Académique Documents
Professionnel Documents
Culture Documents
www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Page:
Project:
Fastening Point:
Date:
1
Single Beam Force
18/12/2015
Specifier's comments:
1 Input data
Anchor type and size:
Material:
A4
Approval No.:
ETA 07/0260
Issued I Valid:
26/06/2013 | 16/05/2018
Proof:
Design method SOFA design method + fib (07/2011) - after ETAG BOND testing
Stand-off installation:
eb = 0 mm (no stand-off); t = 30 mm
Baseplate:
Profile:
Base material:
cracked concrete, C30/37, fc = 30.00 N/mm2; h = 275 mm, Temp. short/long: 0/0 C
Installation:
Reinforcement:
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
2
Single Beam Force
Page:
Project:
Fastening Point:
Date:
18/12/2015
y
1
Shear force y
0.000
0.000
0.000
0.000
x
Tension
Compression
Capacity [kN]
98.252
Utilisation bN [%]
2
Status
OK
5.324
100.732
OK
5.324
82.996
OK
N/A
N/A
N/A
N/A
Steel failure*
Splitting failure**
* most unfavourable anchor
gM,s
2.860
NRd,s [kN]
98.252
NSd [kN]
1.507
A0p,N [mm2]
156816
yA,Np
2.884
2
tRk,ucr,25 [N/mm ]
13.00
scr,Np [mm]
396
yc
1.040
2
tRk,cr [N/mm ]
6.24
yg,Np
1.000
yg,Np
1.000
ec1,N [mm]
12
yec1,Np
0.945
ec2,N [mm]
0
yec2,Np
1.000
ys,Np
1.000
N0Rk,p [kN]
77.629
NRk,p [kN]
211.537
gM,p
2.100
NRd,p [kN]
100.732
NSd [kN]
5.324
ccr,Np [mm]
198
cmin [mm]
450
yre,Np
1.000
A0c,N [mm2]
156816
yA,N
2.884
ccr,N [mm]
198
scr,N [mm]
396
ec1,N [mm]
12
yec1,N
0.945
ec2,N [mm]
0
yec2,N
1.000
ys,N
1.000
N0Rk,c [kN]
63.961
gM,c
2.100
NRd,c [kN]
82.996
NSd [kN]
5.324
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
yre,N
1.000
k1
7.700
www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
3
Single Beam Force
Page:
Project:
Fastening Point:
Date:
18/12/2015
Capacity [kN]
58.824
Utilisation bV [%]
37
Status
OK
N/A
N/A
N/A
N/A
Pryout failure**
86.000
245.936
35
OK
43.000
43.475
99
OK
gM,s
2.380
VRd,s [kN]
58.824
VSd [kN]
21.500
A0c,N [mm2]
156816
yA,N
2.884
ccr,N [mm]
198
scr,N [mm]
396
k4
2.000
ec1,V [mm]
0
yec1,N
1.000
ec2,V [mm]
0
yec2,N
1.000
ys,N
1.000
yre,N
1.000
N0Rk,c [kN]
63.961
gM,c,p
1.500
VRd,c1 [kN]
245.936
VSd [kN]
86.000
dnom [mm]
30.0
kV
1.700
a
0.066
b
0.063
c1 [mm]
950
c'1 [mm]
300
Ac,V [mm2]
357500
A0c,V [mm2]
405000
yA,V
0.883
ys,V
1.000
yh,V
1.279
ya,V
1.000
ec,V [mm]
0
yec,V
1.000
V0Rk,c [kN]
82.503
n1
2
gM,c
1.500
VRd,c [kN]
43.475
VSd [kN]
43.000
yre,V
1.400
y90,V
2.000
5 Combined tension and shear loads SOFA (fib (07/2011), section 10.3)
steel
bN
0.015
bV
0.366
a
2.000
Status
OK
concrete
0.064
0.989
1.500
100
OK
bN + bV <= 1
1.116 [kN]
dN
0.007 [mm]
VSk
15.926 [kN]
dV
0.478 [mm]
dNV
0.478 [mm]
1.116 [kN]
dN
0.021 [mm]
VSk
15.926 [kN]
dV
0.796 [mm]
dNV
0.797 [mm]
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Page:
Project:
Fastening Point:
Date:
4
Single Beam Force
18/12/2015
7 Warnings
Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!
Input data and results must be checked for agreement with the
existing conditions and for plausibility!
The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
Characteristic bond resistances depend on short- and long-term temperatures.
Please contact Hilti to check feasibility of HIT-V rod supply.
The design method fib (07/2011) assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by
filling the gap with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
The compliance with current standards (e.g. EC3) is the responsibility of the user
Checking the transfer of loads into the base material is required in accordance with fib (07/2011)!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
5
Single Beam Force
Page:
Project:
Fastening Point:
Date:
18/12/2015
8 Installation data
Baseplate, steel: Profile: Advance UKB; 307 x 166 x 12 x 12 mm
Hole diameter in the fixture: df = 33 mm
Plate thickness (input): 30 mm
Recommended plate thickness: not calculated
Cleaning: Premium cleaning of the drilled hole is required
Cleaning
Compressed air with required
accessories to blow from the bottom of
the hole
Proper diameter wire brush
Setting
Dispenser including cassette and mixer
Seismic/Filling set
Torque wrench
y
-325
500
50
500
4
50
250
400
250
775
175
x
275
450
275
450
y
200
200
-200
-200
c-x
775
950
775
950
c+x
-
c-y
850
850
450
450
c+y
450
450
850
850
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
50
www.hilti.co.uk
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Page:
Project:
Fastening Point:
Date:
6
Single Beam Force
18/12/2015
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan