CONTENIDO
INTRODUCCIN.................................................................................................... 2
I.
INFORMACIN GENERAL................................................................................ 3
II.
REGLAMENTOS Y NORMAS............................................................................. 3
III.
IV.
ESTRUCTURACIN...................................................................................... 4
V.
PREDIMENSIONAMIENTO DE ELEMENTOS.......................................................4
VI.
PARMETROS SSMICOS.............................................................................. 5
VII.
VIII.
METRADO DE CARGAS.............................................................................. 10
IX.
CENTRO DE GRAVEDAD............................................................................. 12
X.
CENTRO DE RIGIDECES................................................................................. 13
XI.
ANLISIS SSMICO.................................................................................... 17
XII.
RESULTADOS...................................................................................................... 29
BIBLIOGRAGIA................................................................................................... 30
INTRODUCCIN
El Per por su ubicacin geogrfica, al encontrarse en la zona del Cinturn de Fuego,
constituye un pas altamente ssmico, y ello lo demuestra los diferentes sismos ocurridos a
lo largo de nuestra historia. Sismos de mediana a gran intensidad, los cuales causaron
graves daos en nuestra infraestructura e incluso en algunos casos se lleg a la condicin de
colapso total.
Se tiene entonces la necesidad de disear y construir edificios ms resistentes a las
solicitaciones ssmicas (edificios sismo-resistentes), esto se lograr siempre en cuando se
cumplan con los reglamentos existentes en la actualidad en nuestro pas tales como el RNE
(Reglamento Nacional de Edificaciones).
Sin embargo no sucede as, se observa la construccin indiscriminada de edificios que no
cuentan con la asesora de un profesional (Ingeniero Civil), as como el incumplimiento de
las normas existentes. Urge entonces por parte de las autoridades la supervisin de las
viviendas por construirse, es decir prohibir las construccin de estas en caso no cuenten con
las asesora de profesionales.
En el presente informe se sigue la metodologa a seguir para el diseo de edificaciones de
albailera confinada empleando la Norma E-070 del RNE, y el uso de bibliografa cuya
referencia se hace ms adelante.
Se hizo el diseo en planta de una vivienda multifamiliar de cuatro pisos en la ciudad de
Chachapoyas Amazonas, y que por practicidad se tom solo en cuenta la primera planta,
como planta tpica para el clculo de Metrados total de la edificacin, descartando tambin
el Metrado de la escalera para el diseo de los muros donde se apoyaban. Se utiliz la
metodologa del libro de Anlisis y Diseo de Edificaciones de Albailera del autor Ing.
Flavio Abanto Castillo, teniendo en cuenta tambin algunos aspectos del libro
Construcciones de Albailera del autor Ing. ngel San Bartolom que se encuentra ms
arraigado a la Norma E-070 de Albailera.
INFORMACIN GENERAL
II.
Las Normas empleadas para el anlisis y diseo de la estructura son las siguientes:
III.
Albailera
- Ladrillos clase IV slidos (30% de huecos), tipo King Kong de arcilla, t = 13 cm, 23 cm,
fb = 145 kg/cm2
- Mortero tipo P2: cemento-arena 1 : 4 , slump (6)
- Pilas: resistencia caracterstica a compresin = fm = 65 kg/cm2 = 650 ton/m2
- Muretes: resistencia caracterstica a corte puro = vm = 8.1 kg/cm2 = 81 ton/m2
- Mdulo de elasticidad = Em = 500 fm = 32,500 kg/cm2 = 325,000 ton/m2
- Mdulo de corte = Gm = 0.4 Em = 13,000 kg/cm2 Mdulo de Poisson = n = 0.25
Concreto
- Resistencia nominal a compresin = fc = 210 kg/cm2
- Mdulo de elasticidad = Ec = 217,000 kg/cm2 = 2170,000 ton/m2
- Mdulo de Poisson = n = 0.15
Acero de Refuerzo
- Corrugado, grado 60, esfuerzo de fluencia = fy = 4200 kg/cm2 = 4.2 ton/cm2.
IV.
ESTRUCTURACIN
PREDIMENSIONAMIENTO DE ELEMENTOS
V.1.
Para la Mayor Luz entre columnas = 4.80 m, el peralte de la losa igual a h/30 = 16m , pero
asumiremos un espesor de 15cm.
V.3.
La Norma NTE E-070 especifica que el espesor mnimo de las columnas y vigas soleras
deben ser el igual al espesor efectivo del muro. Asimismo, indica que el peralte mnimo
para las columnas de confinamiento es de 15cm y el peralte mnimo de las soleras debe ser
igual al espesor de la losa del techo.
En resumen para el predimensionamiento se tiene:
-
VI.
PARMETROS SSMICOS
Parmetros del Suelo (S) y (Tp), se considera la mayor parte del suelo de Chachapoyas
arcilloso. Segn la Tabla N2 de la Norma E.030, a Chachapoyas le corresponde un tipo
S2
TP
de Suelo
con un valor de S=1.2 y un periodo
= 0.6 seg.
TP
; C 2.50
T
hn
CT
Donde:
hn = 2.55 x 4 pisos = 10.20 m (Altura total del edificio)
CT = 60 (para estructuras de albailera segn Norma E-030
T=
C=2.5 x
0.6
=8.82>2.5 , C=2.5
0.17
Parmetro
Z
U
S
R
C
VII.
Valor
0.30
1.00
1.20
3
2.5
Previo al anlisis estructural es necesario verificar que la edificacin cumpla con algunos
requerimientos, tales como la densidad mnima de muros, el esfuerzo axial mximo permitido y
otras caractersticas que debe tener una edificacin de albailera confinada.
Ap
Donde:
Ap
2
: 144.25 m
:4
: 0.13 m
ZUSN
=0.030
56
Tabla N 2 Densidad de muros en la direccin XX
Muro
X1
L (m)
3.30
Direccin X-X
t (m)
L.t (m2)
N Veces
0.13
0.429
1
6
L.t.N (m2)
0.429
2.88
3.05
3.05
3.70
3.70
3.05
3.70
3.70
3.05
3.70
3.05
4.95
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.374
0.397
0.397
0.481
0.481
0.397
0.481
0.481
0.397
0.481
0.397
0.644
1
1
1
1
1
1
1
1
1
1
1
1
0.374
0.397
0.397
0.481
0.481
0.397
0.481
0.481
0.397
0.481
0.397
0.644
5.8344
Tabla N 3 Densidad de muros en la direccin YY
Muro
Y1
Y2
Y3
Y4
Y5
Y6
Y7
Y8
Y9
Y10
Y11
Y12
L (m)
2.40
4.35
3.00
1.50
2.85
3.25
4.65
4.65
2.75
2.85
4.10
1.60
t (m)
0.13
0.13
0.13
0.13
0.13
0.13
0.23
0.13
0.13
0.13
0.13
0.13
|Direccin Y-Y
L.t (m2)
N Veces
0.312
1
0.566
1
0.390
1
0.195
1
0.371
1
0.423
1
1.070
1
0.605
1
0.358
1
0.371
1
0.533
1
0.208
1
5.399
En XX:
L. t . N / Ap=
L. t . N / Ap=
En YY:
5.399/144.25 = 0.037 > 0.030 OK
L.t.N (m2)
0.312
0.566
0.390
0.195
0.371
0.423
1.070
0.605
0.358
0.371
0.533
0.208
m=
[ ( )]
Pm
h
0.2 f ' m 1
t xL
35 t
0.15 f ' m
Donde:
h = altura de entrepiso
L= longitud total del muro, incluyendo el peralte de las columnas.
.15
2.40
Cargas
Muros de Albailera Tarrajeada:
0.018 ton/m3.cm x 13cm + 0.020 ton/m2.cm x 2cm = 0.274 ton/m2
Peso propio
: 0.274 ton/m2 x 2.40 m x 3.70 m x 4
Solera
: 0.15m x 0.13m x 3.70m x 2.40ton/m3 x 4
Losa
: (0.360 ton/m2 + 0.10 ton/m2) x 11.35m2 x4
Zona de puertas :
Zona de parapetos:
Sobrecarga
: 0.20 ton/m2 x 11.35 m2 x3 + 0.1ton/m2x11.35m2
8
= 9.732 ton
= 0.693 ton
=20.884ton
=0.374 ton
=0.264 ton
=7.945 ton
a)
m=
b)
0.2 f ' m 1
c)
[ ( )]
h
35 t
89.93 ton/m2
[ (
=0.2 x 850 1
2.40
35 x 0.13
) ]=
2
93.83 ton/m2
Se observa que el esfuerzo axial mximo en este muro resulta ser menos que los valores
m
lmites establecidos:
= 89.93 ton/m2 93.83 ton/m2
VII.3. Requisitos Adicionales para Albailera Confinada
Se considerar como muro portante confinado a aquel que cumpla las Siguientes
condiciones:
- El muro debe encontrarse enmarcado en sus cuatro lados por elementos de concreto
armado verticales (columnas) y horizontales (vigas soleras). Para los muros ubicados en el
primer piso se acepta la cimentacin como elemento de confinamiento horizontal.
- Una longitud mayor o igual a 1,20m para ser considerado como contribuyente en la
resistencia a las fuerzas horizontales.
- La distancia mxima centro a centro entre columnas de confinamiento ser dos veces la
distancia entre los elementos horizontales de refuerzo y no mayor de 5 metros.
- Se utiliza en los elementos de confinamiento concreto con una resistencia fc 17.15 Mpa
(175 kg/cm2).
- Se asume que el pao de albailera simple no soporta acciones de punzonamiento
causadas por cargas concentradas.
- El espesor mnimo las vigas soleras ser igual al espesor efectivo del muro y su peralte
mnimo igual al espesor de la losa de techo.
- El peralte mnimo de la columna de confinamiento ser 15cm o el espesor efectivo del
muro.
VIII.
METRADO DE CARGAS
Caractersticas Geomtricas:
- Nmero de pisos
- Altura de entrepiso
- Altura de piso a techo
- rea construida
- Peralte de losa maciza
- Espesor efectivos de muros
:4
: 2.55m
: 2.40m
: 144.25m2
: 0.15m
: 0.13m
: 2.4 ton/m3
: 1.8 ton/m3
: 2.0 ton/m3
Cargas Consideradas:
- Piso terminado
- Sobrecarga pito tpico
- Sobrecarga azotea
:100kg/m2
:200kg/m2
:100kg/m2
Secciones Tpicas
10
.15
.15
.15
.15
.45
1.05
2.40
2.25
1.80
1.20
Muros portantes
a) Cargas Directas
Las cargas directas se refieren al peso propio de alfeizar, ventanas y muros de albailera.
Piso tpico:
Muros Portantes:
W = 2.40x0.274 + 0.15x0.13x2.40 + 0.1x0.13 = 0.717 ton/m
Zona de ventanas bajas:
W = 1.20x0.274 + 1.05x0.02 + 0.352x0.30 =0.455 ton/m
Zona de ventanas altas:
W = 1.80x0.274 + 0.45x0.02 + 0.352x0.30 =0.608 ton/m
Zona de puertas:
W = 0.352x0.30 =0.106 ton/m
Zona de parapetos:
W= 0.274 x 0.90 = 0.247 ton/m
11
= 0.1 ton/m2
1er
75.97 m
4.65 m
2.45 m
0.00 m
6.80 m
1.25 m
10.90 m
2do
75.97 m
4.65 m
2.45 m
0.00 m
6.80 m
1.25 m
10.90 m
3er
75.97 m
4.65 m
2.45 m
0.00 m
6.80 m
1.25 m
10.90 m
4to
75.97 m
4.65 m
2.45 m
59.05 m
6.80 m
1.25 m
10.90 m
Piso
1er
2do
3er
4to
TOTAL
IX.
55.02
55.02
55.02
55.02
220.10
4.90
4.90
4.90
19.46
34.16
51.93
51.93
51.93
51.93
207.72
CENTRO DE GRAVEDAD
IX.1. Centro de Gravedad
12
0.58
0.58
0.58
0.58
2.30
CARGA
MUERTA (D)
112.43
112.43
112.43
126.99
464.28
CARGA
VIVA (L)
7.21
7.21
7.21
3.61
18.03
CARGA
TOTAL
(D+L)
119.64
119.64
119.64
130.60
489.52
geometra de cada muro, su ubicacin en planta y su carga propia. Colocando como ejes
(0;0) la esquina izquierda de debajo de la edificacin.
n
( Pi . X i )
X CG = i=1
( Pi .Y i )
Y CG = i=1
Pi
Pi
i=1
i=1
Tabla N 6. Clculo del Centro de Gravedad con los Datos Geomtricos de Muros.
Muro
X1
X2
X3
X4
X5
X6
X7
X8
X9
X10
X11
X12
X13
Y1
Y2
Y3
Y4
Y5
Y6
Y7
Y8
Y9
Y10
Y11
Y12
X CG =
h
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
L
3.30
2.88
3.05
3.05
3.70
3.70
3.05
3.70
3.70
3.05
3.70
3.05
4.95
2.40
4.35
3.00
1.50
2.85
3.25
4.65
4.65
2.75
2.85
4.10
1.60
t
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.13
0.23
0.13
0.13
0.13
0.13
0.13
Ym
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
Peso (Tn)
1.85
1.62
1.71
1.71
2.08
2.08
1.71
2.08
2.08
1.71
2.08
1.71
2.78
1.35
2.44
1.68
0.84
1.60
1.83
4.62
2.61
1.54
1.60
2.30
0.90
48.53
218.07
=4.49m
48.53
13
x
1.650
6.238
7.475
7.475
1.850
1.850
7.475
1.850
1.850
7.475
1.850
7.475
2.475
0.065
4.875
8.925
8.925
3.615
0.065
4.875
8.925
0.065
4.875
8.925
0.065
y
0.065
0.065
2.915
4.265
4.265
5.515
6.765
9.865
11.265
11.265
15.215
15.215
17.915
3.150
2.175
1.500
3.600
6.875
8.325
9.025
9.025
13.925
16.574
13.250
17.200
P.x
3.06
10.09
12.80
12.80
3.84
3.84
12.80
3.84
3.84
12.80
3.84
12.80
6.88
0.09
11.91
15.04
7.52
5.79
0.12
22.52
23.31
0.10
7.80
20.55
0.06
218.07
P.y
0.12
0.11
4.99
7.31
8.86
11.46
11.59
20.50
23.41
19.30
31.62
26.06
49.80
4.25
5.31
2.53
3.03
11.00
15.19
41.70
23.57
21.51
26.53
30.51
15.46
415.70
415.70
=8.57 m
48.53
X. CENTRO DE RIGIDECES
Para el clculo del centro de rigidez necesitamos conocer las rigidices de cada de muro, que
es la relacin que existe entre la fuerza aplicada y la deformacin generada por esta fuerza.
K=
Ea
3
H fH E a
+
3 I A Ga
Donde:
A axial
A alma
14
: Ec = 217,000 kg/cm2
: Ea=500 f'm= 500x65 = 32500 kg/cm2
: n = Ec / Ea = 6.67 6.70
: treal = 0.15 m
: n x treal = 1.00 m
Ejemplo:
MURO X1
.15
3.00
.15
SECCIN REAL
1.00
2
3.00
SECCIN TRANSFORMADA
.15
rea real
= 0.435m2
15
.13
= 0.69m2
= 0.69/0.435 =1.586
= 1.03725m4
MURO X2
4.35
3.00
.15
1.09
.15
SECCIN REAL
4
.13
3.00
1.00
SECCIN TRANSFORMADA
.15
rea real
rea transformada
f
Iyy seccin transformada
.15
= 0.489m2
= 0.7764m2
= 0.7764/0.489 =1.586
= 0.95729m4
MURO
X1
X2
X3
I
1.03725
0.95729
1.13971
f
1.586
2.04378
2.0809
A
0.69
0.77645
0.8603
16
H
2.55
2.55
2.55
K
16264.72
14409.82
16033.95
1.00025
1.63978
1.66808
1.10675
1.663
1.3715
1.2741
1.6528
1.0898
3.9862
1.6284
1.73183
1.73183
1.99407
1.7464
1.5236
2.339
1.7318
1.9646
1.7049
0.7584
0.8434
0.8434
0.80261
0.84763
0.724
0.94155
0.8434
0.7908
1.1073
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.55
total
16914.89
19743.61
19812.44
15600.56
19746.98
18629.27
16109.17
19775.79
15543.38
29012.43
237597.03
MURO
Y1
Y2
Y3
Y4
Y5
Y6
Y7
Y8
Y9
Y10
Y11
Y12
I
0.6082
2.2268
1.0013
0.1939
0.9112
1.2464
2.411
3.3297
0.8372
0.9612
2.5565
0.2453
f
2.1862
1.6236
1.9
2.7731
1.9967
1.8773
1.4177
1.7499
2.0323
2.1054
1.8494
2.9449
A
0.6952
0.9274
0.7524
0.5574
0.7518
0.8044
0.8655
1.0683
0.7388
0.7927
0.9968
0.6302
H
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.55
2.55
total
KI Y I
Ki
2063156.03
=8.68 m
237597.03
Yi
0.07
0.07
2.92
4.27
4.27
5.52
Ki
16264.72
14409.82
16033.95
16914.89
19743.61
19812.44
17
KiYi
1057.21
936.64
46738.97
72142.02
84206.52
109265.62
K
11154.90
23822.07
15033.47
5396.78
14132.23
16828.59
25520.64
26854.30
13464.06
14328.45
23231.27
6211.51
195978.26
X CR =
KIXI
Ki
6.77
9.87
11.27
11.27
15.22
15.22
17.92
total
15600.56
19746.98
18629.27
16109.17
19775.79
15543.38
29012.43
237597.03
105537.79
194804.00
209858.76
181469.78
300888.59
236492.50
519757.65
2063156.03
993936.48
=5.07 m
195978.26
MURO
Y1
Y2
Y3
Y4
Y5
Y6
Y7
Y8
Y9
Y10
Y11
Y12
XI.
Xi
0.07
4.88
8.93
8.93
3.62
0.07
4.88
8.93
0.07
4.88
8.93
0.07
total
Ki
11154.90
23822.07
15033.47
5396.78
14132.23
16828.59
25520.64
26854.30
13464.06
14328.45
23231.27
6211.51
195978.26
KiXi
725.07
116132.59
134173.69
48166.29
51088.01
1093.86
124413.10
239674.65
875.16
69851.20
207339.11
403.75
993936.48
ANLISIS SSMICO
Se realizar un anlisis por sismo moderado, que de acuerdo a la Norma E-070, el sismo
moderado se define como aquel que origina fuerzas de inercia iguales a la mitad de las
correspondientes al sismo severo (donde R=3, segn la Norma E-030), esto significa que
para el sismo moderado puede emplearse un factor de reduccin de las fuerzas ssmicas
elsticas R=6.
XI.1. Determinacin de las Fuerzas de Inercia (Fi)
18
V=(
ZUCS
P
R
Parmetro
VALORES
s Ssmicos
Z
0.30
ZONA SISMICA :
Descripcin
2 Amazonas
viviendas
multifamiliares
Suelos intermedios
albailera confinada
1.00
Edificacin para:
S
R
Tp
H
Ct
T
Ccalculad
o
Casumido
K
P(Tn)
1.20
6.00
0.60
10.20
60.00
0.170
Tipo de suelo:
Tipo de estructura:
Factor que depende de "S"
Altura total de la Edificacin (metros)
Coeficiente para Estimar el periodo fundamental
Periodo fundamental de la estructura
8.82
2.50
0.150
489.52
V(Tn)
73.43
Fi
Pi hi
v
h
i i
Piso
4
3
2
Pi
130.60
119.64
119.64
hi
10.2
7.65
5.1
Pi*hi
1332.10
915.26
610.18
19
(Pi*hi/Pi*hi
)
0.421
0.289
0.193
Fi
30.93
21.25
14.17
Vi
30.93
52.18
66.35
119.64
489.52
2.55
305.09
3162.62
0.096
7.08
73.43
73.43
Cortante Traslacional
VD
Ki
V
Ki
El anlisis se realizara para los muros del primer piso, puesto que son los que soportante las
mayores solicitaciones ssmicas.
V = 73.43 Ton
Tabla N 12 Y 13. Cortante Traslacional en cada muro en la direcciones XX y YY
Muro
X1
X2
X3
X4
X5
X6
X7
X8
X9
X10
X11
X12
X13
TOTAL
El momento torsor se evala en cada nivel y para cada direccin de sismo; en consecuencia,
se tendr dos momentos torsores para cada direccin de acuerdo a la expresin anterior.
Teniendo en cuenta que:
X
( CG , Y CG )=(4.49; 8.57)
CR
,Y
(
CR )=(5.07 ; 8.68)
Sismo en el sentido X
Excentricidad Real:
e y =Y CG Y CR =0.12
Excentricidad Accidental:
21
0.045m
e X = X CG X CR =0.58
Excentricidad Accidental:
0.90 m
K ix
) y
Em
J
M t 1x (
V 2 ix
K ix
) y
Em
J
M t 2x (
Direccin Y
V 1 iy
K iy
)x
Em
J
M t 1 y(
V 2 iy
K iy
) x
Em
J
M t 2 y(
K ix
K
y 2 + iy x2
Em
Em
y i y cr = y
, x ix cr =x
Donde:
M tx
22
Xi
: Abscisa del centro de gravedad del muro i respecto a un sistema de coordenado referencial
YI
: Ordenada del centro de gravedad del muro i respecto a un sistema de
coordenado referencial
: Abscisa del centro de rigidez del muro i respecto al sistema coordenado cuyo origen es en
: Ordenada del centro de rigidez del muro i respecto al sistema coordenado cuyo origen es
V2
Muro
X1
X2
X3
X4
X5
X6
X7
X8
X9
X10
X11
X12
X13
Y1
Y2
Y3
Y4
Xi
1.650
6.238
7.475
7.475
1.850
1.850
7.475
1.850
1.850
7.475
1.850
7.475
2.475
0.065
4.875
8.925
8.925
Yi
0.065
0.065
2.915
4.265
4.265
5.515
6.765
9.865
11.265
11.265
15.215
15.215
17.915
3.150
2.175
1.500
3.600
x
-2.844
1.744
2.981
2.981
-2.644
-2.644
2.981
-2.644
-2.644
2.981
-2.644
2.981
-2.019
-4.429
0.381
4.431
4.431
-8.501
-8.501
-5.651
-4.301
-4.301
-3.051
-1.801
1.299
2.699
2.699
6.649
6.649
9.349
-5.416
-6.391
-7.066
-4.966
23
Kix/Ea
0.05005
0.04434
0.04934
0.05205
0.06075
0.06096
0.04800
0.06076
0.05732
0.04957
0.06085
0.04783
0.08927
0.00000
0.00000
0.00000
0.00000
Kiy/Ea
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.03432
0.07330
0.04626
0.01661
J
3.61700
3.20450
1.57571
0.96297
1.12401
0.56763
0.15577
0.10246
0.41742
0.36096
2.68971
2.11406
7.80171
0.67322
0.01065
0.90828
0.32606
3.615
0.065
4.875
8.925
0.065
4.875
8.925
0.065
6.875
8.325
9.025
9.025
13.925
16.574
13.250
17.200
-0.879
-4.429
0.381
4.431
-4.429
0.381
4.431
-4.429
-1.691
-0.241
0.459
0.459
5.359
8.008
4.684
8.634
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.04348
0.05178
0.07853
0.08263
0.04143
0.04409
0.07148
0.01911
J
0.03358
1.01563
0.01141
1.62245
0.81258
0.00641
1.40356
0.37488
31.89262
Tabla N 15. Incremento de Fuerza cortante por rotacin en cada muro en la direcciones XX y YY
Direccin XX
Direccin YY
K ix / E m
K iY / E m
MUR
V 2 iy-2.844
O
1 iy
X1
0.05005 V 0.00000
x
X2
X3
X4
X5
X6
X7
X8
X9
X10
X11
X12
X13
Y1
Y2
Y3
Y4
Y5
Y6
Y7
Y8
Y9
Y10
Y11
Y12
0.04434
0.04934
0.05205
0.06075
0.06096
0.04800
0.06076
0.05732
0.04957
0.06085
0.04783
0.08927
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.00000
0.03432
0.07330
0.04626
0.01661
0.04348
0.05178
0.07853
0.08263
0.04143
0.04409
0.07148
0.01911
-8.501
y
-8.501
-5.651
-4.301
-4.301
-3.051
-1.801
1.299
2.699
2.699
6.649
6.649
9.349
-5.416
-6.391
-7.066
-4.966
-1.691
-0.241
0.459
0.459
5.359
8.008
4.684
8.634
1.744
2.981
2.981
-2.644
-2.644
2.981
-2.644
-2.644
2.981
-2.644
2.981
-2.019
-4.429
0.381
4.431
4.431
-0.879
-4.429
0.381
4.431
-4.429
0.381
4.431
-4.429
-0.610
V 1 ix
V
-0.522
2 ix
-0.541
-0.400
-0.321
-0.375
-0.267
-0.124
0.113
0.222
0.192
0.580
0.456
1.197
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
-0.462
-0.342
-0.275
-0.321
-0.228
-0.106
0.097
0.190
0.164
0.496
0.390
1.024
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
Cortante de Diseo
V TORSION :
24
1 Si
valor
V 1 >0
V 1 >0
Se toma el mayor
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
-0.356
0.065
0.480
0.172
-0.089
-0.537
0.070
0.857
-0.430
0.039
0.742
-0.198
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.274
-0.050
-0.370
-0.133
0.069
0.413
-0.054
-0.660
0.331
-0.030
-0.571
0.153
V tras
(Ton)
5.027
4.453
4.955
5.228
6.102
6.123
4.821
6.103
5.757
4.978
6.112
4.804
8.966
-0.610
V 1 ix
-0.541
-0.400
-0.321
-0.375
-0.267
-0.124
0.113
0.222
0.192
0.580
0.456
1.197
V 2 ix
-0.522
V x
(asu
-0.462
mido)
-0.342
-0.275
-0.321
-0.228
-0.106
0.097
0.113
0.190
0.222
0.164
0.192
0.496
0.580
0.390
0.456
1.024
1.197
V5.027
x
(dis
4.453
eo)
4.955
5.228
6.102
6.123
4.821
6.216
5.979
5.170
6.692
5.260
10.163
% abs
6.85%
6.06%
6.75%
7.12%
8.31%
8.34%
6.57%
8.47%
8.14%
7.04%
9.11%
7.16%
13.84%
103.76%
V tras
(Ton)
4.179
8.926
5.633
2.022
5.295
6.305
9.562
10.062
5.045
5.369
8.704
2.327
-0.356
V 1 ix
0.274
V 2 ix
0.065
0.480
0.172
-0.089
-0.537
0.070
0.857
-0.430
0.039
0.742
-0.198
-0.050
-0.370
-0.133
0.069
0.413
-0.054
-0.660
0.331
-0.030
-0.571
0.153
V0.274
x
(asu
0.065
mido)
0.480
0.172
0.069
0.413
0.070
0.857
0.331
0.039
0.742
0.153
25
4.454
8.991
6.113
2.194
5.364
6.719
9.632
10.919
5.375
5.408
9.446
2.480
% abs
6.07%
12.24%
8.32%
2.99%
7.30%
9.15%
13.12%
14.87%
7.32%
7.36%
12.86%
3.38%
104.99%
0.55
Vm
Pg
V .L
1
= e 1
3
Me
Donde:
Ve
Me
26
X1
Peso
propio
muros
(Tn)
2.37
X2
2.07
Muro
Area
tributaria
(m2)
Peso propia
losa (Tn)
zona de
ventana
bajas (m)
5.25
2.42
3.27
1.50
Total de
CV (tn)
1.65
5.12
22.28
3.68
0.60
4.21
16.01
2.29
27
zona de
ventana
altas (m)
zona de
puertas (m)
2.19
5.20
2.39
0.70
19.22
3.64
X4
2.19
2.52
1.16
0.60
4.08
14.49
1.76
X5
2.65
7.41
3.41
1.15
0.70
24.61
5.19
X6
2.65
5.24
2.41
0.55
1.25
21.28
3.67
X7
2.19
4.12
1.90
0.50
4.08
17.42
2.88
X8
2.65
6.32
2.91
0.63
0.63
0.79
0.60
0.63
25.48
4.42
X9
2.65
8.84
4.07
0.60
0.63
0.18
0.45
1.38
29.88
6.19
X10
2.19
7.73
3.56
0.50
23.05
5.41
X11
2.65
11.35
5.22
1.70
1.25
32.08
7.95
X12
2.19
4.28
1.97
0.50
3.40
17.55
3.00
X13
3.55
0.00
0.00
4.95
15.43
0.00
zona de
parapet
os (m)
Total
de CM
(Tn)
Total de
CV (Tn)
3.15
15.50
2.59
30.01
6.34
13.86
1.40
0.55
0.40
Y1
Peso
propio
muros
(Tn)
1.72
Y2
3.12
9.06
4.17
0.75
Y3
2.15
2.00
0.92
0.60
Y4
1.08
0.36
0.17
Y5
2.04
6.34
2.92
Y6
2.33
4.10
1.89
Y7
5.51
11.97
5.51
Y8
3.34
4.64
2.13
Y9
1.97
3.43
1.58
Y10
2.04
3.45
1.59
Y11
2.94
3.61
1.66
Y12
1.15
0.00
0.00
Muro
Area
tributaria
(m2)
Peso
propia
losa (Tn)
zona de
ventana
bajas (m)
3.70
1.70
0.90
zona de
ventana
altas (m)
zona de
puertas
(m)
zona
de
tabiqu
es (m)
3.59
1.50
5.34
0.25
19.96
4.44
18.44
2.87
44.23
8.38
4.65
23.03
3.25
3.20
15.79
2.40
3.05
15.44
2.42
3.95
19.38
2.53
1.45
5.04
0.00
0.74
0.55
3.80
1.00
0.70
1.00
0.55
Tabla N 21
. Anlisis por Control de Fisuracin para Muros en la direccin XX
28
Tabla N 22.
Anlisis por Control de Fisuracin para Muros en la direccin YY
Fuerza Cortante Basal en el primer piso por sismo severo : 146.86 Ton
Tabla N 19 y 20. Verificacin de resistencia al corte del edificio en la direccin XX y YY
DIRECCIN XX
MUROS
Vm
DIRECCIN XX
MUROS
Vm
29
19.83
14.85
17.01
15.81
24.18
23.33
16.55
24.33
25.45
17.99
26.05
16.59
29.61
271.59
Y1
Y2
Y3
Y4
Y5
Y6
Y7
Y8
Y9
Y10
Y11
Y12
total
11.38
30.17
15.25
4.24
15.66
18.46
53.97
29.97
13.84
14.50
26.19
4.57
238.18
OK
OK
Fadm > F a
Donde:
Fadm : Esfuerzo admisible del Muro
Fa
: Esfuerzo axial mximo con S/C100%
[ ( )]
Fadm=0.2 f ' m 1
h
35 t
Fa =
Pm
L.t
Fa =
Pm
>0.05 f 'm , deber llevar refuerzo horizontal con cuanta mmina de 0.001
L.t
30
En los edificios de mas de tres pisos, todos los muros portantes del primer
nivel seran reforzados horizontalmente
La cuanta de acero de refuerzo horizontal ser
RESULTADOS
31
Los muros pre dimensionados al inicio, cumplieron con los requisitos de diseo,
soportando las fuerzas ssmicas y de servicio. Sern reforzadas lateralmente por acero
mnimo todos los muros del primer piso.
El anlisis ssmico manual, es un mtodo que eleva las fuerzas de diseo, los cuales
deben ser reducidas.
BIBLIOGRAGIA
Flavio Abanto Castillo. (2012). Anlisis y Diseo de Edificaciones de Albailera,
Ed. San Marcos. Lima, Per
San Bartolom, Daniel Quiun y Wilson Silva. (2011). Diseo y Construcciones de
Estructuras Sismorresisnte de Albailera. 1ra Ed. PUCP. Lima , Per
Reglamento Nacional de Edificaciones. (2015). Grupo ed. Megabyte, Sexta
edicin. Lima, Per.
Quilli Dueas Fernando. (2012). Diseo de una vivienda de albailera confinada de
4 niveles. Universidad Nacional de San Antonio Abad del Cusco. Cuso, Per.
32