WARNING
WARNING
When you insert or remove the module while backplane power is on,
or connect or disconnect the ControlNet cable with power applied to
the module or any device on the network, an electrical arc can occur.
This could cause an explosion in hazardous location installations. Be
sure that power is removed or the area is nonhazardous before
proceeding.
If you connect or disconnect wiring while the field side power is on,
an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or the
area is nonhazardous before proceeding..
IMPORTANT
ATTENTION
ATTENTION
ATTENTION
ATTENTION
FLEX I/O is grounded through the DIN rail to chassis ground. Use
zinc plated yellow-chromate steel DIN rail to assure proper
grounding. The use of other DIN rail materials (e.g. aluminum, plastic,
etc.) that can corrode, oxidize, or are poor conductors, can result in
improper or intermittent grounding.
European Zone 2 Certification (The following applies when the product bears
the EEx Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by
European Union Directive 94/9/EC.
The LCIE (Laboratoire Central des Industries Electriques) certifies that this
equipment has been found to comply with the Essential Health and Safety
Requirements relating to the design and construction of Category 3 equipment
intended for use in potentially explosive atmospheres, given in Annex II to this
Directive. The examination and test results are recorded in confidential report No. 28
682 010.
Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 50021.
IMPORTANT
EXPLOSION HAZARD
WARNING
AVERTISSEMEN
RISQUE DEXPLOSION
3A
3B
8
7
5
Component Identification
1
Indicators
3A
3B
+24V dc connections
Flexbus connector
2. Hook the lip on the rear of the adapter onto the top of the DIN rail,
and rotate the adapter module onto the rail.
3. Press the adapter module down onto the DIN rail until flush. Locking
tab C will snap into position and lock the adapter module to the DIN
rail.
4. If the adapter module does not lock in place, use a screwdriver or
similar device to move the locking tab down while pressing the
adapter module flush onto the DIN rail, and release the locking tab to
lock the adapter module in place. If necessary, push up on the locking
tab to lock.
5. Connect the adapter wiring as shown under Wiring later in this
document.
Panel/Wall Mounting
If mounting this adapter to a panel or wall, refer to publication 1794-5.13,
Panel Mounting Kit, Cat. No. 1794-NM1.
3
3. Open the module latching mechanism and remove the module from
the base unit to which the adapter will be attached.
4. Push the flexbus connector toward the right side of the terminal base
to unplug the backplane connection.
ATTENTION
Network
Address
Switches
Indicators
30133
C
When the adapter is locked onto the DIN rail, gently push the flexbus connector into
the adapter to complete the backplane
Status
CommB
CommA
Connecting Wiring
LED Indications
Probable Cause
WARNING
Off
No power, or reset
Red
Adapter inoperative
Adapter self-test
Channel disabled
Green
Channel operational
Flashing Green/Off
Flashing Red/Off
Flashing Red/Green
LED Indications
Probable Cause
Status Indicator
Off
No power
Flashing Green
Green
Flashing Red
Red
ControlNet Cable
Certifications (when product is
marked)2
Specifications
1
8 modules
24V dc nominal
19.2V to 31.2 V dc (includes 5% ac ripple)
450mA maximum; 330mA @ 24V dc
23A for 2ms
5M bps
I/O Status - red/green
Comm A - red/green
Comm B - red/green
640mA maximum
Tested at 850V dc for 1s between user power and flexbus
4.6W maximum @ 19.2V dc
7 pound-inches (0.8Nm)
3.4H x 3.7W x 2.7D inches
87H x 94W x 69D mm
General Specifications
Environmental Conditions
Operating Temperature
Storage Temperature
Relative Humidity
Vibration
Shock
Emissions
ESD Immunity
Radiated RF Immunity
EFT/B Immunity
Surge Transient Immunity
Conducted RF Immunity
Enclosure Type Rating
Conductors Wire Size
Category1
Belden RG-6/U
CULUS UL Listed Industrial Control Equipment, certified for US
and Canada
UL UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations
CUL UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for Canada
CSA CSA certified Process Control Equipment
CSA CSA certified for Class I, Division 2, Groups A, B, C and D
Hazardous locations
EEx2 European Union 94/9/EEC ATEX Directive, compliant with:
EN 50021; Potentially Explosive Atmospheres,
Protection n ( Zone 2)
CE2 European Union 89/336/EEC EMC Directive,
compliant with:
EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
C-Tick2 Australian Radiocommunications Act compliant with
AS/NZS CISPR 11, Industrial Emissions
You use this category information for planning conductor routing as described in Allen-Bradley
publication 1770-4.1, Industrial Automation Wiring and Grounding Guidelines.
For the latest up-to-date information, see the Product Certification link at www.ab.com for Declarations of
Conformity, Certificates and other certification details. For notification of any additional release notes, refer to
www.ab.com/manuals/.
Mounting Dimensions
B
2.0
(50)
3.2
(80)
3.4
(87)
1.2
(30)
3.7
(94)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 55C (32 to 131F)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
40 to 85C (40 to 185F)
IEC 60068-2-30 (Test Db, Un-packaged Non-operating
Damp Heat):
5 to 95% non-condensing
IEC60068-2-6 (Test Fc, Operating):
5g @ 10-500Hz
IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g
CISPR 11:
Group 1, Class A (with appropriate enclosure)
IEC 61000-4-2:
4kV contact discharges
8kV air discharges
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz
10V/m with 200 50% Pulse 100% AM at 900MHz
IEC 61000-4-4:
2kV at 5kHz on communication ports
IEC 61000-4-5:
2kV line-earth(CM) on shielded ports
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 30MHz
None (open-style)
1794-ACN15,-ACNR15
3.4Hx3.7Wx2.7D
(87Hx94Wx69D)
A
(1794-ACNR15 shown)
A = DIN rail
B = Secure DIN rail about every 200mm
PN 957899-40