16 kV to 38 kV
vacuum circuit breaker operator module
instruction manual
Installation operation maintenance E50001-F710-A251-X-76US
Important
The information contained herein is
general in nature and not intended for
specific application purposes. It does not
relieve the user of responsibility to use
sound practices in application, installation,
operation and maintenance of the
equipment purchased. Siemens reserves
the right to make changes in the
specifications shown herein or to make
improvements at any time without notice
or obligations. Should a conflict arise
between the general information
contained in this publication and the
contents of drawings or supplementary
material or both, the latter shall take
precedence.
Qualified person
For the purpose of this manual a qualified
person is one who is familiar with the
installation, construction or operation of
the equipment and the hazards involved.
In addition, this person has the following
qualifications:
I s trained and authorized to
de-energize, clear, ground and tag
circuits and equipment in accordance
with established safety procedures.
Table of contents
Introduction
4 -5
6 -8
9 - 10
Vacuum interrupter/operator
11 - 28
Maintenance
29 - 43
Overhaul
44 - 48
49 - 52
Appendix
53 - 58
Note:
These instructions do not purport to cover
all details or variations in equipment, nor
to provide for every possible contingency
to be met in connection with installation,
operation or maintenance. Should further
information be desired or should particular
problems arise that are not covered
sufficiently for the purchasers purposes,
the matter should be referred to the local
sales office.
The contents of this instruction manual
shall not become part of or modify any
prior or existing agreement, commitment
or relationship. The sales contract contains
the entire obligation of Siemens Energy,
Inc. The warranty contained in the contract
between the parties is the sole warranty of
Siemens Energy, Inc. Any statements
contained herein do not create new
warranties or modify the existing warranty.
Introduction
Introduction
Signal words
Introduction
Hazardous Procedures
In addition to other procedures described
in this instruction manual as dangerous,
user personnel must adhere to the
following:
1. A
lways work only on a de-energized
circuit breaker. The circuit breaker
should be isolated, grounded and
have all control power removed
before performing any tests,
maintenance or repair.
2. A
lways perform maintenance on the
circuit breaker after the springcharged mechanisms are discharged
(except for test of the charging
mechanisms). Check to be certain
that the indicator flags read OPEN and
DISCHARGED.
3. A
lways let an interlock device or
safety mechanism perform its
function without forcing or defeating
the device.
Heavy weight.
Improper lifting or hoisting can result in death, serious injury
or property damage.
Obtain the services of a qualified rigger prior to hoisting the
circuit breaker to assure adequate safety margins in the hoisting
equipment and procedures to avoid damage.
Introduction
Receiving procedure
Make a physical inspection of the shipping
container before removing or unpacking
the circuit breaker.
Check for shipment damage or indications
of rough handling by the carrier. Check
each item against the manifest to identify
any shortages.
Accessories (as applicable) such as the
manual charging crank, racking crank or
split-plug jumper are shipped separately.
8. O
btain the original carrier inspection
report and forward it with a copy of the
noted delivery receipt to Siemens.
Approval must be obtained by Siemens
from the carrier before any repair work
can be performed.
efore approval can be obtained,
B
Siemens must have the documents
referenced in the paragraph above. The
carrier inspection report and/or drivers
signature on the delivery receipt does
not constitute approval to repair.
Note: Any determination as to whether the
equipment was properly loaded or properly
prepared by shipper for over-the-road
travel cannot be made at the destination.
Shipments are not released from the
factory without a clear bill of lading.
Approved methods are employed for
preparation, loading, blocking and tarping
of the equipment before it leaves the
Siemens factory. If the equipment is
received in a damaged condition, this
damage to the equipment has to have
occurred while en route due to conditions
beyond Siemens control. If the procedure
outlined above is not followed by the
consignee, purchaser or their agent,
Siemens cannot be held liable for repairs.
Siemens will not be held liable for repairs
in any case where repair work was
performed prior to authorization from
Siemens.
Indoor storage
1. C
arefully remove the shipping carton
from the circuit breaker. Keep the
shipping pallet for later use if the
circuit breaker is to be stored prior to
its installation.
Outdoor storage
Outdoor storage is not recommended.
When no other option is available, the
circuit breaker must be completely covered
and protected from rain, snow, dirt and all
other contaminants.
Space heating
Space heating must be used for both
indoor and outdoor storage to prevent
condensation and corrosion. When
equipment is stored outdoors, 250 watts
per circuit breaker of space heating is
recommended. If the circuit breaker is
stored inside the switchgear enclosure and
the switchgear is equipped with space
heaters, energize the space heaters.
10
1. O
pen control-power circuit by
opening the control powerdisconnect device.
2. E
nergize (close) the control powercircuit disconnect.
3. U
se the Close and Open controls
(refer to Figure 1) to first Close and
then Open the circuit breaker
contacts. Verify contact positions
visually by observing the OPEN/
CLOSED indicator on the circuit
breaker.
4. D
e-energize control power by
repeating Step 1. If a split-plug
jumper was used for temporary
control-power connections,
disconnect the split-plug jumper from
the switchgear first and next from
the circuit breaker.
5. P
erform the spring-discharge check
again. Verify that the closing spring is
discharged and the primary contacts
of the circuit breaker are open.
Final mechanical inspections without
control power
1. Make a final mechanical inspection of
the circuit breaker. Verify the contacts
are in the open position, and the
closing spring is discharged.
2. V
erify mechanical condition of
springs.
3. Check for loose hardware.
Vacuum interrupter/
operator
Introduction
The type 3AH vacuum circuit-breaker
operator is intended for application in a
drawout truck for use in medium-voltage
metal-clad switchgear and for stationary
applications, such as the type SDV6
outdoor distribution circuit breaker. The
type 3AH circuit breaker conforms to the
requirements of ANSI/IEEE standards,
including C37.20.2, C37.04, C37.06,
C37.09 and C37.010.
Rating plate
CLOSE
pushbutton
Opening for
manual spring-charging
CHARGED/DISCHARGED
indicator
OPEN
pushbutton
CLOSED/OPEN
indicator
Operations counter
Figure 1: Front panel controls of circuit breaker and manual charging of closing spring
Pole head
Upper
connection
pad
Pole plate
Upper post
insulator
Mechanism
housing
Vacuum
interrupter
Strut
Lower post
insulator
Lower
connection
pad
Pole bottom
Contact pressure
spring
Insulating
coupler
Vacuum interrupter/
operator
Fixed contact-current connection
Ceramic insulator
Arc shield
Fixed contact
Moving contact
Ceramic insulator
Metal bellows
Guide
Vacuum interrupter/
operator
Vacuum interrupter/operator module
The vacuum interrupter/operator module
consists of the three poles, each with its
vacuum interrupters and primary
insulators, mounted on the common
operating mechanism housing. This
module is shown in Figure 4.
13
Vacuum interrupter/
operator
4. O
perate all these functions
automatically through an electrical
charging motor, cutout switches, an
anti-pump relay, a close coil, an open
coil and an auxiliary switch.
5. Provide indication of the circuit
breaker status (OPEN/CLOSED), spring
condition (CHARGED/DISCHARGED)
and number of operations.
Pole head
Upper
connection
pad
Operator housing
Strut
Vacuum
interrupter
Moving
contact
Lever
Centering
piece
Jack
shaft
Terminal
clamp
Flexible
connector
Eye bolt
Pole bottom
Angled lever
Insulating
coupler (48.0)
Guide link
Contact pressure
spring (49.0)
14
Construction
The essential parts of the operating
mechanism are shown in Figures 6 and
7. The control and sequence
of operation of the mechanism is
described in Figure 8.
Motor-operating mechanism (refer to
Figure 6)
The spring-charging motor (50.4) is
bolted to the charging mechanism (50.2)
gear box installed in the operator
housing. Neither the charging
mechanism nor the motor require any
maintenance.
Mode of operation
The operating mechanism is of the
stored-energy trip-free type. For
example, the charging of the closing
spring is not automatically followed by
the contacts changing position, and
tripping function prevails over the
closing function.
When the stored-energy mechanism has
been charged, the mechanism is ready
for a closing operation at any time.
The mechanical energy for carrying out
an "Open-Close-Open" sequence for
auto-reclosing duty is stored in the
closing and opening springs.
Charging
The details of the closing spring charging
mechanism are shown in Figure 6. The
charging shaft is supported in the
charging mechanism (50.2), but is not
coupled mechanically with the charging
mechanism. Fitted to it are the crank
(62.2) at one end, and the cam (62.3),
together with lever (62.5), at the other.
Vacuum interrupter/
operators
Figure 6: Stored-energy operating mechanism (circuit breaker shown in OPEN position) (straight linkage shown)
55.2
50.2
50.5
62.1
62.5.2
62.2
68.0
53.0
55.1
62.0
53.1
50.4.1
54.1
55.0
54.0
50.4
68.1
64.0
58.0
59.0
60.0
50.2 - Charging mechanism gear box
50.3 - Charging flange
50.3.1 - Driver (not visible)
50.4 - Spring-charging motor 88
50.4.1 - Limit switches
50.5 - Manual spring-charging port
53.0 - Close pushbutton
53.1 - Close coil 52SRC
54.0 - Open pushbutton
54.1 - Trip coil 52T
55.0 - Closing spring-charge
indicator
55.1 - Linkage
55.2 - Control lever
61.8
63.5
63.0 63.1
62.8.3 - Trip-free coupling lever*
63.0 - Jack shaft
63.1 - Lever - phase C
63.5 - Lever - phase B
63.7 - Lever - phase A
64.0 - Opening spring
68.0 - Auxiliary switch
68.1 - Auxiliary switch link
15
Vacuum interrupter/
operator
Closing (refer to Figures 6-11)
If the circuit breaker is to be closed
manually, the closing spring is released
by pressing the Close button (53.0). In
the case of remote electrical control, the
close coil 52SRC (53.1) unlatches the
closing spring (62.0).
62.8.1
62.8.2
62.8
54.0
64.3.1
64.3
16
Vacuum interrupter/
operator
Trip-free operation
(refer to Figures 6 and 7)
Trip-free for all drawout circuit
breakers and some fixed-mounted
circuit breakers
The trip coupling rod (62.8 together with
62.8.1 and 62.8.2) permits the
immediate de-coupling of the drive lever
(62.6) and the jack shaft (63.0) to
override closing action by trip command
or by means of the racking interlocks.
The trip-free coupling rod (62.8) forms a
link between the drive lever (62.6) and
the jack shaft (63.0). The rigidity of this
link depends upon a spring-return latch
(62.8.1) carried within the coupling rod.
The latch pivots within the coupling rod
and is normally positioned to ensure the
rigidity of the coupling rod. Trip-free
coupling link (62.8.2) and trip-free
coupling lever (62.8.3) cause the springreturn latch position to be dependent
upon the normal tripping components
and the racking interlock. Thus,
whenever a trip command is applied or
the circuit breaker is not in the fully
CONNECT or TEST position, the trip-free
coupling rod is no longer rigid,
effectively decoupling the drive lever and
jack shaft. Under these conditions the
vacuum interrupter contacts cannot be
closed.
Trip-free for the type SDV6 outdoor
distribution circuit breaker and some
fixed-mounted circuit breakers
For the type SDV6 outdoor distribution
circuit breaker and some other fixedmounted circuit breakers, the drawout
trip-free linkage (refer to Figures 7-11) is
replaced with simplified linkage. The
trip-free coupling rod (62.8) is replaced
with a straight coupling rod (refer to
Figure 6), and other parts associated
with drawout interlocking are eliminated.
17
Vacuum interrupter/
operator
Figure 8: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism OPEN, closing spring DISCHARGED
62.5.1
62.5
62.1
62.3
50.3
62.2
50.3.1
62.5.2
53.0
64.5*
62.6
62.2.2
53.1
64.2.2
64.0*
62.8.1
64.2.1
54.0
62.8.3
62.8.2
62.8*
64.2*
63.5*
64.3.1*
62.8.5
64.5*
63.0*
48.0*63.5*
63.7
63.5
63.1
62.8.8
18
62.8.7
62.8.6
Vacuum interrupter/
operator
Figure 9: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism OPEN, closing spring DISCHARGED
.
62.2
50.3
62.3
62.5
62.5.1
62.2.2
64.5*
54.1*
62.8*
64.2*
64.3*
* F
or a type SDV6 outdoor circuit breaker and
some fixed-mounted circuit breakers, tripfree coupling rod (62.8) and other parts
associated with drawout interlocking are
eliminated.
** Items moved from position shown in
Figure 11 on trip operation. Underlined
items moved from position shown in
Figure 8 on closed spring-discharge
operation.
50.3.1
62.1
63.5*
63.0*
64.5*
48.0* 63.5*
63.7*
63.5*
63.1*
19
Vacuum interrupter/
operator
Figure 10: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism CLOSED, closing spring DISCHARGED
62.5.1
62.5
62.1
62.2
62.5.2
62.3
53.0
53.1
62.6
62.2.2
64.5
63.5
62.8
63.7
63.5
63.1
48.0
63.0
63.5
20
Vacuum interrupter/
operator
Figure 11: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism CLOSED, closing spring CHARGED
62.2
50.3.1
62.1
62.5 50.3
62.5.1
62.3
62.2.2
21
Vacuum interrupter/
operator
The special hand crank automatically
disengages if the spring-charging motor
operates. In order to avoid injuries as a
result of the motor suddenly starting up,
the circuit breaker spring must only be
charged manually with the special hand
crank (50.0).
22
Vacuum interrupter/
operator
Figure 12: Operator sequential operation diagram
Closing
Control
voltage applied.
Undervoltage device
27 picks up.1
Spring-charge motor
(88.0) energized.
Continuous
closing command.
circuit
circuit
breaker
breaker
No action! Open 52b
open.
closed.
in series with close
Closing
coil (52SRC) blocks
command
closing springwhen
release.
closing
spring not
charged.
52a contacts in
series with the trip
coil (52T) close to
enable a trip
opertion.
Circuit breaker
auxiliary contacts
52a and 52b change
state.
Tripping
Trip
command.
Undervoltage device (27) is
activated by opening a NC
contact in series with 27 or by
loss or reduction of tripping
voltage.1
Undervoltage device
27 unlatches the
opening spring.1
23
Vacuum interrupter/
operator
53.0
50.1
50.0
55.0
54.0
50.5
50.6
50.0
Vacuum interrupter/
operator
Figure 15: Typical elementary diagram
(+)
01
T
01
C
SD16
SD13
21
41
42
SD3
Motor
13
DC supply
22
88
21
LS41
14
31
32
21
LS22
22
MI1
21
TB
1
2
3
4
5
6
SD15
52b
21
52Y
22
14
LS3
13
A1
22 A2
MI2
13
21
14
SD1
SD4
52Y
31
52Y
32
24
52b
23
52a
A1
A1
52SRC
22
LS21
22
52T
52Y
A2
SD14
A2
34
LS9
33
52a
SD2
(-)
SD11
54
53
SD9
64
52a
63
SD12
88.0
91
52a
- Spring-charging motor
92
SD10
LS
SD7
101
52b
102
52b
SD5
74
73
84
52a
83
SD8
- Spring-charged switch
52a
52b
01/T
-W
hite indicating light
(spring-charged)
52Y
52a
111
112
121
52b
52b
122
SD6
Standard:
Fuses in close circuit. Slugs in trip
circuit (fuses optional).
Shown with springs discharged, triplatch reset, circuit breaker open,
connect or withdrawn position.
25
Vacuum interrupter/
operator
21.0
25.0 27.0
33.0
31.0
23.0
11.0
7.0
1.0
13.0
9.0
15.0
5.0
3.0
3.0 - Housing
25.0 - Latch
27.0 - Spring
23.0
25.0
21.0
27.0
Vacuum interrupter/
operator
Construction and mode of operation of
secondary shunt-release and
undervoltage release (refer to Figures
16, 17 and 18)
Position A: locked
29.0
23.0
29.0
Cancel the lock for the undervoltage release by shifting the locking screw (29.0)
from A to B.
23.0 - Striker pin
29.0 - Screw
23.0
01
T
SD5
24
23
120 or 240 Vac
supply
52a
Capacitor
A1
(+)
52T
A2
34
33
52a
(-)
Resistor
2
(+)
Rectifier
(-)
Capacitor trip
Vacuum interrupter/
operator
Since the striker pin of the undervoltage
release 3AX1103 is latched only when the
armature is energized, the undervoltage
release is provided with a screw (29.0), for
locking the striker pin (23.0) in the normal
position for adjusting purposes or for
carrying out trial operations during circuit
breaker servicing. Position A (locked)
disables the undervoltage release. Position
B (unlocked) is the normal operating
position.
Capacitor trip device
The capacitor trip device is an auxiliary
tripping option providing a short-term
means of storing adequate electrical
energy to ensure circuit breaker tripping. If
provided, a capacitor trip device must be
located on the drawout truck or in the
stationary circuit breaker enclosure, as
space is not available inside the type 3AH
operator housing.
This device is applied in circuit breaker
installations lacking independent auxiliary
control power or station battery. In such
installations, control power is usually
derived from the primary source. In the
event of a primary ac source fault or
disturbance the capacitor trip device will
provide short-term tripping energy for
circuit breaker opening due to protective
relay operation or operation of a circuit
breaker control switch.
The capacitor trip converts 120 or 240 Vac
control voltage to a dc full-wave voltage
that is used to charge a large capacitor to
the peak of the converted wave (refer to
Figure 19).
28
Shock absorber
Circuit breakers are equipped with a
hydraulic shock absorber (61.8) (refer to
Figure 6). The purpose of this shock
absorber is to limit overtravel and rebound
of the vacuum interrupter movable
contacts during the conclusion of an
opening operation. The shock absorber
action affects only the end of an opening
operation.
Auxiliary switch (52a/b)
Figure 6 shows the circuit breaker
mounted auxiliary switch (68.0). This
switch provides auxiliary contacts for
control of circuit breaker closing and
opening functions. Contacts are available
for use in relaying and external logic
circuits. This switch is driven by linkage
(68.1) connected to the jack shaft (63.0).
The auxiliary switch contains both "b"
(normally Closed) and "a" (normally Open)
contacts. When the circuit breaker is open,
the "b" contacts are closed and the "a"
contacts are open.
Spring-charging motor (88.0)
Spring-charging motors (50.4) (refer to
Figure 6) are available for either ac or dc
operation. If operated with ac voltage, a
rectifier is installed in the circuit breaker.
Maintenance
Failure to maintain the equipment can result in death, serious injury, property damage or
product failure, and can prevent successful functioning of connected apparatus.
The instructions contained herein should be carefully reviewed, understood and followed.
The maintenance tasks in Table 1 must be performed regularly.
Maintenance
30
Maintenance
The use of unauthorized parts in the repair of the equipment, or tampering by unqualified
personnel can result in hazardous conditions, that can result in death, serious injury or
property damage.
Follow all safety instructions contained herein.
31
Maintenance
Circuit
Number of
breaker type years/closing
operations
(whichever
comes first)
SDV6
All others
5-years/
10,000
operations
10-years/
10,000
operations
32
F
or all lubrication (except electrical
moving or sliding surfaces), use one of
the following:
Klber
Isoflex Topas L32N (spray)
(part 15-172-879-201).
Source:
K
lber Isoflex Topas L32 or L32N:
Klber Lubrication North America L.P.
www.klueber.com.
Fastener check
Inspect all fasteners for tightness. Both
locknuts and retaining rings are used.
Replace any fasteners that appear to have
been frequently removed and replaced.
Manual spring-charging and contacterosion checks
Perform the manual spring-charging check
contained in the section describing the
installation check and initial functional
tests (refer to pages 9-10). The key steps of
this procedure are repeated here:
1. Insert the hand-charging crank into the
manual-charge socket at the front of
the operator control panel. Turn the
crank clockwise (about 48 revolutions)
to charge the closing spring. Continue
cranking until the CHARGED flag
appears in the window of the spring
indicator.
2. P
ress the Close (black) pushbutton. The
contact-position indicator on the
operator control-panel should indicate
that the circuit breaker contacts are
Closed.
Maintenance
Figure 20: Operator mechanism lubrication
33
Maintenance
3. P
erform the contact-erosion check.
Contact erosion occurs when high
fault-currents are interrupted.
Determination of acceptable contact
condition is checked by the visibility of
the white contact-erosion mark shown
in Figure 21. The white contact-erosion
mark is located on the movable stem of
the vacuum interrupter, near the
plastic guide-bushing. The contacterosion check procedure is:
a) Be sure the circuit breaker primary
contacts are Closed.
b) O
bserve the white contact-erosion
mark (refer to Figure 21) of each
pole. When any part of the white
contact-erosion mark is visible,
contact wear is within acceptable
limits.
4. P
ress the red Open pushbutton after
completing the contact-erosion check.
Visually verify the Discharged condition
of the closing spring and that the
circuit breaker contacts are Open.
5. P
ress the black Close pushbutton.
Nothing should happen. The manualspring check should demonstrate
smooth operation of the operating
mechanism.
34
Maintenance
1. O
nce the circuit breaker springs are
charged, move the switchgearmounted Close/Trip switch to the Close
position. Verify by both the sound of
the circuit breaker closing and by the
main contact status indicator that the
circuit breaker contacts are closed.
2. A
s soon as the circuit breaker has
closed, the automatic spring-charging
process is repeated.
3. A
fter a satisfactory close operation is
verified, move the switchgear-mounted
Close/Trip switch to the Trip position.
Verify by both the sound of the circuit
breaker opening and by the main
contact status indicator that the circuit
breaker contacts are open.
4. A
fter a satisfactory open operation is
verified, hold the circuit breaker
manual Trip button and apply and
maintain an electrical close signal. The
circuit breaker should close,
immediately trip, the close spring
should charge, and the circuit breaker
should not attempt to close again.
Completion of these checks demonstrates
satisfactory operation of auxiliary
switches, internal relays and open and
close coils.
35
Maintenance
Table 3: Typical vacuum interrupter contact life expectancy
Rated
maximum
voltage kV
Interrupting
class
MVA
Vacuum
interrupter
type
Graph
Right hand
limit of
curve (refer
to Figure
22)1
4.76
250
VS-17006
VS-17040
A
E
36
36
4.76
350
VS-15052
49
8.25
500
VS-15052
41
15.0
500
VS-17006
23
15.0
750
VS-15052
VS-17040
B
E
36
36
15.0
1,000
VS-15052
48
38.0
1,500
VS-30030
35
Rated
maximum
voltage kV
Interrupting
class
kA
Vacuum
interrupter
type
Graph
Right hand
limit of
curve (refer
to Figure
22)1
4.76
31.5
31.5
VS-17006
VS-17040
A
E
31.5
31.5
4.76
40
40
VS-15052
VS-17040
B
E
40
40
36
4.76
50
50
VS-15052
50
4.76
63
63
VS-17085
63
8.25
40
40
VS-15052
VS-17040
B
E
40
40
15.0
20
20
VS-17006
20
15.0
25
25
VS-17006
25
15.0
31.5
31.5
VS-17006
VS-17040
A
E
31.5
31.5
15.0
40
40
VS-15052
VS-17040
B
E
40
40
15.0
50
50
VS-15052
50
15.0
63
63
VS-17085
63
15.5
20
20
VS-25008
20
15.5
25
25
VS-25008
25
15.5
31.5
31.5
VS-15052
31.5
15.5
40
40
VS-15052
40
27.6
20
20
VS-25008
20
27.6
25
25
VS-25008
25
38.0
20
20
VS-30030
20
38.0
25
25
VS-30030
25
38.0
31.5
31.5
VS-30041
31.5
38.0
40
40
VS-30041
40
Footnote:
1.
Maximum symmetrical interrupting current rating of circuit breaker (refer to Tables 11 and 12).
Maintenance
Figure 22: Typical vacuum interrupter contact life curves
20,000
10,000
5,000
2,000
1,000
500
200
100
50
20
C
10
1
10
20 25 31.540 50
100
37
Appendix
Figure 22: Typical vacuum interrupter contact life curves (continued)
20,000
10,000
5,000
2,000
1,000
500
200
100
50
20
D
B F
10
1
10
20
40
50 63
100
38
Maintenance
Checks of the spring-charging motor
(88.0)
Anti-pump relay
If it is necessary to remove the connections
to the anti-pump relay, use care to avoid
damaging the relay. Replace the relay if the
relay terminals are damaged or loose in
the relay body.
Vacuum interrupters
The life expectancy of vacuum interrupters
is a function of the numbers of
interruptions and magnitude of current
interrupted (refer to Table 3 and Figure
22).
The vacuum interrupters must be replaced
before the number of mechanical
operations (listed in Table 2) are reached,
or when the contacts have been eroded
beyond allowed limits. Vacuum interrupter
replacement procedures are detailed in the
following maintenance instructions.
The vacuum interrupter contact life curves
(refer to Figure 22) are offered as a guide
to expected life.
39
Maintenance
High-potential tests
The next series of tests (vacuum-integrity
test and insulation tests) involve use of
high-voltage test equipment. The circuit
breaker under test should be inside a
suitable test barrier equipped with warning
lights.
Vacuum-integrity check (using dielectric
test)
A high-potential test is used to verify the
vacuum integrity of the circuit breaker. The
test is conducted on the circuit breaker
with its primary contacts in the Open
position.
Vacuum integrity test procedure
1. O
bserve safety precautions listed in the
danger and warning advisories.
Construct the proper barrier and
warning light system.
2. G
round the frame of the circuit
breaker, and ground each pole not
under test.
3. A
pply test voltage (refer to Table 4)
across each pole for one minute (circuit
breaker Open).
4. If the pole sustains the test voltage for
that period, its vacuum integrity has
been verified.
40
Maintenance
Equipment
maximum voltage
rating kV
Equipment rated
power-frequency
withstand kV (rms)
Maximum ac
rms test voltage
kV
Maximum dc
average test
voltage
4.76
19
14
20
8.25
36
27
38
15.0
36
27
38
15.5
50
38
53
27.6
60
45
64
38
80
60
85
41
Maintenance
48.0 - Insulating coupler
48.6 - Lever
48.6
7. F
or drawout applications, connect all
points of the secondary disconnect
with a shorting wire. For stationary
applications, disconnect secondary
circuits for the operating mechanism
by disconnecting the multiple pin-plug
at the upper right corner of the
operator, and connect all pins on the
operator side with a shorting wire.
Connect the shorting wire to the highpotential lead of the high-voltage
tester, and ground the circuit breaker
housing. Starting with zero voltage,
gradually increase the test voltage to
1,500 volts rms, 60 Hz. Maintain test
voltage for one minute.
48.0
48.6
48.0
Figure 23: Circuit breaker pole assembly/vacuum-check mechanical/contact-resistance
test
42
6. D
isconnect the leads to the springcharging motor.
9. D
isconnect the shorting wire, reattach
the multiple pin-plug (if applicable)
and reattach the leads to the springcharging motor.
10. P
erform contact-resistance tests of the
primary contacts. The resistance
should be read between the lower and
upper connection pads (refer to Figure
23).Contact resistance should not
exceed the values listed in Table 5.
Maintenance
Inspection and cleaning of circuit
breaker insulation
1. P
erform the spring-discharge check
(refer to page 9) on the circuit breaker
after all control power is removed. The
spring-discharge check consists of:
a) P
ressing the red Open pushbutton
b) P
ressing the black Close pushbutton
c) P
ressing again the red Open
pushbutton.
ll of these controls are on the circuit
A
breaker front panel (refer to Figure 1).
Visually verify the Discharged condition
of the springs.
Functional tests
Refer to the installation checklist in
the installation checks and initial
functional tests section of this
instruction manual (refer to pages
9-10). Functional tests consist of
performing at least three manual
spring-charging checks and three
automatic spring-charging checks.
After these tests are complete, and
the springs are fully discharged, all
fasteners and connections are
checked again for tightness and
condition.
Current
rating
A
Contact
resistance
Micro-Ohms
1,200
35
2,000
30
3,000
30
2. R
emove any inter-phase and
outerphase barriers if furnished
(applicable for certain types only).
3. C
lean barriers and post insulators using
clean cloth dipped in isopropyl alcohol.
4. R
eplace all barriers. Check all visible
fasteners again for condition and
tightness.
Note: Do not use any cleaning compounds
containing chlorinated hydrocarbons, such
as: trichlorethylene, perchlorethylene or
carbon tetrachloride.
These compounds will damage the
phenylene ether copolymer material used
in the barriers and other insulation on the
circuit breaker.
43
Overhaul
Circuit
breaker type
SDV6 outdoor
distribution
circuit breaker
All others
Closing
operations
10,000
Introduction
The following procedures along with the
troubleshooting charts in this instruction
manual (refer to pages 47-51), provide
maintenance personnel with a guide to
identifying and correcting possible
malfunctions of the circuit breaker.
Circuit breaker overhaul
10,000
1. R
eplace vacuum interrupter;
instructions follow.
2. Close coil (52SRC) and trip coil (52T).
a) R
emove two "push on" terminal
connections
b) Remove two M4 hex-head screws
and remove solenoid.
c) Install replacement coils with new
M4 x 10 hex-head screws (Siemens
part # 00-000-443-820) and new
lock washers for M4 (Siemens part #
00-000-288-316).
d) The coil-mounting screws must be
installed using thread locking
adhesive (Loctite #222, Siemens
part 15-133-281-007) and primer
(Loctite primer T (#7471), Siemens
part 15-133-281-005).
e) Connect wires to coils with new wire
terminals (Siemens part # 15-171600-002).
3. L ubricate operating mechanism
according to maintenance and
lubrication information (refer to page
32).
4. W
hen work is finished, operate circuit
breaker and close and open several
times, and check that all screw
connections are tight.
Replacement of vacuum interrupters
Replacement vacuum interrupters are
furnished as a complete assembly. They
have been completely tested and
dielectrically and mechanically
conditioned.
It is recommended that one vacuum
interrupter be removed and replaced
completely rather than removing two or
more vacuum interrupters at a time.
The following procedure in check list
format describes the procedure for
removing and replacing a vacuum
interrupter. Components may be identified
by reference to Figures 24 and 25.
44
Overhaul
Instructions herein apply for replacement
of all vacuum interrupters except type VS17085 vacuum interrupters, and
interrupters on 3,000 A circuit breakers
having the flexible connector (refer to 29.1
in Figure 24) electron-beam welded to the
moving terminal (refer to 36.1 in Figure
24) of the vacuum interrupter. These
interrupters must be replaced by factorytrained personnel. Contact Siemens
medium-voltage customer service at +1
(800) 347-6659 or +1 (919) 365-2200
outside the U.S.
1.4 R
emove coupling pin from the eye
bolt (36.3).
1.
1.8 U
sing a 24 mm socket with an
extension, loosen and remove hexcap screw fastening the pole head to
the post insulator. Completely remove
the pole head and set aside.
1.5 F
ree struts (28.0) from the pole head
(20.0). Loosen the strut hardware on
the pole bottom (40.0) and swing the
struts forward and downward.
1.6 L oosen screws fastening the
centering ring (28.1).
1.7 R
emove bolt (31.2), lock washer and
large washer at the stationary contact
of the vacuum interrupter (18 mm or
24 mm socket with extension).
1.9 G
rasp the vacuum interrupter (30.0)
and withdraw vertically. Assistance
may be required to work the terminal
clamp off the movable stem of the
vacuum interrupter. DO NOT USE
UNDUE FORCE OR TWISTING MOTION.
If the terminal clamp (29.2) cannot be
easily removed, STOP!, check to be
certain hardware is loose, and that
the terminal clamp (29.2) is not
binding.
2.
45
Overhaul
Figure 24: Vacuum interrupter replacement illustration
20.0
31.2
28.0
36.1
28.1
29.3
29.2
29.1
36.3
40.0
48.6
48.5
48.0
48.9
46
48.9
Overhaul
2.4 F
asten the pole head to the post
insulator (16.1) "finger tight" using
hex-head bolt, lock washer and flat
washer.
2.5 A
ttach struts (28.0) to the upper polesupport (20.0), replace hardware
(M10), but do not tighten at this
time.
2.6 C
ouple levers (48.6) and drive link
(48.9) to the eye bolt (36.3), using
the pin supplied. Apply retaining clips.
Appropriate pin is modestly
chamfered, not to be confused with
pin for the insulating coupler.
2.7 R
aise the terminal clamp (29.2)
against the step or the spacer (if
applicable) of the moving contact
(36.1) of the vacuum interrupter
(30.0) so that the radius of the
movable contact faces the connecting
surface of the flexible connector
(29.1). Employ technique illustrated
to fasten terminal clamp (refer to
Figure 25). Note opposing wrenches.
Tighten the bolt(s) of the terminal
clamp to a torque of 40 Nm (30 ft-lb),
taking care to see that the terminal of
the vacuum interrupter is not
subjected to excessive bending
movement.
Note: Excessive bending movement
exerted while fastening the terminal clamp
will damage the vacuum interrupter.
2.8 A
lign pole head (20.0) correctly and
tighten bolt fastening it to the post
insulator. Torque M16 bolt to 130 Nm
(96 ft-lb). Fasten securely all bolts
associated with struts (28.0).
Vacuum interrupter
Torque wrench
Direction of force (P)
Figure 25: Illustration showing required technique for fastening terminal-clamp hardware
2.9 T
ighten vacuum interrupter fastening
bolt (31.2) on the pole head (20.0)
holding the vacuum interrupter firmly
by its upper insulator and operate
levers (48.6), by hand, to see whether
the movable contact moves freely. If
any binding or lack of freedom is
noted, loosen bolt (31.2) and adjust
the vacuum interrupter in pole head
by turning and moving it slightly.
Torque M12 bolt to 60 Nm (44 ft-lb)
and M16 bolt to 130 Nm (96 ft-lb).
2.10 The centering ring (28.1) has been
loose and "floating" during
installation of the vacuum interrupter.
Check that the movable contact is
free to move vertically without
binding, and then tighten the
hardware which secures the
centering ring. Recheck that the
movable contact is free to move
vertically without binding.
47
Overhaul
2.11 Attach insulating coupler (48.0) and
lever (48.6) together, using pin
(48.5). Apply retaining clips. Correct
pin has ends that have been
generously chamfered.
4.
5.
3.
C
hecking the contact stroke
3.1 O
pen the circuit breaker.
3.2 F
ree insulating coupler (48.0) by
removing pin (48.5). The vacuum
interrupter contacts must now close
automatically as a consequence of
atmospheric pressure.
3.3 O
bserve the terminal clamp (29.2)
through the openings on each side of
the pole bottom (40.0). Using vernier
calipers, measure the distance from
the bottom surface of the terminal
clamp to the bottom edge of the
cutout opening. Measure carefully
and record your result.
3.4 C
onnect the insulating coupler (48.0)
using pin (48.5) and the retaining
clips provided.
3.5 R
epeat the measurement described in
step 3.3 again with care to maximize
accuracy. Record your result.
3.6 D
etermine difference between the
measurements made under steps 3.3
and 3.5. Your results should be per
Table 7.
3.7 If you fail to achieve the listed results,
carefully repeat the entire procedure
making certain of your
measurements.
3.8 L oosen eye bolt locking nut on
insulating coupler (48.0), and retain
position of the eye. Make adjustments
in one-half turn increments. After
adjustment is completed, tighten eye
bolt locking nut to 26-34 ft-lb. (35-45
Nm).
48
Maintenance and
Troubleshooting
Footnotes:
1.
The vacuum interrupter type
designation is labeled on the
vacuum interrupter. If the vacuum
interrupter installed does not
match that indicated in this table,
contact the nearest Siemens
representative.
2.
If you need assistance achieving
the indicated stroke setting,
contact the nearest Siemens
representative.
Vacuum
interrupter
Continuous
current
Stroke2
kV
MVA
kA
Type
mm
4.76
250
29 kA@4.76 kV;
36 kA@3.85 kV
VS-17006
VS-17040
1,200, 2,000
1,200, 2,000
7-9
7-9
4.76
350
41 kA@4.76 kV;
49 kA@4.0 kV
VS-15052
8.5-9.5
8.25
500
33 kA@8.25 kV;
41 kA@6.6 kV
VS-15052
8.5-9.5
15.0
500
18 kA@15.0 kV;
23 kA@11.5 kV
VS-17006
1,200, 2,000
7-9
15.0
750
28 kA@15.0 kV;
36 kA@11.5 kV
VS-15052
VS-17040
8.5-9.5
7-9
15.0
1,000
37 kA@15.0 kV;
48 kA@11.5 kV
VS-15052
8.5-9.5
38.0
1,500
21 kA@38.0 kV;
25 kA@23.0 kV
VS-30030
18-22
Vacuum
interrupter
Continuous
current
Stroke2
kA
kA
Type
mm
4.76
31.5
31.5 kA@4.76 kV
VS-17006
VS-17040
1,200, 2,000
1,200, 2,000
7-9
7-9
4.76
40
40 kA@4.76 kV
VS-15052
VS-17040
8.5-9.5
7-9
4.76
50
50 kA@4.76 kV
VS-15052
8.5-9.5
8.25
40
40 kA@8.25 kV
VS-15052
VS-17040
8.5-9.5
7-9
15.0
20
20 kA@15.0 kV
VS-17006
1,200, 2,000
7-9
15.0
25
25 kA@15.0 kV
VS-17006
1,200, 2,000
7-9
15.0
31.5
31.5 kA@15.0 kV
VS-17006
VS-17040
1,200, 2,000
1,200, 2,000
7-9
7-9
15.0
40
40 kA@15.0 kV
VS-15052
VS-17040
8.5-9.5
7-9
15.0
50
50 kA@15.0 kV
VS-15052
8.5-9.5
15.0
63
63 kA@15.0 kV
VS-17085
10-11
15.5
20
20 kA@15.5 kV
VS-25008
1,200, 2,000
15-16
15.5
25
25 kA@15.5 kV
VS-25008
1,200, 2,000
15-16
15.5
31.5
31.5 kA@15.5 kV
VS-15052
8.5-9.5
15.5
40
40 kA@15.5 kV
VS-15052
8.5-9.5
27.6
20
20 kA@27.6 kV
VS-25008
1,200, 2,000
15-16
27.6
25
25 kA@27.6 kV
VS-25008
1,200, 2,000
15-16
38.0
20
20 kA@38.0 kV
VS-30030
18-22
38.0
25
25 kA@38.0 kV
VS-30030
18-22
38.0
31.5
31.5 kA@38.0 kV
VS-30041
18-22
38.0
40
40 kA@38.0 kV
VS-30041
18-22
49
Maintenance and
troubleshooting
Table 8: Troubleshooting
Problem
Symptoms
1. S
econdary control circuit is de-energized or
control circuit fuses are blown. Check and
energize or replace if necessary.
2. S
econdary multi-pin plug contacts A1 or
D16 are not engaging. Check and replace if
required.
3. D
amage to wiring, terminals or connectors.
Check and repair as necessary.
4. F
ailure of charging motor (88.0). Replace if
required.
5. M
otor cut-off switch LS21 or LS22 fails to
operate. Replace if necessary.
6. M
echanical failure of operating
mechanism. Check and contact the factory
or Siemens field service at +1 (800) 3476659 or +1 (919) 365-2200 outside the
U.S.
1. S
econdary control circuit de-energized or
control circuit fuses blown. Correct as
indicated.
2. N
o closing signal to secondary disconnect
pin A2. Check for continuity and correct
protective relay logic.
3. S
econdary disconnect contacts 13 or 15 are
not engaging. Check and correct as
required.
4. F
ailure of anti-pump relay (52Y) contacts
21 to 22, 31 to 32 or 13 to 14. Check and
replace as required.
5. F
ailure of close coil (solenoid) (52SRC).
Check and replace as required.
6. A
uxiliary switch NC contacts 41 to 42 are
open when circuit breaker contacts are
open. Check linkage and switch. Replace or
adjust as necessary.
50
1. M
echanical failure of operating
mechanism. Check and contact the factory
or Siemens field service at +1 (800) 3476659 or +1 (919) 365-2200 outside the
U.S.
Maintenance and
troubleshooting
Table 8: Troubleshooting (continued)
Problem
Symptoms
Electrical problem
1. N
uisance or false closing signal to
secondary disconnect multi-pin plug
contact. Check protective relay logic.
Correct as required.
2. C
losing coil (52SRC) terminal A2 is
shorted-to-ground. Check to determine
if problems are in wiring or coil. Correct
as required.
Mechanical problem
1. M
echanical failure of operating
mechanism. Check and contact the
factory or Siemens field service at +1
(800) 347-6659 or +1 (919) 365-2200
outside the U.S.
1. S
econdary control power is deenergized or control power fuses are
blown. Correct as indicated.
2. D
amage to wiring, terminals or
connectors. Check and repair as
necessary.
3. N
o tripping signal to secondary
disconnect contact C2. Check for
continuity and correct protective relay
logic.
4. S
econdary multi-pin plug contacts C1 or
D2 are not engaging. Check and replace
if required.
5. F
ailure of trip coil (52T). Check and
replace if necessary.
6. A
uxiliary switch 52a NO contacts 23 to
24 or 33 to 34 are open when circuit
breaker is closed. Check linkage and
switch. Replace or adjust as necessary.
1. F
ailure of tripping spring or its
mechanical linkage. Check and replace
if required.
1. M
echanical failure of operating
mechanism. Check and contact the
factory or Siemens field service at +1
(800) 347-6659 or +1 (919) 365-2200
outside the U.S.
2. O
ne or more of the vacuum interrupters
are held closed. Check and replace as
necessary.
51
Maintenance and
troubleshooting
Table 8: Troubleshooting (continued)
Problem
Symptoms
Electrical problem
1. T
ripping signal remains energized on
secondary multi-pin plug contact C2.
2. C
heck for improper protective relay
logic.
Mechanical problem
52
1. M
echanical failure of operating
mechanism. Check and contact the
factory or Siemens field service at +1
(800) 347-6659 or +1 (919) 365-2200
outside the U.S.
Appendix
Table 9: Circuit breaker control data
Close coil
Trip coil
Range
Inrush
(Peak)
Charging
Close
Trip
A1
A1
Seconds
24 Vdc
19-28
14-28
5.7
15/----
----
----
----
48 Vdc
36-56
28-56
11.4
11.4/303
25
10
125 Vdc
100-140
70-140
2.1
4.8/7.43
18
10
250 Vdc
200-280
140-280
2.1
4.2/9.63
10
10
120 Vac
104-127
104-127
2.0
----2
----
10
240 Vac
208-254
208-254
2.0
----2
----
10
Footnotes:
1.
2.
3.
4.
240 Vac
48 Vdc
125 Vdc
250 Vdc
Non-inductive
10
10
10/301
9.6
4.8
Inductive
10
10
Footnotes:
1.
2.
wo contacts in series.
T
ll switches are non-convertible.
A
53
Appendix
These ratings are in accordance Table 11: Type 3AH vacuum circuit breaker ratings (new "constant kA" ratings basis)
with:
A
NSI/IEEE C37.04-1999
Standard Rating Structure for
AC High-Voltage Circuit
Breakers
A
NSI/IEEE C37.06-2009 AC
High-Voltage Circuit Breakers
Rated on a Symmetrical
Current Basis - Preferred
Ratings and Related Required
Capabilities for Voltages
Above 1,000 Volts
31.5
5-3AH-40
4.76
1.0
19
60
1,200, 2,000,
3,000
40
5-3AH-50
4.76
1.0
19
60
1,200, 2,000,
3,000
50
5-3AH-63
4.76
1.0
19
60
1,200, 2,000,
3,000
63
7-3AH-40
8.25
1.0
36
95
1,200, 2,000,
3,000
40
15-3AH-20
15.0
1.0
36
95
1,200, 2,000
20
15-3AH-25
15.0
1.0
36
95
1,200, 2,000
25
15-3AH-31.5
15.0
1.0
36
95
1,200, 2,000,
3,000
31.5
15-3AH-40
15.0
1.0
36
95
1,200, 2,000,
3,000
40
15-3AH-50
15.0
1.0
36
95
50
1,200, 2,000,
3,000
15-3AH-63
15.0
1.0
36
95
1,200, 2,000,
3,000
63
15.5-3AH-20
15.5
1.0
50
110
1,200, 2,000
20
15.5-3AH-25
15.5
1.0
50
110
1,200, 2,000
25
15.5-3AH-31.5
15.5
1.0
50
110
1,200, 2,000,
3,000
31.5
15.5-3AH-40
15.5
1.0
50
110
1,200, 2,000,
3,000
40
27-3AH-20
27.6
1.0
60
150
1,200, 2,000
20
27-3AH-25
27.6
1.0
60
150
1,200, 2,000
25
38-3AH-20
38.0
1.0
80
150/2006
1,200, 2,000,
3,000
20
38-3AH-25
38.0
1.0
80
150/2006
1,200, 2,000,
3,000
25
38-3AH-31.5
38.0
1.0
80
150/2006
1,200, 2,000,
3,000
31.5
38-3AH-40
38.0
1.0
80
150/2006
1,200, 2,000,
3,000
40
7.
54
kA rms sym
1,200, 2,000,
3,000
- 3 min. - CO.
6.
A rms
60
line-to-line faults.
5.
Lightning
impulse
(BIL)
kV crest
Short-circuit
(I)3,4
19
4.
Power
frequency
kV rms
Continuous
current7
1.0
Footnotes:
3.
kV rms
Withstand voltage
levels
4.76
A
NSI/IEEE C37.010-1999
Application Guide for AC
High-Voltage Circuit Breakers
Rated on a Symmetrical
Current Basis.
2.
Maximum Voltage
design
range
voltage
factor
(V)1
(K)2
5-3AH-31.5
A
NSI/IEEE C37.09-1999
Standard Test Procedure for
AC High-Voltage Circuit
Breakers Rated on a
Symmetrical Current Basis
1.
Circuit
breaker type
Appendix
Interrupting
time5
Permissible
tripping delay
(y)
Max. sym.
interrupting
(I)
% dc
component
Short-time
current (I) (3
s)
Circuit
breaker type
ms/cycles
kA rms sym
kA rms
Asymmetrical
(1.55 x I)
kA rms
Peak
(2.6 x I)
kA peak
83/5
31.5
47
31.5
49
82
5-3AH-31.5
83/5
40
47
40
62
104
5-3AH-40
83/5
50
47
50
78
130
5-3AH-50
83/5
63
47
63
98
164
5-3AH-63
83/5
40
47
40
62
104
7-3AH-40
83/5
20
47
20
31
52
15-3AH-20
83/5
25
47
25
39
65
15-3AH-25
83/5
31.5
47
31.5
49
82
15-3AH-31.5
83/5
40
47
40
62
104
15-3AH-40
83/5
50
47
50
78
130
15-3AH-50
83/5
63
47
63
98
164
15-3AH-63
83/5
20
47
20
31
52
15.5-3AH-20
83/5
25
47
25
39
65
15.5-3AH-25
83/5
31.5
47
31.5
49
82
15.5-3AH-31.5
83/5
40
47
40
62
104
15.5-3AH-40
83/5
20
47
20
31
52
27-3AH-20
83/5
25
47
25
39
65
27-3AH-25
83/5
20
47
20
31
52
38-3AH-20
83/5
25
47
25
39
65
38-3AH-25
83/5
31.5
47
31.5
49
82
38-3AH-31.5
83/5
40
47
40
62
104
38-3AH-40
55
Appendix
Table 12:Type 3AH vacuum
circuit breaker ratings (historic
"constant MVA" ratings basis)
Circuit
breaker
type
Withstand voltage
levels
MVA
kV rms
A rms
----
Power
frequency
kV rms
Lightning
impulse
(BIL)
kV crest
5-3AH-250
4.16
250
4.76
1,200, 2,000
1.24
19
60
5-3AH-350
4.16
350
4.76
1,200, 2,000,
3,000
1.19
19
60
7-3AH-500
7.2
500
8.25
1,200, 2,000,
3,000
1.25
36
95
15-3AH-500
13.8
500
15.0
1,200, 2,000,
3,000
1.30
36
95
15-3AH-750
13.8
750
15.0
1,200, 2,000,
3,000
1.30
36
95
15-3AH-1000
13.8
1000
15.0
1,200, 2,000,
3,000
1.30
36
95
38-3AH-1500
38.0
1,500
38.0
1,200, 2,000
1.65
80
150
3.
2.
Voltage
range
factor
(K)2
kV
Footnotes:
1.
Continuous
current11
4.
56
Appendix
Shortcircuit (at
rated
maximum
design
voltage)
(I)3, 4, 8
Interrupting
time9
Permissible
tripping
delay (y)
Rated
maximum
design
voltage (V)
divided by
K
(= V/K)
Maximum
symmetrical
interrupting
(K x I)5
Short-time
current (I)
(three
seconds)
kA rms sym
ms / cycles
Sec
kA rms
kA rms sym
kA rms
Asymmetrical
(1.6 x
K x I)6
kA rms
Peak
(2.7 x
K x I)6
kA peak
29
83 / 5
3.85
36
36
58/7810
97/13210
5-3AH-250
41
83 / 5
4.0
49
49
78
132
5-3AH-350
33
83 / 5
6.6
41
41
66/7710
111/13010
7-3AH-500
18
83 / 5
11.5
23
23
37/5810
62/9710
15-3AH-500
28
83 / 5
11.5
36
36
58/7710
97/13010
15-3AH-750
37
83 / 5
11.5
48
48
77
130
15-3AH1000
21
83/5
23.0
35
35
56
95
38-3AH1500
5.
6.
7.
9.
S
tandard rating interrupting time is five-cycles
(83 ms). Optional rated interrupting time of
three-cycles (50 ms) is available (except with
24 Vdc tripping).
10.
Circuit
breaker
type
57
Appendix
Table 13: Type 3AH vacuum circuit breaker weight in lbs (kg) (circuit breaker operator only)
Interrupting
capability kA
(MVA)
symmetrical)
4.76
31.5 (250)
242 (110)
264 (120)
----
4.76
40
246 (112)
268 (122)
390 (177)
58
Continuous current
1,200 A
2,000 A
3,000 A
4.76
50 (350)
330 (150)
363 (165)
396 (180)
8.25
40 (500)
246 (112)
268 (122)
390 (177)
15.0
20 (500)
165 (75)
257 (117)
----
15.0
25
165 (75)
257 (117)
----
15.0
31.5 (750)
242 (110)
264 (120)
----
15.0
40
246 (112)
268 (122)
390 (177)
15.0
50 (1,000)
330 (150)
363 (165)
396 (180)
15.5
20
262 (119)
278 (126)
----
15.5
25
273 (124)
298 (131)
----
15.5
31.5
298 (135)
313 (142)
385 (175)
15.5
40
309 (140)
324 (147)
390 (177)
27.6
20
276 (125)
291 (132)
----
27.6
25
287 (130)
302 (137)
----
38.0
20
353 (160)
375 (170)
386 (175)
38.0
25
353 (160)
375 (170)
386 (175)
38.0
31.5
363 (165)
385 (175)
----
38.0
40
375 (170)
397 (180)
408 (185)
Footnote:
1.
Appendix
Table 14: Circuit breaker operating times (type 3AH3 operator)
10 s
Up to 15.5 kV
55 ms
65 ms
Over 27.6 kV up to 38 kV
70 ms
Up to 15.5 kV
56 ms
56 ms
Over 27.6 kV up to 38 kV
56 ms
Up to 15.5 kV
43 ms
43 ms
Over 27.6 kV up to 38 kV
43 ms
Up to 15.5 kV
38 ms
38 ms
Over 27.6 kV up to 38 kV
38 ms
59