Transducer ETM 15

DATA SHEET - N00300

For alternating current or voltage

Pgina 1/4
july 2005

Charactersties

Measuring of sinusoidal electric magnitudes.


Measuring RMS (Optional) of sinusoidal eletric magnitudes or
not sinusoidal
Linear measuring field.
Output signal with or without suppressed zero.
Galvanic isolation between in- and output and auxiliary power
supply.
Reduced size for mouting space saving.
Case type housing for fastening with screws or on rail .

Application

Conversion of an alternating sinusoidal voltage or current into a


signal of direct current or voltage, which is independent on the
load.

Functioning

The transducer ETM 15 with alternating sinusoidal voltage or


current input is a fully electronic instrument, whick work on the
principle of rectification.

Technical data (NBR 8145)


Input

Voltage
Current
Consumption

Rated frequency
Overload

Output

Current
The transformer (1) attenuates the input signal for the rectifierador (2)
and effectuates a galvanic isolation between the in- and output signals.
The amplifier (3) converts the input signal into an output of alternating
voltage or current.
The rectifier (2) and the output modelu (3) need an auxiliary power
supply (4).

Characteristic curves

Signal limit
Load limit
Output with load
divider (Optional)
Voltage
Residual ripple

Power supply

0..100/110/220/380/500V
(others on consult)
0..1/2/5A (others on consult)
voltage input: 0,65VA for error limit
of 0,5%
1,00VA for error limit 0,25%
Current input: 0,15VA
50;60 Hz 10% (others on consult)
permanently: 1,5 x UrtdI ; 2 x IrtdI
briefly: 4 x UrtdI/1s; 50 x IrtdI/1s
Mximum: 250A/1s

0...1/5/10/20mA, 4...20mA
(others on consult)
1,5 IrtdI, UrtdI. 25V
RC = infinite
Rc=
15.000(mV)

max. output signal (mA)


f.ex.: Rc=750 for 20mA
To calculate RC use 7.500mV
instead of 15.000mV, the results will be the
same for both outputs
0...10V; Rc500 (others on consult)
0,5% (peak to peak)

85...265Vca and 90...300Vcc


20...60Vca/Vcc
consumption 4VA approx

Transducer ETM 15

DATA SHEET - N00300

For alternating current or voltage

Influence magnitudes
Error Limit

Reference conditions
Input:

Frequency:
Form factor:
Auxiliary power supply :
Load:
Ambient temperature
Heat up time:
Additional error above
1,2IErtdI ou UrtdI
Linearity deviation
Load
Temperature
Auxiliary power supply
Response time
External magnetic fields
Radio frequency
interference

Construction and mounting

0,5% (normal)
0,25% (optional)

Type
Housing

Case
Base and cover of plastic

U I = UrtdI
II = 0...IrtdI
for sinusoidal
electrical magnitudes without
zero displacement
frtd 2%
1,111
UAX 2%
0,5RC max.
25C 2K
20 min. approx.

Fastening

Surface mouting with two screws M4, or using


DIN rail.
Frontal terminals for eye and fork type cable
sgoes

0,2%
0,2% (included in error limit)
RC = 0....RC max.
0,05%
(included in error limit)
0,2% /10 K; rated
temperature 25C
0,05% within the permitted
tolerance range for the supply
voltage
200 ms
0,5%
for field intensity of
0,4 kA/m
0,5% between 27...460MHz
at a distance 1m; power 1 W
0,5% entre 27...460MHz
distncia 1m; potncia 1 W

Electrical test

Uax 85V 2,5KV/1mim; 60Hz (for all circuits mutually).


Uax 60V 2,5KV/1mim; 60Hz (for all circuits mutually).
Pulse voltage
Peaks

Pgina 2/4
july 2005

5kV; 1,2/50us; 0,5Ws


2,5kV;1MHz; 400 pulses / 1s

Electrical
connection
Protection
class
(NBR 6146)
Weight

IP 50 in housing
IP 20 at the connection terminals
0,7 kg approx

Climatic conditions

Operation temperature
Functioning temperature
Transport and storage temp.
Relative humidity

Mechanical test
Mecnicos

Impact
Vibration

-20...+60C
-25...+70C
-40...+80C
75% of anual average with light
condensation
(others on consult)

acceleration 30g during 11ms


acceleration 2g frequency
5..150Hz

Notes:
Related to the final outuput value.
UrtdI = Reted voltage
IrtdI = Rated Current
Response times below 200ms result in bigger residual ripple.

Transducer ETM 15

DATA SHEET - N00300

For alternating current or voltage

Pgina 3/4
july 2005

Additional information

Electric Connections

II
I I , UI
UAx
O1
O2

2
UI
=
=
=
=

13 14
UAX

+ _ + _
61 62 63 64
O1

O2

Input Current or Voltage


Auxiliary power supply
Current or voltage output - normal
Output with load divider (double output)
optional

Notes:
When using only O2 jump terminals 61 and 62
When using double output, there is no galvanic isolation
between the output signals.

Dimensional Drawing
Dimensions in mm

The following items contain tips and cautions to be observed by the user
for a good functional performance, as well as the maintenance of the
instrument and the safety of the installations.

Cautions

Be sure the voltages and currents to be connected to the instrument, are


compatible.
Loosen all connections from the instrument before removing it from the
installation .

Mounting Instructions

Oserve the ambient temperature range. At the place of installation, values


for vibration, dust, dirt and humidity, which must remain between the
limits, established by the protection class of the housing and the climatic
group, specified in this data sheet, have to be observed
.
For fastening on flat area use two M4 screws. For mounting on DIN rail,
use the snap-in device on the rear of the instrument.
The connections can be made with eye or fork type cable shoes.

Instructions for use

When connections have been made, switch on the power supply and
check at the output the functioning of the transducer.
For quoting and ordering please issue your order according to the
specification text.
Example:
Transducer ETM 15
Rated frequency:
Measuring range:
Auxiliary power supply:
Output signal:
Optional:
Additional information:

60Hz
05A
220Vac
420mADC
Error limit 0,25%
Standard

Code number: N003002804511

Transducer ETM 15

DATA SHEET - N00300

For alternating current or voltage

Pgina 4/4
july 2005

Ordering information
Catalog number
TRANSDUCER ETM-15 for alternated current or alternated voltage

Housing
Normal
RMS

0
1

Rated Frequency
50 Hz
60 Hz
400 Hz
Others

1
2
3
0

Measuring range:
Voltage: between 0...10 up to 0..20VAC
between 0...21 up to 0...50VAC
between 0...51 up to 0...97VAC
between 0...98 up to 0...180VAC
between 0...181 up to 0...340VAC
between 0...341 up to 0...600VAC
Current: 0...1A
0...5A
Others
Auxiliary Power Supply
2060Vca/Vcc
85265Vca and 90300Vcc

1
2
3
4
5
6
7
8
0
12
13

Output Signal
0...1mADC
0...5mADC
0...10mADC
0...20mADC
4...20mADC
0...10VDC
Others( 0...1mAdc at 20mAdc e 0...1Vdc at 0...15Vdc)
Optional
Error Limit 0,25%
Output with load divider (double output)
Others response times between 50ms and 2s
Standard (Class 0,5%)
Additional information
Standard
Complement (Inform input signal voltage)

ABB Ltda - ATLV/IE Instrumentation Electrical