voltage: 0500Vca (phase-phase)
Auxiliary supply:
85265VAC/90300VDC
Interface: Without RS485
Standard Configuration
Code: N0040772424311

N 0 0 4 0 7

1
2
4

1
2
4
3
1
2
1
C

Contact
ABB Ltda.
Avenida dos Autonomistas, 1496
Osasco So Paulo - Brazil
Zip code 06020-902
Telephone 0800 014 9111
Email: abbatende@br.abb.com

Note:
We reserve the right to make technical changes
or modify the contents of this document without
prior notice. With regard to purchase orders,
the agreed particulars shall prevail. ABB BR
does not accept any responsibility whatsoever
for potential errors or possible lack of
information in this document.
CopyRight 2012
All rights reseverd

Vous aimerez peut-être aussi