Vous êtes sur la page 1sur 62

1 July 2010

Application guidelines for


selected fluid power components
Accumulators
Cylinders
Hydraulic valves
Pneumatic filters, regulators and lubricators
Selection of position transducers

published by

NATIONAL FLUID POWER ASSOCIATION, INC.


3333 N. Mayfair Road / Milwaukee, WI 53222-3219 USA
PHONE: +1 414 778 3344 / FAX: +1 414 778 3361 / E-mail: nfpa@nfpa.com

Copyright 2010 by the


NATIONAL FLUID POWER ASSOCIATION
Printed in the USA
All standards, recommended practices, information reports, and bibliographies (collectively, NFPA
Documents) are advisory only. Use thereof by anyone for any purpose is entirely voluntary and in any
event without risk of any nature to the National Fluid Power Association (NFPA), its officers, directors
or authors of such work. There is no agreement by or between anyone to adhere to any NFPA
Document. In formulating and approving NFPA Documents, NFPA and/or its councils and committees
will not investigate or consider citations, references or patents which may or may not apply to such
subject matter since prospective users of such NFPA Documents alone are responsible for establishing
necessary safeguards in connection with utilization of such matters, including technical data,
proprietary rights or patentable materials.
The information and data contained in NFPA Documents has been obtained from sources believed to
be reliable. However, it should not be assumed that all acceptable or applicable sources of
information, procedures, methods or techniques are contained in NFPA Documents, or that additional
measures may not be required under certain circumstances or conditions.
NFPA Documents and/or policies and procedures are subject to periodic review and may be changed
without notice. NFPA Documents are only current as of their publication date. NFPA Documents, after
publication, may be revised or withdrawn at any time and current information on all NFPA Documents
may be received by calling or writing NFPA. Additionally, the various codes and regulations referenced
in NFPA Documents may be amended from time to time and it should not be assumed that the
versions referenced therein are the most current versions of such codes and regulations. Please
consult the appropriate regulatory authorities for the most up-to-date versions.
NFPA Documents imply a consensus of those substantially concerned with their scope and provisions
and are intended as a guide to aid the manufacturer, the consumer and the general public. The
publication of NFPA Documents does not in any respect preclude anyone, whether they have
participated in the development of or approved such NFPA Documents or not, from manufacturing,
marketing, purchasing, or using of products, processes or procedures not conforming to the NFPA
Documents. NFPA Documents do not constitute or indicate a warranty of any sort, express or implied,
including but not limited to a warranty or representation as to quality, merchantability or fitness for a
particular use or purpose.
Participation by federal agency representative(s) or person(s) affiliated with the industry is not to be
interpreted as government or industry endorsement of an NFPA Document(s).
NOTICE
NFPA Documents do not express or imply any judgment, certification or endorsement of or with respect
to, the safety, design or performance of any product, component, or its use.
NFPA does not examine, investigate, test, recommend, or certify the design, use or safety of any
product or component, even those which may incorporate one or more NFPA Documents. NFPA
Documents therefore have no application to and do not express or imply any recommendation,
representation or warranty, with respect to the safety, design, use, performance, or functional
interchangeability of components or products which incorporate NFPA Documents.
This publication may not, in whole or in part, be reproduced, copied or disseminated, entered into or
stored in a computer database or retrieval system, or otherwise utilized without the prior written
permission of NFPA.

Application guidelines Table of contents

Application guidelines for selected fluid power


components

Table of contents
Accumulators
Cylinders

...

page 1

page 9

Hydraulic valves

Pneumatic filters, regulators, lubricators


Selection of position transducers

.....

page 21
page 31
page 39

Application guidelines - Accumulators

Application guidelines Accumulators

Introduction
In fluid power systems, power is transmitted and controlled through a fluid (liquid or gas) under pressure within an
enclosed circuit.
An accumulator is defined as a device for storing hydrostatic energy and subsequently releasing it to do useful work.
The energy can be stored in the form of a compressed spring, lifted weight or compressed gas. By far the compressed
gas (which must be an inert gas such as nitrogen) is the most common and is the type discussed in this document. This
type is called a hydropneumatic accumulator. This is defined as an accumulator in which compressed gas applies force
to the stored liquid.

Scope

This recommended practice applies to bladder, diaphragm, and piston types of accumulators for their use in fluid power
systems for industrial, marine, and mobile applications.

Normative references

The following normative documents contain provisions which, through reference in this text, constitute provisions of the
Application guidelines Accumulators section (pages 1-7) of this NFPA document. For dated references, subsequent
amendments to, or revisions of, any of these publications do not apply. However, parties to agreements based on this
NFPA document are encouraged to investigate the possibility of applying the most recent editions of the normative
documents indicated below. For undated references, the latest edition of the normative document referenced applies.
NFPA maintains registers of currently valid NFPA Standards. Standards development organization contact information
and links can be found on the NFPA website (www.nfpa.com).
EN 982 (latest edition), Safety of machinery Safety requirements for fluid power systems and their components
Hydraulics.
ISO 4413 (latest edition), Hydraulic fluid power General rules relating to systems.
ISO 5598 (latest edition), Fluid power systems and components Vocabulary.

Definitions

For the purposes of this recommended practice, the terms and definitions given in ISO 5598 apply.

Application guidelines - Accumulators

Accumulator types

The following is a description of commonly used hydropneumatic accumulators. For their official definitions see
ISO 5598.
a)

A bladder accumulator is an accumulator in which the liquid and gas are separated by an elastic bag or bladder.

b)

A diaphragm accumulator is an accumulator in which the liquid and gas are separated by a flexible diaphragm.

c) A piston accumulator is an accumulator in which the liquid and gas are separated by a floating piston.
d) A nonseparator accumulator is an accumulator in which the compressed gas operates directly on liquid within the
pressure chamber. This type of an accumulator is not normally recommended because of safety reasons.
Standards such as ISO 4413 state that circuits incorporating accumulators shall vent the accumulator liquid
pressure or shall positively isolate the accumulator when the equipment is shut off.

General

5.1 A hydropneumatic accumulator works by storing energy in the form of a compressed gas. Normally this is an inert
gas such as nitrogen. The accumulator is initially charged with some amount of gas pressure (the actual value of this
pressure depends on the application); see Figure 1. At some point in the machine cycle, a pump will typically push
hydraulic fluid into the hydraulic fluid side of the accumulator. At this point, the separator (a bladder, diaphragm or
piston) will compress the gas to the same pressure as the hydraulic fluid; see Figure 2.
Separator

Gas precharge
As charged

Figure 1 Accumulator empty of hydraulic fluid and containing some amount of gas precharge
Separator

Hydraulic
fluid

Gas
pressure

Maximum operating pressure

Figure 2 Accumulator charged with hydraulic fluid at maximum system pressure


5.2

When hydraulic fluid flow from the accumulator is required, a valve in the hydraulic system will direct the fluid to
the component or components while the expanding gas pushes on the separator, expelling the hydraulic fluid
from the accumulator. The pressure of the hydraulic fluid coming from the accumulator will follow the
thermodynamic laws as applied to the expanding gas on the other side of the separator. Since the gas volume is
not infinite, the hydraulic pressure will drop as an accumulator is discharged; see Figure 3.

Application guidelines - Accumulators

Separator

Hydraulic
fluid

Gas pressure
Minimum required system pressure
NOTE All of the hydraulic fluid has not been expelled. It is considered a good practice to maintain some fluid in the accumulator
at the end of the discharge cycle for longer accumulator life.

Figure 3 Accumulator, after it has been discharged and system is at minimum required system pressure
5.3

The general gas law for expansion or compression of a gas is described by the following equation:

P1 V1n = P2 V2n

where
P1

is the initial pressure;

V1

is the initial volume;

P2

is the final pressure;

V2

is the final volume;

is the polytropic exponent.

5.4 If an accumulator is discharged very slowly (this is seldom the case), the polytropic exponent is the isothermal
exponent and is equal to 1.0. However, if the discharge is rapid, this value will be closer to the adiabatic exponent and
is greater than 1.0. For nitrogen this factor will vary depending on several operating conditions. Consult your
accumulator supplier for specific applications. The gas pressure may also vary when an accumulator is charged based
on the rate at which it is charged. Again, consult your accumulator supplier for specific applications.
5.5 On occasions, especially when the operation requires the maximum and minimum operating pressures to be
close to each other a large amount of gas volume may be required. An auxiliary gas bottle may be used as shown in
Figure 4.

Application guidelines - Accumulators

Auxiliary gas bottle

Gas pressure
Separator
Gas pressure
Hydraulic fluid

Figure 4 Illustration of an auxiliary gas bottle used with a hydropneumatic accumulator.


5.6 Hydropneumatic accumulators are considered pressure vessels and, as a result, they may be subject to certain
laws. Each state in the U.S. as well as each province in Canada has laws concerning pressure vessels. Foreign
countries also have laws concerning pressure vessels.
5.7 Several national and international standards cover the application of an accumulator such as ISO 4413 and
EN 982. Other industries may have their own standards.

Applications

6.1

General

Accumulators are used to store or absorb energy. Typical applications are:


a) energy storage;
b) pulsation dampening;
c) compensation for thermal expansion;
d) hydraulic shock suppression.

6.2

Energy storage

6.2.1

Supplementing pump flow

6.2.1.1
In cases where relatively high actuator velocities are required with dwell time between cycles, it is possible
to use an accumulator in conjunction with a pump to make a more efficient system. During the dwell time in the cycle,
the pump charges the accumulator. Then when the actuator is activated, both the accumulator and the pump supply
fluid under pressure to the actuator.
6.2.1.2

Minimum information required for this application:

a) maximum hydraulic fluid pressure required at actuator;


b) minimum hydraulic fluid pressure required at the actuator;
4

Application guidelines - Accumulators

c) hydraulic fluid flow rate and volume required by actuator or actuators;


d) pump displacement (volumetric);
e) dwell time.
6.2.2

Leakage compensation

6.2.2.1
Hydraulic valves and cylinder pistons may have some internal leakage. In some applications, it may be
desirable to make up this leakage by using an accumulator. This is possible as long as there is some dwell time in the
machine cycle so that the pump can recharge the accumulator.
6.2.2.2

Minimum information required for this application:

a) maximum hydraulic fluid pressure required at actuator;


b) minimum hydraulic fluid pressure required at the actuator;
c) expected leakage volume;
d) pump displacement (volumetric);
e) dwell time.
6.2.3

Emergency (auxiliary) power source

6.2.3.1
Certain equipment may require some sort of stored energy to be used in an emergency. In such cases, an
accumulator is charged with hydraulic fluid that can be relieved manually or electrically in an emergency.
6.2.3.2

Minimum information required for this application:

a) maximum hydraulic fluid pressure required;


b) minimum hydraulic fluid pressure required at the actuator;
c) hydraulic fluid flow rate and volume required by actuator or actuators.

6.3

Pulsation dampening

6.3.1 Positive displacement pumps, especially piston type, generate hydraulic flow that may exhibit pressure ripple,
which is not always desirable. The exact amount of ripple depends on pump displacement, pressure and number of
pumping chambers. Accumulators can be used to smooth out these pressure ripples.
6.3.2

Minimum information required for this application:

a) pump displacement (volumetric);


b) number of pumping chambers in pump;
c) rotational speed of pump;
d) system pressure.

Application guidelines - Accumulators

6.4

Compensation for thermal expansion

6.4.1 Thermal expansion, if not compensated for in a closed loop hydraulic system, can increase pressure beyond
acceptable limits. Accumulators absorb the volume increase and return fluid to the line when the temperature falls.
6.4.2

Minimum information required for this application:

a) type of hydraulic fluid;


b) fluid conductor material;
c) volume of contained fluid;
d) normal operating temperature;
e) maximum operating temperature;
f)

normal operating pressure;

g) maximum operating pressure.

6.5

Hydraulic shock suppression

6.5.1 When valves open and close quickly, they can generate shock waves in a hydraulic system. Both shock and
vibration can generate noise and also lead to premature wear and tear on machine components. Accumulators have
relatively good damping characteristics over a wide frequency range that effectively reduces shock and vibration.
6.5.2

Minimum information required for this application:

a) flow rate in hydraulic lines;


b) specific gravity of hydraulic fluid;
c) length and size of hydraulic lines;
d) valve closing time;
e) operating pressure;
f)

maximum operating pressure.

Ports

It is suggested that the port at the hydraulic end of the accumulator be of a type that is sealed by an elastomer rather
than an interference fit, such as a pipe thread port. It is also suggested that the port size be sufficiently large for the
required fluid flow rate out of the accumulator.

Environment

Accumulators contain static seals as well as dynamic seals in the separator. These seals, which are available in several
compounds, are exposed to the operating condition of the accumulator as well as the hydraulic fluid. Seal selection

Application guidelines - Accumulators

should be done together with the accumulator manufacturer, taking into account the maximum and minimum operating
temperature and hydraulic fluid used.

Corrosion

Accumulators are considered pressure vessels. As a result, corrosion, both internal and external, should be taken into
account. Internal corrosion that can be caused by the hydraulic fluid will both weaken the pressure vessel and damage
the separator. External corrosion will weaken the pressure vessel. Therefore, the environment to which the accumulator
is exposed must be considered. Some codes also require that a corrosion allowance be addressed in the stress
calculations related to the pressure vessels.

10 Mountings
An accumulator should be securely mounted to a machine frame. The hydraulic plumbing should not be the sole
method by which the accumulator is secured to a machine frame. Care should be taken not to squeeze the body of
piston accumulators by overtightening U-bolt type brackets. Your accumulator supplier should be consulted for the
proper method of securing the accumulator to the machine frame, as well as its orientation.

11 Precharge pressure
11.1 Each specific application shall be accomplished most effectively with a specific value of precharge pressure. The
specific value shall be determined by the system operating conditions. Variation from this pressure will cause the
system to degrade in performance. Since the precharge pressure is gas pressure in a contained vessel, it will vary as a
function of temperature, i.e., if the gas temperature increases, the pressure will increase, and if the gas temperature
decreases, the pressure will decrease.
11.2 In a typical hydraulic system, the operating temperature of the accumulator is usually higher than the temperature
of the surrounding environment. When checking the precharge pressure, it is important to determine the temperature of
the gas. It is easiest to check the pressure when the equipment has been shut down for some time and the gas
temperature has stabilized to the temperature of the surrounding environment. Also, shutting down the equipment may
remove all hydraulic fluid from the accumulator, which will affect the gas precharge pressure value. Therefore, it is
important to know how the precharge pressure in this condition will translate to a gas pressure at operating conditions.
The accumulator supplier can help to determine these two values.

12 Maintenance
12.1 An accumulator should be charged only with an inert gas, such as nitrogen.
12.2 Charging of an accumulator or the periodic checking of proper precharge pressure should be done only in
accordance with the accumulator manufacturers instructions and using only components specified by the accumulator
manufacturer.
12.3 Any repair to an accumulator shall be done after it has been relieved of liquid and gas precharge pressure and
removed from the hydraulic system. The discharging, removal and repair shall be done by a properly trained person
following procedures specified by the accumulator manufacturer.

Application guidelines - Cylinders

Application guidelines Cylinders

Introduction
In fluid power systems, power is transmitted and controlled though a fluid under pressure within an enclosed circuit. The
application of hydraulic and pneumatic cylinders requires precise communication between manufacturer and user. It is
the intent of this recommended practice to provide basic guidance in cylinder applications and to promote
communication. Users of this recommended practice are cautioned, however, to review each clause for applicability
and to utilize sound engineering judgement

1 Scope
This recommended practice will apply to hydraulic and pneumatic fluid power cylinders for their use in hydraulic and
pneumatic systems for industrial, marine, and mobile applications.

2 Normative references
The following standards contain provisions which, through reference in this text, constitute provisions of the Application
guidelines Cylinders section (pages 9-20) of this NFPA document. At the time of publication, the editions indicated
were valid. All documents are subject to revision, and parties to agreements based on this NFPA document are
encouraged to investigate the possibility of applying the most recent editions of the documents indicated below. NFPA
maintains registers of currently valid NFPA standards.
NFPA/T3.6.7 R1-1996, Fluid power systems and products Square head industrial cylinders Mounting dimensions.
ISO 5598:1985, Fluid power systems and components Vocabulary.

3 Definitions
A description of different types of cylinders is given in this document several times. For their official definition as well as
definition of other terms see ISO 5598.

4 Operation and cylinder concepts


Cylinders are used when linear force and motion are required. Cylinders are broken down into two main categories:
pneumatic and hydraulic. Pneumatic cylinders can be operated by several types of gases, however, compressed air is
by far the most common. Hydraulic cylinders can be operated with a very large range of fluids. By far the most common
is petroleum based hydraulic fluid. Fire-resistant fluids are also common, they may be synthetic or water based.

Application guidelines - Cylinders

Cylinders can be broken down into two main components. The pressure containing envelope and the piston and rod
assembly. Typically the pressure containing envelope is fixed on the machine and the piston and rod assembly is
attached to the machine member on which motion and force need to be applied. In rare occasions the opposite is done.
See figure 1.
Pressure
containing
envelope

Piston and Rod


assembly

Motion

Figure 1 Typical cylinder


4.1 Force.
The amount of force applied to the machine member is the product of the fluid pressure multiplied by the effective area
of the piston. Most cylinders contain a single piston rod. Assuming a constant value for the applied pressure, a cylinder
would normally exert more force in the push stroke than it will in the retract stroke. The amount by which the retract
force is less than the extend force depends on the cross-sectional area taken up by the piston rod. See figure 2.
For example, a 100 mm bore (10 cm) cylinder housing a 45 mm (4.5 cm) diameter piston rod operating at 1,000
kilopascals (1,000 kPa) will deliver 7,854 neutons (N) of force in the push direction and 6,264 N in the pull direction.
2
2
Example: one neuton (N) of force = one pascal (Pa) applied to an area one meter square (M ). N=Pa M
Calculation for push stroke surface area =
Calculation for pull stroke surface area =
2

An area of 78.54 cm = 0.007854 M

D bore
2

(D bore - D rod)

F p ull
2

In push direction force (N) = 1,000 kPa x 0.007854 M =7,854 neutons


2

In pull direction force (N) = 1,000 kPa x 0.006264 M =6,264 neutons

10

F p ush

Application guidelines - Cylinders

10 cm Dia piston

Area = 78.54 cm

Area = 62.64 cm

4.5 cm Dia. Piston rod

Figure 2 Effective areas


4.2 Velocity
The velocity at which the piston and rod assembly moves is dependent on the rate at which the fluid is introduced into
the cylinder. Normally a cylinder is connected to a directional valve and sometimes flow control valves. In a pneumatic
system the maximum speed of the piston and rod assembly is dependent on the rate at which the air can flow through
the valving. For a hydraulic cylinder, the maximum piston rod velocity depends on the ability of the hydraulic system to
provide the hydraulic fluid to the cylinder. In most applications piston rod velocity is held in the .3 to .9 m/s. However,
velocities up to 3 m/s have been achieved. See figure 3.

11

Application guidelines - Cylinders

Hydraulic circuit

Pneumatic circuit

Figure 3 Hydraulic and pneumatic circuits

5 Basic construction
The following three types of construction are the more commonly used types of cylinders.

5.1 Square head tie rod


This is a very common type of cylinder used in industrial applications. Head and cap enclosures are secured by tie rods
that run the length of the cylinder. See figure 4.

12

Application guidelines - Cylinders

Figure 4 Square head tie rod cylinder

5.2 Bolted end


These cylinders have flanges that are attached to the barrel. The end caps are attached to these flanges with bolts. See
figure 5.

Figure 5 Bolted end


5.3 Nonbolted end
This type of cylinder has end caps that are usually retained by welding or with a locking ring. In many cases these are
used for mobile applications. Some pneumatic cylinders crimp the tube onto the end caps. See figure 6.

Figure 6 Nonbolted end

6 Types of cylinders
Double acting, single piston rod cylinders are by far the most common types of hydraulic and pneumatic cylinders used
in industry. However, there are other configurations which are used in special situations.

6.1 Double acting


By far, most cylinders are considered double acting. That is, when the cylinder is required to extend, pressure is applied
to the cap end of the cylinder while pressure is exhausted from the rod end. When the cylinder is required to retract,
pressure is applied to the rod end and the cap end is exhausted. See figure 7.

13

Application guidelines - Cylinders

Fluid flow

Fluid flow

Thrust

Fluid flow Fluid flow

Thrust

Figure 7 Double acting


6.2 Single acting
In these types of cylinders pressure is applied only to one side of the piston, and some other force is used to move the
piston and rod assembly in the opposite direction. In some cases it may be gravity; however, in most cases this is
accomplished by a spring. Springs can be mounted on either side of the piston. However, most commonly a spring is
mounted on the rod end of the piston and is used to retract the cylinder. Springs can be mounted in either hydraulic or
pneumatic cylinders. Normally the mechanical force provided by a spring is rather small in comparison to the potential
force which a hydraulic cylinder can apply. Therefore, most single acting cylinders tend to be pneumatic. See figure 8.
Fluid flow
Spring

Figure 8 Single acting


6.3 Double rod
Double rod cylinders can be used so that the applied load to the machine member is the same in both directions.
Sometimes a smaller rod is used on one end to trip limit switches. See figure 9.

Figure 9 Double rod end


6.4 Ram cylinders
The rod and piston are the same diameter. This type of cylinder is usually single acting, with an external force used to
retact the cylinder. A typical application is a lift in a service station. See figure 10.

14

Application guidelines - Cylinders

Figure 10 Ram
6.5 Telescopic cylinders
Telescopic cylinders utilize multiple sections to achieve long strokes when short collapsed lengths are required. This
type of configuration is sometimes used in cylinders for dump trucks or lift trucks. These are usually single acting. The
net force is a function of the smallest section. See figure 11.

Figure 11 Telescopic
6.6 Tandem cylinders
Tandem cylinders consist of two pistons attached to a common piston rod. These cylinders are used in situations where
space requirements are very tight and the combined areas of two pistons can be applied to one piston rod. These are
used to increase force. In some cases such as a press, a tandem cylinder is constructed of a large press cylinder with a
small cylinder attached to the back. This configuration is used where the smaller bore cylinder is pressurized to rapidly
advance the larger cylinder. See figure 12.

Figure 12 Tandem
6.7 Duplex cylinders
Duplex cylinders consist of multiple piston and rod assemblies which are not connected to each other. This
configuration is often used where more than two distinct stopping points are required. See figure 13.

or

Figure 13 Duplex
6.8 Rodless cylinders
These cylinders are typically used when limited space prohibits the use of a cylinder with a piston rod.

15

Application guidelines - Cylinders

6.8.1 Direct coupled


The carriage and piston are directly connected. See figure 14 .
Carriage

Piston

Figure 14 Direct coupled


6.8.2 Magnetically coupled
The carriage is and piston are magnetically coupled. See figure 15.
Carriage

Piston

Figure 15 Magnetically coupled


6.8.3 Cable connected
The carriage is connected to the piston by a cable or flexible band. See figure 16.
Carriage

Fluid
flow

Motion

Piston

Cable/band

Fluid
flow

Figure 16 Cable connected

16

Application guidelines - Cylinders

7 Mounting
7.1 Fixed and pivot
The pressure containing envelope is normally mounted to the machine. This is normally done with one of two types of
mounting configurations. A fixed type mounting or a pivot type mounting. If the machine member moves in a straight
line type motion, a fixed mount can be used. If the machine member is required to move in an arc a pivot mounting
must be used. See figure 17.

Fixed mount

Pivot mount

Figure 17 Fixed and pivot mounts


7.2 Types
Fixed mounts are available in many configurations. Typical mountings may be front or rear flange mountings, tie rod
extended mounts, or foot mounts. Pivot mounts can be head, cap or center trunnions, or a rear cap pivot mount. For a
more complete list of the mounts, consult the manufacturer or NFPA/T3.6.7. See figure 18 for some examples.

Figure 18 Typical mounts

17

Application guidelines - Cylinders

7.3 Mounting enhancements


Selection of any mounting style depends primarily upon the operating specifications of the application. Cylinder
mounting directly affects the maximum operating pressure at which the cylinder may be used. Whether the cylinder is
used in thrust (push) or tension (pull), its stroke length, piston rod diameter and method of connection to the load must
be considered when selecting a mounting style.
Fixed mountings that absorb the force on the centerline of the cylinder are considered the best for straight line force
transfer. The symmetrical mountings allow the thrust or tension forces to be distributed uniformly within the mounting
framework. Flange mounts are considered the best mounting styles within this category. Front flange mounts are ideally
suited when the piston rod is in tension (pull), while cap flanges are recommended for thrust (push) applications.
Fixed noncenterline mountings do not absorb forces on their centerline. The offset thrust introduces bending stresses
and additional loads on the mounting bolts. This is especially true in short stroke applications. This type should be very
well aligned for maximum service life. Use of shear pins or keys should be considered when these cylinders are
subjected to high pressures or shock loads. These mountings are among the easiest to use for mounting and
replacement ease.
If the path of the load is curved or misalignment is a problem, a pivoted centerline mounting should be used. These
mounts offer compensation for non-linear travel in only one plane. Pivot mounts require a pivot type rod attachment.
Threaded rod end attachments should be torqued tightly against a threaded shoulder to minimize bending and reduce
fatigue stresses.

8 Design considerations
8.1 Column strength
Piston rod column failure (buckling) can occur if the rod diameter is not sized to match the stroke and load. The
manufacturer should be consulted for application assistance. Reference figure 19 for an example of piston rod column
failure.

Figure 19 Piston rod column failure


8.2 Bearing load
Cylinders are normally intended to push and pull without excessive side load. If a side load exists, the manufacturer
should be consulted. Usually bearing load can be reduced with the addition of a stop tube. The use of a stop tube
increases the distance between the piston bearing and piston rod bearing. See figure 20.
Piston bearing

Stop tube
Piston rod
bearing

Figure 20 Stop tube

18

Application guidelines - Cylinders

8.3 Cushions
The purpose of a cushion is to decelerate the piston and rod assembly as it nears the end of stroke, preventing
excessive mechanical stresses. Cushions may be of either a fixed or adjustable design. Both designs function by
providing a bypass passage to remove the pressurized fluid trapped between the piston and the cylinder head when the
cushion sleeve has entered the cushion bore. Varying the orifice opening with an adjustable cushion screw allows the
user to select the best cushion rate for the system. A check valve in the cushion assembly allows for the free flow of
fluid back to the piston face for quick acceleration when the rod is withdrawn. Heavy loads may also require an external
device to stop the motion. Cushions are available on either or both ends of the cylinder. Consult manufacturer for the
conditions under which cushions should be used. See figure 21.
Fluid
flow

Piston rod motion

Figure 21 Cushions
8.4 Eccentric Loads
A very important general consideration is to keep the cylinder thrust as close as possible to the centerline of the piston
rod and free from misalignment or side thrust. Off-center thrust or side loads can substantially reduce the service life
expected from the rod bearing and seals. Off-center thrust and side loading can be caused by cylinder deflection under
load, machine frame deflection, rod bending or sagging, as well as by poor design of the machine. See figure 22.

Piston rod centerline

Applied load

Figure 22 Eccentric Loads

9 Compatibility
The temperature and fluid type must be considered in any application to ensure proper seal effectiveness and life. The
manufacturer should be consulted for assistance.

10 Corrosion
Surfaces of either hydraulic or pneumatic cylinders can be corroded by water or other substances. Although paint may
be suitable protection against corrosion for most indoor industrial uses, the cylinder specifier should be aware of
corrosion potential in the operating environment. The material content and surface preparation of the piston rod must
be considered in any application where a corrosive environment exists. Consult the cylinder manufacturer for corrosion
protection recommendations.

19

Application guidelines - Cylinders

11 Maintenance
Cylinder maintenance primarily involves replacing seals and/or bearings. Consult the manufacturer for maintenance
guidelines.
11.1 Visual inspection
Degradation of cylinder thrust or erratic motion can indicate seal leakage. Prior to disassembly, visual inspection can be
performed on the rod seal and tube end seals. This is accomplished by inspecting these locations for either oil or
escaping air depending on whether the cylinder is hydraulic or pneumatic. Inspection of the piston seals and bearing
require disassembly.
11.2 Disassembly
Prior to performing any maintenance that requires the disassembly of the cylinder, the pressure within the cylinder must
be zero. The machine manufacturer should be consulted for any lock-out requirements.
Follow the cylinder manufactures recommended disassembly and reassembly procedures, paying particular attention
to prescribed fastener torque values and internal springs. While the cylinder is disassembled, inspect all components
for evidence of unusual wear. Signs of internal corrosion may indicate the presence of water or lack of lubrication. Signs
of contamination may indicate improper filtration. Proper preventative maintenance will extend seal and bearing life.
Wear can be caused by misalignment of the cylinder and load, or other problems that should be remedied before the
cylinder is returned to service.
11.3 Preventative maintenance.
Preventative maintenance such as hydraulic oil filtration and compressed air filtration/drying will extend cylinder service
intervals.

20

Application guidelines - Hydraulic valves

Application guidelines Hydraulic valves

Introduction
In hydraulic fluid power systems, power is transmitted and controlled through a liquid under pressure within an enclosed
circuit. The application of hydraulic valves requires precise communication between manufacturer and user. It is the
intent of this recommended practice to provide basic guidance in valve application and to promote communication.
Users of this recommended practice are cautioned, however, to review each section for applicability and to utilize sound
engineering judgment.

1 Scope
1.1 This recommended practice is applicable to hydraulic valves used in industrial, marine and mobile equipment.
1.2 This recommended practice provides basic guidance for the selection, installation, operation, and maintenance of
hydraulic valves.

2 Normative references
The following normative documents contain provisions which, through reference in this text, constitute provisions of the
Application guidelines -- Hydraulic valves section (pages 21-29) of this document. For dated references, subsequent
amendments to, or revisions of, any of these publications do not apply. However, parties to agreements based on this
NFPA document are encouraged to investigate the possibility of applying the most recent editions of the normative
documents indicated below. For undated references, the latest edition of the normative document referenced applies.
NFPA maintains registers of currently valid NFPA Standards. Standards development organization contact information
and links can be found on the NFPA website (www.nfpa.com).
NFPA/T2.6.1 R2-2001 (R2005), Fluid power components Method for verifying the fatigue and establishing the burst
pressure ratings of the pressure containing envelope of a metal fluid power component
NFPA/T2.24.2 (latest edition), Hydraulic fluid power systems Methods for preventing external leakage.
NFPA/T3.5.1 (latest edition), Hydraulic fluid power Valves Mounting surfaces.
NFPA/T3.5.14 (latest edition), Hydraulic fluid power Directional control valves Method for determining the

metering characteristics.
NFPA/T3.5.15 (latest edition), Hydraulic fluid power Valves Method for determining the internal leakage
characteristics.
NFPA/T3.5.16 (latest edition), Hydraulic fluid power Flow control valves Method for measuring and reporting

regulating characteristics.
NFPA/T3.5.26 R2-2000 (R2005), Hydraulic valve Pressure rating supplement to NFPA/T2.6.1 R2-2000 Method for
verifying the fatigue and burst pressure ratings of the pressure containing envelope of a metal fluid power hydraulic
valve

21

Application guidelines - Hydraulic valves


IEEE/ASTM SI 10 (latest edition), Standard for Use of the International System of Units (SI): The Modern Metric

System.
ISO 1000 (latest edition), SI units and recommendations for the use of their multiples and of certain other units.
ISO 1219-1 (latest edition), Fluid power systems and components Graphic symbols and circuit diagrams Part 1:
Graphic symbols for conventional use and data processing applications (second edition)
ISO 1219-2 (latest edition), Fluid power systems and components Graphic symbols and circuit diagrams Part 2:

Circuit diagrams
ISO 4401 (latest edition), Hydraulic fluid power Four-port directional control valves Mounting surfaces.
ISO 4406 (latest edition), Hydraulic fluid power Fluids Method for coding level of contamination by solid particles.
ISO 5598 (latest edition), Fluid power systems and components Vocabulary.
ISO 6149-1 (latest edition), Connections for hydraulic fluid power and general use Ports and stud ends with ISO 261

metric threads and O-ring sealing Part 1: Port with truncated housing for O-ring seal (second edition)
ISO 6149-2 (latest edition), Connections for hydraulic fluid power and general use Ports and stud ends with ISO 261

threads and O-ring sealing Part 2: Dimensions, design, test methods and requirements for heavy-duty (S series) stud
ends (second edition)
ISO 6149-3 (latest edition), Connections for hydraluic fluid power and general use Ports and stud ends with ISO 261
threads and O-ring sealing Part 3: Dimensions, design, test methods and requirements for light-duty (L series) stud
ends (second edition)
ISO 6162-1 (latest edition), Hydraulic fluid power Flange connectors with split or one-piece flange clamps and metric
or inch screws Part 1: Flange connectors for use at pressures of 3,5 MPa (35 bar) to 35 MPa (350 bar), DN 13 to DN
127
ISO 6162-2 (latest edition), Hydraulic fluid power Flange connectors with split or one-piece flange clamps and metric

or inch screws Part 2: Flange connectors for use at pressures of 35 MPa (350 bar) to 40 MPa (400 bar), DN 13 to DN
51
ISO 7368 (latest edition), Hydraulic fluid power Two-port slip-in cartridge valves Cavities.
ISO 10770-1 (latest edition), Hydraulic fluid power Electrically modulated hydraulic control valves Part 1: Test
methods for four-way directional flow control valves.
ISO 11926-1 (latest edition), Connections for general use and fluid power Ports and stud ends with ISO 725 threads

and O-ring sealing Part 1: Ports with O-ring seal in truncated housing
ISO 11926-2 (latest edition), Connections for general use and fluid power Ports and stud ends with ISO 725 threads
and O-ring sealing Part 2: Heavy-duty (S series) stud ends
ISO 11926-3 (latest edition), Connections for general use and fluid power Ports and stud ends with ISO 725 threads
and O-ring sealing Part 3: Light-duty (L series) stud ends
SAE J518 (latest edition), Hydraulic flanged tube, pipe, and hose connections, 4 bolt split flange type.
SAE J1783 (latest edition), Selection of hydraulic directional control valves for marine vehicle applications.

22

Application guidelines - Hydraulic valves

3 Terms and definitions


For the purposes of this NFPA document, the terms and definitions given in ISO 5598 apply.

4 General
4.1 Valve classifications
Hydraulic valves can be classified into four general categories based on their function. These categories are described
in 4.1.1 through 4.1.4.
Valve assemblies or subassemblies comprise components from more than one valve category, such as a directional
valve incorporating an internal pressure control valve. See ISO 1219-1 and ISO 1219-2 for hydraulic valve graphic
symbols and their use in circuit diagrams.
4.1.1

Directional control valves

Directional control valves connect or isolate one or more flow paths. They are commonly used to control speed and
direction of a hydraulic actuator. They may range from a simple two-port check valve to a multiple-port directional valve.
Application guidelines for these valves are contained in clause 5.
4.1.2

Pressure control valves

Pressure control valves are commonly used to limit or control pressure excursions of the pump or of portions of the
hydraulic circuit. They may range from direct-acting relief valves to pilot-operated counterbalance valves. Application
guidelines for these valves are contained in clause 6.
4.1.3

Flow control valves

Flow control valves are used to limit or control flow with the circuit or portions of the circuit. They may range from a
simple fixed orifice to a pressure- and temperature-compensated flow control valve. Application guidelines for these
valves are contained in clause 7.
4.1.4

Load holding valves

Load holding valves are used to prevent drift of a loaded actuator and to prevent uncontrolled movement of an actuator
due to overrunning loads. Application guidelines for these devices are contained in clause 8.

4.2 Fluids
Hydraulic fluids may range from petroleum oils to synthetics, fire resistant fluids and biodegradable fluids. Select a fluid
that is appropriate for the system and machine type and environment.
Fluid types and equipment manufacturers recommendations may vary widely among mobile, industrial, and marine
systems. Ensure that valves, including seals and electrical wiring, are compatible with the system fluid.

4.3 Fluid conditioning


Fluid filtration requirements depend upon several factors, including the type of system and components, the severity of
the application, the operating environment, and the level and frequency of maintenance. Filtration should be provided
to maintain the system fluid within the cleanliness level recommended by the valve manufacturer and system designer.
The system design and installation should minimize entrained air and other contaminants, such as water. The fluid
temperature and water content should be maintained at levels consistent with the fluid and component manufacturers
recommendations. Acceptable fluid temperature ranges will differ among mobile, industrial, and marine systems.

23

Application guidelines - Hydraulic valves

4.4 Ports
Valve ports should be of the O-ring sealed straight thread type conforming to ISO 6149-1 or ISO 11926-1, or of the
flange type conforming to ISO 6162-1, ISO 6162-2 or SAE J518. Ports with pipe threads should not be used because
of the potential for external leakage. See also NFPA/T2.24.2 for additional information on port types and their
characteristics.

4.5 Mounting
Valves are available in many different construction and mounting configurations, including:
a)

independently mounted, of monoblock, sectional, or combination block construction

b)

subplate or manifold mounted, in accordance with ISO 4401, NFPA/T3.5.1, or custom interface design

c)

cartridge design and installation, of the screw-in type in accordance with ISO 7789 or NFPA/T3.5.50, or of other
custom design.

d)

cartridge design and installation, of the slip-in type in accordance with ISO 7368, or of other custom design

e)

actuator installed or direct mounted

The function or at rest mode of some valves may be influenced by the mounting direction. Consult the manufacturer for
recommendations regarding preferred mounting.

4.6 Location
In most cases, valves should be mounted as close to the actuators as practical. Valves should also be installed so that
they are accessible for maintenance and removal. In the case of manual valves, ease of actuation shall be taken into
account.

4.7 Pressure rating and reliability


Valve selection should take into account the maximum pressure excursions in the system, the operating duty cycle, and
the expected service life. The potential for overloads, external mechanical loads, and other abnormal conditions should
be considered. Fatigue rating of the pressure containing envelope(s) of valves should be in accordance with
NFPA/T2.6.1 and NFPA/T3.5.26.

4.8 Repair and maintenance


Specific instructions for maintenance and repair should be contained in the equipment manual(s) and/or on equipment
decals. If a repair involves disassembly of a valve or its hydraulic connections, care shall be taken to ensure that the
cleanliness levels recommended in 4.3 are maintained before the valve is returned to service. Replacement fluid shall
be of the proper type and shall meet the cleanliness requirements of 4.3.

4.9 Other application considerations


Other system and application characteristics that may affect the performance or reliability of valves include:
a)

excessive vibration or shock, particularly if valves are cantilever mounted or if the system could be unstable under
certain conditions;

b)

intermittent temperature extremes, such as cold startup conditions or temporary overheating;

c)

exposure to unusual or extreme environments, such as water spray or immersion, corrosive chemicals, fine dust,
abrasive materials, etc. See SAE J1783 for marine application guidance;

d)

hazardous locations that may require explosion-proof or intrinsically safe devices.

24

Application guidelines - Hydraulic valves

5 Directional control valve application guidelines


5.1 Check (non-return) valves
Unpiloted two-port check (non-return) valves are one of the simplest forms of directional control valves, blocking flow in
one direction and allowing essentially free flow or flow at a prescribed pressure in the opposite direction. The check
valve shall be sized to provide an acceptable pressure drop at maximum flow and shall be designed to provide
acceptable internal leakage control in the blocking condition. Check valves normally are spring-biased to assist in rapid
closing, stability, and leakage control. The spring bias adds to the pressure drop in the open condition.
Three-port check valves, also known as shuttle valves, are utilized to connect the higher or lower pressure of two lines
to a third connection. Pilot-to-open and pilot-to-close check valves are also available for situations in which the check
valve must respond to an external pilot pressure. See clause 8 for a more detailed discussion of load holding valves.

5.2 Directional control valves


Directional control valves may be actuated mechanically, hydraulically, pneumatically or electrically. Electrical actuation
can be on/off or proportional. In the case of hydraulically, pneumatically or electrically piloted valves, the pilot system
shall be designed to provide satisfactory response and acceptable characteristics in the event of failure. Directional
control valves are normally spring-centered but may also contain mechanical detents, electromagnetic detents or other
devices. Valves shall be sized to provide acceptable pressure drops at maximum flow rates, recognizing that individual
ports may have different flow rates. If the internal leakage characteristics of the directional control valve are such that
actuator creep is a concern, the use of pilot-operated check valves or other blocking valves should be considered.
5.2.1

Two-port valves

Two-port spool, poppet, gate, or other mechanical valves are used to connect or disconnect two-ports. They differ from
check valves in that they are typically bidirectional when open. Internal leakage characteristics may differ from check
valves, depending upon the design.
5.2.2

Three-port valves

Three-way valves provide a means to connect and disconnect three ports. A typical application of a two-position, threeport valve is to bypass pump flow to tank in one position and to connect pump flow to an actuator in the other.
5.2.3

Four-port valves

Four-port valves provide a means to connect and disconnect four ports. A two-position, four-port valve can be used to
control an actuator in forward and reverse directions by connecting opposite actuator ports to pump flow or to tank.
Intermediate or transition characteristics of the valve may have a significant impact on pump and actuator pressures
and metering, and should be selected based on the requirements of the application.
Four-port valves are often applied in a three-position configuration, with the third (center) position providing a neutral
condition for the pump and a holding or freewheeling condition for the actuator. A holding or blocked actuator port,
center position is normally used with cylinders in order to maintain a load in position. The valve shall have internal
leakage characteristics that result in acceptable drift rates for the loaded cylinder. A freewheeling, or vented-to-reservoir
actuator port, center position is normally used with motors in order to allow the motor to coast to a stop after pump inlet
flow is disconnected, avoiding large pressure spikes. With regard to the pump, the three-position valve can be open
center, in which the pump flow is bypassed to the reservoir, or closed center, in which the pump flow path is blocked.
An open center valve is normally used with a fixed displacement pump, and a closed center valve is typically selected
for use with a variable displacement pump or a fixed displacement pump with an integral unloading device. Closed
center valves may also be load sensing, controlling a pressure and flow compensated pumps displacement by means
of a sensing line downstream of the valves metering element.
Special four-position options are also available with four-port valves. A relatively common fourth position option with
cylinders is float, in which both sides of the cylinder are connected to the reservoir (unlike the center, or holding,
position in which both ports are blocked). Regeneration, in which the supply side of the cylinder is connected to both the
pump and the return (rod) side of the cylinder, is another option. This provides faster cylinder speed, but at the expense
of available force, since the pressure is effectively only acting on the rod area of the cylinder.
25

Application guidelines - Hydraulic valves


5.2.4

Circuit types

Multi-function directional valve circuits may be of the parallel, series parallel, or series type. In a parallel circuit, the
individual control spools are connected to the valve inlet by a common passage, so that any one of the spools can
receive flow from the pump, or all spools can receive flow simultaneously. However, unless the valve is closed center
and has some means of pressure compensation, the function with the lowest load pressure will receive the flow. Series
parallel (sometimes called conventional) circuits are similar to parallel circuits except that the first spool receives all of
the flow if it is fully stroked. These circuits are utilized when it is desired to give one function priority over all of the
others. Series circuits connect the work port return flow from an upstream function to the inlet of the adjacent
downstream function, thereby ensuring simultaneous operation capability of two or more functions. However, the load
pressures of individual functions are additive in series circuits. The actuators shall be sized appropriately to move the
desired loads at less-than-full pump pressure.
Open center directional valves may also incorporate a feature known as power beyond (sometimes called high pressure
carryover), which directs pump flow to a port that can be used to supply another downstream valve. Flow is available at
the power beyond port if all of the valve spools are in their neutral positions, but if any one of the valve spools is fully
stroked, flow to the power beyond port is cut off.
5.2.5

Proportional valves and servovalves

Electrohydraulic proportional valves and servovalves offer more sophisticated directional control options, but may
require more care in their proper selection and application. Servovalves are normally higher cost, but may be
distinguished from proportional valves by their improved performance in terms of dynamic response, hysteresis,
repeatability, and threshold. Improvements in proportional valve frequency response have reduced the distinction
between proportional and servovalves based on this parameter. Manufacturers literature should be consulted for
specific data.
Probably the most common physical differentiator between proportional valves and servovalves is their spool center or
lap conditions. Servovalves are critically lapped by carefully matching the width and position of the spool lands to the
appropriate metering lands within the body. Proportional valve spools and bodies typically lack this matching, resulting
in a center overlap, and a corresponding flow deadband of up to 3% of the valving element stroke.
Proportional valves may be direct-operated or pilot-operated, and they may or may not have an internal feedback loop.
Servovalves are two-stage devices, with the first stage most commonly of the flapper nozzle, jet pipe, or jet diverter
design. Due to the relatively small orifices or clearances in these designs, servovalves normally require that they be
used in a system with finer filtration than do proportional valves.

6 Pressure control valve application guidelines


6.1 Direct-acting relief valves
Direct-acting relief valves are normally closed devices biased to the closed position by a spring. They are rapid opening
devices that can be produced in low internal leakage designs, making them suitable for shock limiting and structure
protecting applications. Back pressure in the outlet line is additive to the spring setting. Direct-acting relief valves may
exhibit considerable rise in pressure from initial opening to full opening. They will act as a fixed orifice when fully open,
so care shall be taken to avoid exceeding their rated flow. Poppet or differential area type direct-acting relief valves are
generally more tolerant of contamination.

6.2 Pilot-operated relief valves


Pilot-operated relief valves are normally closed devices biased to the closed position by a spring and by pilot pressure.
They typically do not open as quickly as direct-acting relief valves, but their flow capacity is much greater in the same
package size. Back pressure in the outlet line is additive to the spring setting. Pilot-operated relief valves also normally
have lower pressure increase from initial opening to the full open position but have greater internal leakage. They are
suited to system relief applications for pump and circuit pressure protection.

26

Application guidelines - Hydraulic valves

6.3 Sequence valves


Sequence valves are normally closed devices that differ from standard relief valves in that the outlet flow is directed to
another pressurized function rather than to the reservoir when the valve opens. Since outlet flow is pressurized, they
require an externally drained spring or pilot cavity. Sequence valves are utilized to ensure that one operation occurs
before a second begins.

6.4 Unloading valves


Unloading valves are normally closed devices that are controlled by a sensing line from the main circuit. They are often
used to bypass the flow from a fixed displacement pump to the reservoir at low pressure when no functions are
operating and to bypass excess flow to the reservoir at a small margin above load pressure when one or more functions
are operating at flows less than full pump capacity. The unloading valve is spring biased to produce a preset margin
pressure above sensing line pressure. Unloading valves are also often used in circuits with accumulators to reduce
pump pressure when the accumulator is adequately charged.

6.5 Pressure-reducing valves


Generally, pressure-reducing valves are normally open devices that close to restrict or block flow from the main circuit
to a secondary circuit, thereby maintaining a relatively constant reduced pressure in the secondary circuit. They are
often used to provide a source of pilot pressure, or to supply a secondary circuit that requires lower pressure.

6.6 Pressure-reducing/relieving valves


Reducing/relieving valves add the function of a full-flow relief valve from the reduced pressure port to the reservoir.
Thus, they will maintain a constant reduced pressure under backflow conditions.

6.7 Electrically-operated relief valves


Relief valves may incorporate integral solenoids to connect or vent the pilot stage. This allows the relief valve to be
enabled or disabled electrically.
Electrohydraulic proportional relief valves are also available. These incorporate an electrohydraulic device in
combination with a spring to provide a relief setting proportional to input electrical current.

6.8 Other pressure controlled devices


See clause 8 for discussion of counterbalance valves and other pressure controlled devices specifically designed for
load holding.

7 Flow control valve application guidelines


7.1 Noncompensated flow control valves
Flow control valves can be fixed, mechanically adjusted, hydraulically piloted, pneumatically piloted, or electrically
modulated.
7.1.1

Orifices and needle valves

Simple fixed orifices, needle valves, gate valves, or globe valves are the least expensive flow control devices. They are
normally used only in noncritical applications because their flow rate at a given orifice opening or setting varies with the
pressure drop and fluid density. Fixed orifices are often used in combination with a check valve to provide free flow in
one direction and controlled flow in the opposite direction.

27

Application guidelines - Hydraulic valves


7.1.2

Velocity fuses

Velocity fuses are designed to close and remain closed upon sensing an abnormally high flow velocity. They are used in
hoist circuits to prevent load drop in the event of a line break.
7.1.3

Pressure-compensated flow control valves

Pressure-compensated flow controls improve the accuracy of flow regulation by incorporating a spring that maintains a
constant pressure drop across the metering orifice independent of variations in supply or load pressure. Further
accuracy gains can be achieved with temperature compensation, to offset variations due to fluid viscosity and density.
7.1.4

Flow limiters

Flow limiters or bypass flow regulators are two-port devices that limit flow by means of an internal orifice with a preset
pressure differential determined by a bias spring. They are typically used to prevent actuator overspeed.
7.1.5

Proportional flow dividers

Proportional flow dividers are three-port devices that split inlet flow into two outlet flows that are normally each a fixed
proportion of inlet flow. If flow proportioning in both the forward and reverse flow direction is required, special flow
divider/combiner valves shall be used. Spool type flow dividers are not subject to the pressure intensification effects
common to gear type flow dividers.
7.1.6

Flow dividers and priority flow control valves

Three-port flow divider valves may be of the bypass flow regulator type, restrictive flow regulator type, fixed flow priority
type, adjustable flow priority type, or load sensing priority type.

7.2 Electrohydraulic flow control valves


The simplest type of electrohydraulic flow control valve produces a metering orifice opening proportional to input
current. There are noncompensated devices, as discussed in 7.1 and 7.1.1, and are sometimes thought of as an
electrically variable needle valve.
More sophisticated electrohydraulic flow controls include compensation, and are available for use in the various circuit
types listed in 7.2.3. Application criteria for these devices include response time, linearity, repeatability, and hysteresis.
Pulse width modulation or dither techniques are often used in the electronic controller to minimize hysteresis.

8 Load control valve application guidelines


8.1 Pilot-operated check valves
When a pilot-operated check valve is used in combination with a multiple-position directional control valve, the
directional control valve should be of the type that relaxes pressure on the pilot connection when the valving element is
in the neutral or centered position. If a proportional or closed center directional control valve is used, an externally
drained pilot operated check valve should be used to ensure that the effective pilot ratio is maintained.
Pilot-to-open check valves are nonmodulating, on/off devices that allow essentially free flow in one direction and block
reverse flow until a pilot pressure is supplied to a pilot piston to unseat the check poppet. They have extremely low
internal leakage when closed, and thus are used in applications requiring very little drift of a loaded cylinder. They are
not suited for use with hydraulic motors that leak internally. The pilot pressure required to unseat the check is directly
proportional to the load pressure (typically expressed as the pilot ratio). A thermal relief valve should be considered if
the possibility of damaging overpressure exits due to large temperature increases and the resulting thermal expansion
of the trapped fluid between the check valve and the cylinder.
Pilot-to-close check valves are also available. These block flow when the product of the pilot pressure and the area ratio
is greater than the load pressure, and open when the pilot pressure is vented.

28

Application guidelines - Hydraulic valves

8.2 Counterbalance valves


Counterbalance valves are modulating devices that allow essentially free flow in one direction and block reverse flow
until a combination of load pressure and pilot assist pressure overcome the major spring bias. They improve motion
control in overrunning load situations by ensuring that the unloaded side of the actuator has positive pressure before
exhausting fluid from the load holding side of the actuator. In general, lower pilot ratios provide better motion control
and stability, especially in spongy systems and systems with inertial loads.

8.3 Motor control valves


Counterbalance valves may be utilized to provide cushioning and modulation in motor circuits with overrunning loads,
such as swing and winch drives. High pilot ratios are often acceptable in motor circuits. The use of separate
anticavitation check valves is recommended. Due to motor internal leakage, brakes are required to lock static loads.
Crossover relief valves with anticavitation check valves may also provide acceptable acceleration and deceleration
control in motor circuits.

29

Application guidelines - Pneumatic filters, regulators and lubricators

Application guidelines Pneumatic filters, regulators and lubricators

Introduction
In fluid power systems, power is transmitted and controlled through a fluid (liquid or gas) under pressure within an
enclosed circuit.
Pneumatic fluid power begins at the compressor. The purpose of the compressor is to draw atmospheric air from the
environment, increase its pressure and deliver it in sufficient volume to the air pneumatic system. A compressor does
this by forcing atmospheric air into a confined chamber and reducing the volume, which increases the pressure.
Raw air from the compressor should not be used until it is conditioned. As air is compressed it becomes very hot and,
along with oil from the compressor, dirt particles and condensed moisture, can produce unwanted chemicals in the air.
These chemicals reduce the life expectancy of air tools, valves, cylinders and other pneumatic equipment. The
conditioning is initially done by primary air processing which includes after-coolers, filters, dryers and other devices.
Secondary air processing is done closer to the operating equipment by filters, regulators and lubricators (FRLs).
CAUTION: Compressors can generate high pressure. It is good practice to check the maximum rating on all
components to make sure the equipment is properly rated to handle the pressure generated by the compressor. Often,
the maximum pressure ratings of pneumatic components are below what the compressor can generate and, therefore,
regulators are used to reduce the presure to an acceptable level for components used in the system.
Through misuse, age or malfunction, components used in a fluid power system can fail in various modes. The system
designer should consider the failure modes of all components used in the fluid power systems and consideration should
be given to provide adequate safeguards to prevent injury or damage to equipment in the event of such a failure mode.
System designers should also provide for all OSHA requirements including Title 29 CFR 1910.147, Lockout/Tagout.

Scope

This recommended practice applies to filters, regulators and lubricators for their application in a pneumatic fluid power
system. The purpose of the recommended practice is also to provide guidelines for the selection, sizing, installation,
operation and other good practices for filters, regulators and lubricators.

Normative references

The following normative documents contain provisions which, through reference in this text, constitute provisions of the
Application guidelines Pneumatic filters, regulators and lubricators section (pages 31-38) of this NFPA document. For
dated references, subsequent amendments to or revisions of, any of these publications do not apply. However, parties
to agreements based on this NFPA document are encouraged to investigate the possibility of applying the most recent
editions of the normative documents indicated below. For undated references, the latest edition of the normative
document referenced applies. NFPA maintains registers of currently valid NFPA Standards. Standards development
organization contact information and links can be found on the NFPA website (www.nfpa.com).
ISO 1000 (latest edition), SI units and recommendations for the use of their multiples and of certain other units.
ISO 1219-1 (latest edition), Fluid power systems and components Graphic symbols and circuit diagrams Part 1:
Graphic symbols.
31

Application guidelines - Pneumatic filters, regulators and lubricators

ISO 5598 (latest edition), Fluid power systems and components Vocabulary.
ISO 8778 (latest edition), Pneumatic fluid power Standard reference atmosphere.

Definitions

For the purposes of this standard, the terms and definitions given in ISO 5598 apply.

Primary air processing

4.1

Filters

A large filter is usually placed on the inlet of the compressor to prevent particles from being drawn in. A second filter is
usually placed on the outlet side of the compressor to protect downstream components. This filter removes smaller dirt
particles that were not removed by the intake filter.

4.2

Coolers

As air is compressed, it becomes heated. Compressed air is often 149 C (300 F) or hotter. At this temperature, air
can hold large amounts of water vapor which, when condensed downstream, has the potential to damage pneumatic
equipment. It is good practice to use a cooler. Coolers can be found either outside (after-cooler) or inside the
compressor. Coolers use either atmospheric air or water in a heat exchanger to bring down the temperature of the
compressed air.

4.3

Dryers

4.3.1 The air is saturated with water vapor after going through the cooler and further cooling causes the water vapors
to condense in the system. Thus, it is good practice to install a dryer to remove the moisture.
4.3.2

There are various types of dryers: for example refrigerated, desiccant, deliquescent, membrane and others.

NOTE
it is a very good practice to use one of these drying methods to remove the moisture. The closer the drying method is to
the compressor, the better. The purpose is to limit moisture from being distributed thoughout the air system.

Secondary air processing

Secondary air processing is located at each air line drop from the main distribution system and conditions the air that is
used at that point. It is used to further remove moisture and contaminants, regulate the pressure and add lubrication.
The equipment to accomplish this usually consists of filters, regulators and lubricators (FRLs).

5.1

Filters

5.1.1 In most filters, the incoming air passes through a set of baffles, which causes a high velocity rotary motion that
forces most of the dirt and moisture droplets to separate by centrifugal force. These contaminants collect in the bottom
of the bowl and are discharged through the drain cock (when mounted vertically). The filter drain can be operated
manually, semi-automatically or automatically.
5.1.2 Then the air passes through a filter element to strain out solid particles. The elements may consist of screens,
sintered bronze or various porous materials. The elements are typically sized in nominal ratings of 40, 20 and 5 microns
(micrometers) and the smaller the nominal rating, the finer the filtration.
32

Application guidelines - Pneumatic filters, regulators and lubricators

5.1.3 Filters should be selected to adequately protect the downstream pneumatic components. Elements rated at
40 microns (micrometers) are often used, as it gives adequate filtration for most industrial pneumatic components
(cylinders, valves, air motors, etc.). In most cases, an element rated at 40 microns (micrometers) provides a higher flow
than the smaller element sizes.
5.1.4 However, there are applications for the other element sizes. The 5 micrometer element could be used in an air
bearing application where the cleaner air is required. It is good practice to discuss the filter requirements with the
downstream equipment manufacturer.
5.1.5 A second level of filtration, called coalescing, is used to remove the liquid oil droplets carried over from the
compressor. A standard filter should be installed upstream, before the coalescing unit, to protect the special coalescing
element from dirt and moisture.
5.1.6 A third level of filtration, for the removal of hydrocarbon vapors, is also available for special applications.
Contact your filter supplier for more information.
5.1.7 Consideration should be given to the type of bowl used on the filter. Clear plastic bowls provide easy monitoring
of the fluid level, but are not compatible with some materials. Therefore, filter manufacturers offer metal or composite
bowl options for chemical compatibility and safety. Metal bowls can be plain or have sight gauges for viewing fluid
levels. Composite bowls usually do not allow for viewing of the fluid level. When selecting the filter bowl, strong
consideration should be given to the environment the filter will be placed in. Chemicals in the atmosphere and in the
compressed air must be considered, as well as, the material used to clean the bowl and element. Make sure all items
are compatible with the bowl material and element. For further information, consult the instruction materials from your
filter supplier.
5.1.8 Filters are manufactured with a wide variety of port sizes. Consult the manufacturers literature to determine the
flow ratings for each size (not by just matching port sizes to other components in the system). The filter should always
be sized to provide a higher air flow than the downstream equipment requires. This will allow for pressure and flow loss
due to fittings and other restrictions in the distribution system.
5.1.9

5.2

Make sure the pressure and temperature ratings of the filter are adequate for the application.

Regulators

5.2.1 The regulator is used to control and maintain a nearly constant downstream air pressure. Often, the
compressor will supply a higher pressure than the downstream pneumatic equipment requires for optimum
performance and, therefore, the regulator is used to reduce pressure to the desired level.
5.2.2 The regulator provides a more consistent delivery of air pressure to the downstream equipment. As pneumatic
equipment is turned on and off during an operating cycle, air pressure in the distribution system will vary. The regulator
minimizes this fluctuation.
EXAMPLE
As the air consumption varies, system pressure could drop from a high of 896.35 kPa (130 psi) to as low as
689.5 kPa (100 psi) at any given point in the system. A regulator set at 620.55 kPa (90 psi) for its point of use will supply
approximately 620.55 kPa (90 psi) to downstream equipment, regardless of the upstream variations.

5.2.3 Typically, a regulator has a spring that exerts a force against a diaphragm or piston, which pushes on the valve
stem, holding the valve open. The compression of the spring determines the downstream pressure. The compressed
air passes through the open valve to the downstream system. As downstream pressure begins to build, it creates
increased force on the diaphragm or piston, against the spring, until that force exceeds the force of the spring. When
this happens, the valve opening is automatically reduced enough to keep the downstream pressure at the preset level.
5.2.4 Regulators usually have several different spring ranges. The different spring ranges allow the regulator to react
and perform better in the desired pressure range.

33

Application guidelines - Pneumatic filters, regulators and lubricators

EXAMPLE
If a user wants to regulate the supply pressure to 103.43 kPa (15 psi), a 6.90 to 206.85 kPa (1 to 30 psi) spring
allows for a finer adjustment than a 34.475 to 861.88 kPa (5 to 125 psi) spring. Therefore, it is good practice to know the required
downstream pressure requirement and choose the regulator with a spring range to achieve the desired pressure.

5.2.5 In addition, some regulators are air-piloted instead of spring-biased. Air-piloted regulators are controlled by pilot
pressure from another source.
5.2.6 Elastomers in regulators are generally provided in nitrile and fluorocarbon. When selecting the elastomer type,
consider the application temperature and fluids that may come in contact with the regulator.
5.2.7 Almost all regulators have at least one gauge port to sense the downstream pressure. It is good practice to use
a gauge at the regulator so that the downstream pressure can be measured when adjusting or initially setting the
regulator.
5.2.8 Regulators are manufactured in a wide variety of sizes. Consult the manufacturer's literature to determine the
flow ratings for each size. The regulator should always be sized to provide a higher flow than the downstream devices
require and often it is the lowest flowing component in the filter-regulator-lubricator set. Over sizing will allow more
flexibility for pressure and flow loss due to connectors and other restrictions in the distribution system.
5.2.9

Two types of available regulators

5.2.9.1

Relieving

5.2.9.1.1
If the downstream pressure becomes higher than the regulator setting, the excess pressure is released or
relieved into the atmosphere. The increased downstream pressure can be a result of expansion due to heat, a falling
load on a cylinder or a reduction in the regulator setting. To achieve the relief, there is a small hole in the center of the
piston or diaphragm. The valve stem normally seals the relief hole, but when the downstream pressure is higher than
the spring setting, the pressure lifts the piston or diaphragm from the valve stem, relieving the excess pressure through
the hole. The advantage of the relieving regulator is that the downstream equipment starts up close to the pressure at
which the regulator has been set. This will occur even when the regulator has been placed in a dead-ended, no flow
system.
5.2.9.1.2

The relieving regulator is more commonly used than the non-relieving type.

5.2.9.2

Non-relieving

5.2.9.2.1
Non-relieving regulators do not have a relief hole in the piston or diaphragm; so, air cannot escape when
the downstream pressure increases above the setting. Non-relieving regulators are often used in special applications or
in cases where the air or gas passing through the regulator cannot be released into the atmosphere for safety or cost
reasons. In these cases, some means such as a relief valve must be employed to avoid excessive pressure build up of
the downstream pressure.
5.2.9.2.2

5.3

The regulator should be positioned after the filter.

Filter-regulator unit

5.3.1 A filter and regulator are often combined into one unit. The air comes in a common inlet port, is filtered,
regulated and then exits out a common outlet port.
5.3.2

34

The two functions are done in one unit, providing major space savings and reduction in installation time.

Application guidelines - Pneumatic filters, regulators and lubricators

5.4

Lubricators

5.4.1 A lubricator is used to provide a consistent supply of lubricated air to downstream equipment. Often,
downstream equipment such as air tools, motors, cylinders, boosters, etc., require lubrication to reduce wear and heat.
This can lengthen the service life of the downstream devices.
5.4.2 In a basic lubricator, a portion of the inlet air passes through a venturi causing a pressure drop in the venturi
and accelerates the stream of air. The air pressure upstream from the venturi is applied to the surface of the oil
reservoir (i.e. oil in the bowl). This pressure forces oil through a tube to the top of the lubricator, where a control sight
feed dome meters the amount of oil feed, before the oil drops into the venturi throat. The oil is broken into a fine aerosol
by the velocity of the air flowing through the venturi throat.
5.4.3 Each lubricator has an adjustment to control the oil feed rate. The rate of oil delivery does vary with the flow
rate. A rule of thumb is to feed one drop of oil for every 9.44 l/sec, ANR (20 standard cubic ft/min, SCFM) required by
the downstream component. However, one should be prepared to fine tune the lubricator adjustment for the first couple
of weeks after installation. One technique calls for adjusting the lubricator and then, after a few days, measure the
amount of oil that has gone through the system by using a piece of paper at the tool exhaust. If there is a lot of oil, then
the lubricator needs to be adjusted to provide less oil feed and the system re-tested a few days later. If there is no oil,
then the lubricator needs to be adjusted to provide more oil feed and the system re-tested a few days later. If there is a
little mist on the paper, then the lubricator is properly adjusted.
5.4.4 It is also good practice to install one lubricator per piece of equipment requiring lubrication. If only one
lubricator is used to supply oil to several pieces of equipment, the piece of equipment closest to the lubricator may get
flooded, while other pieces of equipment receive very little oil. Also, lubricators should be installed downstream from the
filter and regulator and as close as possible to the point of use.
5.4.5 The lubricator must be filled with oil that is suitable for the downstream equipment and compatible with the
materials in the lubricator, particularly plastic bowls. Consult the manufacturers literature for compatibility of oils. Also, if
the downstream equipment requires lubrication, consult the equipment supplier for recommendation concerning the
type and amount of oil the equipment requires.
5.4.6 An injection lubricator is another lubricator design. The injection lubricator is positive displacement, air-impulseoperated, with adjustment for variable lubricate delivery. They are used for lubricating a number of pneumatic devices
from a convenient, central location. A station may consist of one or more oil injectors, using a common oil supply and a
common pressure signal for operation. The air pressure for injector operation is taken from a normally closed port on
an existing pneumatic control valve that operates at some regular frequency. The oil injectors dispense a consistent,
metered quantity of oil with each cycle and can be individually adjusted to suit the device being lubricated. Consult your
manufacturer for specific details.
5.4.7 Lubricators are manufactured in a wide variety of port sizes. Consult the manufacturers literature to determine
the flow ratings for each size. The lubricator should always be sized to provide a higher air flow rate than the
downstream equipment requires. This will allow for pressure and flow loss due to connectors and other restrictions in
the distribution system.

5.5

Uses and connections

5.5.1 Filters, regulators and lubricators (FRLs) can be used as stand alone components, but are often used in
combination with each other. It is very common to use a filter, regulator and lubricator (FRL set) connected together at a
point of use.
5.5.2 In some applications, a lubricator is not used because the downstream device does not require lubrication or
the user does not want lubrication to be expelled into the atmosphere through exhaust passages from the downstream
device, for example, air valves or tools. Often, a lubricator is not used in food processing or clean room applications.

35

Application guidelines - Pneumatic filters, regulators and lubricators

5.5.3 If an application requires both lubricated and non-lubricated air, then a branch line can be installed after the
regulator and before the lubricator. Some manufacturers offer a manifold block to be installed between the regulator
and lubricator for this purpose.
5.5.4 The FRL set is either connected together by pipe nipples or a modular design. Pipe nipples are connected to
the outlet of one device (filter) and the inlet of the other (regulator). A modular design eliminates pipe nipples by using a
series of spacers and clamps. Typically, the modular design can be assembled in less time, which reduces the
installation cost. Both designs are widely used.

5.6

Piping system for air distribution

Energy loss is the result of loss in pressure between the air compressor and the points of use. Therefore, the air
distribution system is critical to conserve the energy stored in the compressed air. As a general rule, the piping system
delivering the compressed air to the point of use should not see a pressure loss greater than 10 % of the initial
pressure. Future expansion and additional compressed air capacity should be considered during the early design stage.
Two common methods of installation are used: the linear and loop systems.
5.6.1

Linear system

The linear system delivers air from the compressor to each point of use through a single line. The pressure is fed into
the distribution system from only one side. It then flows one direction to the other end of the distribution system. With
this type of installation, a large consuming device near the compressor can deprive the rest of the downstream
equipment from its required amount of compressed air.
5.6.2

Loop system

5.6.2.1
In a looped system, the main line starts at the compressor, passes each point of use and returns to the
compressor. This provides each drop with supply from both directions. In turn, each drop receives a more consistent
flow of compressed air.

Figure 1 Loop system


5.6.2.2
Piping should slope downward, away from the compressor. The rule-of-thumb is to have a slope rate of
.125 in/ft to .250 in/ft, if possible. This allows condensation to flow to the lowest point in the line, where a drain should
be installed.

36

Application guidelines - Pneumatic filters, regulators and lubricators

5.7

Air drop

5.7.1 At each point of use, an air drop is required. Branch lines should be taken from the top of the main line allowing
sediments to remain in the main line, eventually to be delivered to the drain. Vertical air drop lines should extend down
to a convenient height. Air drops should be equipped with a drain at the bottom. A horizontal leg extending off the
vertical drop is where the FRL set is usually installed. If the drop is being connected to a machine, the FRL set is usually
mounted on the machine.
5.7.2 It is good practice to install a shut off/dump valve on each branch line so that each line can be shut off for
maintenance, independent from the rest of the system. Often this is a lockout/tagout device.

Summary

6.1 The proper planning and layout of an air distribution system is very important in achieving the most efficient use
of compressed air and the equipment it operates. A properly designed system can maximize the performance and
extend the life of all pneumatic equipment.
6.2 The filter-regulator-lubricator (FRL) sets that are properly installed at each point of use, are essential components
in the pneumatic system. Proper use and sizing will reduce the operating cost of pneumatic equipment, which in turn
increases operating time and productivity.

37

Application guidelines - Pneumatic filters, regulators and lubricators

Annex A
(informative)
Bibliography
Identification
Number

38

Title

Source

Date of
Issue

Compressed Air and Gas Handbook

CAGI

1989

NFPA/T2.6.1 R2

Fluid power components Method for verifying the


fatigue and establishing the burst pressure ratings
of the pressure containing envelope of a metal fluid
power component

NFPA

2001

NFPA/T3.12.10 R2

Air line filter, regulator and/or lubricator Pressure


rating supplement to NFPA/T2.6.1 R2-2000, Fluid
power components Method for verifying the
fatigue and establishing the burst pressure ratings
of the pressure containing envelope of a metal fluid
power FRL

NFPA

2000

ISO 4414

Pneumatic fluid power General rules relating to


systems (second edition)

NFPA

1998

ISO 5782-1

Pneumatic fluid power Compressed air filters


Part 1 : Main characteristics to be included in
suppliers literature

NFPA &
ISO

1997

ISO 5782-2

Pneumatic fluid power Compressed air filters


Part 2 : Test methods to determine the main
characteristics to be included in suppliers literature

NFPA &
ISO

1997

ISO 6301-1

Pneumatic fluid power Compressed air


lubricators Part 1 : Main characteristics to be
included in suppliers literature and product-marking
requirements

NFPA &
ISO

2009

ISO 6301-2

Pneumatic fluid power Compressed air


lubricators Part 2 : Test methods to determine the
main characteristics to be included in suppliers
literature

NFPA &
ISO

2006

ISO 6953-1

Pneumatic fluid power Air line pressure


regulators Part 1: Main characteristics to be
included in commercial literature and specific
requirements

NFPA &
ISO

2000

ISO/6953-2

Pneumatic fluid power Compressed air pressure


regulators and filter-regulators Part 2: Test
methods to determine the main characteristics to
be included in literature from suppliers

NFPA &
ISO

2000

ISO 8573-1

Compressed air for general use


Part 1: Contaminants and quality classes

ISO

1991

Application guidelines - Selection of position transducers

Application guidelines Selection of position transducers

Introduction
Today's hydraulic and pneumatic applications involve interfacing a number of fluid power components with electronic
instrumentation to form a complete system. The system designer must bring a variety of technical disciplines into play
to achieve the desired end result a functional and controllable transfer of energy. The components involved can
include pumps, cylinders, valves, transducers and electronic controllers. The disciplines include hydraulics, pneumatics,
mechanics and electronics.
The National Fluid Power Association (NFPA) is increasingly aware of the multidisciplinary approach necessary to
achieve a realistic and successful system. The NFPA also recognizes properly designed systems as a strong proponent
to the growth of fluid power.
Fluid power is frequently used to move or displace various parts of a mechanism or load in response to commanded
inputs. For control or quality purposes, it is often required to measure displacement that the load undergoes. A position
transducer provides a measure of the displacement of some portion of a mechanism relative to a reference point. Two
specific types of displacement can generally be measured. The first is linear displacement, which is commonly referred
to as distance. The second is angular or rotary displacement.
Position transducers produce an electrical output proportional in amplitude or time to the position of the load relative to
a reference point. The actual sensing mechanism may utilize one of many different technologies. Typical sensing
technologies include the following: acoustics, capacitance, induction, magnetism, Hall effect, magnetostriction, optical
gratings, optical interferometry, RF/microwaves and resistance, as well as mechanical means.
The selection of an appropriate position-sensing transducer requires consideration of a number of criteria involving both
measurement and environmental parameters. Considering the typical characteristics and environments of fluid power
systems, some of the above sensing technologies have proven more commonly used than others. This guide will be
limited to the most commonly used proportional position sensing technologies and will not include discrete on/off
position sensors, such as mid-stroke and end-of-stroke switching. This guide is aimed at technical personnel with
limited exposure to the subject matter or those desiring a quick overview. It is not intended to provide a comprehensive
discussion of all forms of position measurement.
Developers of fluid power position transducers can be found in the NFPA Product Locator at
http://www.nfpa.com/default.asp?pid=99.

NOTE
These application guidelines rely heavily on information generally in the public domain and were excerpted from a
substantial number of previously published documents given on these topics.

Scope

1.1 The technical presentation of this document identifies the factors involved in selecting a reliable and functional
position transducer. The selection of components and the success of the installation remain the responsibility of the
individuals actually involved in the process. NFPA assumes no responsibility for improper application of any of the
technologies described in this guide.

39

Application guidelines - Selection of position transducers

1.2 This guide presents parameters and requirements of position transducers for use in mobile and industrial fluid
power systems. The intent is to make readers aware of the type of information needed to select fluid power position
transducers. Lastly, transducer manufacturers may find this guide helpful in communicating with potential users within
the fluid power industry.

Normative references

The following normative documents contain provisions which, through reference in this text, constitute provisions of the
Application guidelinesSelection of position transducers section (pages 39-58) of this NFPA document. For dated
references, subsequent amendments to or revisions of, any of these publications do not apply. However, parties to
agreements based on this NFPA document are encouraged to investigate the possibility of applying the most recent
editions of the normative documents indicated below. For undated references, the latest edition of the normative
document referenced applies. NFPA maintains registers of currently valid NFPA Standards. Standards development
organization contact information and links can be found on the NFPA website (www.nfpa.com).
ANSI ISA-S37.12 (latest edition), Specification and tests for potentiometric displacement transducers.
ISO 5598 (latest edition), Fluid power systems and components Vocabulary.

Definitions

For the purposes of this recommended practice, the terms and definitions given in ISO 5598 and the following apply:
3.1

accuracy: The degree to which the output (or reading) is free from errors.

3.2

analog: A system in which the information is carried in the amplitude of the signal.

3.3

digital (binary): A system in which information is represented as a combination of bits.

3.4

digital output: An electronic pulse strain proportional to the distance moved by the transducer.

3.5

displacement: An object's physical position with respect to a reference point.

3.6 hysteresis: Difference in controlled parameters, at the same control setting, when adjusting the quantity upwards
and then downwards or vice versa.
3.7 impedance (electrical): A mathematical representation showing the ratio of the magnitude and phase of the
voltage across a device divided by the magnitude and phase of the current flowing through that device. The impedance
of electrical devices, which do not alter the phase relationship between applied voltage and current, is frequently
referred to as resistance.
3.8

input impedance: The impedance measured across the input terminals of an electronic device.

3.9 linearity: The closeness of a calibration curve to a specified straight line. Manufacturers use different methods of
determining the specified straight line.
3.10 repeatability: Quantitative expression of the random error associated with a single tester in a given laboratory,
obtaining successive results with the same apparatus under constant operating conditions on identical test material.
3.11 resolution: The smallest increment of position change that the transducer can detect and register as a
measurable output signal.

40

Application guidelines - Selection of position transducers

3.12 stroke: The distance of a single movement of a piston or similar device.


3.13 temperature sensitivity: The degree to which the output signal and, therefore, the indicated position, is affected
by ambient temperature changes.

Position transduction general

4.1 A position transducer typically consists of two fundamental parts: one part remains fixed in position while the
other part moves with the mechanism whose displacement is being measured. The exact nature and, therefore, the
size of the fixed and moving portions depend upon the sensing technology being used. Some transducers are intended
to be mounted integral to the mechanism (see figure 1), while others are designed to be mounted external to the
mechanism.
4.2 If a transducer is configured for mounting inside a cylinder, a hole usually is drilled down the center of the piston
rod and the cylinder end cap is machined to accommodate the transducer. This method usually consumes the least
amount of space, but makes the transducer less accessible than mounting it externally. Mounting the transducer
alongside the cylinder eliminates the time, effort and expense of machining, but exposes the transducer to the
environment.
4.3 An electrical power source is required for all position transducers. The power is applied to one of the two
fundamental parts. The other part is passive and does not require power. Normally, it is desirable to have the powered
part be stationary to avoid problems associated with moving cables, cable strain and cable routing. In addition to
position and displacement outputs, these transducers, through supporting electronics, can provide speed and velocity
or acceleration outputs.
4.4 Primary consideration should be given to the mounting space available and type of electrical power to be used
when selecting a transducer. For example, a transducer that requires 120 VAC is not as appropriate for mobile
equipment as one that needs 12 VDC. Additional considerations should be given to environmental conditions of the
application.

41

Application guidelines - Selection of position transducers

Split collar (or magnet in magnetostrictive


technologies or wiper in resistive devices)

Piston rod

Transducer core

O-Ring
Optional signal
conditioning
electronics

Transducer
bulkhead fitting

Cylinder head

Piston
Transducer probe (coil)

Figure 1 Cross section of cylinder with internal transducer

42

Gun-drilled hole

Application guidelines - Selection of position transducers

4.5 Output from the position transducer can be a signal whose amplitude is proportional to position (i.e. an analog
voltage or current signal) or proportional to time (i.e. a digital pulse whose duration is proportional to position). This can
be a series of pulses where each pulse represents movement of a fixed increment or it may be a unique code for each
measured position.

Types of position transducers

There are a variety of transducer designs used in a vast array of relatively long-stroke applications. The inherent design
of a particular type usually determines whether or not it is suitable for a specific fluid power application.

5.1

Encoders

5.1.1 Encoders are non-contact digital devices that, in their simplest configuration, provide a defined number of
pulses per revolution or per unit of linear displacement. Encoders produce digital pulses typically in 5 VDC by
consecutively completing and breaking an electronic circuit. This on/off sequence allows changes in position to be
detected and measured. There are two typical transduction methods used in encoders: optical and magnetic.
5.1.2 An optical encoder (see figure 2) consists of a light source, a light sensor and a grid. The grid can be
constructed of glass, metal or plastic. It consists of alternate transparent and opaque areas that either allow or prohibit
the passage of light from the source to the sensor. This blocking and unblocking of light causes the associated
electronics to generate a string of pulses. Magnetic encoders replace the grid with magnets, and the light source and
sensor are replaced with devices that sense the changes in magnetic fields.
5.1.3 There are two types of encoders: incremental and absolute. An incremental optical encoder is shown in figure 2
and an absolute encoder is shown in figure 4.
Disc

Conditioning
electronics
Light source

Sensor

Figure 2 Components of an optical incremental encoder


5.1.4 For incremental encoders, a separate electronic controller determines position by counting the pulses.
Incremental encoders, whether linear or rotary, will lose position when the electrical power is removed. Since counting
must commence from a known point, a reference or home position must be established upon powering up the encoder
and its electronics. In practice, the operator of a machine generally initiates a homing routine to set the reference
position before the machine is brought into use.

43

Application guidelines - Selection of position transducers

5.1.5 To ensure that an incremental encoder can determine direction, a second pulse output is added 90 out of
phase with the first output. This phase shift is referred to as quadrature output (see figure 3) and it allows the controller
to determine direction of travel and eliminates false counts caused by vibration when motion has stopped. A third output
generates a single index pulse at a discrete position. This output is generally used for homing or indexing routines and
for counting turns in rotary multiturn applications.

Track A

Track B

90
Figure 3 Quadrature = 90
5.1.6 Typical absolute encoders overcome this loss of position sensing by using an elaborate pattern on the grid with
eight or more light source detector pairs that generate parallel pulse outputs, which are available in a variety of output
formats. The combination of elaborate patterns and number of light source detector pairs provides a number of unique
outputs for the travel of the device.

Figure 4 Absolute encoder disc


5.1.7 For incremental encoders, the higher the line count, the greater the resolution of the device. For absolute
encoders, the greater the number of outputs, the greater the resolution of the device. The cost of the encoder increases
as resolution becomes greater.

5.2

Inductive sensors

5.2.1 An inductive sensor is a non-contact device that measures the change in impedance (effective resistance) of a
coil. The operation is similar to that of an inductive proximity switch. Alternating current flowing through a coil forms a
magnetic field around the coil. Ferrous metal or non-ferrous metal at higher frequencies disrupts the field when the
metal enters it. The disruption of the field causes the inductance of the coil to change.
44

Application guidelines - Selection of position transducers

5.2.2 A proximity switch reacts to a metal target approaching the face of the switch. Position sensors replace the
target with a core or spoiler, which is essentially the same length as the coil. The amount of overlap between the coil
and the core determines the inductance of the coil (i.e. if the core is fully inserted, then the inductance is at minimum or
maximum depending on the physics of operation). Conversely, when there is no overlap between coil and core, the
opposite is true. The output between these limits is a linear analog signal proportional to the amount of overlap.
5.2.3 Transducer designs are available with the core penetrating the inside diameter of the coil, while others have the
core slide over the outside of the coil (see figures 1 and 5). The internal core design of the externally mounted cylinder
device is best suited for retrofit applications where gun drilling is not desired. The external core is normally used for
mounting inside hydraulic cylinders having a gun-drilled piston and piston rod.

Transducer coil (fixed)

Core (moveable)

Figure 5 Typical inductive transducer for external mounting


5.2.4 All inductive position transducers use a signal conditioner or signal processor to generate the excitation current
to the coil and to detect and amplify the inductance change. The physical location of the signal processor may be on the
rear of the transducer (see figure 12) or at the end of a cable between the two. The length of the cable may vary from
1 m to as much as 75 m, depending on the application. These transducers may be powered by low voltage DC to
115/230 VAC, depending on the manufacturer and model. For example, the transducers provide a 0 to 10 VDC or
4 to 20 mA output, which is usable by most programmable, motion or dedicated controllers.

5.3

Linear and rotary variable differential transformers (LVDTs and RVDTs)

5.3.1 A linear or rotary variable differential transformer (LVDT or RVDT) is a non-contact transducer that converts,
respectively, a linear or rotational displacement into an analog electrical output signal. The LVDT consists of a primary
transformer coil wound on a non-magnetic cylindrical coil form. Two secondary transformer coils are wound on each
side of the primary one. This coil assembly is then installed in a mechanical housing. The other major component is a
ferromagnetic core moving inside the coil form.
5.3.2 In operation, the primary coil is excited typically at 3 to -8 VAC at 60 Hz to 20 kHz. The alternating current in the
primary winding creates an axial magnetic flux field that is concentrated in the core. This flux is coupled to the
secondary windings through the core, inducing an output voltage in each secondary winding.

45

Application guidelines - Selection of position transducers

5.3.3 When the core is centered between the two identical secondary windings, the voltage induced in each is
identical (see figure 6). The voltage induced in Secondary a (Va) is in phase and Secondary b (Vb) will be 180 out of
phase with the excitation voltage. The output, Va-Vb will be zero. The core position where the output voltage (Va-Vb) is
zero is referred to as the null position.

Excitation

Vp

Primary

Core

Displacement
Secondary b

Secondary a

Vb

Va

Va-Vb
NOTE

The physical appearance of an LVDT maybe similar to that of an inductive sensor.

Figure 6 Typical LVDT


5.3.4 When the core is moved in either direction from the null position, the amplitude of Va -Vb changes in direct
proportion to the displacement. The phase relationships of the summed output with the excitation also change. In one
direction, the summed output signal will be in phase with the excitation and 180 out of phase in the other direction. The
summed output voltage, therefore, has two components: 1) amplitude indicating the magnitude of the displacement and
2) phase relationship indicating direction of displacement. A typical in-cylinder mounting configuration is shown in
figure 1. The LVDT normally uses a special signal conditioning circuit called a phase sensitive demodulator, which
reconstructs the polarity of the DC output voltage.
5.3.5 For most applications, such as the one shown in figure 7, you will not need to be concerned with connecting
directly with the AC voltage coils. A signal conditioner, either external or internal to the transducer, will generate the
excitation and provide DC voltage or current output that is proportional to displacement of the core. When the signal
conditioner is included in the package, the package is referred to as a DCDT. If the input motion is rotational, the device
is referred to as a RVDT.

46

Application guidelines - Selection of position transducers

5.4

Magnetostriction

5.4.1 Magnetostriction is a property of some ferromagnetic materials in which the material expands or contracts
when placed in a magnetic field (see figure 8). The sensing element of a magnetostrictive position sensor is the
waveguide, a long, thin ferromagnetic wire or tube. Another property of these materials is the Wiedemann effect: when
a current is passed through the waveguide in the presence of an axial magnetic filed, a torsional force is exerted on the
waveguide.
5.4.2

The sequence of events in a position measurement is:

a)

a current pulse, called the interrogation pulse, is applied to the waveguide (the circuit is completed with a copper
return wire) and a timer is started;

b)

a torsional force is generated at the location of the position magnet due to the Wiedemann effect. This produces a
sonic pulse that travels down the waveguide, traveling at the speed of sound in the waveguide material;

c)

when the sonic pulse arrives at the sensor element head, it is detected and the timer is stopped;

d)

the elapsed time represents the distance between the position magnet and the sensor element head. Long-term
stability and temperature sensitivity are controlled by the speed of sound in the waveguide material;

e)

the time period measurement is used to produce the desired output, such as analog voltage, 4 to 20 mA, pulse
width modulation, CANbus, Synchronous Serial Interface (SSI), etc.

5.4.3 Accurate, non-contact position sensing is thus achieved with absolutely no wear to any of the sensing elements.
Since a return pulse will be generated for each magnet located along the sensor, sensors can be designed with multiple
marker magnets.
5.4.4 The magnetostrictive linear displacement transducer (MLDT) relies on the basic principle of magnetostriction,
which causes some ferromagnetic materials to change dimension when subjected to magnetic fields. The construction
of a typical MLDT includes an electronic sensing head and a conducting wire coaxially mounted in a waveguide. The
waveguide is made of a magnetostrictive material that is mounted within a protective housing made of a non-magnetic
material. The waveguide is spring mounted on one end for damping. An external magnet moves along the exterior of
the housing.
5.4.5 A current (interrogation) pulse is launched along the conducting wire in the waveguide. This generates a
circumferential magnetic field around the waveguide as the current in the pulse travels down the conducting wire. When
the magnetic field from the current (interrogation) pulse intersects the field of the external magnet, the interaction of the
two fields form a third field that causes the waveguide to experience a minute torsional strain or twist. The strain pulse
travels at ultrasonic speeds along the waveguide and into a pickup mounted in the head of the instrument.
5.4.6 There are different methods of sensing the torsional strain pulse. Each of the variations of strain pulse sensing
detects the dynamic strain induced in the waveguide and produces a signal that is sent to the conditioning electronics
for amplification and shaping.

47

Application guidelines - Selection of position transducers

Optional electrical
connector

LVDT

SIGNAL
C ONDITIONING
C IRC UIT

+ P WR
= FDB K
C OMMON

V
V

Optional internal
electronics (DCDT)
Figure 7 LVDT/DCDT (for valving element position sensing)

Current (interrogation) pulse


Magnified from current
pulse
Strain
pulse

Waveguide

Strain
pulse
Damping
element
NOTE

Movable
position magnet

Current (interrogation) pulse and the position magnet generate strain pulse, which is sensed by the pickup.

Figure 8 Typical magnetostrictive linear displacement transducer (MLDT)

48

Application guidelines - Selection of position transducers

5.4.7 The precise position of the magnet is determined from the time interval between the initiation of the current
(interrogation) pulse and the arrival of the torsional strain pulse in the head, as seen in figure 9. This time interval
multiplied by the travel speed of the strain pulse along the waveguide indicates the position.

Figure 9 Waveshapes
5.4.8 The output is digital in nature. The most common are start/stop and pulse width modulated (PWM). These
electronic circuits are either self-contained or available as a separate module. An analog conversion is readily available
that generally provides 0-10 VDC or 4-20 mA as an output interface. Most units use DC excitation. The output is
available in SSI, CANbus, Profibus, DeviceNet, Ethernet and others.
5.4.9 MLDTs are available in external and internal mounting configurations. Internal mounting resembles the one
shown in figure 10. The piston rod is hollow to allow the stationary waveguide tube to fit inside as the piston rod retracts.
A magnet is embedded in the piston to allow the MLDT to generate a feedback signal representing position of the
piston and, therefore, the load.
(A)
Waveguide

Mode
converter

(B)

(C)

Waveguide

Waveguide

Leads
Piezoelectric film

Pickup coil

Pickup
coil

Bias magnet
(A) a thin ribbon passing through a coil
(B) a coil directly sensing the pulse
(C) a piezoelectric element mechanically sensing the pulse
Figure 10 Three methods of sensing a strain pulse

49

Application guidelines - Selection of position transducers

5.4.10 Recently, new applications referred to as embedded have positioned the electronics housing adjacent to the
cylinder end cap instead of inline with the probe on the back of the end cap, as illustrated in figure 11.

Cylinder end cap

Sensor retaining screw


(customer supplied)
Electrical stroke

Dead zone
(stroke dependent)

End cap (ref)


Magnet

Cable

Piston head and rod assembly

Spacer
Chamfered rod bushing
(Customer provided, optional)

Adapter plate

To pigtail cable or connector

NOTE The illustration above represents a typical cylinder with a 3- to 8-inch bore. Some installation requirements may be
application specific.
Figure 11 Adjacent magnostrictive

50

Application guidelines - Selection of position transducers

5.4.11 Where aluminum, stainless steel or non-metallic cylinder tubes are used, non-contact external mounting
without the need to mechanically couple the transducer to the piston rod may be used, as illustrated in figure 12. In this
technology, the transducer waveguide element obtains position information from magnetic fields induced from pistonmounted magnets used for standard reed and Hall switches.

Figure 12 Non-contact external mount

5.5

Resistive sensors

5.5.1 A resistive sensor, commonly called a potentiometer, uses electrical resistance as a means of measuring
position. An electrical circuit is established between the two ends of the conductive strip of material (see figure 13). A
constant voltage is applied across the conductive strip. A wiper moves along the strip and picks up the voltage along
the strip. Voltage increases as the wiper moves closer to the positive end of the strip. These resistive sensors are
available in either linear motion or rotary motion designs.
Resistance

Wiper

V1

+
Vo

NOTE
With V1 constant, a hydraulic cylinder or other component moving up or down with the wiper causes voltage Vo to
increase or decrease, respectively.

Figure 13 Electrical schematic of resistive transducer

51

Application guidelines - Selection of position transducers

5.5.2 The linear motion version can be mounted internally or externally to the cylinder. The rotary unit is generally
mounted externally and measures angular position directly, but some rotary potentiometers measure linear position by
using a spring-loaded drum and fine cable that pays in and out with changes in position. These are called string pots
and are useful for long stroke lengths.
Dimensions in inches

3/8-32 NEF -2A thread intern.


lockwasher and nut
included

1.065 radius
1.437

0.2497

Optional
locating pins
0.69
2.75
optional
0.69
2
CW
1

Figure 14A Rotary motion resistive sensor

52

Application guidelines - Selection of position transducers

Green
Yellow
Red

0.750
Shaft free to rotate
0.750
2 in up to 12-1/2 in
Red
2
In

Out

1
Yellow

3
Green

Figure 14B Linear motion resistive sensor


5.5.3 The output of a resistive sensor is ratiometric to the voltage the user applies. Since resistive sensors are not
generally provided with any form of signal conditioning electronics, the user is responsible to ensure appropriate
electrical parameters are evaluated. These parameters include, but are not limited to, excitation voltage, power
dissipation and wiper current as it relates to the input impedance of the controller. As a rule of thumb, the resistance of
the device should be less than 0,1 times the resistance of the controller to assure better linearity.

5.6

Hall effect position transducers (Hall effect sensors)

5.6.1 A Hall effect position transducer is a non-contact device that detects the position of a magnet. The magnet
moves along the length of the sensing element and is attached to the object whose position is to be determined.
5.6.2 The Hall effect position transducer relies on the basic principle of magnetic flux, forcing electrons to one side of
a plate generating a voltage. The generation of voltage is known as the Hall effect. Only the perpendicular component
of the flux is measured on the sensor.
5.6.3 There are different types of Hall effect position transducers available. The least expensive Hall effect position
transducers are switches and latches, which have a digital output in response to the presence of a magnetic signal.
More expensive are the linear devices, which output a voltage proportional to the perpendicular flux. Sensors are
available in a variety of packages from small printed circuit board mounted sensors to fully enclosed fluid tight sensors
used on hydraulic valves. The voltage and current requirements vary widely depending on manufacturer and type.
5.6.4 The flux path can be created for different purposes. For linear position feedback, the magnet would be moved
in front of a linear Hall effect position transducer to obtain a linear voltage signal proportional to position, as shown in
figure 15.

53

Application guidelines - Selection of position transducers

Output

Distance from neutral


Hall effect position transducer

Stationary magnet
Figure 15 Linear position feedback using Hall effect position transducer and magnet
5.6.5 Alternatively, a pulse waveform can be created from a digital output Hall effect position transducer and a series
of varying flux fields moved in front of the sensor. Placing a small magnet in the package with the Hall effect position
transducer sometimes augments this application. By adding the magnet to the sensor, the assembly becomes a sensor
to ferrous materials. If there is no ferrous material present, the Hall effect switch is off. If there is ferrous material, the
flux increases and the digital Hall effect switches on. Classically, this application is used for gear tooth timing and
counting on engines.
5.6.6 For hydraulic applications, Hall effect position transducers can be used for valving element position feedback,
cylinder position feedback, safety presence or rotary position feedback. In general, linear Hall effect position
transducers are good candidates for short motion measurement (<0.1 m) or limited rotary motion measurement
(<180).

Measurement error

6.1 All position transducers are electromechanical devices and are made from more than one material. For this and
other reasons, they respond not only to changes in position, but also to variations in temperature, shock, vibration and
excitation. The output of the transducer will likely vary if operated from one end of its specified temperature range to the
other end. The electronics may also experience catastrophic failure if subjected to prolonged exposure at temperature,
vibration and humidity levels beyond the manufacturer's specifications.
6.2 There are many other characteristics such as linearity, hysteresis, repeatability, etc., that help quantify the
measurement accuracy of a position transducer. Other factors, though equally important, are more elusive and include

54

Application guidelines - Selection of position transducers

packaging, configuration, materials of construction and internal design. Each of these can be appraised only on the
basis of field-testing and/or experience.
6.3 All of the above factors must be considered along with the particulars of the application and the expertise of the
individuals involved in making the system perform as required. The wise buyer will choose a transducer based on
operating principles, specifications, price and the reputation of the seller.

Physical considerations

7.1 Two important considerations are the operating principle and the construction of the transducer. Both of these
considerations affect size, life, accessibility, maintainability and durability. The operating principle also influences
linearity, repeatability, resolution, temperature sensitivity, maximum velocity/response time and interface.
7.2 The operating principle involves the choice between a contact vs. non-contact type device. A properly installed
non-contact type device will typically have less maintenance and greater longevity than a contact type device.
7.3 The operating principle also determines the complexity of the signal-conducting electronics. A contact type
device, such as a resistive sensor, requires simpler electronics than non-contacting devices and, thus, is generally less
expensive. Additionally, the package length is closer to the operating length of the resistive sensor.
7.4 A transducer's internal construction must be rugged enough to stand up to physical abuse. The construction of
the position transducer installed in a cylinder may be dictated by the fluid media temperature or pressure. A protruding
transducer can make a convenient step for maintenance personnel climbing on the equipment. Falling debris is another
potential source of physical damage to the transducer or interconnect cables. When possible, transducers should be
accessible, but not in areas subjected to potentially damaging conditions. Internal mounting of the transducers may be
the best way of protecting the device.

Other specifications

8.1 There are many design features that do not appear in published specifications but that may be important over the
life of the application. These design factors and technologies all need to be examined against the user's actual
applications.
8.2 For transducers mounted on moving structures, one needs to consider mounting orientation, cable length and
routing. Certain locations or attitudes subject the transducer to severe vibration that can cause catastrophic failure.
8.3 External mounting is often preferred for retrofit applications because the expense of gun drilling and machining
the cylinder is avoided.

Application considerations

9.1 One of the first operating characteristics that should be considered is whether the transducer is a contact or noncontact device. These considerations are summarized in table 1.

55

Application guidelines - Selection of position transducers

Table 1 Initial considerations


Consider a contact device when
the following criteria are
important:

Consider a non-contact device


when the following criteria are
important:

Low initial cost

Longer life

Small size

Wider variety of outputs

Stroke length vs. package length

High velocity (for in-cylinder


hydraulic applications)

Simplicity

Noise immunity
Hostile environment/media

9.2 The application checklist in annex B was developed to highlight some of the main points to consider when
selecting a transducer. The list illustrates the type of information that must be gathered before specifying a transducer.
9.3

Always consider the total system when selecting a transducer.

9.3.1 If reference voltages from a controller are to be used as a power source for the transducer, make sure there is
enough current capability.
9.3.2

Make sure the controller can process the transducer output (digital or analog).

9.3.3 The controller is usually easier to set up if the command and feedback input signals are the same: both
1 to +10 or both 4 to -20 mA. If they are not the same, the controller needs to be able to scale and bias the feedback.
9.3.4 If the transducer provides a 4 to -20 mA signal, which is often used for longer distances, verify that the
controller input impedance is acceptable to the transducer. Typical value is 500 . Also verify whether the input to the
controller is differential (floating) or if the return side is connected to common. Some transducer outputs can be
common.
9.3.5 Consider the failsafe position, and define the command signals and required result. For example, if the
feedback cable breaks, should the cylinder retract or extend? Should a command of 0 V cause the cylinder to retract or
extend?
9.3.6

Update the speed.

10 Summary
It is evident that no one transducer can meet the design criteria of all applications. It is important to understand the
features and benefits of each position transducer. One must also be able to interpret the specifications and how they
will be affected by the particular application.

56

Application guidelines - Selection of position transducers

Annex A
(informative)
Glossary

A.1

ambient conditions: The conditions of the medium surrounding the case of the transducer.

A.2

CPC: Counts per centimeter.

A.3

CPI: Counts per inch.

A.4 CPR: Counts per revolution. The output pulses from an encoder. This is related to the number of light source
interruptions made by the scale. This quantity is also referred to as pulses per revolution (PPR).
A.5 compensation: Provision of a supplemental device, circuit or special materials to counteract known sources of
error. Its manufacturer typically builds these circuits into the transducer.
A.6

continuous rating: The rating applicable to a specified operation for an uninterrupted length of time.

A.7

drift: An undesired change in output over a period of time, which is not a function of displacement.

A.8 electromagnetic interference (EMI): An undesired change in the output of the transducer due to the presence
of magnetic or electric fields near the transducer or system wiring. This is a complex subject treated by other standards
writing organizations such as SAE, IEEE, FCC and ISO.
A.9

end points: The outputs at the specified upper and lower limits of the range of travel.

A.10 gradient: The inverse of the velocity of propagation of the magnetostrictive pulses through the waveguide.
A.11 insulation resistance: The resistance measured between specified insulated portions of a transducer when a
specified DC voltage is applied at room conditions, unless otherwise stated.
A.12 load impedance: The impedance presented to the output terminals of a transducer by the associated external
circuitry.
A.13 misalignment: The error resulting from mechanical deformation of the transducer during the mounting phase.
A.14 non-linearity: Linearity error. See also linearity (3.9).
A.15 sensitivity: The ratio of the change in transducer output to a change in the value of displacement.
A.16 span: The algebraic difference between the end points of the range.

57

Application guidelines - Selection of position transducers

Annex B
(informative)
Application checklist
Use this checklist to help determine the type of position transducer needed for your application. Refer to the document
or glossary for explanation, clarification and elaboration of the terminology and concepts contained in the checklist.
Performance
Mechanical stroke:
______________ units _____________
Measurement stroke:
______________ units _____________
Maximum pressure (in hyd. cyl., if so mounted): _____________ units _____________
Desired repeatability:
______________ units _____________
Resolution:
______________ units _____________
Maximum hysteresis/linearity: __________ units _____________
Maximum velocity:
______________ units _____________
Environment
Type of application:

______________ Industrial _________ Mobile


______________ Laboratory ________ Other
Pressure media (type of fluid): ______________________________________
Vibration:
Low __________ Medium ___________ High _____________
Shock:
Low __________ Medium ___________ High _____________
Humidity:
Low __________ Normal ___________ High _____________
Hazardous environment exposure (yes or no) _____________ If yes type _________
Operating temperature:
of fluid:
Minimum _______________ Maximum _________
ambient:
Minimum _______________ Maximum _________
Storage temperature:
of fluid:
Minimum _______________ Maximum _________
ambient:
Minimum _______________ Maximum _________
Agency/certification:
________________________________________
CE mark:
_______________________________________________
NEMA/IP class:
_______________________________________________

Electrical
Input (excitation): AC __________ DC _______________ Current __________ Other _________
Output requirements: mV ______ V _______________ 4 20 mA _________
Hz _______________________ CPC (CPI) or CPR ___________________ Other___________
EMI exposure: low ____________ medium ___________ high _____________
Other _____________________________________________
Zero adjust: (yes or no) ______________
Full scale adjust: (yes or no) ___________
Response time:__________ ___________ units ____________
Current consumption:
Maximum size: ________
Weight: ______________
Mounting: Foot _________
Termination:
Cable __________
Terminals _______
Connector ______

58

Other
Physical
x ________________ x _____________ units
units _____________
Rod end(s) _______ Shaft _________ Integral __________ Other ________
length ___________ units __________
type _____________
type _____________

Vous aimerez peut-être aussi