The TOSHIBA Controls Manual

Contents
1

Basic Controls
1.1
1.2
1.3
1.4

RBC-AMT31
RBC- AS21E
TCB-AX21U/E
RBC-EX21E

Timed ON/OFF Control


2.1 RBC-SMTI
2.2 RBC-SMCN61
2.3 RBC-IT3
2.4 RBC-IT4

RBC-SMFI
RBC-SMIM2
RBC-SMIM3
RBC-FDP2F-PE
RBC-FDP2BMS-PE
TCB-IFCB-4E

Fan Interface
Indicator Module for Cool, Heat and Fan
Indicator module for Operation and Fault
Fault Indication Module
Analogue BMS Control Module
ON/OFF Fault Indication

Output Circuits (Outdoor)


4.1
4.2
4.3
4.4

ON/OFF control at standard Remote


ON/OFF Lock control at indoor unit
ON/OFF Control at indoor Unit Daiseikai
ON/OFF Control at indoor Unit DI/SDI &
SHRM

Output Circuits (Indoor)


3.1
3.2
3.3
3.4
3.5
3.6

Standard Remote Controller


Simplified Remote
Infrared Remote Control
Weekly Timer

TCB-PCM02E
TCB-PCIN2E
TCB-PCDM2E
TCB-PCOS1E

ON/OFF and Mode selection PCB (SM)


Operation and fault indication PCB (SM)
Peak Power Cut PCB (SM)
Application Control PCB (DI)

Central Control
5.1
5.2
5.3
5.4

RBC-SC642TLE
RBC-CC163TLE
TCB-PCNT20TLE
TCB-PCNT30TLE

Central Controller
ON/OFF Central Controller
XY Network Adapter
TCCLink Network Adapter

*SM This accessory can only be used on SMMS, SHRM and Mini SMMS units
*DI This accessory can only be used on DI and SDI units
These controls accessories cannot be used on the Flexi Units

Windows Control
6.1 Windows control Package
6.2 Windows Energy Monitoring
6.3 Windows Control and Other Equipment

Touch Screen
7.1 Touch screen Solution

. LonWorks
8.1 LonWorks Solution

BACnet
9.1 BACnet Solution

10 BEMS Solutions
10.1
10.2

TREND Solution
MODBUS Solution

11 VN Units
11.1

VN Unit Controls

1.1 RBC-AMT31 Standard Remote Controller


Description
The standard remote controller gives access to all of the functions for the indoor
unit. It also gives access to the configurable engineers menu and data retrieval
features of the system, such as fault code and sensor information. The device is
compatible with DI/ SDI/SMMS and SHRM indoor units.

Application
The standard remote controller can be used to control individual units or groups of
units up to a maximum of eight. Two remote controllers may be connected on any
group or single application, with one remote being designated as a master.
The device is fitted with an internal room temperature sensor, which may be
configured manually through the engineers menu. Once configured the indoor unit
will sense the room temperature from the remote rather than the indoor unit return
air sensor

Diagram

Connections
The remote controller connects to the indoor unit via a 0.75mm2 two-core cable.

Limitations
The remote controller can control an individual or a group of eight indoor units.
This is reduced to a maximum of seven indoor units where a second remote
controller is to be used.

1.2 RBC- AS21E Simplified Remote


Description
The simplified remote controller is a reduced function remote controller. It allows
the setting of all of the functions for the indoor unit, however the remote does not
allow access to the engineers menu or data retrieval functions. Fault code
information is displayed on the device, using format as the standard remote
controller. Compatibility is with DI/SDI/SMMS and SHRM systems.

Application
The simplified remote is used to control an individual indoor unit or a group of up to
eight units. Two devices may be used to control individual or grouped units, where
one device is configured to be a master. The devices are also equipped with
internal room temperature sensors, which may be configured to take priority over
the indoor unit return air sensor. This controller would commonly be used where
simplified operation is beneficial, such as hotel room applications.

Diagram

Connections
The remote controller connects to the indoor unit via a 0.75mm2 two-core cable.

Limitations
The remote controller can control an individual or a group of eight indoor units.
This is reduced to a maximum of seven indoor units where a second remote
controller is to be used.

1.3 Infrared Remote Control


Description
The infrared remote control can be added to any DI/SDI/SMMS or SHRM indoor
unit, although the model of the device varies for different indoor unit models.
TCB-AX21U (W)-E2 Cassette Units
TCB-AX22CE2 Ceiling Suspended Units
TCB-AX21E2 Ducted Units

Application
The infrared remote can be used to control a group of up to eight indoor units and
is equipped with an internal room temperature sensor, which may be configured to
take priority over the indoor unit return air sensor. Should the device be taken
outside its operational range, the indoor unit will automatically revert to sampling
from the indoor unit return air sensor. The device can be used to interrogate the
indoor unit to receive system fault codes, however the engineers menu and data
retrieval function of the standard wired remote controller are not available. Where
indoor units require additional configuration it will be necessary to temporarily
connect a standard wired remote controller, whilst the modifications are made.

Connections
The infrared remote receivers are connected to the indoor units by the AB network
the infrared remote kits used for the different models are listed below. The wall
units have the infrared kit included except the MMK-AP0151H, MMK-APO181H
and MMK-APO241H these models need to be hard wired or use the infrared kit
TCB-AX21E.
TCB-AX21U(W)-E
TCB-AX22CE
TCB-AX21E

4 Way cassette
Ceiling units
Ducted units or for surface mounting

Limitations
The remote controller can control an individual or a group of eight indoor units.
This is reduced to a maximum of seven indoor units where a second remote
controller is to be used.

1.4 RBC-EX21E Weekly Timer


Description
The weekly timer is a fully programmable device with three time functions per day
and seven day functionality. Each day may be programmed with different operation
times and days omitted where necessary.

Application
The timer connects directly to a standard or central controller via the 4-core lead,
supplied with the installation kit. No auxiliary power supply is required as the
device obtains a supply via the remote or central controller. Any system being
controlled from the remote or central controller will be enabled or disabled
according to the programmed settings. It should be noted that individual units
cannot be omitted from the program sequence.

Diagram

Limitations
It is important to note that when an RBC-EX21E timer is used other timer
interfaces must not be used. This is essential to avoid conflicting operational
commands.

2.1 RBC-SMTI Timer Interface Lead


Description
The interface lead consists of a 1 meter two core cable and connector, designed
for direct connection to the following accessories:
RBC-AMT21E (first generation wired remote controller)
RBC-AMT31E (second generation wired remote controller)
TCB-SC64TLE (central remote controller)
TCB-CC163TLE2 (on/off central controller)

Application
The interface lead is used to allow single or groups of units connected to the above
devices to be enabled or disabled by means of an external contact.

Diagram

Volt free contact

RBC-SMT1 Timer interface lead.


Switch Green Wire.

15vdc Live Yellow.

Connector for
external Timer

Connection
To Indoor Unit

Connections
The interface lead is connected to the CN02 connection, which is also used for
interfacing the Weekly Timer option (RBC-EXW21E).

Limitations
It should be noted that when the external contact is operated, all connected
systems will be enabled or disabled, depending on whether the contact is opened
or closed. Individual units cannot be omitted from the on/off control process.
The interface lead may be extended to a maximum total length of 25 meters when
using a screened cable, with a cross sectional area of 0.75mm.

2.2 RBC-SMCN61 ON/OFF Lock control at


Indoor unit
Description
The interface lead consists of a 1 meter three core cable, which can connect to any
R410A DI/SDI or SMMS/SHRM indoor unit. The accessory allows the indoor unit to
be enabled / disabled by a volt free contact closure. It also allows the remote to be
locked to prevent the unit being switched on.

Application
The interface lead is used to allow single or groups of units connected to a master
unit to be remotely enabled by an external volt free contact. Also the ON/OFF
function can be locked by a volt free contact.

Diagram
This will RUN the indoor unit
or group

1
2

Vinyl Tube

This will lock the on / off


function of the remote

Connections
The interface lead is connected to the CN61 connector located on the indoor PCB.
If this lead is to be used for the ON/OFF function Jumper J05 is to be removed.

Limitations
It should be noted that when the external contact is operated, all connected
systems will be enabled or disabled, depending on whether the contact is opened
or closed. Individual units cannot be omitted from the on/off control process.
The Locking function only locks the operation function however if the remote is
locked OFF it is not possible to adjust any functions of the remote.
The interface lead may be extended to a maximum total length of 25 meters when
using a screened cable, with a cross sectional area of 0.75mm.
10

2.3 RBC-IT3 ON/OFF Control For DAISEIKAI


Description
The RBC-IT3PE time switch interface is intended for use with the TOSHIBA
Daiseikai range of indoor units and is designed to allow these systems to be
externally switched on and off by means of any volt-free external terminals rated at
230 volts a/c.

Application
The RBC-IT3-PE would typically be used to interface an external switch, which
may be a room occupancy sensor, timer, on/off control from a BMS or any other
suitably rated volt-free contacts.
.

Diagram

Daiseikai Wiring diagram External Switch

INDOOR
UNIT
TERMINALS

1
2
E

L
N
E
E
EN
L

External
Switch

SWL

Terminal
s1 & 2 are 230 volts a/c.
Site
Wiring

CN06 ON
INDOOR
PCB

BLACK LEAD
1.5m

11

4
3
2
1

SOLDERED
CONNECTIONS

RBC-IT3

Daiseikai Wiring diagram PIR Sensor

INDOOR
UNIT
TERMINALS
PIR
Sensor

L
N
E

1
2
E

E
N
L

E
N
L

SWL

SWL
Terminal
s
1 & 2 are 230 volts a/c.
Site
Wiring

CN06 ON
INDOOR
PCB

BLACK LEAD

4
3 SOLDERED
2 CONNECTIONS
1

RBC-

Connections
The device is connected to the indoor unit via the CN06 socket on the indoor PCB
and the indoor units supply terminals as illustrated.

Limitations
It is important to note that when an RBC-IT3-PE interface is used the standard
24hour timer functions within the Toshiba remote must not be selected to avoid
conflict in switching commands.
The remote controller on/off button will be overridden whenever an interface is
connected to socket CN06, regardless of whether the RBC-IT3PE is in use or not.
All other functions of the remote controller remain unaffected.
It is recommended that the power supply (230v.a.c.) be taken from the respective
indoor unit, as indicated on the wiring diagram.
The field sourced time-switch may be located in any area. The a/c system will start
when terminal 1 of the interface is energised and will override the remote controller
on/off functions.
Due to the logic used, it is recommended that a minimum switching interval of 30
seconds be adopted. When first energised, it may be noticed that the indoor unit
starts briefly and then stops, this is normal and does not indicate a fault with the
system.

12

2.4 RBC-IT4 ON/OFF Control For


DI/SDI/SMMS/SHRM
Description
The RBC-IT4PE time switch interface is intended for use with the TOSHIBA
DI/SDI/SMMS/SHRM range of indoor units and is designed to allow these systems
to be externally switched on and off by means of any volt-free external terminals
rated at 230 volts a/c.

Application
The RBC-IT4-PE would typically be used to interface an external switch, which
may be a room occupancy sensor, timer, on/off control from a BMS or any other
suitably rated volt-free contacts.
.

Diagram

Digital Inverter Wiring diagram 560 and 800 KRT


Splice
Brown

External
Switch

INDOOR
UNIT
TERMINALS

Terminals
1 & 2 are 230 volts a/c.
A & B are 12 volts a/c
Site Wiring

1
2
3
A
B
C

CN06 ON
INDOOR
PCB

13

RBC IT4 - PE
BLue
Orange
Yellow

BLACK LEAD 1.5m

1
2
3
4
5
6
7
8

DI/SDI/SMMS/SHRM
Splice
Brown

External
Switch

INDOOR
UNIT
TERMINALS

Terminals
1 & 2 are 230 volts a/c.
A & B are 15 volts d/c
Site Wiring

RBC IT4 - PE

1
2
3
A
B

BLue
Orange
Yellow

CN61 ON
INDOOR
PCB

1
2
3
4
5
6
7
8

BLACK LEAD 1.5m

Converter

Connections
The device is connected to the indoor unit PCB via the CN06 socket on the
560/800 KRT models and the CN61 socket on all other models. An adaptor lead is
supplied with the installation kit to facilitate both options.

Limitations
It is important to note that when an RBC-IT4-PE interface is used the standard
24hour timer functions within the Toshiba remote or central controllers must not
be selected to avoid conflict in switching commands. Do not use the standard
RBC-WT1-PE or a RBC-EX21E seven day timer.
The remote controller on/off button will be overridden whenever an interface is
connected to socket CN06 or CN61, regardless of whether the RBC-IT4PE is in
use or not. All other functions of the remote controller remain unaffected.

When more than one system is connected for group operation, it is


essential to arrange the power supply to the outdoor units so that the
control circuits for all the indoor units are fed from the same phase.
The interface should only be fitted to the master indoor unit. If fitted to a slave
indoor unit then system shut down may occur.
It is recommended that the power supply (230v.a.c.) be taken from the respective
indoor unit, as indicated on the wiring diagram.
The field sourced time-switch may be located in any area. The a/c system will start
when terminal 1 of the interface is energised and will override the remote controller
on/off functions.
Due to the logic used, it is recommended that a minimum switching interval of 30
seconds be adopted.

14

3.1 RBC-SMFI Fan Interface Module


Description
The fan interface module will allow an external ventilation fan to be controlled from
an indoor unit. The device consists of a single pole relay housed in a small
electrical enclosure, which connects to a Digital Inverter or VRF indoor unit via the
supplied connection lead.

Application
The module is intended to facilitate the installation and control of an external
ventilation fan, which may be used to supply fresh air or to move conditioned air to
another location. The external fan is enabled with the indoor unit, however this can
be over-ridden using the external fan control button on the RBC-AMT21/31E
remote controllers.

Diagram

Fan Run

Red

Red

14
15

To Socket
CN32

Enclosure dimensions: 115mm x 65mm x 30mm

15

Connection/Installation Procedure
The interface should be mounted adjacent to the indoor unit and secured with the
self-adhesive fasteners supplied. Only when the device has been adequately
secured should the CN32 connection be made to the indoor unit PCB. The Live
Supply of the external fan should then be connected via the relay contacts located
in the fan interface enclosure. On completion of the installation works, the remote
controller will require configuring to allow the operation of the auxiliary ventilation
button.
Remote Controller Configuration Procedure
1) Enter the engineering mode by pressing the SET + CL and CHECK buttons
Simultaneously for 3 seconds.
2) Using the temperature set buttons select menu item number 31.
3) Change the value in menu item 31 from 0000 to 0001 using the timer buttons.
4) Press the SET button to confirm the change.
5) Press the CHECK button to return to normal operation.
Limitations
The relay contacts are rated at 230 Volts, 6Amps resistive or 1.5Amps inductive
load.
Loads in excess of this will require the installation of an additional power relay.
It is the responsibility of the installing contractor to ensure that a means of safe
isolation is provided and that all electrical wiring conforms to the current edition of
BS7671.

16

3.2 RBC-SMIM2 Indicator Module for Heat Cool or


Fan Operation
Description
The device is designed to give the operational status of DI/SDI/SMMS/SHRM
systems.
An indication of whether a system is heating, cooling or the fan is operating is
given via a series of LEDs and the activation of a relay output. The volt free relay
output terminals allow for remote interfacing with a control panel or BMS system.

Application
The device would be used where the remote indication of a systems status is
required. This may be required in order to disable other systems to avoid
conflicting heating and cooling demands.

Diagram
1

FAN
Yellow LED

11
2

COOL
Green LED

Yellow

12
13
3

HEAT
Red LED

Black

10

Blue

14
15

Red

To Socket
CN60

Connections
The device should be located adjacent to the indoor unit and connected to the PCB
via the CN60 socket.

Limitations
The relay output terminals are rated at 230 Volts A/C with 6 Amp resistive or 1.5
Amp inductive loads.

17

3.3 RBC-SMIM3 Indicator Module For Operation &


Fault
Description
The device is designed to give the operation and fault status for
DI/SDI/SMMS/SHRM systems. An indication of whether a system operating or has
a stopping fault is given via a pair of LEDs located on the device and the activation
of a relay output. The volt free relay output terminals allow for remote interfacing
with a control panel or BMS system.

Application
The device would be used where the remote indication of a systems status is
required. This may be required in critical areas such as server rooms and
laboratories.

Diagram
2

Operation
Green LED

13
3

Fault
Red LED

Yellow

12

Black

14
15

Blue

To Socket
CN61

Connections
The device should be located adjacent to the indoor unit and connected to the PCB
via the CN61 socket.

Limitations
The relay output terminals are rated at 230 Volts A/C with 6 Amp resistive or 1.5
Amp inductive loads.

18

3.4 RBC-FDP2F-PE Fault Display Panel


Description
The FDP is a module that has several different levels of operation in its most basic
form will allow any fault on a unit to operate the relay to give an indication of a
fault. The FDP has many built in functions to give preset operation, duty share /
unit runs in fault. The device connects to a Digital Inverter or VRF indoor unit via
the remote controller AB network.

Application
The FDP2-F was principally designed to allow a fault condition to be transmitted to
external systems via a relay contact. The FDP2 has several modes of operation
these are configured by using the dipswitches SW1-7 they are as follows.
Fault monitoring
Fault monitoring + locked Cooling preset
Fault monitoring + locked Heating preset
Fault monitoring + locked Auto preset
The FDP2-F has the ability to control two units in a duty share configuration the
units will automatically change over on a 24hour basis and in the event of any fault
both units will be enabled an FDP2-F is required for each indoor unit.
FDP2-F can be networked to give advanced functionality the FDP2-F can be used
as a group controller to control large groups of multiples of eight indoor units. The
controller can linked to other Realtime controls products to give stand-alone BMS
applications for retail or residential applications. Further details of advanced control
options are available on request.

19

Diagram
Indoor Unit

TCC-NET

D-BUS

RELAY

B D1 D2 C R1 R2

TCC-NET
To fault monitoring
A

Toshiba Remote Controller

Connection/Installation Procedure
The interface can be mounted within 500m of the indoor unit is contained in a
metal housing it connects to the indoor unit via the AB network.

Limitations
The relay contacts are rated at 1A 24VAC or 1A30VDC.

20

3.5 RBC-FDP2BMS-PE Analogue BMS Control


Module
Description
The FDP2- BMS is an interface that has the ability to accept inputs from an
analogue BMS system. The inputs to the controller can be either voltage or
resistance this can be configured on the FDP2-BMS. The device also has a relay
output that closes in the event of a fault within the system.

Application
The FDP2-BMS has been designed to give a straightforward BMS solution it
accepts voltage or restive inputs to set the following functions on the air
conditioner.
Set point, Fan speed, Mode, Louver, On/Off and local remote Lock the inputs for
these functions can be configured to be 0 to 10Volt or 0 to 10Kohms restive. A
dipswitch SW1 selects the mode.
If the inputs go open circuit the FDP2-BMS assumes a default value for that input.
This is useful in the event of a failure in the BMS inputs to the device.
The FDP2-BMS can be customized to suit particular applications for a hotel or
residential applicants where a specific control is required. An example is the set
back requirements from a key card or a switch plate to match other electrical
accessories in the room.
FDP2-BMS can be networked to give advanced functionality the FDP2-BMS can
be used as a group controller to control large groups of multiples of eight indoor
units. The controller can linked to other Realtime controls products to give standalone BMS applications for retail or residential applications. Further details of
advanced control options are available on request.

21

Diagram

Indoor Unit

TCC-NET

D-BUS

RELAY

B D1 D2 C R1 R2

TCC-NET
To fault monitoring
A

Toshiba Remote Controller

Connection/Installation Procedure
The interface can be mounted within 500m of the indoor unit is contained in a
metal housing it connects to the indoor unit via the AB network.

Limitations / Specifications
The relay contacts are rated at 1A 24VAC or 1A30VDC.
Voltage inputs 0 to 10 V or Resistive inputs 0.4K Ohms to 10K Ohms.

22

3.6 TCB-IFCB-4E ON/OFF Fault And Operation


Indication Module
Description
The device is designed to give remote on/off control, operation and remote fault
indication for DI/SDI/SMMS/SHRM systems. The device may be connected to
single indoor units or one device may be connected to a group of indoor units.

Application
The device would typically be used where it was necessary to remotely enable or
disable a system and provide a means of operation and fault monitoring. An
example of this would be a simple and cost effective means of integration to an
existing BMS system.
.

Diagram

23

Connections
The device is enclosed in a galvanized steel enclosure, which should be mounted
adjacent to the indoor unit and connected to the indoor PCB via the CN61 socket.
The power supply for the device is obtained from the indoor unit supply terminals.

Limitations
The output contacts for operation/fault indication are limited to 230 Volts and 0.5
Amps.
ON/OFF control cabling is limited to 500m using 2-core 0.75mm2 cable.
Operation/fault output cabling is limited to 200m when using 3-core 0.75mm2 cable
or 400m when using 1.5mm2 cable.
Enclosure Dimensions: 66 x 170 x 200

24

4.1 TCB-PCM02E On/Off And Mode Selection PCB


Description
The accessory is designed to fit into the SMMS or SHRM outdoor unit; it is a PCB
that can be used to perform several different functions. The PCB accepts an input
that would be volt free from an external source to enable the required function.

Application
For each of the applications listed below the PCB is mounted in the outdoor
electrical box and plugs into different connectors to give the following functions

External Master ON/OFF


The PCB plugs into CN512 when a contact is made between common and cool all
of the units connected to that system will start in their previous mode of operation.
When the contact is made between common and heat the connected units will
stop.

An example time switch would be a Sangamo Suntracker ref 0456 these are
available from RS or most Electrical Wholesalers

Operation Mode selection Control


The PCB plugs into CN510 when no inputs are present to the PCB the indoor units
can independently control their mode. If a contact is made between common and
cool the indoor units will be locked in cooling a mode locked will be displayed on
any remote controller. If the contact is made between common and Heat the indoor
units are locked in that mode.

25

Night Operation (Sound Reduction) Control


The PCB plugs into CN508 when a contact is made between common and cool the
night operation is activated. This limits the compressor and outdoor fan speed. The
noise level will be reduced to 50dBA at 1M (free field)

Snow Fall Fan Control


The PCB plugs into CN509 when a contact is made between common and cool the
out door fan is enabled to remove any snow from the condenser.

Connection/Installation Procedure
The PCB is connected to the outdoor interface PCB where indicated to achieve the
required function. The PCB is then connected to a switch or relay contact to
activate the PCB as required.

Limitations
The maximum distance the contacts can be from the PCB mounted in the outdoor
unit is 500M is a 2 or 3 core 0.75mm screened cable is used.

26

4.2 TCB-PCIN2E Operations And Fault Indication


PCB
Description
The device is designed for use on the SMMS/SHRM systems and consists of a
PCB, which provides a relay contact closure when the system is operating or in the
event of a fault.

Application
The device is mounted in the outdoor electrical enclosure and is connected to the
interface PCB via terminal CN511 on the header unit. The device would typically
be used where a remote operation and fault signal may be required, (critical
areas).

Diagram

Connection/Installation Procedure
The PCB is connected to the outdoor interface PCB where indicated. The relay outputs of the PCB are then connected to
the required indicators.

Limitations
The maximum distance the contacts can be from the PCB mounted in the outdoor
unit is 500M is a 2 or 3 core 0.75mm screened cable is used.

27

4.3 TCB-PCDM2E Peak Power PCB


Description
This device is intended for use on the SMMS/SHRM systems and is designed to
limit the maximum operating capacity of a system, which will consequently restrict
the power consumption.

Application
The device is designed for use where it is necessary to limit the electrical demand
of systems at certain times. This may be where the electrical supply into a building
is insufficient to meet the peak demand. At these times a signal can be sent to the
device via a relay contact closure, which will limit the demand to preset levels.
Various options are available and can be configured to suit the application.

Diagram
Option 1

28

Option 2 Expanded Function

Connection/Installation Procedure
The device is mounted in the outdoor using the fixing kit provided and connects
directly to the interface PCB via the CN513 socket.

Limitations
Input wiring: Maximum 500M screened 2 or 3 core 0.75mm2 cable.
Output wiring: Maximum 200M screened 2 core 0.75mm2 / 400m 1.5mm2 cable.

29

4.4 TCB-PCOS1E Application Control PCB


Description
The device is intended for installation on the DI outdoor unit range and has been
designed to limit the outdoor unit noise production in the cooling mode by 5dB, limit
the maximum power consumption and give a compressor operation signal. The
noise and power functions are individually initiated by a relay contact closure,
which may be a time clock, switch or any other suitably rated device. The
compressor operation signal is given via a volt free contact closure.

Application
The device would be used where it was necessary to limit noise production at
certain times of the day, typically at night in residential areas or where it was
necessary to limit power consumption at certain times.

Diagram

30

Connection/Installation Procedure
The PCB and power transformer are mounted in the outdoor unit using the
installation kit provided. Electrical connections are required to the outdoor unit
supply terminals and the inverter assembly using the connectors supplied.

Limitations
Compressor operation contacts are rated at 12-250VDC 10mA-1A
Power peak control is in three stages: 0% 50% 75%
Only one power peak option may be selected at any one time.

31

5.1 TCB-SC642TLE2 Central Controller


Description
The central controller is a product that is capable of controlling 64 indoor units from a
single location. The device has the facility to set all of the operating parameters for
individual or zoned indoor units, whether they are VRF or individual split systems. It is also
capable of displaying individual fault codes for any units on the network.

Application
The controller is normally used on an installation where there are multiple indoor units in
one location. It gives the ability to link multiple refrigerant systems together for time clock
control and to give an indication of any faults within the systems. There are auxiliary inputs
for on/off control and relay outputs for remote run and fault indication. It is possible to
connect up to ten central controllers on one network, which controls up to 64 master
indoor units from multiple locations.

Connections

The controller requires a 240 Volt single phase 3 Amp power supply, which
connects directly to the mains input terminals on the rear of the device.

32

The two-core network cable should be screened and have a minimum cross-sectional area
of 1.5mm for networks of up to 1000 meters. This should be increased to 2.5mm for
networks of 1000 to 2000 meters total length. The network cable terminates at the U1/U3
and U2/U4 connections on the rear of the device.
Terminals A1, A2 and A3 are used to remotely operate all of the connected indoor units.
The indoor units can be enabled with a pulse voltage of 24 Volts applied for 0.5 seconds
between terminals A1-A3 and disabled by applying the same voltage between terminals
A2-A3.
Terminals B1, B2 and B3 provide dry contact outputs for connection to other systems. A
relay contact will close between B3 and B1 indicating system operation and B3 and B2
indicating a fault on any connected units.
Terminal CN02 can be used to connect a 7day timer (RBC-EXW21E) or alternatively the
RBC-SMTI interface lead can be connected and used as a means of remote switching.

Diagram

OUTDOOR
UNIT

OUTDOOR
UNIT

OUTDOOR
UNIT

TCB-SC642TLE

380/415 V AC
Three-Phase
Neutral & Earth

4-Pole Isolator

4-Pole Isolator
380/415 V AC
Three-Phase
Neutral & Earth

L1
L2
L3
N
U1 U2 U3U4 U5 U6

L1
L2
L3
N
U1U2 U3 U4 U5U6

380/415 V AC
Three-Phase
Neutral & Earth

L1
L2
L3
N
U1 U2 U3U4 U5 U6

CN02
U1/U3
U2/U4
C3
C4

TOS HIBA

A1
A2
A3
B1
B2
B3

4-Pole Isolator

Single Phase
220/240 V AC
2-Core & Earth

2-Core
Twisted
Screened
Non-polar

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

A B

A B

A B

A B

A B

A B

A B

T OS H I B A

T O S H IB A

TO S H I B A

E
N
L

T O SH I B A

TO S H I BA

T OS H I B A

T O S H IB A

TCC-LINK
CONTROLLER

15 V DC
2-Core
Non-polar

A B
INDOOR U1U2
L N CN81
UNIT

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1U2
A B
L N CN81

2-Pole Isolator
220/240 V AC
Single-Phase
2-Core & Earth

33

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1U2

A B

L N CN81

FSU
CN02
CN01

Limitations
Individual control of 64 master indoor units, (7 slave units per master possible)
All indoor units will be affected by any timer functions or remote operation signals.

Dimensions (L x W x H)

Solution Components
TCB-SC642TLE2
Central remote to be located in the building containing the controlled air conditioners.

TCB-PCNT30TLE2
Network adapters will be required for each Master indoor unit when the central controller is
used in conjunction with DI/SDI slit systems.

34

5.2 RBC-CC163TLE2 ON/OFF Controller


Description
The on/off controller is a product that is capable of operating 16 indoor units from a single
location. The device consists of 16 individual on/off buttons, which allows any connected
units to be enabled or disabled via a single button operation. It is also possible to enable
or disable all of the connected units via single button operation.

Application
The device is ideally suited to locations where it may be necessary to remotely enable or
disable indoor units. An example of this would be a hotel reception desk, where the
receptionist may wish to enable a customers room air conditioning during the check-in
process or disable it on the departure of a customer. Each of the on/off buttons has a label
facility and again using the example of a hotel installation, the buttons could be labeled
with a room number. For larger installations up to 4 controllers could be installed on one
network, thus allowing 64 master indoor units to be controlled from one location.
The device also has the facility for interfacing time clock control, remote switching, remote
run signal and remote fault indication from a set of auxiliary contacts.

Connections

The controller requires a 240 Volt single phase 3 Amp power supply, which connects
directly to the mains input terminals on the rear of the device.

35

The two-core network cable should be screened and have a minimum cross-sectional area
of 1.5mm for networks of up to 1000 meters. This should be increased to 2.5mm for
networks of 1000 to 2000 meters total length. The network cable terminates at the U1/U3
and U2/U4 connections on the rear of the device.
Terminals A1, A2 and A3 are used to remotely operate all of the connected indoor units.
The indoor units can be enabled with a pulse voltage of 24 Volts applied for 0.5 seconds
between terminals A1-A3 and disabled by applying the same voltage between terminals
A2-A3.
Terminals B1, B2 and B3 provide dry contact outputs for connection to other systems. A
relay contact will close between B3 and B1 indicating system operation and B3 and B2
indicating a fault on any connected units.
Terminal CN02 can be used to connect a 7day timer (RBC-EXW21E) or alternatively the
RBC-SMTI interface lead can be connected and used as a means of remote switching.

Diagram

TCB-CC163TLE
OUTDOOR
UNIT

OUTDOOR
UNIT

4-Pole Isolator

OUTDOOR
UNIT

4-Pole Isolator

01

02

03

04

05

06

07

08

09

10

11

12

13

14

15

16

ALL ON ALL OFF

L1
L2
L3
N
U1U2 U3 U4 U5U6

380/415 V AC
Three-Phase
Neutral & Earth

TOSHIBA ON -OFF CONTROLLE R

L1
L2
L3
N
U1 U2 U3U4 U5 U6

CN02
U1/U3
U2/U4
C3
C4

E
A1
A2
A3
B1
B2
B3

380/415 V AC
Three-Phase
Neutral & Earth

L1
L2
L3
N
U1 U2 U3U4 U5 U6

N
L

Single Phase
220/240 V AC
2-Core & Earth

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

A B

A B

A B

A B

A B

A B

A B

TOSHIBA

TOSHIBA

TOSHIBA

TOSHIBA

TOSHIBA

TOSHIBA

TOSHIBA

TCC-LINK
CONTROLLER

15 V DC
2-Core
Non-polar

U1U2
A B
L N CN81

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1U2
A B
L N CN81

FSU
CN02
CN01

U1U2
A B
L N CN81

FSU
CN02
CN01

U1 U2
A B
L N CN81

36

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1 U2

A B

L N CN81

FSU
CN02
CN01

Limitations
Individual control of 16 master indoor units, (7 slave units per master possible)
All indoor units will be affected by any timer functions or remote operation signals.
Only on/off control is provided

Dimensions (L x W x H)

Solution Components
TCB-CC163TLE2
Central remote to be located in the building containing the controlled air conditioners.

TCB-PCNT30TLE2
Network adapters will be required for each Master indoor unit when the central controller is
used in conjunction with DI/SDI slit systems.

37

5.3 TCB-PCNT20TLE X&Y Protocol Converter


Description
The device is intended for use on the DI/SDI/SMMS/SHRM ranges of equipment
and is designed to convert TCC Link to AI Network protocol. This enables earlier
types of control equipment to be interfaced with the current range.

Application
The device consists of a PCB and Transformer, which should be installed in or
adjacent to the indoor unit. Where indoor units are in Group Format it is only
necessary to install one device on the lead unit. Typically the protocol converter
would be used to integrate new equipment onto an existing AI control system. This
may be an RBC-CR1/64-PE Central Controller or a Building Management System
of some description.

Diagram

38

Connections
Power for the primary side of the Transformer is obtained from the CN309 socket
on the indoor PCB. A further connection is then made to the A & B terminals from
CN02.
Multiple devices would be connected together in a daisy chain fashion and each
device given a unique address via dipswitches SW01.

Limitations
It is recommended that 1.5mm2 2-core screened cable be used on all networks up
to a maximum of 500Mtrs.

Addressing

Bit1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON

Bit 2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON

SW01 L.A.N. Address Switch


Bit3
Bit4
Bit5
Bit6
Bit7
OFF OFF OFF OFF ON
OFF OFF OFF OFF ON
OFF OFF OFF OFF ON
OFF OFF OFF OFF ON
ON
OFF OFF OFF ON
ON
OFF OFF OFF ON
ON
OFF OFF OFF ON
ON
OFF OFF OFF ON
OFF
ON
OFF OFF ON
OFF
ON
OFF OFF ON
OFF
ON
OFF OFF ON
OFF
ON
OFF OFF ON
ON
ON
OFF OFF ON
ON
ON
OFF OFF ON
ON
ON
OFF OFF ON
ON
ON
OFF OFF ON

Bit1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON

Bit 2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON

SW01 L.A.N. Address Switch


Bit3
Bit4
Bit5
Bit6
Bit7
OFF OFF OFF
ON
ON
OFF OFF OFF
ON
ON
OFF OFF OFF
ON
ON
OFF OFF OFF
ON
ON
ON
OFF OFF
ON
ON
ON
OFF OFF
ON
ON
ON
OFF OFF
ON
ON
ON
OFF OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
ON
ON

Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16

Bit1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON

Bit 2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON

SW01 L.A.N. Address Switch


Bit3
Bit4
Bit5
Bit6
Bit7
OFF OFF
ON OFF
ON
OFF OFF
ON OFF
ON
OFF OFF
ON OFF
ON
OFF OFF
ON OFF
ON
ON
OFF
ON OFF
ON
ON
OFF
ON OFF
ON
ON
OFF
ON OFF
ON
ON
OFF
ON OFF
ON
OFF
ON
ON OFF
ON
OFF
ON
ON OFF
ON
OFF
ON
ON OFF
ON
OFF
ON
ON OFF
ON
ON
ON
ON OFF
ON
ON
ON
ON OFF
ON
ON
ON
ON OFF
ON
ON
ON
ON OFF
ON

Zone 17
Zone 18
Zone 19
Zone 20
Zone 21
Zone 22
Zone 23
Zone 24
Zone 25
Zone 26
Zone 27
Zone 28
Zone 29
Zone 30
Zone 31
Zone 32

Zone 33
Zone 34
Zone 35
Zone 36
Zone 37
Zone 38
Zone 39
Zone 40
Zone 41
Zone 42
Zone 43
Zone 44
Zone 45
Zone 46
Zone 47
Zone 48

Bit1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON

Bit 2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON

SW01 L.A.N. Address Switch


Bit3
Bit4
Bit5 Bit6
Bit7
OFF OFF
ON
ON
ON
OFF OFF
ON
ON
ON
OFF OFF
ON
ON
ON
OFF OFF
ON
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON

Zone 49
Zone 50
Zone 51
Zone 52
Zone 53
Zone 54
Zone 55
Zone 56
Zone 57
Zone 58
Zone 59
Zone 60
Zone 61
Zone 62
Zone 63
Zone 64

39

5.4 TCB-PCNT30TLE TCC Link Network Adaptor


Description
The device is intended for use on all the DI/SDI units other than the KRT High
Wall, which is supplied with the adaptor built in. The device is designed to allow
Network devices such as Central Controllers and BMS systems to be interfaced.

Application
The device consists of a small PCB, which should be installed within the indoor
unit and would typically be used where the indoor unit/units will be interfaced with a
Central Controller or any other network device, such as a BMS system. One device
is required for each indoor unit or group of indoor units. Where indoor units are
grouped together they will be assigned with one address on the central device and
will consequently all receive the same operational instructions.

Diagram

40

Connections
The device connects to the indoor unit PCB via socket CN50 and will provide two
terminal network connection designated U3 & U4.
Where multiple devices are to be installed it is necessary to set one unit with a
100ohm termination resistance. This would normally be on the device connected to
the unit with the lowest network address. The resistance being set by SW01 bit
being set to ON.
When the device/devices have been installed and a termination resistance applied
it is then necessary to apply a unique network and refrigerant line address to each
unit.

Addressing Procedure
The address setting is carried from a standard RBC-AMT21/31E remote controller.
Where units do not have standard remote controllers installed, one should be
temporarily attached in order to carry out the configuration process.
Accessing the Engineers configuration menu
Press Set CL & Check Simultaneously for 4 seconds.
Navigate to menu item 12 (refrigerant line address) using the Temperature Set
Buttons.
Set a unique line address using the Timer Set Buttons and then press SET.
Navigate to menu item 03 (network address) using the Temperature Set Buttons.
Set a unique network address using the Temperature Set Buttons and then press
SET
Press the CHECK button to complete the setting process
Generally speaking the refrigerant line address would mirror the network address,
however this would not be the case with grouped units, which would have the
same network address but different line addresses.

Limitations
It is recommended that 1.5mm2 2-core screened cable be used on all networks up
to a maximum of 500Mtrs in length.
The KRT range of units do not require adaptors as they are supplied with U3 & U4
connections and also have a termination resistance facility on the indoor PCB. The
termination resistance being set by SW01 bit 1 being set to ON.

41

6.1 RBC-WP1-PE Windows Control Package


Description
The RBC-WP1-PE is a front-end software package that controls all aspects of the air
conditioning systems installed on a site. The software is installed on a PC, which then
connects to a TCB-IFLN640TLE2 LonWorks gateway for connection to the indoor units.
The software allows all of the units operating parameters to be adjusted from the one PC.
It allows faults to be reported and re-transmitted via email, fax or text message. The
software can be accessed remotely either by telephone or via the Internet. The software
can log data and provide graphical representation of data. It has a schedule built-in for
time control and it can also be used to reset set points or modes of operation.
When the software is installed, it will automatically install the gateways and power meters
and it will then generate basic graphics.

Application
The software is used when a computer solution is required in order to provide a flexible
solution to allow the air conditioning to be fully controlled from one central point. It offers
much functionality, which is suited to small and large systems.

Features of the Software


Customization
The software being very flexible, it allows for a fully adaptable graphical representation of
the building to be included.

Frost Protection
The software has the ability to sample the air temperature from an individual or a selection
of indoor units. Then, based on this data, operate the air conditioning to give frost and
fabric protection to the building

Energy monitoring
The energy monitoring software can be included to calculate the running costs of the
individual indoor units. This data can then be provided in structured bills for the building
tenants. This data is calculated from the demand given from the indoor units and the
power consumed by the system. The RBC-EM1-PE power meter is required for this
function. This option is covered in a separate data sheet.

42

Control of other devices


We have a simple digital Input / Output module that we use to control other plant systems.
For example, we could enable boilers or other air-handling units. The module can accept
inputs also; examples would be an input from a fire alarm where the air conditioners are
shutdown or an input to switch on the air conditioners from an external source. The RBCDI1 module is required for this function. This option is covered in a separate data sheet.

Diagram
24 V Power Supply

8 individual outputs

RBC-EM1-PE KIT
GND
PWR
DO1A
DO1B
DO2A
DO2B
DO3A
DO3B
DO4A
DO4B
DO5A
DO5B
DO6A
DO6B
DO7A
DO7B
DO8A
DO8B

(See seperate data sheet for full details)

A
B
DI1
GND
DI2
GND
DI3
GND
DI4
GND
DI5
GND
DI6
GND
DI7
GND
DI8
GND

RBC-DI1-PE
380/415 V AC
Three-Phase
Neutral & Earth

8 individual inputs
RBC-AMT31E
VRF
OUTDOOR
UNIT

VRF
OUTDOOR
UNIT

L1
L2
L3
N
U1U2 U3 U4 U5U6

L1
L2
L3
N
U1 U2U3U4 U5 U6

TOSHIBA

RBC-AMT31E

RBC-AMT31E

TCB-SC642TLE

TCB-IFLN640TLE

L1
L2
L3
N
U1 U2 U3U4 U5 U6

A
B
U1/U3
U2/U4

CN02
U1/U3
U2/U4
C3
C4

N
L

TOS HIBA

Single Phase
220/240 V AC
2-Core & Earth

4-Pole Isolator
2-Core
Twisted
Screened
Non-polar

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

RBC-EXW21E

TIMER TMNL

E
N
L

Single Phase
220/240 V AC
2-Core & Earth

RBC-AMT31E

DIGITAL INVERTER
INDOOR
UNIT

RBC-AMT31E

U3 U4 A B

15 V DC
2-Core
Non-polar

FSU
CN02
CN01

U1 U2 A B
L N CN81

FSU
CN02
CN01

U1U2 A B
L N CN81

FSU
CN02
CN01

U1U2 A B
L N CN81

FSU
CN02
CN01

U1 U2 A B
L N CN81

FSU
CN02
CN01

U1 U2 A B
L N CN81

15 V DC
2-Core
Non-polar

TOS HIBA

TCC-LINK
CONTROLLER

INDOOR U1U2 A B
L N CN81
UNIT

TCC-LINK
CONTROLLER

A B

COMPUTER RUNNING
A
B RBC-WP1-PE
WINDOWS PACKAGE

A1
A2
A3
B1
B2
B3

VRF
OUTDOOR
UNIT

FSU
CN02
CN01

U1U2

A B

L N CN81

NETWORK
ADAPTER

A B
1 2 3

220/240V AC
Single Phase
3 Core + Earth

FSU
CN02
CN01

3 Pole Isolator

POWER WIRING FROM


DIGITAL INVERTER OR SUPER DIGITAL INVERTER
OUTDOOR UNITS

2-Pole Isolator
220/240 V AC
Single-Phase
2-Core & Earth

Connection
The Windows Package (RBC-WP1-PE) connects to a LonWorks gateway via the AB
network.
The AB network is connected via a two part screw terminal connector the recommended
cable is 2-Core Screened 1.5mm2. The connector is mounted on a full height PCI card that
is fitted to the PC
Limits
The windows package can control up to 1024 indoor units connected through the
LonWorks gateways (one gateway required per 64 indoor units).

43

PC Specification (Minimum)
Toshiba does not provide the PC. The minimum requirements for this PC to run the
Toshiba Windows Package are:
P4 2GHz or Equivalent
20G HDD
512M RAM
Separate Video Card
Full size case to Accept a Standard size PCI card

Solution Components
RBC-WP1-PE
Windows package will be required to configure and receive alarms from the remote site.

TCB-IFLN640TLE2
The LonWorks gateway will be required for every 64 indoor units.

TCB-PCNT30TLE2
Network adapters will be required for each Toshiba Digital Inverter and Super Digital
Inverter indoor unit.

RBC-EM1-PE
If energy monitoring is required, an RBC-EM1-PE kit is required for each refrigerant

system.

RBC-DI1-PE
If external control is required for other equipment, the RBC-DI1-PE will provide 8 digital
inputs and 8 relay outputs.

44

6.2 RBC-EM1-PE Windows Energy Monitoring


Description
The RBC-EM1-PE consists of a power meter and current transformers. All these
components are required to be mounted in a suitable enclosure. The power meters then
connect directly to the windows package. The RBC-EM1-PE kit consists of a Lon works
power meter and a set of three current transformers, one for each phase.

Application
The RBC-EM1-PE allows the total power consumption data to be divided between the
indoor units and be included on the tenant bill. A power meter for each refrigerant circuit is
recommended.

Diagram

TO BE HOUSED IN A
SUITABLE E NCLOSURE
* CO MPONENTS INCLUDED IN RBC-E M1-PE:
CT1 , CT2 & CT3 CURRENT TRANSFORMERS;
POWER METER

MCB

L1 L2L3 N

L1 L2 L3 N

L1 L2 L3 N

L1 L2 L3 N

L1

L2

L3

MCB MCB

P2

SECO NDAR Y

S1

S1

P2

P1

SEC OND ARY

S2

3 Phase 4 -W ire
from MCB's in
Di strib uti on Bo ar d

*C T3

P1

SECO NDA RY

S2

L1 L2 L3 N

N
N
L1
L2
L3

*C T2

*CT1
P2 P1

L1 L2L3 N

S1

S2

11

23/A 24/B

*POWER METER

380/415 V AC
Three-Phase
Neutral & Earth

L1
L2
L3
N
U1 U2 U3U4 U5 U6

OUTDOOR
UNIT

L1
L2
L3
N
U1 U2 U3 U4 U5 U6

COMPUTER RUNNING
A
B RBC-WP1-PE
WINDOWS PACKAGE

TCB-IFLN640TLE

L1
L2
L3
N
U1 U2 U3U4 U5 U6

A
B
U 1/U3
U 2/U4

RBC-AMT21E

T OSHIBA

Single Phase
220/240 V AC
2-Core & Earth

2-Core
Twisted
Screened
Non-polar

RBC-AMT21E

CN 02
U1/U3
U2/U4
C3
C4

N
L

4-Pole Isolator

RBC-AMT21E

TCB-SC642TLE

A1
A2
A3
B1
B2
B3

OUTDOOR
UNIT

OUTDOOR
UNIT

RBC-AMT21E

RBC-AMT21E

RBC-EXW21E

TIM ER TMNL

TO SH IBA

N
L

Single Phase
220/240 V AC
2-Core & Earth

RBC-AMT21E

RBC-AMT21E
TCC-LINK
CONTROLLER

15 V DC
2-Core
Non-polar

A B
INDOOR U1U2
L N CN81
UNIT

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

2-Pole Isolator
220/240 V AC
Single-Phase
2-Core & Earth

45

U1U2
A B
L N CN81

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1 U2

A B

L N CN81

FSU
CN02
CN01

Connections
The power meter connects to the PC and LonWorks gateway via the AB network the
recommended cable is 2-Core Screened 1.5mm2.
The current transformers connect to the power meter by a 1.5mm2 cable
The power meter requires a reference voltage from each phase the power meter should
be protected by a circuit breaker.
The supply to the outdoor unit should pass through the centre of the current transformer.

Limits
One power meter for each refrigerant circuit, i.e. one RBC-EM1-PE is required per system.

Dimensions (L x H x D)
Power meter: 150mm x 80mm x 120mm
Current Transformer: 800mm x 80mm x 600mm

Solution Components
RBC-WP1-PE
Windows package will be required to control the air conditioning allow remote access and
provide the energy billing function.

TCB-IFLN640TLE2
The Lon works gateway will be required for every 64 indoor units.

TCB-PCNT30TLE2
Network adapters will be required for each split indoor unit.

RBC-EM1-PE
If energy monitoring is required, an RBC-EM1-PE kit is required for each refrigerant

system.

46

6.3 RBC-DI1 Windows Control and Other


Equipment
Description
The RBC-DI1 is a module that connects to the LonWorks network that links back to
the Interactive Intelligence software running on a PC in the building. The module
has 8 digital inputs and eight relay outputs. These inputs can be used to control
external plant or except inputs from other plant.

Application
The application of this module is very versatile as it is an interface to other
equipment. If an input is made to the module Interactive intelligence can act on the
input and perform an operation i.e. enable units in specific modes, indicate status
of external plant on the PC etc. The relay outputs can be used to enable external
plant in conjunction with the AC or independently.
Examples of use for the Inputs
Fire Alarm Shutdown
Extend unit operation for a fixed time
Hotel key card unit set back
Examples of use for the Outputs
Enable air handling plant
Toshiba VN unit control
Lighting control
Fault Output

47

Diagram

GND
PWR
DO1A
DO1B
DO2A
DO2B
DO3A
DO3B
DO4A
DO4B
DO5A
DO5B
DO6A
DO6B
DO7A
DO7B
DO8A
DO8B

24 V AC or DC

A
B
DI1
GND
DI2
GND
DI3
GND
DI4
GND
DI5
GND
DI6
GND
DI7
GND
DI8
GND

RBC-DI1-PE

OUTDOOR
UNIT

OUTDOOR
UNIT

4-Pole Isolator

380/415 V AC
Three-Phase
Neutral & Earth

380/415 V AC
Three-Phase
Neutral & Earth

L1
L2
L3
N
U1 U2 U3U4 U5 U6

COMPUTER RUNNING
A
B RBC-WP1-PE
WINDOWS PACKAGE

TCB-SC642TLE

RBC-EXW21E

4-Pole Isolator
L1
L2
L3
N
U1U2 U3 U4 U5U6

380/415 V AC
Three-Phase
Neutral & Earth

TCB-IFLN640TLE

L1
L2
L3
N
U1 U2 U3U4 U5 U6

A
B
U1/U3
U2/U4

CN02
U1/U3
U2/U4
C3
C4

N
L

TOS HIBA

A1
A2
A3
B1
B2
B3

4-Pole Isolator

TO FIRE ALARM SHUT DOWN VIA


PANEL (BY OTHERS).

OUTDOOR
UNIT

Single Phase
220/240 V AC
2-Core & Earth

2-Core
Twisted
Screened
Non-polar

RBC-AMT21E

RBC-AMT21E

RBC-AMT21E

RBC-AMT21E

RBC-AMT21E

RBC-AMT21E

A B

A B

A B

A B

A B

A B

A B

TO S H IB A

TO S H IB A

TO S H I BA

T OS H I BA

TOSHIBA

Single Phase
220/240 V AC
2-Core & Earth

RBC-AMT21E

TO S H IB A

TIMER TMNL

N
L

T OS H I BA

T OS H I BA

TCC-LINK
CONTROLLER

15 V DC
2-Core
Non-polar

A B
INDOOR U1U2
L N CN81
UNIT

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1U2
A B
L N CN81

FSU
CN02
CN01

A B
U1U2
L N CN81

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1 U2

A B

L N CN81

FSU
CN02
CN01

2-Pole Isolator
220/240 V AC
Single-Phase
2-Core & Earth

Module Dimensions: 114mm x 115mm x 58mm

Connection/Installation Procedure
The module is connected to the LonWorks network that links the components to
the Interactive Intelligence software. The device requires a 24Vac 0.5A supply this
is normally derived from a panel-mounted transformer. The module mounts on a
piece of standard Din rail the device should be housed in a suitable enclosure. The
device has eight inputs these are volt free and could be connected to a contact
closure this input can be used within interactive intelligence. The eight outputs are
relay contact closures the contacts are rated at 24V 0.5A resistive load.

Limitations
Each device requires a power supply
Each device has a limit of eight inputs and Eight Outputs.

48

7.1 Touch Screen Controller


Description
The Touch Screen Controller is an advanced central controller, which is available
in various different formats. It is available in four formats, to control sixty-four or
five hundred and twelve indoor units, each of which are available with or without
the billing function. The Touch Screen allows full unit control of all connected
indoor units and is capable of giving full fault and operating information. The
controller has the ability to schedule on/off times for each individual indoor unit.
The Touch Screen is compatible with all SMMS/SHRM systems DI and SDI
systems may also be added, but network adapters are required.

Application
The Touch Screen would be used in an application where multiple unit control is
required from one location. The Touch Screen can be combined with other
components to provide energy monitoring or a common fault input/output signal,
which could be used for a fire alarm shutdown or similar facility. If the billing
function is used a PC running Excel is required.

Diagram
TO BE HOUSED IN A
SUITABLE ENCLOSURE
*COMPONEN TS INCLUDED IN RBC-EM1-PE:
CT1, CT2 & CT3 CURRENT TRANSF ORMERS;
POWER METER

MCB

L1 L2L3 N

L 1L2 L3 N

L1 L2L3 N

L 1L2 L3 N

L1

L2

L3

MCB MCB

*C T2
P2

S1

P1

P2

SE CONDARY

S2

S1

3 Phas e 4-Wire
fr om M CB's in
Distribu tion Board

*C T3
P1

SECONDARY

S1

S2

S2

TOUCH SCREEN
BMS-TP5120TWELN

COMPUTER RUNNING

11

A
B

OUTDOOR
UNIT

OUTDOOR
UNIT

OUTDOOR
UNIT

L1
L2
L3
N
U1 U2 U3U4 U5 U6

L1
L2
L3
N
U1U2 U3 U4 U5U6

L1
L2
L3
N
U1 U2 U3U4 U5 U6

RELAY I/F
BMS-IFDD01E

TCB-SC642TLE

CN02
U1 /U3
U2 /U4
C3
C4

N
E

U1/U3
U2/U4

TOSHIBA

Single Phase
220/240 V AC
2-Core & Earth

2-Core
Twisted
Screened
Non-polar

RBC-AMT21E

RBC-EXW21E

RELAY INTERFACE
A BMS-IFLSV2E2 L
B

4-Pole Isolator

RBC-AMT21E

L
N
E

POWER METER I/F


A
L
B BMS-IFWH3E N
A
B

RBC-AMT21E

HUB

RS-485

RBC-AMT21E

ETHERNET

INTELLIGENT SERVER
BMS-LSV4E LN

*P OWER METER

380/415 V AC
Three-Phase
Neutral & Earth

EXCEL FOR BILLS

2 3/A 2 4/B

A1
A2
A3
B1
B2
B3

P2 P1
SECONDARY

L1 L2L3 N

N
N
L1
L2
L3

* CT1

L1 L2L3 N

RBC-AMT21E

T IME R TMNL

TOSHIBA

N
L

Single Phase
220/240 V AC
2-Core & Earth

RBC-AMT21E

RBC-AMT21E
TCC-LINK
CONTROLLER

15 V DC
2-Core
Non-polar

A B
INDOOR U1U2
L N CN81
UNIT

FSU
CN02
CN01

U1 U2 A B
L N CN81

FSU
CN02
CN01

U1U2
A B
L N CN81

FSU
CN02
CN01

U1U2 A B
L N CN81

2-Pole Isolator
220/240 V AC
Single-Phase
2-Core & Earth

49

FSU
CN02
CN01

U1 U2 A B
L N CN81

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1U2

A B

L N CN81

FSU
CN02
CN01

Connection/Installation Procedure
The Touch Screen connects to an RS485 Network, which links the screen to the
Relay Interfaces. The Relay Interfaces are then connected to the Air Conditioning
Network via the U3 & U4 connection. The RS485 Network also connects to the
power meter and digital input/out interfaces. If the energy monitoring facility is
being used a separate PC will be required to run the energy monitoring software.
This PC will require Microsoft Excel and will need to be connected to the Touch
Screen via a network connection. The Touch Screen requires a 240V 3A mains
power supply
Additional Components
TCS Net Relay Interface BMS-IFLSV2E2
The Relay Interface connects to the Touch Screen Controller via the RS485
Network using connections A & B. The air conditioning network connects to
terminals U1 & U2 (U3 & U4 at the outdoor unit) and a maximum of 64 Indoor units
may be served. The relay interface requires a 240V 3 A mains power supply.
Energy Monitoring Relay Interface BMS-IFWH4E2
The energy monitoring Relay Interface connects to the RS485 Network and
provides a means of interface to the pulse power meters. Up to eight power meters
can be connected to each Relay Interface.
Digital Input Output Relay Interface BMS-IFDD02E2
The D/I module connects to the RS485 network and provides 8 inputs and 4
outputs, which could be used to interface a fire alarm system or a room occupancy
sensor. The D/I module output could be used as a means of remote fault indication
to another system.

Software
Site-specific software is written for the Touch Screen, which gives specific names
and locations for easy end-user operation. The software also configures the D/I
module and the Energy Monitoring Interfaces.
Energy monitoring software is installed on a separate PC. The software being
Excel based and using Macros to produce the reports for each Tenant.

50

Limitations
The total length of the U1/U2 network for each relay interface is as follows
1.5mm2 Screened up to 1000m
2.5mm2 Screened up to 2000m
The total length of the RS485 Network A/B
1.5mm2 Screened up to 500m

Components
Touch Screens
BMS-TP0641ACE
BMS-TP0641PWE
BMS-TP5121ACE
BMS-TP5121PWE

Touch screen for 64 indoor units


Touch screen for 64 indoor units with energy billing
Touch screen for 512 indoor units
Touch screen for 512 indoor units with energy billing

Interface Components
BMS-IFLSV2E2
BMS-IFWH4E2
BMS-IFDD02E2

TCS Net Relay Interface


Energy Monitoring Relay Interface
Digital Input Output Relay Interface

51

8.1 TCB-IFLN642TLE LonWorks Interface


Description
The LonWorks gateway is a device that allows the Toshiba indoor units to be
connected to a LonWorks based BMS. The gateway uses all standard network
variables contained in individual function blocks for each indoor unit. The gateway
can communicate with up to 64 indoor units on a U1/U2 Network.

Application
The device is used to connect to a LonWorks Network, which many BMS
companies are able to communicate with, (open network protocol). The LonWorks
Gateway is used with Interactive Intelligence Software (RBC-WP1) and also with
the Realtime LTX solutions for connection to other types of BMS, please see
section 9.0.
All of the data for each indoor unit is available on the LonWorks Network; there are
twenty-nine standard network variables for each indoor unit, all of which are
available on the gateway.

Diagram

OUTDOOR
UNIT

OUTDOOR
UNIT

OUTDOOR
UNIT
LONWORKS BMS

380/415 V AC
Three-Phase
Neutral & Earth

4-Pole Isolator
380/415 V AC
Three-Phase
Neutral & Earth

L1
L2
L3
N
U1 U2 U3U4 U5 U6

4-Pole Isolator
L1
L2
L3
N
U1U2 U3 U4 U5U6

380/415 V AC
Three-Phase
Neutral & Earth

TCB-IFLN640TLE

L1
L2
L3
N
U1 U2 U3U4 U5 U6

A
B
U1/U3
U2/U4

C N02
U1/U3
U2/U4
C3
C4

N
L

TOSHIBA

A1
A2
A3
B1
B2
B3

4-Pole Isolator

TCB-SC642TLE

Single Phase
220/240 V AC
2-Core & Earth

2-Core
Twisted
Screened
Non-polar

E
N
L

Single Phase
220/240 V AC
2-Core & Earth

RBC-AMT21E

RBC-AMT21E

RBC-AMT21E

RBC-AMT21E

RBC-AMT21E

RBC-AMT21E

RBC-AMT21E

A B

A B

A B

A B

A B

A B

A B

TO S H I B A

T O S HI B A

TO S H I B A

T O SH I B A

TO S H I B A

T O SH I B A

TO S H I BA

TCC-LINK
CONTROLLER

15 V DC
2-Core
Non-polar

A B
INDOOR U1U2
L N CN81
UNIT

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1U2
A B
L N CN81

FSU
CN02
CN01

U1U2
A B
L N CN81

2-Pole Isolator
220/240 V AC
Single-Phase
2-Core & Earth

52

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1 U2
A B
L N CN81

FSU
CN02
CN01

U1U2

A B

L N CN81

FSU
CN02
CN01

Connection/Installation Procedure
The gateway connects to the air conditioner network via U1 & U2 and the
LonWorks network connects via the A & B connection. A 240V 3A mains supply is
required for the gateway.

Limitations
The total length of the air conditioner U1/U2 network for each relay interface is as
follows.
1.5mm2 Screened up to 1000m
2.5mm2 Screened up to 2000m
The LonWorks network should be 1.5mm2 Screened up to 500m

53

9.1 BACnet Interface


Description
The BACnet solution allows the Toshiba indoor units to be connected to a BACnet
over IP based BMS. The gateway uses all standard BACnet objects for the control
and monitoring of each indoor unit.

Application
The BACnet solution is intended for use in systems where control of the air
conditioning is being carried out by another system that is a part of the wider BMS
for a large building. BACnet is a standard protocol adopted by many BMS
companies as a standard network protocol they support

Diagram

BACNET
SYSTEM

OUTDOOR
UNIT

OUTDOOR
UNIT

ETHERNET

OUTDOOR
UNIT
RS-485

380/415 V AC
Three-Phase
Neutral & Earth

4-Pole Isolator
380/415 V AC
Three-Phase
Neutral & Earth

L1
L2
L3
N
U1 U2 U3U4 U5 U6

TCB-SC642TLE

4-Pole Isolator
L1
L2
L3
N
U1U2 U3 U4U5U6

380/415 V AC
Three-Phase
Neutral & Earth

RELAY INTERFACE
BMS-IFLSV2E2 L

L1
L2
L3
N
U1U2 U3U4U5 U6

A
B
U1/U3
U2/U4

CN02
U1/U3
U2/U4
C3
C4

N
E

TOS HIBA

A1
A2
A3
B1
B2
B3

4-Pole Isolator

INTELLIGENT SERVER
BMS-LSV4E NL
BMS-STBN05E E

Single Phase
220/240 V AC
2-Core & Earth

2-Core
Twisted
Screened
Non-polar

E
N
L

Single Phase
220/240 V AC
2-Core & Earth

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

RBC-AMT31E

A B

A B

A B

A B

A B

A B

A B

T O SH I B A

T O SH I B A

T OS H I B A

TO S H I BA

TO S H IB A

TO S HI B A

T O SH I B A

TCC-LINK
CONTROLLER

15 V DC
2-Core
Non-polar

INDOOR U1U2 A B
L N CN81
UNIT

FSU
CN02
CN01

U1 U2 A B
L N CN81

FSU
CN02
CN01

U1U2 A B
L N CN81

FSU
CN02
CN01

U1U2 A B
L N CN81

2-Pole Isolator
220/240 V AC
Single-Phase
2-Core & Earth

54

FSU
CN02
CN01

U1 U2 A B
L N CN81

FSU
CN02
CN01

U1 U2 A B
L N CN81

FSU
CN02
CN01

U1U2

A B

L N CN81

FSU
CN02
CN01

Connection/Installation Procedure
The BACnet solution consists of several different components, which have been
listed below. The maximum number of indoor units that may be controlled is 128
per Intelligent Server. Up to a maximum of eight Relay Interfaces can be
connected per Intelligent Server.
Intelligent Server BMS-LSV4E
The intelligent server connects to the BACnet system by a network connection,
usually to a local hub. The Relay Interfaces connect to the server by the RS485
network and up to eight Relay Interfaces may be connected, with a maximum of
128 indoor units. The Intelligent Server requires a 240V 3A mains supply.
BACnet Software BMS-STBN05E
The BACnet software is contained on a standard Compact Flash Card, which plugs
directly into the Intelligent Server.
TCS Net Relay Interface BMS-IFLSV2E2
The Relay Interface connects to the Touch Screen Controller via the RS485
Network, (A & B connections). The air conditioner network connects to the U1 &
U2 connections, with a maximum of 64 indoor units served. The Relay Interface
requires a 240V 3 A mains supply.

Software
Site-specific software is written for the BACnet solution and then uploaded to the
Intelligent Server. This gives site-specific names and locations, which are then
presented to the BACnet network.

Limitations
The total length of the air conditioner U1/U2 network for each relay interface is as
follows.
1.5mm2 Screened up to 1000m
2.5mm2 Screened up to 2000m
The total length of the RS485 Network A/B
1.5mm2 Screened up to 500m
The total length of the Ethernet cable from the Hub to the server should be a
maximum of 100M
The IP Address range should not be used xx.xx.0.xx

55

10.1 Trend Solution (LTX-21)


Description
The LTX-21 is a product that has been developed to enable Toshiba air
conditioners to directly connect to a Trend BMS system. The LTX-21 connects
directly to the Trend outstation supervisor port. The interface is capable of setting
all of the operating parameters for each indoor unit. It also provides error codes
and the return air temperatures.

Application
The LTX-21 solution is designed to allow connection to a Trend BMS system. It
allows a fully functional solution to be achieved. The LTX-21 and associated
Toshiba LonWorks gateway are usually mounted in the control panel with the
outstation. We have two possible variations, which are outlined below.
LTX-21 and RBC-LG1 Combination
This uses a LTX-21 and an RBC-LG1-PE, which connects to a maximum of
sixteen indoor units however; the TCB-PCNT20TLE network adapters are required
to convert back to the AI network. This option will be cost effective for single split
installations with less than 7 indoor units for all other situations use the solution
below.
LTX-21, LTX-VCI and TCB-IFLN640TLE Combination
This solution uses an LTX-VCI and TCB-IFLN640TLE for the control of a maximum of 64
indoor units. The solution uses an LTX-21 for every 16 indoor units as these connect to
the Trend outstations. For example, for a total of 64 indoor units you would use four LTX21s.
In each of the above cases, multiples of the above combinations can be used to
accommodate larger systems.

56

Connections
LTX-21 and RBC-LG1-PE Combination
The LTX-21 requires a 24V dc supply and the LonWorks gateway requires a 240v supply.
The devices are linked on a LonWorks network.
The XY network is connected via a screw terminal connector. The recommended cable is
2-Core Screened 1.5mm2.
A serial cable connects the LTX-21 to the outstation.

Diagram
OUTDOOR
UNIT

TREND BMS OUT-STATION


(SUPPLIED BY OTHERS)

OUTDOOR
UNIT

Digital Inverter
System
RBC-AMT31E

4-Pole Isolator

380/415 V AC
Three-Phase
Neutral & Earth

RS232 Serial Cable to


Supervisor Port
24V
DC

4-Pole Isolator

VRF
System

L1
L2
L3
N
U1 U2 U3U4 U5 U6

380/415 V AC
Three-Phase
Neutral & Earth

L1
L2
L3
N
U1U2 U3 U4 U5U6

15 V DC
2-Core
Non-polar

Twisted Screened
2-Core Non Polar
Twisted Screened
2-Core Non Polar

All X & Y wiring to be 2 Core


Twisted Screened (1.5mm)

SERIAL PORT LON NETWORK

LTX21
(TREND GATEWAY)
SUPPLIED BY REALTIME SYSTEMS CONTROL

X Y A B

X Y
240 V
AB
LON NETWORK COMMS
AC
MAINS
L N

RBC-LG1-PE
(LONWORKS GATEWAY)

PROTOCOL
CONVERTER

U1U2
A B
L N

2-Pole Isolator
220/240 V AC
Single-Phase
2-Core & Earth

X Y A B

PROTOCOL
CONVERTER

U1 U2 A B
L N

X Y A B

PROTOCOL
CONVERTER

U1U2
A B
L N

X Y A B
PROTOCOL
CONVERTER

A B
1 2 3

220/240 V ac
Single Phase 3
Core + Earth
Digital Inverter
Outdoor Unit

1 2 3
L N

220/240V AC
20A Rating
Single Phase
Neutral + Earth 2 Pole Isolator

57

LTX-21, LTX-VCI and TCB-IFLN640TLE Combination


The LTX-21 and LTX-VCI require a 24V dc supply and the LonWorks gateway requires a
240v supply. The devices are linked on a LonWorks network.
U3/U4 network is connected via a screw terminal connector. The recommended cable is
2-Core Screened 1.5mm2.
A serial cable connects the LTX-21 to the outstation.

Diagram
System
RBC-AMT31E

OUTDOOR
UNIT

VRF
System

OUTDOOR
UNIT

15 V DC
2-Core
Non-polar

TREND BMS OUT-STATION


(SUPPLIED BY OTHERS)

RS232 SERIAL CABLE TO


SUPERVISOR PORT

4-Pole Isolator

24 V
DC

SERIAL PORT

380/415 V AC
Three-Phase
Neutral & Earth

4-Pole Isolator
L1
L2
L3
N
U1 U2 U3U4 U5 U6

380/415 V AC
Three-Phase
Neutral & Earth

L1
L2
L3
N
U1U2 U3 U4 U5U6

B A
LON NETWORK

Single Phase
220/240 V AC
2-Core & Earth

LTX21
(TREND GATEWAY)
SUPPLIED BY REALTIME SYSTEMS CONTROL

Twisted Screened
2-Core Non Polar

U3U4 A B
Network
Adaptor

TCB-IFLN640TLE
24 V
DC

A B
LON NETWORK

A
B
U1/U3
U2/U4

A B
1 2 3

N
L

LTXVCI
SUPPLIED BY REALTIME SYSTEMS CONTROL

U1U2 A B
L N

U1 U2 A B
L N

2-Pole Isolator

U1U2 A B
L N

220/240 V ac
Single Phase 3
Core + Earth
Digital Inverter
Outdoor Unit

1 2 3
L N

220/240V AC
20A Rating
Single Phase
Neutral + Earth 2 Pole Isolator

220/240 V AC
Single-Phase
2-Core & Earth

58

Limits
LTX-21 and RBC-LG1-PE Combination
This solution can control a maximum of sixteen indoor units and the TCB-PCNT20TLE
network adapters are required for all indoor units.

LTX-21, LTX-VCI and TCB-IFLN640TLE Combination


This solution can control a maximum of sixty-four indoor units with one LTX-21 for every
sixteen indoor units.

Dimensions* (H x W x D), mm
LTX-21
LTX-VCI
RBC-LG1-PE
TCB-IFLN640TLE

155 x 190 x 55
155 x 190 x 55
227 x 157 x 65
250 x 250 x 60

*Dimensions include clearances

Solution Components
LTX-21 and RBC-LG1 Combination
LTX-21
RBC-LG1-PE
TCB-PCNT20TLE

LonWorks to Trend Gateway


LonWorks to Toshiba Gateway
Network adapter AB to XY

Supplier
Realtime
Toshiba
Toshiba

LTX-21, LTX-VCI and TCB-IFLN640TLE Combination


LTX-21
LTX-VCI
TCB-IFLN640TLE
TCB-PCNT30TLE

LonWorks to Trend Gateway


Realtime
LonWorks Adapter
Realtime
LonWorks to Toshiba Gateway
Toshiba
Network adapter to U3/U4 only used for split systems
Toshiba

Full details and product support for the LTX products can be obtained from
Realtime Controls
Park House
Greenhill crescent
Watford Business Park
Watford WD1 8QU
Tel
01923 233384
Fax
01923 233385
www.realtime-controls.co.uk

59

10.2 Modbus Solution (LTX-51)


Description
The LTX-51 interface is a product that has been developed to enable Toshiba air
conditioners to directly connect to a Modbus serial port on a BMS outstation. The
interface is capable of setting all of the operating parameters for each indoor unit. It
also provides error codes and the return air temperatures.

Application
The LTX-51 solution is designed to allow connection to a Trend BMS system. It
allows a fully functional solution to be achieved. The LTX-51 and associated
Toshiba LonWorks gateway are usually mounted in the control panel with the
outstation. We have two possible variations, which are outlined below.
LTX-51 and RBC-LG1 Combination
This uses a LTX-51 and an RBC-LG1-PE, which connects to a maximum of
sixteen indoor units; however, the TCB-PCNT20TLE network adapters are
required to convert back to the AI network. This option will be cost effective for
single split installations with less than 7 indoor units for all other situations use the
solution below.
LTX-51, LTX-VCI and TCB-IFLN640TLE Combination

This solution uses an LTX-VCI and TCB-IFLN640TLE for the control of a maximum
of 64 indoor units. The solution uses an LTX-51 for every 16 indoor units as these
connect to the Trend outstations. For example, for a total of 64 indoor units you
would use four LTX-51s.
In each of the above cases, multiples of the above combinations can be used to
accommodate larger systems.

60

Connections
LTX-51 and RBC-LG1-PE Combination
The LTX-51 requires a 24V dc supply and the LonWorks gateway requires a 240v supply.
The devices are linked on a LonWorks network.
The XY network is connected via a screw terminal connector. The recommended cable is
2-Core Screened 1.5mm2.
A serial cable connects the LTX-51 to the outstation.

Diagram

OUTDOOR
UNIT

MODBUS BMS OUT-STATION


(SUPPLIED BY OTHERS)

OUTDOOR
UNIT

Digital Inverter
System
RBC-AMT31E

4-Pole Isolator

4-Pole Isolator
380/415 V AC
Three-Phase
Neutral & Earth

RS232 Serial Cable to


Modbus Port
24V
DC

VRF
System

L1
L2
L3
N
U1U2 U3U4U5 U6

380/415 V AC
Three-Phase
Neutral & Earth

L1
L2
L3
N
U1U2 U3U4 U5U6

15 V DC
2-Core
Non-polar

Twisted Screened
2-Core Non Polar
Twisted Screened
2-Core Non Polar

All X & Y wiring to be 2 Core


Twisted Screened (1.5mm)

SERIAL PORT LON NETWORK

LTX-51
(MODBUS GATEWAY)
SUPPLIED BY REALTIME SYSTEMS CONTROL

X Y A B

X Y
240 V
AB
LON NETWORK COMMS
AC
MAINS
L N

RBC-LG1-PE
(LONWORKS GATEWAY)

PROTOCOL
CONVERTER

U1U2 A B
L N

2-Pole Isolator
220/240 V AC
Single-Phase
2-Core & Earth

X Y A B

PROTOCOL
CONVERTER

U1 U2 A B
L N

X Y A B

PROTOCOL
CONVERTER

U1U2 A B
L N

X Y A B
PROTOCOL
CONVERTER

A B
1 2 3

220/240 V ac
Single Phase 3
Core + Earth
Digital Inverter
Outdoor Unit

1 2 3
L N

220/240V AC
20A Rating
Single Phase
Neutral + Earth 2 Pole Isolator

61

LTX-51, LTX-VCI and TCB-IFLN640TLE Combination


The LTX-51 and LTX-VCI require a 24V dc supply and the LonWorks gateway requires a
240v supply. The devices are linked on a LonWorks network.
U3/U4 network is connected via a screw terminal connector. The recommended cable is
2-Core Screened 1.5mm2.
A serial cable connects the LTX-51 to the outstation.

Diagram
System
RBC-AMT31E

VRF
System

OUTDOOR
UNIT

OUTDOOR
UNIT

15 V DC
2-Core
Non-polar

MODBUS BMS OUT-STATION


(SUPPLIED BY OTHERS)

RS232 SERIAL CABLE TO


MODBUS PORT

4-Pole Isolator

24 V
DC

SERIAL PORT

380/415 V AC
Three-Phase
Neutral & Earth

4-Pole Isolator
L1
L2
L3
N
U1 U2 U3U4 U5 U6

380/415 V AC
Three-Phase
Neutral & Earth

L1
L2
L3
N
U1U2 U3 U4 U5U6

B A
LON NETWORK

Single Phase
220/240 V AC
2-Core & Earth

LTX-51
(MODBUS GATEWAY)
SUPPLIED BY REALTIME SYSTEMS CONTROL

Twisted Screened
2-Core Non Polar

U3U4 A B
Network
Adaptor

TCB-IFLN640TLE
24 V
DC

A B
LON NETWORK

A
B
U1/U3
U2/U4

A B
1 2 3

N
L

220/240 V ac
Single Phase 3
Core + Earth

LTXVCI
SUPPLIED BY REALTIME SYSTEMS CONTROL

U1U2
A B
L N

2-Pole Isolator

U1 U2
A B
L N

U1U2
A B
L N

Digital Inverter
Outdoor Unit

1 2 3
L N

220/240V AC
20A Rating
Single Phase
Neutral + Earth 2 Pole Isolator

220/240 V AC
Single-Phase
2-Core & Earth

62

Limits
LTX-51 and RBC-LG1-PE Combination
This solution can control a maximum of sixteen indoor units and the TCB-PCNT20TLE
network adapters are required for all indoor units.
LTX-51, LTX-VCI and TCB-IFLN640TLE Combination
This solution can control a maximum of sixty-four indoor units with one LTX-51 for every
sixteen indoor units.

Dimensions* (H x W x D), mm
LTX-51
LTX-VCI
RBC-LG1-PE
TCB-IFLN640TLE

155 x 190 x 55
155 x 190 x 55
227 x 157 x 65
250 x 250 x 60

*Dimensions include clearances

Solution Components
LTX-51 and RBC-LG1 Combination
LTX-51
RBC-LG1-PE
TCB-PCNT20TLE

LonWorks to Trend Gateway


LonWorks to Toshiba Gateway
Network adapter AB to XY

Supplier
Realtime
Toshiba
Toshiba

LTX-51, LTX-VCI and TCB-IFLN640TLE Combination


LTX-51
LTX-VCI
TCB-IFLN640TLE
TCB-PCNT30TLE

LonWorks to Trend Gateway


Realtime
LonWorks Adapter
Realtime
LonWorks to Toshiba Gateway
Toshiba
Network adapter to U3/U4 only used for split systems
Toshiba

Full details and product support for the LTX products can be obtained from
Realtime Controls
Park House
Greenhill crescent
Watford Business Park
Watford WD1 8QU
Tel
01923 233384
Fax
01923 233385
www.realtime-controls.co.uk

63

11.1 VN Unit Controls


Description
This section is subdivided into four sections for diferent applications of the VN
units. The VN is supplied with a 240V control option as standard this is a starting
point but often requires development for specific applications.

Application
Option 1
The first option is the simplest form of control it does not allow control with the air
conditioner system. The mechanical switch is straightforward to install as it only
involves the switching of the relays. If required the fan speed or the damper can be
fixed in a particular mode
Option 2
The Second option allows the VN unit to be enabled from an indoor unit this
utilizes the RBC-SMFI Fan interface. This link means the unit needs to be operated
in conjunction with an associated indoor unit.
Option 3
Option 3 is a low voltage option, which gives a dedicated controller for the VN unit
this control option, will allow a Heater to be controlled to protect the fabric of the
unit. This option can also be integrated with the indoor units via the RBC-SMFI fan
interface.
Option 4
The final option indicates the procedure for connecting and control using
interactive intelligence. This allows full control from the PC of the VN unit the units
can independently time controlled to only provide ventilation when the building is
occupied.

64

Option 1: 3-Gang switch


The simplest form of ventilation heat exchanger unit (VN unit) control is with
electro-mechanical switches. These are not supplied by Toshiba but can be
obtained from the usual DIY stores. Three switches should be used with one VN
unit.

Controls:
ON/OFF (switch 1)
Fan Speed - High/Low (switch 2)
Mode - Bypass/Heat Exchange (Damper on/off) (switch 3)
For some of the smaller projects, this may be the most convenient and cost
effective solution.
Note that this option is only available if there are no Toshiba heaters provided with
the heat exchangers.

220-240 V AC
Single-Phase
Neutral & Earth

HEAT
EXCHANGE
VENTILATION
UNIT
L
N
COMMON
LOW
HIGH
DAMPER

Switch Positions
1 - Off
2 - On
3 - High Fan Speed
4 - Low Fan Speed
5 - Heat Exhange Ventilation
6 - Bypass Ventilation

Switch
(By Others)

65

Option 2: External relay


RBC-SMFI
If the requirements are for the heat exchanger unit to be turned ON whenever a
certain fan coil unit is turned ON; then using a RBC-SMFI is the solution. Two
switches as introduced in option 1 above should be used for the fan speed and
damper operation and control.

Controls:
ON/OFF (via the indoor unit)

Fan Speed - High/Low (switch 1)


Mode - Bypass/Heat Exchange (Damper on/off) (switch 2)
The RBC-SMFI will connect to the PC board of one indoor unit as shown below.
RBC-AMT31E

A B
220-240 V AC
Single-Phase
Neutral & Earth

HEAT
EXCHANGE
VENTILATION
UNIT

L
N
COMMON
LOW
HIGH
DAMPER

12 V DC 2-Core

1
2

CN32

15 V DC 2-Core
A B
1 2 3

INDOOR
UNIT

RBC-SMFI - External Fan Interface (Relay & CN32 Lead)


Switch/Relay Positions
1 - Off
2 - On
3 - High Fan Speed
4 - Low Fan Speed
5 - Heat Exhange Ventilation
6 - Bypass Ventilation

1 2 3
L N

6
220/240V AC
20A Rating
Single Phase
Neutral + Earth

Switch
(By Others)

3 Pole Isolator
Minimum 5A

220/240 V AC
Single Phase
3 Core + Earth

OUTDOOR
UNIT
2 Pole Isolator

More than one heat exchanger unit can be connected to the same indoor fan coil
unit. In order to do so, the heat exchanger units need to be wired in parallel.
However, the current may be too large and an additional higher amperage relay
(provided by others) may be required. The RBC-SMFI would then turn the relay
ON.
Note that this option is only available if there are no Toshiba heaters provided with
the heat exchangers.

66

Option 3: Hard Wired Wall Mounted Controller


RBC-VNC1 & RBC-VNP1
The Wall Mounted LCD Heat Exchanger Controller is the RBC-VNC1. The
controller MUST be used with the Heat Exchanger PCB (RBC-VNP1) (Incl PreHeat, or Re-Heat Control). The PCB is a direct replacement for the original
supplied PCB in the heat exchanger unit.
Controls:
ON/OFF
Fan Speed - High/Low
Mode - Bypass/Heat Exchange (Damper on/off)
Heater - Adjustable Pre-Heater or Re-Heater activation temperature (if
heaters are provided)
In addition to the RBC-VNC1 and RBC-VNP1, a RBC-SMFI can also be connect to
the PC board of one indoor unit for ON/OFF option via an indoor fan coil unit.
One RBC-VNC1 and one RBC-VNP1 are required for each heat exchanger unit
(even if a heater is not fitted).
Also note that there is a set of contacts on the PCB board (RBC-VNP1), which can
be connected back to a BMS system for ON/OFF option only.
DIFFERENTIAL
PRESSURE
SWITCH

AMBIENT
AIR

HEATER
PRECUT-OUTS HEATER
TAPPING
POINT

HEAT
EXCHANGE
VENTILATION
UNIT

Low Voltage
2 Core 0.5mm
220/240 V ac
2 Core Sized
For Heater
Capacity

RBC-VNP1

S1
S2
S3
S4
S5
S6
S7
S8
L
N
E

H1
H2
H3
H4
H5
H6

SUPPLY
AIR

TAPPING
POINT

REMOTE
ON/OFF LINK
(SHORT IF
NOT REQUIRED)

220/240 V ac
Single Phase
2 Core + Earth
Cable & Fuse Size
is Heater Capacity
Dependant

T
T
S3
S4
S5
S6
S7
S8

Low Voltage
6 Core 0.5mm

RBC-AMT31E

RBC-VNC1

12 V DC 2-Core

U1U2 A B
1
L N CN81
2

RBC-SMFI - External Fan Interface (Relay & CN32 Lead)

67

CN32

AMBIENT AIR
SENSOR

FSU
CN02
CN01

Option 4: Interactive Intelligence


RBC-VNP1, RBC-DI1-E and RBC-VNT1
Heat Exchanger PCB (Incl Pre-Heat, or Re-Heat Control)
Control by Interactive Intelligence can be achieved with the use of DI Modules
(RBC-DI1-E). Each of the functions will require one of the eight outputs available
from a DI Module:
Output 1 - On/Off
Output 2 - High/Low Fan Speed
Output 3 - Bypass/Heat Exchange (Damper on/off)
Output 4 - Heater On/Off (if applicable)
The DI module will then be connected to the Windows Package via the AB
network.
One RBC-VNP1 will be required for every heat exchange ventilation unit (even if a
heater is not fitted).
An RBC-VNT1 will be required with every heater fitted on this option. This is
a manually adjustable thermostat to set the activation temperature

DIFFERENTIAL
PRESSURE
SWITCH
HEATER
PRECUT-OUTS HEATER

AMBIENT AIR
SENSOR
AMBIENT
AIR

TAPPING
POINT

TAPPING
POINT

HEAT
EXCHANGE
VENTILATION
UNIT

Low Voltage
2 Core 0.5mm
220/240 V ac
2 Core Sized
For Heater
Capacity

RBC-VNP1

S1
S2
S3
S4
S5
S6
S7
S8
L
N
E

H1
H2
H3
H4
H5
H6

REMOTE
ON/OFF LINK
(SHORT IF
NOT REQUIRED)

COMPUTER RUNNING
A
B RBC-WP1-PE
WINDOWS PACKAGE

GND
PWR
DO1A
DO1B
DO2A
DO2B
DO3A
DO3B
DO4A
DO4B
DO5A
DO5B
DO6A
DO6B
DO7A
DO7B
DO8A
DO8B

INTERACTIVE INTELLIGENCE

220/240 V ac
Single Phase
2 Core + Earth
Cable & Fuse Size
is Heater Capacity
Dependant

RBC-DI1-PE
A
B
DI1
GND
DI2
GND
DI3
GND
DI4
GND
DI5
GND
DI6
GND
DI7
GND
DI8
GND

COMMON
N/O
1
RBC-VNT1 2
3
4

68

SUPPLY
AIR

Notes

69

Notes

70

Notes

71

Toshiba products are supplied by:

Telephone: 01707 378670

The manufacturer reserves the right to change the product specifications and images without notice.