Chvac - Full Commercial HVAC Loads Calculation Program

METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 1

Air Handler #1 - FCU-12.10.045 - Summary Loads


Zn
No

Description
Zone Peak Time

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

12.10.045 MRI
5pm December

44
3
131

-602
0
0.00

9,694
880
20.10

1,286
0
0

None
0
0

None
0
0

Zone Peak Totals:


Total Zones: 1
Unique Zones: 1

44
3
131

-602
0
0.00

9,694
880
20.10

1,286
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 2

Air Handler #1 - FCU-12.10.045 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.045 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.88 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.90
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

5pm in December.
Clg: 33 DB, 30 WB, 26.54 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

-602
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

-602 Watts

Heating Supply Air: -602 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
9,435
Infiltration sensible gain:
259
Draw-thru fan sensible gain:
877
Supply duct sensible gain:
1,202
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
11,773 Watts

Cooling Supply Air: 11,773 / (1.000 X 1.23 X 11) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
455
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:

880 L/s
0 L/s

Watts
Watts
Watts
Watts

0 L/s
455 Watts
12,228 Watts

Zone space latent gain:


198 Watts
Infiltration latent gain:
1,088 Watts
Outside air latent gain:
0 Watts
Total latent gain on air handling system:
Total system sensible and latent gain:

1,286 Watts
13,514 Watts

Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

880 L/s
0 L/s
44
20.0991
3.2411
0.3085
-13.75

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

-0.60 kW
13.51 kW

11.4 Sq.m/Ton
0.0877 Tons/Sq.m

3.84 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 3

Air Handler #2 - FCU-12.10.059 - Summary Loads


Zn
No

Description
Zone Peak Time

12.10.059
Preparation Area
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

15
3
46

-91
0
0.00

2,317
188
12.39

569
0
0

None
0
0

None
0
0

15
3
46

-91
0
0.00

2,317
188
12.39

569
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 4

Air Handler #2 - FCU-12.10.059 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.059 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.19 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.83
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

-91
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

-91 Watts

Heating Supply Air: -91 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
2,221
Infiltration sensible gain:
97
Draw-thru fan sensible gain:
187
Supply duct sensible gain:
257
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
2,762 Watts

Cooling Supply Air: 2,762 / (1.000 X 1.23 X 12) =


Summer Vent Outside Air (0.0% of supply) =

188 L/s
0 L/s

Return duct sensible gain:


97 Watts
Return plenum sensible gain:
0 Watts
Outside air sensible gain:
0 Watts
Blow-thru fan sensible gain:
0 Watts
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

0 L/s
97 Watts
2,859 Watts

198 Watts
371 Watts
0 Watts
569 Watts
3,428 Watts

Check Figures
Total Air Handler Supply Air (based on a 12 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

188 L/s
0 L/s
15
12.3838
4.4346
0.2255
-5.97

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

-0.09 kW
3.43 kW

15.6 Sq.m/Ton
0.0641 Tons/Sq.m

0.97 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 5

Air Handler #3 - FCU-12.10.047 - Summary Loads


Zn
No

Description
Zone Peak Time

12.10.047 MRI
Control Room
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

20
3
59

0
0
0.00

1,693
113
5.77

673
0
0

None
0
0

None
0
0

20
3
59

0
0
0.00

1,693
113
5.77

673
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 6

Air Handler #3 - FCU-12.10.047 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.047 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.11 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.74
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

0 Watts

Heating Supply Air: 0 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
1,569
Infiltration sensible gain:
124
Draw-thru fan sensible gain:
112
Supply duct sensible gain:
154
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
1,959 Watts

Cooling Supply Air: 1,959 / (1.000 X 1.23 X 14) =


Summer Vent Outside Air (0.0% of supply) =

113 L/s
0 L/s

Return duct sensible gain:


58 Watts
Return plenum sensible gain:
0 Watts
Outside air sensible gain:
0 Watts
Blow-thru fan sensible gain:
0 Watts
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

0 L/s
58 Watts
2,017 Watts

198 Watts
475 Watts
0 Watts
673 Watts
2,690 Watts

Check Figures
Total Air Handler Supply Air (based on a 14 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

113 L/s
0 L/s
20
5.7725
7.2483
0.1380
0.00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0.00 kW
2.69 kW

25.5 Sq.m/Ton
0.0392 Tons/Sq.m

0.76 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 7

Air Handler #4 - FCU-12.10.046 - Summary Loads


Zn
No

Description
Zone Peak Time

12.10.046 MRI
Technical
5pm February
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

14
3
41

-136
0
0.00

15,104
1,488
110.20

533
0
0

None
0
0

None
0
0

14
3
41

-136
0
0.00

15,104
1,488
110.20

533
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 8

Air Handler #4 - FCU-12.10.046 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.046 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 1.49 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.97
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

5pm in February.
Clg: 33 DB, 30 WB, 26.54 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

-136
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

-136 Watts

Heating Supply Air: -136 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
15,024
Infiltration sensible gain:
80
Draw-thru fan sensible gain:
1,482
Supply duct sensible gain:
2,031
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
18,617 Watts

Cooling Supply Air: 18,617 / (1.000 X 1.23 X 10) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
768
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

1,488 L/s
0 L/s

Watts
Watts
Watts
Watts

0 L/s
768 Watts
19,385 Watts

198 Watts
335 Watts
0 Watts
533 Watts
19,919 Watts

Check Figures
Total Air Handler Supply Air (based on a 10 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

1,488 L/s
0 L/s
14
110.1958
0.6778
1.4755
-10.08

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

-0.14 kW
19.92 kW

2.4 Sq.m/Ton
0.4195 Tons/Sq.m

5.66 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 9

Air Handler #5 - FCU-12.10.043 - Summary Loads


Zn
No

Description
Zone Peak Time

12.10.0043
Mammogram
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

17
3
50

0
0
0.00

1,560
106
6.37

603
0
0

None
0
0

None
0
0

17
3
50

0
0
0.00

1,560
106
6.37

603
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 10

Air Handler #5 - FCU-12.10.043 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.043 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.11 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.75
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

0 Watts

Heating Supply Air: 0 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
1,454
Infiltration sensible gain:
106
Draw-thru fan sensible gain:
105
Supply duct sensible gain:
144
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
1,809 Watts

Cooling Supply Air: 1,809 / (1.000 X 1.23 X 14) =


Summer Vent Outside Air (0.0% of supply) =

106 L/s
0 L/s

Return duct sensible gain:


55 Watts
Return plenum sensible gain:
0 Watts
Outside air sensible gain:
0 Watts
Blow-thru fan sensible gain:
0 Watts
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

0 L/s
55 Watts
1,864 Watts

198 Watts
405 Watts
0 Watts
603 Watts
2,467 Watts

Check Figures
Total Air Handler Supply Air (based on a 14 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

106 L/s
0 L/s
17
6.3655
6.7300
0.1486
0.00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0.00 kW
2.47 kW

23.7 Sq.m/Ton
0.0423 Tons/Sq.m

0.70 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 11

Air Handler #6 - FCU-12.10.078 - Summary Loads


Zn
No

Description
Zone Peak Time

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

12.10.078 USG
3pm December

17
3
50

0
0
0.00

3,760
333
20.07

603
0
0

None
0
0

None
0
0

Zone Peak Totals:


Total Zones: 1
Unique Zones: 1

17
3
50

0
0
0.00

3,760
333
20.07

603
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 12

Air Handler #6 - FCU-12.10.078 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.078 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.33 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.88
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

0 Watts

Heating Supply Air: 0 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
3,654
Infiltration sensible gain:
106
Draw-thru fan sensible gain:
332
Supply duct sensible gain:
455
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
4,546 Watts

Cooling Supply Air: 4,546 / (1.000 X 1.23 X 11) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
172
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

333 L/s
0 L/s

Watts
Watts
Watts
Watts

0 L/s
172 Watts
4,718 Watts

198 Watts
405 Watts
0 Watts
603 Watts
5,321 Watts

Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

333 L/s
0 L/s
17
20.0646
3.1197
0.3205
0.00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0.00 kW
5.32 kW

11.0 Sq.m/Ton
0.0911 Tons/Sq.m

1.51 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 13

Air Handler #7 - FCU-12.10.014 - Summary Loads


Zn
No

Description
Zone Peak Time

12.10.014 DEXA
Room
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

20
3
61

0
0
0.00

1,954
139
6.80

695
0
0

None
0
0

None
0
0

20
3
61

0
0
0.00

1,954
139
6.80

695
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 14

Air Handler #7 - FCU-12.10.014 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.014 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.14 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.76
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

0 Watts

Heating Supply Air: 0 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
1,824
Infiltration sensible gain:
130
Draw-thru fan sensible gain:
138
Supply duct sensible gain:
189
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
2,282 Watts

Cooling Supply Air: 2,282 / (1.000 X 1.23 X 13) =


Summer Vent Outside Air (0.0% of supply) =

139 L/s
0 L/s

Return duct sensible gain:


72 Watts
Return plenum sensible gain:
0 Watts
Outside air sensible gain:
0 Watts
Blow-thru fan sensible gain:
0 Watts
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

0 L/s
72 Watts
2,353 Watts

198 Watts
497 Watts
0 Watts
695 Watts
3,048 Watts

Check Figures
Total Air Handler Supply Air (based on a 13 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

139 L/s
0 L/s
20
6.7940
6.6919
0.1494
0.00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0.00 kW
3.05 kW

23.5 Sq.m/Ton
0.0425 Tons/Sq.m

0.87 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 15

Air Handler #8 - FCU-12.10.030 - Summary Loads


Zn
No

Description
Zone Peak Time

12.25.030 Stress
Room
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

10
3
30

0
0
0.00

1,811
147
14.57

444
0
0

None
0
0

None
0
0

10
3
30

0
0
0.00

1,811
147
14.57

444
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 16

Air Handler #8 - FCU-12.10.030 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.030 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.15 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.83
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

0 Watts

Heating Supply Air: 0 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
1,747
Infiltration sensible gain:
64
Draw-thru fan sensible gain:
147
Supply duct sensible gain:
201
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
2,159 Watts

Cooling Supply Air: 2,159 / (1.000 X 1.23 X 12) =


Summer Vent Outside Air (0.0% of supply) =

147 L/s
0 L/s

Return duct sensible gain:


76 Watts
Return plenum sensible gain:
0 Watts
Outside air sensible gain:
0 Watts
Blow-thru fan sensible gain:
0 Watts
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

0 L/s
76 Watts
2,235 Watts

198 Watts
246 Watts
0 Watts
444 Watts
2,679 Watts

Check Figures
Total Air Handler Supply Air (based on a 12 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

147 L/s
0 L/s
10
14.5685
3.7701
0.2652
0.00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0.00 kW
2.68 kW

13.3 Sq.m/Ton
0.0754 Tons/Sq.m

0.76 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 17

Air Handler #9 - FCU-12.10.070 - Summary Loads


Zn
No

Description
Zone Peak Time

12.10.070 Stress
Room
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

10
3
30

0
0
0.00

1,802
147
14.84

439
0
0

None
0
0

None
0
0

10
3
30

0
0
0.00

1,802
147
14.84

439
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 18

Air Handler #9 - FCU-12.10.070 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.070 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.15 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.83
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

0 Watts

Heating Supply Air: 0 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
1,739
Infiltration sensible gain:
63
Draw-thru fan sensible gain:
146
Supply duct sensible gain:
200
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
2,149 Watts

Cooling Supply Air: 2,149 / (1.000 X 1.23 X 12) =


Summer Vent Outside Air (0.0% of supply) =

147 L/s
0 L/s

Return duct sensible gain:


76 Watts
Return plenum sensible gain:
0 Watts
Outside air sensible gain:
0 Watts
Blow-thru fan sensible gain:
0 Watts
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

0 L/s
76 Watts
2,225 Watts

198 Watts
241 Watts
0 Watts
439 Watts
2,664 Watts

Check Figures
Total Air Handler Supply Air (based on a 12 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

147 L/s
0 L/s
10
14.8332
3.7162
0.2691
0.00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0.00 kW
2.66 kW

13.1 Sq.m/Ton
0.0765 Tons/Sq.m

0.76 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 19

Air Handler #10 - FCU-12.10.082 - Summary Loads


Zn
No

Description
Zone Peak Time

10

12.10.082 Stress
Treadmill
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

21
3
62

0
0
0.00

2,298
174
8.41

703
0
0

None
0
0

None
0
0

21
3
62

0
0
0.00

2,298
174
8.41

703
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 20

Air Handler #10 - FCU-12.10.082 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.082 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.17 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.79
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

0 Watts

Heating Supply Air: 0 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
2,166
Infiltration sensible gain:
132
Draw-thru fan sensible gain:
173
Supply duct sensible gain:
238
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
2,709 Watts

Cooling Supply Air: 2,709 / (1.000 X 1.23 X 13) =


Summer Vent Outside Air (0.0% of supply) =

174 L/s
0 L/s

Return duct sensible gain:


90 Watts
Return plenum sensible gain:
0 Watts
Outside air sensible gain:
0 Watts
Blow-thru fan sensible gain:
0 Watts
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

0 L/s
90 Watts
2,799 Watts

198 Watts
505 Watts
0 Watts
703 Watts
3,502 Watts

Check Figures
Total Air Handler Supply Air (based on a 13 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

174 L/s
0 L/s
21
8.4087
5.9116
0.1692
0.00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0.00 kW
3.50 kW

20.8 Sq.m/Ton
0.0481 Tons/Sq.m

1.00 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 21

Air Handler #11 - FCU-12.10.081 - Summary Loads


Zn
No

Description
Zone Peak Time

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

13

12.10.081 X-Ray
3pm December

32
3
96

0
0
0.00

6,887
620
19.38

978
0
0

None
0
0

None
0
0

Zone Peak Totals:


Total Zones: 1
Unique Zones: 1

32
3
96

0
0
0.00

6,887
620
19.38

978
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 22

Air Handler #11 - FCU-12.10.081 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.081 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.62 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.89
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

0 Watts

Heating Supply Air: 0 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
6,683
Infiltration sensible gain:
204
Draw-thru fan sensible gain:
618
Supply duct sensible gain:
847
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
8,352 Watts

Cooling Supply Air: 8,352 / (1.000 X 1.23 X 11) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
320
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

620 L/s
0 L/s

Watts
Watts
Watts
Watts

0 L/s
320 Watts
8,672 Watts

198 Watts
780 Watts
0 Watts
978 Watts
9,650 Watts

Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

620 L/s
0 L/s
32
19.3827
3.3161
0.3016
0.00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0.00 kW
9.65 kW

11.7 Sq.m/Ton
0.0857 Tons/Sq.m

2.74 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 23

Air Handler #12 - FCU-12.10.012 - Summary Loads


Zn
No

Description
Zone Peak Time

12

12.10.012 Recovery
Injection
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

18
3
54

-91
0
0.00

2,781
230
12.70

639
0
0

None
0
0

None
0
0

18
3
54

-91
0
0.00

2,781
230
12.70

639
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 24

Air Handler #12 - FCU-12.10.012 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.012 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.23 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.84
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

-91
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

-91 Watts

Heating Supply Air: -91 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
2,665
Infiltration sensible gain:
115
Draw-thru fan sensible gain:
229
Supply duct sensible gain:
314
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
3,323 Watts

Cooling Supply Air: 3,323 / (1.000 X 1.23 X 12) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
119
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

230 L/s
0 L/s

Watts
Watts
Watts
Watts

0 L/s
119 Watts
3,442 Watts

198 Watts
441 Watts
0 Watts
639 Watts
4,081 Watts

Check Figures
Total Air Handler Supply Air (based on a 12 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

230 L/s
0 L/s
18
12.7013
4.4348
0.2255
-5.01

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

-0.09 kW
4.08 kW

15.6 Sq.m/Ton
0.0641 Tons/Sq.m

1.16 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 25

Air Handler #13 - FCU-12.10.009 - Summary Loads


Zn
No

Description
Zone Peak Time

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

11

12.10.009 CT
10am December

38
3
114

-547
0
0.00

13,470
1,280
33.60

984
0
0

None
0
0

None
0
0

Zone Peak Totals:


Total Zones: 1
Unique Zones: 1

38
3
114

-547
0
0.00

13,470
1,280
33.60

984
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 26

Air Handler #13 - FCU-12.10.009 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.009 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 1.28 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.94
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

11am in December.
Clg: 30 DB, 29 WB, 25.47 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Because of the diversity in zone, plenum and ventilation loads, the zone sensible peak time in December at 10am is
different from the total system peak time, hence the air system L/s was computed using a zone sensible load of 13,470.
Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

-547
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

-547 Watts

Heating Supply Air: -547 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
13,276
Infiltration sensible gain:
176
Draw-thru fan sensible gain:
1,275
Supply duct sensible gain:
1,747
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
16,474 Watts

Cooling Supply Air: 16,493 / (1.000 X 1.23 X 10) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
661
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

1,280 L/s
0 L/s

Watts
Watts
Watts
Watts

0 L/s
661 Watts
17,135 Watts

198 Watts
891 Watts
0 Watts
1,089 Watts
18,224 Watts

Check Figures
Total Air Handler Supply Air (based on a 10 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

1,280 L/s
0 L/s
38
33.5957
2.0906
0.4783
-14.37

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

-0.55 kW
18.22 kW

7.4 Sq.m/Ton
0.1360 Tons/Sq.m

5.18 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 27

Air Handler #14 - FCU-12.10.053 - Summary Loads


Zn
No

Description
Zone Peak Time

14

12.10.053 Operator
Room
10am February
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

17
3
51

-285
0
0.00

9,241
893
52.86

547
0
0

None
0
0

None
0
0

17
3
51

-285
0
0.00

9,241
893
52.86

547
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 28

Air Handler #14 - FCU-12.10.053 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.053 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.89 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.95
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

10am in February.
Clg: 29 DB, 28 WB, 23.43 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

-285
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

-285 Watts

Heating Supply Air: -285 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
9,176
Infiltration sensible gain:
65
Draw-thru fan sensible gain:
890
Supply duct sensible gain:
1,219
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
11,350 Watts

Cooling Supply Air: 11,350 / (1.000 X 1.23 X 10) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
461
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

893 L/s
0 L/s

Watts
Watts
Watts
Watts

0 L/s
461 Watts
11,811 Watts

198 Watts
349 Watts
0 Watts
547 Watts
12,358 Watts

Check Figures
Total Air Handler Supply Air (based on a 10 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

893 L/s
0 L/s
17
52.8583
1.3676
0.7312
-16.88

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

-0.29 kW
12.36 kW

4.8 Sq.m/Ton
0.2079 Tons/Sq.m

3.51 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 29

Air Handler #15 - FCU-12.25.002 - Summary Loads


Zn
No

Description
Zone Peak Time

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

15

12.25.002 Sub-Wait
3pm December

32
3
97

0
0
0.00

2,065
117
3.61

988
0
0

None
0
0

None
0
0

Zone Peak Totals:


Total Zones: 1
Unique Zones: 1

32
3
97

0
0
0.00

2,065
117
3.61

988
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 30

Air Handler #15 - FCU-12.25.002 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.25.002 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.12 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.70
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

0 Watts

Heating Supply Air: 0 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
1,859
Infiltration sensible gain:
206
Draw-thru fan sensible gain:
116
Supply duct sensible gain:
160
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
2,342 Watts

Cooling Supply Air: 2,342 / (1.000 X 1.23 X 16) =


Summer Vent Outside Air (0.0% of supply) =

117 L/s
0 L/s

Return duct sensible gain:


60 Watts
Return plenum sensible gain:
0 Watts
Outside air sensible gain:
0 Watts
Blow-thru fan sensible gain:
0 Watts
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

0 L/s
60 Watts
2,402 Watts

198 Watts
790 Watts
0 Watts
988 Watts
3,390 Watts

Check Figures
Total Air Handler Supply Air (based on a 16 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

117 L/s
0 L/s
32
3.6098
9.5581
0.1046
0.00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0.00 kW
3.39 kW

33.6 Sq.m/Ton
0.0297 Tons/Sq.m

0.96 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 31

Air Handler #16 - FCU-12.10.058 - Summary Loads


Zn
No

Description
Zone Peak Time

16

12.10.058 PET-CT
Room
10am February
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

36
3
108

-263
0
0.00

13,040
1,248
34.76

938
0
0

None
0
0

None
0
0

36
3
108

-263
0
0.00

13,040
1,248
34.76

938
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 32

Air Handler #16 - FCU-12.10.058 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.058 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 1.25 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.94
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

10am in February.
Clg: 29 DB, 28 WB, 23.43 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

-263
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

-263 Watts

Heating Supply Air: -263 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
12,902
Infiltration sensible gain:
138
Draw-thru fan sensible gain:
1,243
Supply duct sensible gain:
1,704
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
15,987 Watts

Cooling Supply Air: 15,987 / (1.000 X 1.23 X 10) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
645
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

1,248 L/s
0 L/s

Watts
Watts
Watts
Watts

0 L/s
645 Watts
16,632 Watts

198 Watts
740 Watts
0 Watts
938 Watts
17,570 Watts

Check Figures
Total Air Handler Supply Air (based on a 10 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

1,248 L/s
0 L/s
36
34.7615
2.0433
0.4894
-7.32

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

-0.26 kW
17.57 kW

7.2 Sq.m/Ton
0.1392 Tons/Sq.m

5.00 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 33

Air Handler #17 - FCU-12.10.011 - Summary Loads


Zn
No

Description
Zone Peak Time

17

12.10.011 Recovery
Injection
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

16
3
48

0
0
0.00

1,638
116
7.29

586
0
0

None
0
0

None
0
0

16
3
48

0
0
0.00

1,638
116
7.29

586
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 34

Air Handler #17 - FCU-12.10.011 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.011 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.12 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.76
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

0 Watts

Heating Supply Air: 0 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
1,536
Infiltration sensible gain:
101
Draw-thru fan sensible gain:
115
Supply duct sensible gain:
158
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
1,911 Watts

Cooling Supply Air: 1,911 / (1.000 X 1.23 X 13) =


Summer Vent Outside Air (0.0% of supply) =

116 L/s
0 L/s

Return duct sensible gain:


60 Watts
Return plenum sensible gain:
0 Watts
Outside air sensible gain:
0 Watts
Blow-thru fan sensible gain:
0 Watts
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

0 L/s
60 Watts
1,971 Watts

198 Watts
388 Watts
0 Watts
586 Watts
2,557 Watts

Check Figures
Total Air Handler Supply Air (based on a 13 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

116 L/s
0 L/s
16
7.2863
6.2190
0.1608
0.00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0.00 kW
2.56 kW

21.9 Sq.m/Ton
0.0457 Tons/Sq.m

0.73 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 35

Air Handler #18 - FCU-12.10.057 - Summary Loads


Zn
No

Description
Zone Peak Time

18

12.10.057 Post
Endoscopy
10am February
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

34
3
101

-182
0
0.00

8,761
818
24.29

893
0
0

None
0
0

None
0
0

34
3
101

-182
0
0.00

8,761
818
24.29

893
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 36

Air Handler #18 - FCU-12.10.057 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.057 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.82 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.92
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

10am in February.
Clg: 29 DB, 28 WB, 23.43 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

-182
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

-182 Watts

Heating Supply Air: -182 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
8,631
Infiltration sensible gain:
130
Draw-thru fan sensible gain:
815
Supply duct sensible gain:
1,117
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
10,693 Watts

Cooling Supply Air: 10,693 / (1.000 X 1.23 X 11) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
423
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

818 L/s
0 L/s

Watts
Watts
Watts
Watts

0 L/s
423 Watts
11,116 Watts

198 Watts
695 Watts
0 Watts
893 Watts
12,009 Watts

Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

818 L/s
0 L/s
34
24.2852
2.8062
0.3563
-5.40

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

-0.18 kW
12.01 kW

9.9 Sq.m/Ton
0.1013 Tons/Sq.m

3.41 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 37

Air Handler #19 - FCU-12.10.018 - Summary Loads


Zn
No

Description
Zone Peak Time

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

19

12.10.018 Endoscopy
3pm December

25
3
75

0
0
0.00

6,561
601
24.14

805
0
0

None
0
0

None
0
0

Zone Peak Totals:


Total Zones: 1
Unique Zones: 1

25
3
75

0
0
0.00

6,561
601
24.14

805
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 38

Air Handler #19 - FCU-12.10.018 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.018 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.60 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.91
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

0 Watts

Heating Supply Air: 0 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
6,402
Infiltration sensible gain:
159
Draw-thru fan sensible gain:
599
Supply duct sensible gain:
820
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
7,980 Watts

Cooling Supply Air: 7,980 / (1.000 X 1.23 X 11) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
310
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

601 L/s
0 L/s

Watts
Watts
Watts
Watts

0 L/s
310 Watts
8,290 Watts

198 Watts
607 Watts
0 Watts
805 Watts
9,095 Watts

Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

601 L/s
0 L/s
25
24.1354
2.7376
0.3653
0.00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0.00 kW
9.10 kW

9.6 Sq.m/Ton
0.1039 Tons/Sq.m

2.59 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 39

Air Handler #20 - FCU-12.10.054 - Summary Loads


Zn
No

Description
Zone Peak Time

20

12.10.054
Opthalmology
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

21
3
62

0
0
0.00

3,948
344
16.63

703
0
0

None
0
0

None
0
0

21
3
62

0
0
0.00

3,948
344
16.63

703
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 40

Air Handler #20 - FCU-12.10.054 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.054 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.34 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.87
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

0 Watts

Heating Supply Air: 0 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
3,816
Infiltration sensible gain:
132
Draw-thru fan sensible gain:
343
Supply duct sensible gain:
470
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
4,761 Watts

Cooling Supply Air: 4,761 / (1.000 X 1.23 X 11) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
178
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

344 L/s
0 L/s

Watts
Watts
Watts
Watts

0 L/s
178 Watts
4,939 Watts

198 Watts
505 Watts
0 Watts
703 Watts
5,641 Watts

Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

344 L/s
0 L/s
21
16.6253
3.6695
0.2725
0.00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0.00 kW
5.64 kW

12.9 Sq.m/Ton
0.0775 Tons/Sq.m

1.60 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 41

Air Handler #21 - FCU-12.10.051 - Summary Loads


Zn
No

Description
Zone Peak Time

21

12.10.051 NonInvasive
2pm June
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

16
3
48

-142
0
0.00

5,093
469
29.14

593
0
0

None
0
0

None
0
0

16
3
48

-142
0
0.00

5,093
469
29.14

593
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 42

Air Handler #21 - FCU-12.10.051 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.051 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.47 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.91
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

2pm in June.
Clg: 33 DB, 30 WB, 26.30 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

-142
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

-142 Watts

Heating Supply Air: -142 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
4,993
Infiltration sensible gain:
100
Draw-thru fan sensible gain:
467
Supply duct sensible gain:
640
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
6,201 Watts

Cooling Supply Air: 6,201 / (1.000 X 1.23 X 11) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
242
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

469 L/s
0 L/s

Watts
Watts
Watts
Watts

0 L/s
242 Watts
6,443 Watts

198 Watts
395 Watts
0 Watts
593 Watts
7,036 Watts

Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

469 L/s
0 L/s
16
29.1339
2.2884
0.4370
-8.83

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

-0.14 kW
7.04 kW

8.0 Sq.m/Ton
0.1243 Tons/Sq.m

2.00 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 43

Air Handler #22 - FCU-12.10.049 - Summary Loads


Zn
No

Description
Zone Peak Time

22

12.10.049 NonInvasive
7pm June
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

13
3
39

-172
0
0.00

4,225
387
29.56

516
0
0

None
0
0

None
0
0

13
3
39

-172
0
0.00

4,225
387
29.56

516
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 44

Air Handler #22 - FCU-12.10.049 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.049 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.39 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.91
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

7pm in June.
Clg: 31 DB, 30 WB, 26.10 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

-172
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

-172 Watts

Heating Supply Air: -172 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
4,161
Infiltration sensible gain:
63
Draw-thru fan sensible gain:
386
Supply duct sensible gain:
529
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
5,139 Watts

Cooling Supply Air: 5,139 / (1.000 X 1.23 X 11) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
200
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

387 L/s
0 L/s

Watts
Watts
Watts
Watts

0 L/s
200 Watts
5,339 Watts

198 Watts
318 Watts
0 Watts
516 Watts
5,854 Watts

Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

387 L/s
0 L/s
13
29.5549
2.2377
0.4469
-13.16

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

-0.17 kW
5.85 kW

7.9 Sq.m/Ton
0.1271 Tons/Sq.m

1.66 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 45

Air Handler #23 - FCU-12.10.023 - Summary Loads


Zn
No

Description
Zone Peak Time

23

12.10.023 Generic
Screening
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

14
3
43

0
0
0.00

3,659
327
22.72

549
0
0

None
0
0

None
0
0

14
3
43

0
0
0.00

3,659
327
22.72

549
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 46

Air Handler #23 - FCU-12.10.023 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.023 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.33 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.89
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

0 Watts

Heating Supply Air: 0 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
3,567
Infiltration sensible gain:
92
Draw-thru fan sensible gain:
326
Supply duct sensible gain:
447
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
4,431 Watts

Cooling Supply Air: 4,431 / (1.000 X 1.23 X 11) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
169
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

327 L/s
0 L/s

Watts
Watts
Watts
Watts

0 L/s
169 Watts
4,600 Watts

198 Watts
351 Watts
0 Watts
549 Watts
5,149 Watts

Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

327 L/s
0 L/s
14
22.7177
2.7965
0.3576
0.00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0.00 kW
5.15 kW

9.8 Sq.m/Ton
0.1017 Tons/Sq.m

1.46 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 47

Air Handler #24 - FCU-12.10.024 - Summary Loads


Zn
No

Description
Zone Peak Time

24

12.10.024 Generic
Screening
3pm December
Zone Peak Totals:
Total Zones: 1
Unique Zones: 1

Area
People
Volume

Htg.Loss
Htg.L/s
L/s/Sqm

Sen.Gain
Clg.L/s
L/s/Sqm

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.L/s
Act.L/s

Clg.O.A.
Req.L/s
Act.L/s

14
3
42

0
0
0.00

3,640
326
23.29

539
0
0

None
0
0

None
0
0

14
3
42

0
0
0.00

3,640
326
23.29

539
0
0

0
0

0
0

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 48

Air Handler #24 - FCU-12.10.024 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

FCU-12.10.024 Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 0.33 kW
75% motor and fan efficiency with 0.75 kPa across the fan
0.89
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

3pm in December.
Clg: 33 DB, 30 WB, 26.19 grams moisture per kg dry air, Htg: 28 DB
Clg: 22 DB, 50% RH (avg.), Htg: 22 DB

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Watts
Watts
Watts
Watts
Watts
Watts

0 L/s
0 L/s

0 Watts

Heating Supply Air: 0 / (1.000 X 1.21 X 0) =


Winter Vent Outside Air (0.0% of supply) =
Zone space sensible gain:
3,551
Infiltration sensible gain:
89
Draw-thru fan sensible gain:
325
Supply duct sensible gain:
445
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

0 L/s
0 L/s
Watts
Watts
Watts
Watts
Watts
4,410 Watts

Cooling Supply Air: 4,410 / (1.000 X 1.23 X 11) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
168
Return plenum sensible gain:
0
Outside air sensible gain:
0
Blow-thru fan sensible gain:
0
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Zone space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

326 L/s
0 L/s

Watts
Watts
Watts
Watts

0 L/s
168 Watts
4,579 Watts

198 Watts
341 Watts
0 Watts
539 Watts
5,118 Watts

Check Figures
Total Air Handler Supply Air (based on a 11 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

326 L/s
0 L/s
14
23.2895
2.7354
0.3656
0.00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0.00 kW
5.12 kW

9.6 Sq.m/Ton
0.1039 Tons/Sq.m

1.46 Tons

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 49

Zone Detailed Loads (At Zone Peak Times)


Load
Unit
-SCCLTD
U.Fac
Sen.
Lat.
Htg.
Htg.
Description
Quan
CFAC
SHGF
-CLFGain
Gain
Mult.
Loss
Zone 1-12.10.045 MRI peaks (sensible) in December at 5pm, Air Handler 1 (FCU-12.10.045), Group 1,
1.0 x 43.8, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-W-C-M
Wall-3-S-C-M
Partition-1-5
Gls-W-1-90-Tran
0%S-0-NS-Solar
Gls-S-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

7
10
43.8
20.1
20.1
5.8
5.8
876
2,000
3.0
18
0

0.83
0.83
1.000
0.320
1.000
0.320
1.000
1.000
1.000

11.5
13.8
6/0
10
733
10
410

2.660
2.660
2.660
2.100
0.640
2.100
0.790

Sub-total
Safety factors:

211
381
699
439
3,017
127
601
876
2,000
225
236
8,813
+10%
--------9,694

Total w/ safety factors:

-15.960
-15.960
0.000
-12.600

-110
-166
0
-253

-12.600

-73

0.000

0
180
989
1,169
+10%
--------1,286

-602
+0%
---------602

Zone 2-12.10.059 Preparation Area peaks (sensible) in December at 3pm, Air Handler 2 (FCU12.10.059), Group 1, 1.0 x 15.2, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-S-C-M
Partition-1-5
Gls-S-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

0
15.2
7.2
7.2
304
300
3.0
6
0

0.83
1.000
0.320
1.000
1.000
1.000

13.0
6/0
11
410

2.660
2.660
2.100
0.820

Sub-total
Safety factors:

0
243
173
775
304
300
225
88
2,107
+10%
--------2,317

Total w/ safety factors:

0.000
0.000
-12.600

0
0
-91

0.000

0
180
337
517
+10%
--------569

-91
+0%
---------91

Zone 3-12.10.047 MRI Control Room peaks (sensible) in December at 3pm, Air Handler 3 (FCU12.10.047), Group 1, 1.0 x 19.5, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

19.5
390
500
3.0
8
0

6/0
1.000
1.000
1.000

Sub-total
Safety factors:
Total w/ safety factors:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

2.660

311
390
500
225
113
1,539
+10%
--------1,693

0.000

0.000

0
180
432
612
+10%
--------673

0
+0%
--------0

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 50

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load
Unit
-SCCLTD
U.Fac
Sen.
Lat.
Htg.
Htg.
Description
Quan
CFAC
SHGF
-CLFGain
Gain
Mult.
Loss
Zone 4-12.10.046 MRI Technical peaks (sensible) in February at 5pm, Air Handler 4 (FCU-12.10.046),
Group 1, 1.0 x 13.5, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-W-C-M
Partition-1-5
Gls-W-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

0
13.5
10.8
10.8
270
11,000
3.0
6
0

0.83
1.000
0.320
1.000
1.000
1.000

12.3
6/0
10
774

2.660
2.660
2.100
0.640

Sub-total
Safety factors:

0
215
236
1,712
270
11,000
225
73
13,731
+10%
--------15,104

Total w/ safety factors:

0.000
0.000
-12.600

0
0
-136

0.000

0
180
305
485
+10%
--------533

-136
+0%
---------136

Zone 5-12.10.0043 Mammogram peaks (sensible) in December at 3pm, Air Handler 5 (FCU-12.10.043),
Group 1, 1.0 x 16.6, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

16.6
332
500
3.0
7
0

6/0

2.660

1.000
1.000
1.000

Sub-total
Safety factors:

265
332
500
225
96
1,418
+10%
--------1,560

Total w/ safety factors:

0.000

0.000

0
180
368
548
+10%
--------603

0
+0%
--------0

Zone 6-12.10.078 USG peaks (sensible) in December at 3pm, Air Handler 6 (FCU-12.10.078), Group 1,
1.0 x 16.6, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

16.6
332
2,500
3.0
7
0

6/0

2.660

1.000
1.000
1.000

Sub-total
Safety factors:

265
332
2,500
225
96
3,418
+10%
--------3,760

Total w/ safety factors:

0.000

0.000

0
180
368
548
+10%
--------603

0
+0%
--------0

Zone 7-12.10.014 DEXA Room peaks (sensible) in December at 3pm, Air Handler 7 (FCU-12.10.014),
Group 1, 1.0 x 20.4, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4

20.4
408
700
3.0

6/0
1.000
1.000
1.000

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

2.660

326
408
700
225

0.000

0
180
Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 51

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load
Description
Cool. Infil.AC/hr
Heat. Infil.AC/hr

Unit
Quan

-SCCFAC

CLTD
SHGF

U.Fac
-CLF-

9
0

Sub-total
Safety factors:

Sen.
Gain

Lat.
Gain

118

452

1,777
+10%
--------1,954

Total w/ safety factors:

Htg.
Mult.

Htg.
Loss

0.000

632
+10%
--------695

0
+0%
--------0

Zone 8-12.25.030 Stress Room peaks (sensible) in December at 3pm, Air Handler 8 (FCU-12.10.030),
Group 1, 1.0 x 10.1, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

10.1
202
1,000
3.0
4
0

6/0

2.660

1.000
1.000
1.000

Sub-total
Safety factors:

161
202
1,000
225
58
1,647
+10%
--------1,811

Total w/ safety factors:

0.000

0.000

0
180
224
404
+10%
--------444

0
+0%
--------0

Zone 9-12.10.070 Stress Room peaks (sensible) in December at 3pm, Air Handler 9 (FCU-12.10.070),
Group 1, 1.0 x 9.9, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

9.9
198
1,000
3.0
4
0

6/0

2.660

1.000
1.000
1.000

Sub-total
Safety factors:

158
198
1,000
225
57
1,638
+10%
--------1,802

Total w/ safety factors:

0.000

0.000

0
180
219
399
+10%
--------439

0
+0%
--------0

Zone 10-12.10.082 Stress Treadmill peaks (sensible) in December at 3pm, Air Handler 10 (FCU12.10.082), Group 1, 1.0 x 20.7, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

20.7
414
1,000
3.0
9
0

6/0
1.000
1.000
1.000

Sub-total
Safety factors:
Total w/ safety factors:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

2.660

330
414
1,000
225
120
2,089
+10%
--------2,298

0.000

0.000

0
180
459
639
+10%
--------703

0
+0%
--------0

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 52

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load
Unit
-SCCLTD
U.Fac
Sen.
Lat.
Htg.
Htg.
Description
Quan
CFAC
SHGF
-CLFGain
Gain
Mult.
Loss
Zone 11-12.10.009 CT peaks (sensible) in December at 10am, Air Handler 13 (FCU-12.10.009), Group 1,
1.0 x 38.1, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-E-C-M
Wall-3-S-C-M
Partition-1-5
Gls-E-1-90-Tran
0%S-0-NS-Solar
Gls-S-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

7
8
38.1
16.5
16.5
8.7
8.7
762
6,900
3.0
16
0

0.83
0.83
1.000
0.320
1.000
0.320
1.000
1.000
1.000

9.8
11.3
6/0
5
733
5
410

2.660
2.660
2.660
2.100
0.570
2.100
0.630

Sub-total
Safety factors:

181
225
608
187
2,206
99
719
762
6,900
225
133
12,246
+10%
--------13,470

Total w/ safety factors:

-15.960
-15.960
0.000
-12.600

-110
-120
0
-208

-12.600

-110

0.000

0
180
714
894
+10%
--------984

-547
+0%
---------547

Zone 12-12.10.012 Recovery Injection peaks (sensible) in December at 3pm, Air Handler 12 (FCU12.10.012), Group 1, 1.0 x 18.1, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-S-C-M
Partition-1-5
Gls-S-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

0
18.1
7.2
7.2
362
600
3.0
8
0

0.83
1.000
0.320
1.000
1.000
1.000

13.0
6/0
11
410

2.660
2.660
2.100
0.820

Sub-total
Safety factors:

0
289
173
775
362
600
225
105
2,528
+10%
--------2,781

Total w/ safety factors:

0.000
0.000
-12.600

0
0
-91

0.000

0
180
401
581
+10%
--------639

-91
+0%
---------91

Zone 13-12.10.081 X-Ray peaks (sensible) in December at 3pm, Air Handler 11 (FCU-12.10.081), Group
1, 1.0 x 32.0, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

32
640
4,700
3.0
13
0

6/0
1.000
1.000
1.000

Sub-total
Safety factors:
Total w/ safety factors:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

2.660

511
640
4,700
225
185
6,261
+10%
--------6,887

0.000

0.000

0
180
709
889
+10%
--------978

0
+0%
--------0

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 53

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load
Unit
-SCCLTD
U.Fac
Sen.
Lat.
Htg.
Description
Quan
CFAC
SHGF
-CLFGain
Gain
Mult.
Zone 14-12.10.053 Operator Room peaks (sensible) in February at 10am, Air Handler 14 (FCU12.10.053), Group 1, 1.0 x 16.9, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-E-C-M
Partition-1-5
Gls-E-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

4
16.9
17.7
17.7
338
4,698
3.0
7
0

0.83
1.000
0.320
1.000
1.000
1.000

10.7
6/0
5
774

2.660
2.660
2.100
0.570

Sub-total
Safety factors:

111
270
201
2,499
338
4,698
225
59
8,400
+10%
--------9,241

Total w/ safety factors:

Htg.
Loss

-15.960
0.000
-12.600

-62
0
-223

0.000

0
180
317
497
+10%
--------547

-285
+0%
---------285

Zone 15-12.25.002 Sub-Wait peaks (sensible) in December at 3pm, Air Handler 15 (FCU-12.25.002),
Group 1, 1.0 x 32.4, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

32.4
648
300
3.0
14
0

6/0

2.660

1.000
1.000
1.000

Sub-total
Safety factors:

517
648
300
225
188
1,878
+10%
--------2,065

Total w/ safety factors:

0.000

0.000

0
180
718
898
+10%
--------988

0
+0%
--------0

Zone 16-12.10.058 PET-CT Room peaks (sensible) in February at 10am, Air Handler 16 (FCU12.10.058), Group 1, 1.0 x 35.9, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-E-C-M
Partition-1-5
Gls-E-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

0
35.9
20.9
20.9
718
7,033
3.0
15
0

0.83
1.000
0.320
1.000
1.000
1.000

10.7
6/0
5
774

2.660
2.660
2.100
0.570

Sub-total
Safety factors:

0
573
237
2,944
718
7,033
225
125
11,855
+10%
--------13,040

Total w/ safety factors:

0.000
0.000
-12.600

0
0
-263

0.000

0
180
673
853
+10%
--------938

-263
+0%
---------263

Zone 17-12.10.011 Recovery Injection peaks (sensible) in December at 3pm, Air Handler 17 (FCU12.10.011), Group 1, 1.0 x 15.9, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5

15.9

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

6/0

2.660

254

0.000

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 54

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load
Description
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

Unit
Quan

-SCCFAC

318
600
3.0
7
0

1.000
1.000
1.000

CLTD
SHGF

U.Fac
-CLF-

Sub-total
Safety factors:

Sen.
Gain

Lat.
Gain

318
600
225
92

0
180
352

1,489
+10%
--------1,638

Total w/ safety factors:

Htg.
Mult.

Htg.
Loss

0.000

532
+10%
--------586

0
+0%
--------0

Zone 18-12.10.057 Post Endoscopy peaks (sensible) in February at 10am, Air Handler 18 (FCU12.10.057), Group 1, 1.0 x 33.7, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-E-C-M
Partition-1-5
Gls-E-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

3
33.7
10.7
10.7
674
4,700
3.0
14
0

0.83
1.000
0.320
1.000
1.000
1.000

10.7
6/0
5
774

2.660
2.660
2.100
0.570

Sub-total
Safety factors:

85
538
121
1,504
674
4,700
225
118
7,964
+10%
--------8,761

Total w/ safety factors:

-15.960
0.000
-12.600

-48
0
-134

0.000

0
180
632
812
+10%
--------893

-182
+0%
---------182

Zone 19-12.10.018 Endoscopy peaks (sensible) in December at 3pm, Air Handler 19 (FCU-12.10.018),
Group 1, 1.0 x 24.9, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

24.9
498
4,700
3.0
10
0

6/0

2.660

1.000
1.000
1.000

Sub-total
Safety factors:

397
498
4,700
225
144
5,965
+10%
--------6,561

Total w/ safety factors:

0.000

0.000

0
180
552
732
+10%
--------805

0
+0%
--------0

Zone 20-12.10.054 Opthalmology peaks (sensible) in December at 3pm, Air Handler 20 (FCU-12.10.054),
Group 1, 1.0 x 20.7, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

20.7
414
2,500
3.0
9
0

6/0
1.000
1.000
1.000

Sub-total
E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

2.660

330
414
2,500
225
120
3,589

0.000

0.000

0
180
459
639

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 55

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load
Description

Unit
Quan

-SCCFAC

CLTD
SHGF

U.Fac
-CLF-

Safety factors:
Total w/ safety factors:

Sen.
Gain

Lat.
Gain

+10%
--------3,948

+10%
--------703

Htg.
Mult.

Htg.
Loss
+0%
--------0

Zone 21-12.10.051 Non-Invasive peaks (sensible) in June at 2pm, Air Handler 21 (FCU-12.10.051),
Group 1, 1.0 x 16.1, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-N-C-M
Partition-1-5
Gls-N-1-90-Tran
0%S-0-NS-Solar
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

2
16.1
9.0
9.0
322
2,500
3.0
7
0

0.83
1.000
0.320
1.000
1.000
1.000

15.4
6/0
10
515

2.660
2.660
2.100
0.650

Sub-total
Safety factors:

74
257
197
964
322
2,500
225
91
4,630
+10%
--------5,093

Total w/ safety factors:

-15.960
0.000
-12.600

-29
0
-113

0.000

0
180
359
539
+10%
--------593

-142
+0%
---------142

Zone 22-12.10.049 Non-Invasive peaks (sensible) in June at 7pm, Air Handler 22 (FCU-12.10.049),
Group 1, 1.0 x 13.1, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Wall-2-N-C-M
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

11
13.1
262
2,500
3.0
5
0

0.83

20.4
6/0

2.660
2.660

1.000
1.000
1.000

Sub-total
Safety factors:

587
209
262
2,500
225
58
3,840
+10%
--------4,225

Total w/ safety factors:

-15.960
0.000

-172
0

0.000

0
180
289
469
+10%
--------516

-172
+0%
---------172

Zone 23-12.10.023 Generic Screening peaks (sensible) in December at 3pm, Air Handler 23 (FCU12.10.023), Group 1, 1.0 x 14.4, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

14.4
288
2,500
3.0
6
0

6/0
1.000
1.000
1.000

Sub-total
Safety factors:
Total w/ safety factors:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

2.660

230
288
2,500
225
83
3,326
+10%
--------3,659

0.000

0.000

0
180
319
499
+10%
--------549

0
+0%
--------0

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 56

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load
Unit
-SCCLTD
U.Fac
Sen.
Lat.
Htg.
Description
Quan
CFAC
SHGF
-CLFGain
Gain
Mult.
Zone 24-12.10.024 Generic Screening peaks (sensible) in December at 3pm, Air Handler 24 (FCU12.10.024), Group 1, 1.0 x 14.0, Construction Type: 1 (Light), SIDB: 22C, WIDB: 22C
Partition-1-5
Lights-Prof=1
Equipment-Prof=4
People-Prof=4
Cool. Infil.AC/hr
Heat. Infil.AC/hr

14
280
2,500
3.0
6
0

6/0
1.000
1.000
1.000

Sub-total
Safety factors:
Total w/ safety factors:

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

2.660

223
280
2,500
225
81
3,310
+10%
--------3,640

Htg.
Loss

0.000

0.000

0
180
310
490
+10%
--------539

0
+0%
--------0

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 57

Air System #1 (FCU-12.10.045) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

877
0
1,202
9,694
0

11.126
0.810
0.000
1.110
8.954
0.000

66
0
90
725
0

11,773
455
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

880

12,228

22.420

880

7.756

1,286

0.494

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

1,286

8.249

0.000

Entering Coil Condition

1,286

8.249

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

880
880

x(
x(

22.420
8.249

11.126
7.756

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

880

x(

43.593

30.826

)=
=

12,227
1,286
---------13,514
13,485
13,514

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

13,485 / (
-602 / (
-602 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.6 L/s
0.0 L/s
-0.62 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.93
43.59 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


11.13
10.63
94.00
30.83 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 58

Air System #2 (FCU-12.10.059) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

187
0
257
2,317
0

10.072
0.810
0.000
1.110
10.010
0.000

13
0
18
158
0

2,762
97
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

188

2,859

22.420

188

7.223

569

1.020

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

569

8.244

0.000

Entering Coil Condition

569

8.244

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

188
188

x(
x(

22.420
8.244

10.072
7.223

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

188

x(

43.578

28.410

)=
=

2,858
569
---------3,427
3,426
3,428

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

3,426 / (
-91 / (
-91 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.1 L/s
0.0 L/s
-0.09 kg./hr

Entering Heating Coil Conditions


22.42
15.59
48.89
43.58 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


10.07
9.59
94.00
28.41 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 59

Air System #3 (FCU-12.10.047) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

112
0
154
1,693
0

7.852
0.810
0.000
1.110
12.230
0.000

6
0
9
97
0

1,959
58
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

113

2,017

22.420

113

6.207

673

2.021

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

673

8.228

0.000

Entering Coil Condition

673

8.228

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

113
113

x(
x(

22.420
8.228

7.852
6.207

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

113

x(

43.539

23.593

)=
=

2,017
673
---------2,690
2,694
2,690

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

2,694 / (
0 /(
0 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.1 L/s
0.0 L/s
0.00 kg./hr

Entering Heating Coil Conditions


22.42
15.58
48.81
43.54 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


7.85
7.41
94.00
23.59 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 60

Air System #4 (FCU-12.10.046) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

1,482
0
2,031
15,104
0

11.825
0.810
0.000
1.110
8.256
0.000

118
0
162
1,207
0

18,617
768
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

1,488

19,385

22.420

1,488

8.127

533

0.121

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

533

8.249

0.000

Entering Coil Condition

533

8.249

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

1,488
1,488

x(
x(

22.420
8.249

11.825
8.127

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

1,488

x(

43.591

32.477

)=
=

19,385
533
---------19,918
19,839
19,919

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

19,839 / (
-136 / (
-136 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.8 L/s
0.0 L/s
-0.14 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.93
43.59 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


11.82
11.31
94.00
32.48 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 61

Air System #5 (FCU-12.10.043) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

105
0
144
1,560
0

8.079
0.810
0.000
1.110
12.003
0.000

6
0
8
91
0

1,809
55
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

106

1,864

22.420

106

6.305

603

1.927

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

603

8.232

0.000

Entering Coil Condition

603

8.232

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

106
106

x(
x(

22.420
8.232

8.079
6.305

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

106

x(

43.548

24.069

)=
=

1,864
603
---------2,466
2,470
2,467

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

2,470 / (
0 /(
0 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.1 L/s
0.0 L/s
0.00 kg./hr

Entering Heating Coil Conditions


22.42
15.58
48.83
43.55 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


8.08
7.63
94.00
24.07 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 62

Air System #6 (FCU-12.10.078) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

332
0
455
3,760
0

10.902
0.810
0.000
1.110
9.179
0.000

24
0
33
275
0

4,546
172
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

333

4,718

22.420

333

7.640

603

0.611

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

603

8.251

0.000

Entering Coil Condition

603

8.251

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

333
333

x(
x(

22.420
8.251

10.902
7.640

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

333

x(

43.597

30.305

)=
=

4,718
603
---------5,321
5,312
5,321

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

5,312 / (
0 /(
0 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.2 L/s
0.0 L/s
0.00 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.95
43.60 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


10.90
10.41
94.00
30.31 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 63

Air System #7 (FCU-12.10.014) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

138
0
189
1,954
0

8.617
0.810
0.000
1.110
11.466
0.000

8
0
11
119
0

2,282
72
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

139

2,353

22.420

139

6.541

695

1.695

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

695

8.236

0.000

Entering Coil Condition

695

8.236

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

139
139

x(
x(

22.420
8.236

8.617
6.541

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

139

x(

43.560

25.212

)=
=

2,353
695
---------3,048
3,051
3,048

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

3,051 / (
0 /(
0 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.1 L/s
0.0 L/s
0.00 kg./hr

Entering Heating Coil Conditions


22.42
15.58
48.85
43.56 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


8.62
8.16
94.00
25.21 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 64

Air System #8 (FCU-12.10.030) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

147
0
201
1,811
0

10.073
0.810
0.000
1.110
10.010
0.000

10
0
14
123
0

2,159
76
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

147

2,235

22.420

147

7.224

444

1.020

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

444

8.244

0.000

Entering Coil Condition

444

8.244

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

147
147

x(
x(

22.420
8.244

10.073
7.224

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

147

x(

43.578

28.412

)=
=

2,234
444
---------2,678
2,678
2,679

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

2,678 / (
0 /(
0 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.1 L/s
0.0 L/s
0.00 kg./hr

Entering Heating Coil Conditions


22.42
15.59
48.89
43.58 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


10.07
9.59
94.00
28.41 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 65

Air System #9 (FCU-12.10.070) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

146
0
200
1,802
0

10.104
0.810
0.000
1.110
9.979
0.000

10
0
14
123
0

2,149
76
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

147

2,225

22.420

147

7.239

439

1.011

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

439

8.250

0.000

Entering Coil Condition

439

8.250

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

147
147

x(
x(

22.420
8.250

10.104
7.239

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

147

x(

43.594

28.482

)=
=

2,224
439
---------2,664
2,663
2,664

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

2,663 / (
0 /(
0 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.1 L/s
0.0 L/s
0.00 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.93
43.59 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


10.10
9.62
94.00
28.48 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 66

Air System #10 (FCU-12.10.082) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

173
0
238
2,298
0

9.347
0.810
0.000
1.110
10.736
0.000

11
0
15
148
0

2,709
90
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

174

2,799

22.420

174

6.876

703

1.364

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

703

8.240

0.000

Entering Coil Condition

703

8.240

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

174
174

x(
x(

22.420
8.240

9.347
6.876

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

174

x(

43.568

26.797

)=
=

2,799
703
---------3,501
3,503
3,502

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

3,503 / (
0 /(
0 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.1 L/s
0.0 L/s
0.00 kg./hr

Entering Heating Coil Conditions


22.42
15.59
48.87
43.57 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


9.35
8.88
94.00
26.80 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 67

Air System #11 (FCU-12.10.081) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

618
0
847
6,887
0

11.052
0.810
0.000
1.110
9.029
0.000

46
0
63
512
0

8,352
320
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

620

8,672

22.420

620

7.717

978

0.533

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

978

8.250

0.000

Entering Coil Condition

978

8.250

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

620
620

x(
x(

22.420
8.250

11.052
7.717

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

620

x(

43.594

30.654

)=
=

8,671
978
---------9,649
9,630
9,650

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

9,630 / (
0 /(
0 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.4 L/s
0.0 L/s
0.00 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.93
43.59 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


11.05
10.55
94.00
30.65 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 68

Air System #12 (FCU-12.10.012) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

229
0
314
2,781
0

10.246
0.810
0.000
1.110
9.835
0.000

16
0
22
192
0

3,323
119
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

230

3,442

22.420

230

7.309

639

0.939

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

639

8.248

0.000

Entering Coil Condition

639

8.248

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

230
230

x(
x(

22.420
8.248

10.246
7.309

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

230

x(

43.590

28.803

)=
=

3,442
639
---------4,081
4,079
4,081

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

4,079 / (
-91 / (
-91 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.2 L/s
0.0 L/s
-0.09 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.93
43.59 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


10.25
9.76
94.00
28.80 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 69

Air System #13 (FCU-12.10.009) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

1,275
0
1,747
13,470
0

11.523
0.810
0.000
1.110
8.557
0.000

99
0
136
1,045
0

16,493
661
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

1,280

17,154

22.420

1,280

7.965

1,089

0.287

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

1,089

8.253

0.000

Entering Coil Condition

1,089

8.253

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

1,280
1,280

x(
x(

22.420
8.253

11.523
7.965

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

1,280

x(

43.601

31.760

)=
=

17,153
1,089
---------18,243
18,187
18,224

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

18,187 / (
-547 / (
-547 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.8 L/s
0.0 L/s
-0.56 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.95
43.60 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


11.52
11.02
94.00
31.76 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 70

Air System #14 (FCU-12.10.053) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

890
0
1,219
9,241
0

11.669
0.810
0.000
1.110
8.411
0.000

70
0
96
727
0

11,350
461
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

893

11,811

22.420

893

8.043

547

0.207

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

547

8.250

0.000

Entering Coil Condition

547

8.250

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

893
893

x(
x(

22.420
8.250

11.669
8.043

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

893

x(

43.595

32.106

)=
=

11,811
547
---------12,357
12,314
12,358

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

12,314 / (
-285 / (
-285 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.5 L/s
0.0 L/s
-0.29 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.93
43.59 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


11.67
11.16
94.00
32.11 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 71

Air System #15 (FCU-12.25.002) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

116
0
160
2,065
0

5.727
0.810
0.000
1.110
14.360
0.000

6
0
8
103
0

2,342
60
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

117

2,402

22.420

117

5.356

988

2.854

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

988

8.210

0.000

Entering Coil Condition

988

8.210

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

117
117

x(
x(

22.420
8.210

5.727
5.356

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

117

x(

43.492

19.295

)=
=

2,401
988
---------3,389
3,396
3,390

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

3,396 / (
0 /(
0 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.1 L/s
0.0 L/s
0.00 kg./hr

Entering Heating Coil Conditions


22.42
15.56
48.70
43.49 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


5.73
5.32
94.00
19.30 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 72

Air System #16 (FCU-12.10.058) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

1,243
0
1,704
13,040
0

11.584
0.810
0.000
1.110
8.497
0.000

97
0
133
1,018
0

15,987
645
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

1,248

16,632

22.420

1,248

7.997

938

0.254

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

938

8.251

0.000

Entering Coil Condition

938

8.251

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

1,248
1,248

x(
x(

22.420
8.251

11.584
7.997

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

1,248

x(

43.598

31.902

)=
=

16,631
938
---------17,570
17,513
17,570

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

17,513 / (
-263 / (
-263 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.7 L/s
0.0 L/s
-0.27 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.95
43.60 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


11.58
11.08
94.00
31.90 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 73

Air System #17 (FCU-12.10.011) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

115
0
158
1,638
0

8.588
0.810
0.000
1.110
11.494
0.000

7
0
10
99
0

1,911
60
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

116

1,971

22.420

116

6.529

586

1.708

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

586

8.236

0.000

Entering Coil Condition

586

8.236

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

116
116

x(
x(

22.420
8.236

8.588
6.529

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

116

x(

43.560

25.150

)=
=

1,971
586
---------2,556
2,559
2,557

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

2,559 / (
0 /(
0 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.1 L/s
0.0 L/s
0.00 kg./hr

Entering Heating Coil Conditions


22.42
15.58
48.85
43.56 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


8.59
8.13
94.00
25.15 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 74

Air System #18 (FCU-12.10.057) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

815
0
1,117
8,761
0

11.376
0.810
0.000
1.110
8.704
0.000

62
0
86
671
0

10,693
423
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

818

11,116

22.420

818

7.887

893

0.369

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

893

8.256

0.000

Entering Coil Condition

893

8.256

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

818
818

x(
x(

22.420
8.256

11.376
7.887

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

818

x(

43.609

31.412

)=
=

11,116
893
---------12,009
11,977
12,009

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

11,977 / (
-182 / (
-182 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.5 L/s
0.0 L/s
-0.19 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.97
43.61 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


11.38
10.87
94.00
31.41 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 75

Air System #19 (FCU-12.10.018) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

599
0
820
6,561
0

11.204
0.810
0.000
1.110
8.877
0.000

45
0
62
494
0

7,980
310
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

601

8,290

22.420

601

7.796

805

0.453

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

805

8.249

0.000

Entering Coil Condition

805

8.249

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

601
601

x(
x(

22.420
8.249

11.204
7.796

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

601

x(

43.591

31.008

)=
=

8,290
805
---------9,095
9,074
9,095

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

9,074 / (
0 /(
0 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.4 L/s
0.0 L/s
0.00 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.93
43.59 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


11.20
10.70
94.00
31.01 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 76

Air System #20 (FCU-12.10.054) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

343
0
470
3,948
0

10.753
0.810
0.000
1.110
9.328
0.000

25
0
34
285
0

4,761
178
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

344

4,939

22.420

344

7.563

703

0.690

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

703

8.253

0.000

Entering Coil Condition

703

8.253

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

344
344

x(
x(

22.420
8.253

10.753
7.563

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

344

x(

43.601

29.960

)=
=

4,938
703
---------5,641
5,633
5,641

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

5,633 / (
0 /(
0 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.2 L/s
0.0 L/s
0.00 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.95
43.60 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


10.75
10.26
94.00
29.96 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 77

Air System #21 (FCU-12.10.051) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

467
0
640
5,093
0

11.252
0.810
0.000
1.110
8.829
0.000

35
0
48
385
0

6,201
242
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

469

6,443

22.420

469

7.821

593

0.427

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

593

8.248

0.000

Entering Coil Condition

593

8.248

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

469
469

x(
x(

22.420
8.248

11.252
7.821

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

469

x(

43.591

31.121

)=
=

6,442
593
---------7,035
7,018
7,036

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

7,018 / (
-142 / (
-142 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.3 L/s
0.0 L/s
-0.15 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.93
43.59 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


11.25
10.75
94.00
31.12 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 78

Air System #22 (FCU-12.10.049) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

386
0
529
4,225
0

11.209
0.810
0.000
1.110
8.872
0.000

29
0
40
318
0

5,139
200
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

387

5,339

22.420

387

7.799

516

0.450

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

516

8.249

0.000

Entering Coil Condition

516

8.249

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

387
387

x(
x(

22.420
8.249

11.209
7.799

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

387

x(

43.591

31.019

)=
=

5,338
516
---------5,854
5,840
5,854

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

5,840 / (
-172 / (
-172 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.2 L/s
0.0 L/s
-0.18 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.93
43.59 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


11.21
10.71
94.00
31.02 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 79

Air System #23 (FCU-12.10.023) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

326
0
447
3,659
0

10.987
0.810
0.000
1.110
9.094
0.000

24
0
33
270
0

4,431
169
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

327

4,600

22.420

327

7.683

549

0.567

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

549

8.250

0.000

Entering Coil Condition

549

8.250

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

327
327

x(
x(

22.420
8.250

10.987
7.683

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

327

x(

43.595

30.501

)=
=

4,600
549
---------5,149
5,139
5,149

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

5,139 / (
0 /(
0 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.2 L/s
0.0 L/s
0.00 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.93
43.60 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


10.99
10.49
94.00
30.50 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Chvac - Full Commercial HVAC Loads Calculation Program


METSiS
Mechanical Division

Elite Software Development, Inc.


EKA Hospital
Page 80

Air System #24 (FCU-12.10.024) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

325
0
445
3,640
0

11.002
0.810
0.000
1.110
9.079
0.000

24
0
33
269
0

4,410
168
0
0
0
0

22.000
0.420
0.000
0.000
0.000
0.000

326

4,579

22.420

326

7.691

539

0.559

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 L/s
Blow-Thru Fan

539

8.250

0.000

Entering Coil Condition

539

8.250

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010.387)


PR x
1.23 x L/s x (DB entering - DB leaving)
PR x
2.96 x L/s x (g/kg entering - g/kg leaving)
PR x
1.20 x L/s x (Enthalpy entering - Enthalpy leaving)
1.000
1.000

x
x

1.23
2.96

x
x

326
326

x(
x(

22.420
8.250

11.002
7.691

)=
)=

SUM
=
GTH
=
1.000
Total System Load

1.20

326

x(

43.595

30.538

)=
=

4,578
539
---------5,118
5,108
5,118

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

5,108 / (
0 /(
0 /

5.60
0.00
970

x
x

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

=
=
=

0.2 L/s
0.0 L/s
0.00 kg./hr

Entering Heating Coil Conditions


22.42
15.60
48.93
43.59 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

4,179
4,179

Dry bulb temperature:

22.00

Leaving Heating Coil Conditions


11.00
10.51
94.00
30.54 kJ/kg

E:\TA1054 Eka Hospital\Eka Hospital Floor 12 (+10).CHV

Dry bulb temperature:

22.00

Sunday, July 05, 2015, 07:05 PM

Vous aimerez peut-être aussi