Académique Documents
Professionnel Documents
Culture Documents
Marko Pikkarainen
Tampere University of Technology
The Department of Electrical Energy Engineering
marko.pikkarainen@tut.fi
Marko Pikkarainen
Marko Pikkarainen
29.3.2012
29.3.2012
Consequences of poor PQ
Poor power quality can have different effects. The range reaches from
disturbing effect on human beings (flicker) up to consequences on
operation of equipment.
There are long term and momentary effects. Harmonics and unbalance
cause increased losses in the utilities equipment and reduce life time of
components.
Momentary effects are a sudden malfunction or damage of a device.
They commonly appear with the quality parameters such as: voltage
interruption, voltage dips and transient overvoltage.
The most commonly reported symptoms of power quality phenomena
are light flickering, circuit breakers tripping and computers locking up or
restarting. Also some damages are reported due to voltage quality
problems
Marko Pikkarainen
Marko Pikkarainen
29.3.2012
29.3.2012
There are several regulations, standards and laws that regulate the
distribution utilities actions and design and use of electrical equipments
national laws and regulations
directives and standards
general guidelines by field of business
EMC standard
IEC 61000 series
61000-1-x
General
61000-2-x
Environment
61000-3-x
Limits
Emission limits
Immunity limits
61000-4-x
Measurement techniques
Testing techniques
61000-5-x
Installation guidelines
Mitigation methods and devices
61000-6-x
Generic standards
61000-9-x
Miscellaneous
Marko Pikkarainen
Marko Pikkarainen
29.3.2012
29.3.2012
EN 50160
Flicker (PST, PLT) is the subjective impression of luminance variations of lightning as a result of voltage
fluctuations.
Flicker is more a physiological than a physical value.
The flicker effect depends on: the amplitude of the relative voltage fluctuation and the repetition rate of the
appearance of the voltage fluctuation. With the same frequency of the voltage fluctuation the flicker effect is
directly proportionally to the amplitude of the voltage variation.
Flicker causes normally no damage of devices or an interference of their function.
PST and PLT occurs without dimension (pu).
The borderline was established laboratory tests with individuals. (for incandescent lamps)
Covers only normal operation and even for that case only during 95% of time
obligatory
u (t)
U
U
[%]
U
For some power quality parameters only indicative values are given
2 U
P st=1
0.1
0.1
0.00 1
Marko Pikkarainen
1
0.01
10
0.1
10 0
100 0
10
re gu lar
sin u so ida l
v o lta g e
flu c tua tio n
reg u lar
re c tan g ula r
v olta ge
flu ctu a tio n
arb itra ry
re cta ng u lar
vo ltag e
fluctua tion
10 0 Hz flickerfrequ ency
Marko Pikkarainen
29.3.2012
29.3.2012
10
Under normal operating conditions excluding the periods with interruptions, supply
voltage variations should not exceed 10 % of the nominal voltage Un.
In cases of electricity supplies in networks not interconnected with transmission
systems or for special remote network users, voltage variations should not exceed
+10 % / - 15 % of Un. Network users should be informed of the conditions.
Marko Pikkarainen
Marko Pikkarainen
29.3.2012
29.3.2012
12
11
Voltage unbalance
Voltage unbalance
Remedial measures
ku
U2
Iu
I2
I1
Consequences of unbalance:
U
Increase of the losses in the grid components
Increase losses and vibration moments in electrical machines
Could increase non-characteristical harmonic currents of rectifier and
inverter
1
Limits in EN 50160
during each period of one week, 95 % of the 10 min mean r.m.s. values of the
negative phase sequence component (fundamental) of the supply voltage shall be
within the range 0 % to 2 % of the positive phase sequence component
(fundamental). In some areas with partly single phase or two phase connected
network users' installations, unbalances up to about 3 % at three-phase supply
terminals occur.
Marko Pikkarainen
Marko Pikkarainen
29.3.2012
29.3.2012
14
13
Harmonics
Harmonics
When the waveform of voltage or current is not pure sine wave those can be
modelled using Fourier transform method (in real life it rarely is)
Remedial measures:
Subharmonics: Signal components which frequencies are below the mains frequency (no
limits in EN 50160)
Consequences of harmonics:
increase thermal and mechanical stress of the components and devices, increases grid
losses, might produce influence for ripple-control devices, might produce flicker by
interharmonics.
Limits in EN 50160
during each period of one week, 95 % of the 10 min
Even ha rmonics
The classical harmonics-theory deals with frequencies from 0 Hz to about 2500 Hz (50 th
harmonic, Bashir tell you more about higher frequencies)
Odd ha rmonics
Mul ti ples of 3
Order h Rel ative
Order h Rel ative
a mplitude uh
a mplitude uh
6,00 %
5,00 %
3
9
5,00 %
1,50 %
2
4
2,00 %
1,00 %
6..24
0,50 %
11
3,50 %
15
0,50 %
13
3,00 %
21
0,50 %
17
2,00 %
19
1,50 %
23
1,50 %
25
1,50 %
NOTE: No va l ues are given for harmonics of order higher than 25, a s they a re
us ually s mall, but largely unpredictable due to resonance effects.
Marko Pikkarainen
29.3.2012
29.3.2012
15
16
Frequency
Frequency
Remedial measures
Use of reserve power plants
Load shedding
Limits in EN 50160
Interconnected 49,5 Hz - 50,5 Hz during 99,5% of a year
networks
47 Hz - 52 Hz during 100 % of the time
Islanded
networks
Marko Pikkarainen
Marko Pikkarainen
29.3.2012
29.3.2012
18
17
Remedial measures
Limits in EN 50160
grid
rectifier
The vast majority of voltage dips has a duration less than 1 s and a
residual voltage above 40 %. However, voltage dips with a smaller
residual voltage and longer duration can occur infrequently. In some
areas, voltage dips with a residual voltage between 90 % and 85 % of
Uc can occur very frequently as a result of the switching of loads in
network users installations
Produces costs: shut down costs, standstill costs, restart costs, additional costs
load
~
=
=
energy
storage
inverte r
P
Q
Marko Pikkarainen
Marko Pikkarainen
29.3.2012
29.3.2012
20
19
Interruptions
Interruptions
Definition
Remedial measures
Decrease fault occurrence (overhead lines -> underground cables)
Install remote controlled components to grid (switch, isolator)
Build backup connection or backup power generation units for sensitive
customers
condition in which the voltage at the supply terminals is lower than 5 % of the
reference voltage (EN 50160)
prearranged, when network users are informed in advance; or
accidental, caused by permanent or transient faults, mostly related to
external events, equipment failures or interference. An accidental
interruption is classified as:
Limits in EN 50160
Consequences of interruptions
Produces costs: shut down costs, standstill costs, restart costs, additional costs
Sources for interruptions
Normally, interruptions are caused by the operation of switches or protective
devices. (faults)
Maintenance of components
Marko Pikkarainen
Marko Pikkarainen
29.3.2012
29.3.2012
21
22
Marko Pikkarainen
29.3.2012
29.3.2012
24
23
Marko Pikkarainen
Marko Pikkarainen
29.3.2012
29.3.2012
25
26
Marko Pikkarainen
Marko Pikkarainen
29.3.2012
29.3.2012
27
28
d e mo d u la tion
0.05Hz
35 Hz
we ig h ting filte r
la mp e -e ye
H(s)
squ a rin g a n d
smo o th in g
sta tistical
e va lu a tio n
0.53 Hz
8.8 Hz
Pst
P
lt
u (t)
U
U (t)
U
U (t) weig h ted
mome n ta ry
flicke rleve ll P f
Marko Pikkarainen
29.3.2012
Marko Pikkarainen
29.3.2012
29
30
Power quality monitoring will need information from voltage from each
customer connection point
AMI could short the clarification time of power quality disturbances and
make it more efficient
If the clarification time decreases also it could speed up decisions and acts of
how to decrease the effect of disturbance
Savings
Also customer satisfaction level could increase
Marko Pikkarainen
Marko Pikkarainen
29.3.2012
29.3.2012
31
32
Network
Information
Goal:
To detect power quality and reliability problems automatically
To detect the most probable reason for power quality problems
automatically
To predict the behaviour of different power quality quantities in the
future
Operation
Customer
Information
Measurements
(AMR, condition
monitoring,
PQ, weather,
relay data, etc.)
Future
scenarios
Analysis
Detection of
potential
problems
Priorisation
Immediate
actions
Maintenance
Proactive
actions
Planning
Standards,
recommendations
Methods:
efficient utilization of static and dynamic information
optimization of network monitoring processes and information
management
Marko Pikkarainen
Marko Pikkarainen
29.3.2012
29.3.2012
33
H. Renner, M. Sakulin, Power quality, Textbook to lecture Power quality and supply reliability
H. Renner, Power quality and supply reliability, Lecture notes
Future
scenarios
Measurements
(AMR, condition
monitoring,
PQ, weather,
relay data, etc.)
REFERENCES
Customer
Information
Network
Information
34
M. Pikkarainen, B. A. Siddiqui, P. Pakonen, P. Verho, S. Vehvilinen, 2011, Vision of Power Quality Monitoring and
Management in Future Distribution Networks, Conference paper, CIRED 2011.
M. Pikkarainen, P. Nevalainen, P. Pakonen, P. Verho, 2010, "Practical Case Study: Measurement of Power Quality
Problems Caused by Common New Loads , Conference paper, NORDAC
Analysis
Simulation
Detection of
potential
problems
Priorisation
The Cost of Power Disturbances to Industrial & Digital Economy Companies, 2001, Consortium for Electric
Infrastructure to Support a Digital Society.
European Commission Regulation, 2009, implementing Directive 2005/32/EC of the European Parliament and of the Council
with regard to ecodesign requirements for non-directional household lamps, No 244/2009.
Rong Cai, 2009, Flicker Interaction Studies and Flickermeter Improvement, Dissertation, Eindhoven University of
Technology, Netherland
Planning
EN 50160, 2007, Voltage characteristics of electricity supplied by public distribution networks, Standard
L. P. Frater, N. R. Watson, Light Flicker Sensitivity of High Efficiency Compact Fluorescent Lamps, Power Engineering
Conference, 2007. AUPEC 2007. Australasian Universities
Standards,
recommendations
Marko Pikkarainen
Marko Pikkarainen
29.3.2012
35
Marko Pikkarainen
29.3.2012
29.3.2012