SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

SDG963 SDG96NSDG96E
ELECTRIC POWER METER
Users manual

NANJING SHUANGYOU ELECTRIC


AUTOMATION CO.,LTD.
Add: No.80, Nanrui Road, Nanjing, 210037, China
Tel:0086-025-83479330 Fax:0086025-83479330 E-mail:syo@vip.163.com
htpp//www.chinasyo.com

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

SYO

CATALOG
1 General Description ..................................................................................................... 3

1.1

Application Area ................................................................................................. 3

1.2

Main Function..................................................................................................... 3

1.2.1

Measurement Functions ................................................................................ 3

1.2.2

I/O Functions.............................................................................................. 3

1.2.3

Communications ........................................................................................... 4

1.2.4

Memory ........................................................................................................ 4

1.2.5

High Pricision Measurements......................................................................... 4

Install & Connection ................................................................................................... 4


2.1

Installation .......................................................................................................... 4

2.2

Connection .......................................................................................................... 4

2.2.1

Terminals Defined ......................................................................................... 5

2.2.2

Measureing Loop Connection ........................................................................ 5

2.2.3 Connection Attentions...................................................................................... 6


3

SDG96 Opration Explaination...................................................................................... 6


3.1

Display setting ..................................................................................................... 6

3.2

Parameter setting ................................................................................................ 7

Usage and Maintenance ............................................................................................. 9

Transportation and Storage ........................................................................................ 9

Technic Target .......................................................................................................... 10

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

1 General Description
SDG96 is an intelligent multi-parameter meter and control device. It is widely used in
electric power system. It directly measures power parameters as follows: voltage, current, power,
power factor, frequency, electric energy and etc. It monitors four switch inputs and outputs two
relays.
SDG96 has one independent RS485 communication interfaces which enable convenient
communications with other devices. It also has opening communication agreement open to users.

1.1 Application Area


SDG96 is used as a remote unit in electric power system as well as a versatile measure
meter.
It measures precisely electric energy.

1.2 Mail Functions

1.2.1 Measurements
SDG96 provides real time parameters as follows:
VoltagesUaUbUcUabUbcUca
CurrentsIaIbIc
Four quadrant active powersPaPbPcPs
Four quadrant reactive powersQaQbQcQs
Apparent powersVaIaVbIbVcIc
Power factorsPFaPFbPFcPF
FrequencyF
Energy measurementspositive active energynegative active energy, positive reactive
energynegative reactive energy

1.2.2

I/O Ports

Two relay outputsused for alarm or control outputs.


Four switch inputsused for monitoring ON and OFF status.

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

SYO

1.2.3

Communications

SDG96 has one independent RS485 communication interfaces which to receive and
send

data signals at one time. It has MODBUS communication agreement.

1.2.4

Memory

To set one of the parameters, use the buttons on the panelsuch as the ratio of current
or voltagecommunication address, baud and so on. All settings are reserved in the EEROM
which does not lose any data even when power is off.

1.2.5 High Precision Measurement


In input dynamic range1000:1, the non-linearity is less than 0.2%, and active power error
is less then 0.2Saccording to IEC62053-22GB/T 17883-1998. Reactive power error is less
then 0.2Saccording to IEC62 053-23GB/T 17882-1999

Installation

2.1

Installation

SDG96 is installed in an embed way. The whole size is 9191 m .

Attentions
SDG96 has no adjustable element. Dont open the crust; otherwise the power will be off.

2.2

Connection

2.2.1

Terminals

The terminals of SDG96 are defined as show as figure 2:

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

21 22 23 24 25 26 27 28

29 30 31 32 33 34

B A01 A02 AOCOM

RS485

4-20mA

N PE PE

AC/DC 80 265V

11 12 13 14 15 16 17 18 19 20
IN1 IN2 IN3 IN4 INGND

J1 J1 J2 J2

Ia Ia Ib Ib Ic Ic Ua Ub Uc Un
1

Figure 2SDG96 terminals

2.2.2

Measurement loop

1. 3-phase/4-wires(3-CT)

2. 3-phase/3-wires(2-CT)

9 10

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

2.2.3

Connection Attentions

The communication cable must be shielded double-wire cable.


The terminal A and B are not exchangable.
The length of the cable is less then 1200 meters.
The section of wires shall be satisfied: The current loops are no less than 2.5 square
millimeterthe voltage loops are no less then 1.5 square millimeter.

SDG96

Multi-digit meter keys operating illustration

3.1

Display setting

Keys layout

ESC

MOV

ADD

ENT

MOVThe
ADDThe
1:
2:
3:

key to change displaying unit.


key to change displaying functions as follows:
3-phase currents
3-phase voltages
3-phase total active power , 3-phase total reactive power , 3-phase
average power factor.
4positive active powers energy, negative active powers energy, A-phase
frequency
After setting display mode and unit,To pressMOVorADDkey for several
seconds to write the data into the meter which will work in mode you have set.
MOVADD

Example 1:Selecting 3,To display 3-phase total active powers , 3-phase total
reactive powers , 3-phase average power factor .The unit is M.
The setting step is:
1 3: M

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

1. ADD 3 MOV
M
1.To press ADD key lighting arrowhead 3,to press MOV lighting M.
2. MOVADD3
2.To press MOVorADDfor three seconds ,This setting will write into The
meter which will work according to the setting.

K
M

V A W Wh
V

Var
A Varh
V PF
A Hz

3.2 Setting parameter

To press [ESC][ENT] for three seconds at same time ,you can set parameters:PO-P9.
[ESC][ENT]3 P0-P9

_P0_
CT
LED1 LED2 LED3 LED4
Note: LED1,LED2,LED3,LED4 are fore digit tubes.
LED1,LED2,LED3,LED4 .
When you enter the interface of parameter setting ,The keys are defined as follows:

ESCEscape
MOVRight move
ADDAdd 1
ENTenter
P0: Setting the ratio of current transformer CT .The default value is 1.
CT 1
The range is 09999the setting value=main current/secondary current.

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

09999= /
Example 2: The ratio of currents is 100/5,then setting value CT=20.
2 100/5A CT = 100/5 = 20
The steps are:

1. To press [ESC] and [ENT] keys for three seconds at same time ,It will enter
the interface of setting parameters ,it shown as:
[ESC][ENT]3

_P0_
CT
2.To press ENT key ,it will enter the menu.ENT

_P0_
CT
1
3. To press MOV key to change the parameter.MOV

_P0_
CT
0001

Note: The digit selected will be flash ,to press ADD once the digit
will be add one.
ADD 1
4. To press MOV twice ,the third digit will be selected ,To pressADD
key twice change the digit to two ,then press MOVkey once the forth digit will
be selected, to pressADDkey change the digit to zero.
MOV 2 3 ADD 2MOV 1 4
ADD 0
5.To press ENT key to write the parameters into the meter.
ENT

_P0_
CT
20

6.To press ESC key return to the main menu . To press ADD key to change
other parameters.

To press ESC key twice to exit setting menu .


ESCADD 1
ESC

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

_P0_
CT

_P1_
PT
ADD

_P2_
ADD
ADD

P1: To set the ratio of voltage transformer PT .the default value is 1


PT 1.0
The range is 0999.9the setting value=main voltage value/secondary voltage
value.
0999.9= /
Setting steps are shown as example 2.
2.

P2: To set the address of the meter ,the default value is 1.


1
The range is 1255 1255
Setting steps are shown as example 2.
2.

P3: To setting communication and connection modes , the default value


is 404.
404
LED2 baud
060011200224003480049600519200
LED3checking bit
0null 1odd 2even

LED4connection mode
33-phase /3-wires 4
3-phase/4-wires
Example 2:setting steps
2.
P4: To setting voltage and connection mode, the default value is 14.
14
LED3: Setting voltage mode,
1:line voltage, 2:phase voltage.
LED3
12
LED4: connection mode
3:3 phases 3 wires ,4:3 phases 4 wires

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

LED4
34
Setting steps are shown as example 2.
2.
P5:Setting analog output(4-20mA)

P_05
A

1. To press ENTsetting menu.


ENT

P_05
A1.00
577
2. To press ADDselecting chanel A1,A2,A3.
ADD A1,A2,A3
A1: AO1A2: AO2, A3: AO3
3. To press MOVsetting parameter needed
MOV

P_05
A1.00
577
The parameter type, the order is showed in communication list,

The parameters maxium scale.

10

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

Example 3: A01 to output 3phases average voltage, The second voltage is 57.7V
A02 to output 3phases average current, The second current is 5A.
3A01: 57.7V
A02: 5A

P_05
A1.03
577
After setting ,To press ENTkey, then press ADDselecting channel A2.
ENTADD A2

P_05
A2.00
577
To press MOVkey setting the parameter you need.
MOV

P_05
A2.07
5000
After setting to press ENTkey, then ESCkey to exit.
ENTESC
P6: To permit

the energy reset YES or NO ,the default is NO.

YES NO NO

P_06
Clre

1. To press ENTkey enter the setting menu.


ENT

11

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

P_06
Clre
no
2. To press ADDkey to select YES or NO.
ADD YES-NO
3. To press ENTkey to write the setting into the meter
ENT
4. To press ESC key once to exit, to press ESC key twice to exit main
menu

ESCESC
P7: To execute the energy reset YES or No , the default value is NO.
YES NO NO
After reset P6 and P7 return to default value.
P6,P7

P_07
Clr

1. To press ENTkey enter the setting menu.


ENT

P_07
Clr
no
2. To press ADDkey to select YES .
ADD YES

12

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

P_07
Clr
yes
3. To press ENTkey to clear energy at zero.
Note :To execute the energy reset need that P6 is selected YES at first and P7
is selected YES, After reset shown as follow:

ENT
P6: YES P7:
YES

P_07
Clr
0000
4. To press ENTkey once to exit, to press ENTkey twice to exit from setting
menu.
ESCESC
P8The states of switch IN and OUT

P_08
00
0000
switch out J1

IN1 IN2 IN3 IN4

switch in .
O:open

J2. J1 J2

1:close.

* P9: setting clock


Setting current calendar and time.

13

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

P-09
C-1

1. To press ENTkey enter the setting menu.


ENT

P-09
2010.
02.28
Date: 2010.02.28
2010.02.28
2. To press MOVkey, the selected digital will be flash, To press ADD
key to change it. After change it, to press ENTkey to finish calendar setting.
To press ADDkey again enter time setting in same way as calendar.
MOVADD
ENTADD

P-09
15.
26.38
Time:15:26:38
15.26.38
3. To press ESCkey return to main menu.
ESC
* P10: setting energy time interval

14

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

P-10
C-2

1. To press ENTkey enter the setting menu.


ENT

P-10
b0_0
00.00
b0~b7 express respectively 8 time interval.
b0_x

x: 0-null, 1-sharp 2-peak 3-average 4-valley

LED1 LED2: hour


LED3 LED4: minute

b0~b7 8
b0_x

x: 0- 1- 2- 3- 4-

LED1 LED2:
LED3 LED4:
2. To press MOVkey, the selected digital will be flash, To press ADD
key to change it. After change it, to press ENTkey to finish . To press ADDkey again
enter next time interval setting in same way .
MOVADD
ENTADD

P-10
b1_1
07.30
3. To press ENTkey enter the setting menu.

15

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

ESC

* P11:Setting energy record time. Default 01.00(every mouth 1st 00:00:00)


01.00( 1 0 )

P-11
C-3

1. To press ENTkey enter the setting menu.


ENT

P-11
C-3
01.00

scope()01.00~28.23

2. To press MOVkey, the selected digital will be flash, To press ADD


key to change it. After change it, to press ENTkey to finish.
MOV
ADD
ENT
3. To press ESCkey enter the setting menu.
ESC

P12:Setting circulating display. ON:circulate, OFF: no circulate, default is ON


ON OFF ON

P-12
LOP

16

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

1. To press ENTkey enter the setting menu.


ENT

P-12
LOP
ON
2. To press ADDkey to select ON-OFF.
ADD ON-OFF
3. After selecting ,to press ENTto write into meter.
ENT
4.To press ESCkey enter the setting menu.
ESC
P13: Factory check menu, entering need password.

P-13
PSD

* SDG96

Usage and Maintenance


Check all wires are correctly connected, especially the power wires, before the device is
turned ON.
When the power lamp is on, the power supply is normal; otherwise, check the wires and the
voltage value.

17

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

Transportation and Storage

The product will be packed when it is transported. Keep it clean and uncrushed. The ambient
temperature range is 2070. Relative humidity must not exceed 90%

Technology Targets
As follows in list 4:
parameters
U, I are 0.2%P, Q are 0.2%
Ep is 0.2%Eq is 0.2%

Precision level
Display

0.4LED

Connection

3-phase 3-wire/4-wire
AC100V220V400V

Range

10288V(phase voltage)

Over load

Long timerating1.2; Momentrating2(10


sec.)

Consumption

<0.2VA(per phase)

Impedance

>300k

Rating

AC 1A5A

Range

0.0056A

Over load

Long timerating1.2; Momentrating10(5


sec.)

Consumption

<0.4VA(per phase)

Impedance

<20m

Voltage

Rating

AC Inputs
Current

Frequency

50/60Hz10%

Electric energy
Power
supply
Output

Size

43

+Ep, -Ep, +Qp,-Qp

Range

ACDC 80V270V

Consumption

0.4VA

Communication

RS485MODBUSRTU

Pulse output

Two pulse outputslight couple

Relays ability

AC 220V 5A

Input

Ordinary opening

Work condition

1055relative humidity93%
Sea level2500m

Insulation voltage

input>2kVoutput>2kV
power supply>1.5kV

Insulation resistance

100M

Panel size

9696mm

Hole size

9191mm

18

SYO

SDG963 SDG96NSDG96E ELECTRIC POWER METERUsers manual

Packing size

lengthwidthheight: 157140110