35/11kV
COPPER XLPE 1C
HEAVY DUTY

APPLICATION

STANDARD

AS/NZS 1429.1:2000

Primary supply to urban networks. Suitable unenclosed where


not subject to mechanical damage, buried direct or in underground
ducts.

VOLTAGE

6350/11000V

CONDUCTOR

Compacted Annealed Copper

Suitable for glanding.

INSULATION

TR-XLPE

Heavy duty screen-A minimum screen fault current rating of


13.1KA for 1 second but not exceeding the conductor rating.

SCREEN

Annealed Copper Wire


Heavy Duty

SHEATH

PVC, 5V-90 or
PVC, 5V-90 / HDPE
90 C

MAX. OPERATING TEMP.

Conductor

Overall Diameter

Approximate
Mass

mm2

No of
strands

Minimum
mm

Maximum
mm

kg/km

16
25
35
50
70
95
120
150
185
240
300
400
500
630*

7
7
7
19
19
19
19
19
37
37
37
59
60
92

19.7
21.0
22.4
23.5
26.0
28.3
30.0
30.7
32.6
35.0
37.6
40.5
43.8
49.9

23.0
24.2
25.6
26.7
29.2
31.6
33.3
34.0
35.9
38.3
40.9
43.9
47.1
53.7

580
770
970
1240
1660
2140
2410
2670
3060
3660
4330
5150
6170
7740

*Conductor is circular uncompacted.


Lengths and packing can be supplied to customers requirements.
For glanding details, contact your local service centre.
NB: Stranding in compacted conductors may be subject to minor variations.

4.2.11.6.1.3.3

Bending Radius
Minimum
Minimum
Installed
During
Installation
mm
mm
PVC
HDPE
PVC
HDPE
280
300
310
330
360
380
400
410
440
460
500
530
570
650

350
370
390
410
440
480
500
510
540
580
620
660
710
810

420
440
470
490
530
570
600
620
650
690
740
800
850
970

580
610
640
670
730
790
840
850
900
960
1030
1100
1180
1350

CONDUCTOR
Nominal Area

CURRENT RATING (a)


Unenclosed Buried Direct
Buried In
In Air
Ducts (c)

Max. DC
Resistance
@ 20C

ELECTRICAL CHARACTERISTICS
Max. AC
Equivalent Star
Star
Resistance
Reactance
Capacitance
@ 90C
(trefoil group)
(trefoil group)

3 Phase
Voltage
Drop

ohm/km
mm
16
25
35
50
70
95
120
150
185
240
300
400
500
630

A
110
140
170
210
260
310
355
400
455
530
605
700
790
910

A
115
150
180
215
255
300
340
380
425
485
540
615
680
755

A
110
140
170
200
235
275
305
335
370
415
455
510
555
620

ELECTRICAL CHARACTERISTICS (CONT.)


1 Sec Fault Rating(b)
Maximum
Stress
3 Phase
Screen
Symmetrical
kV/mm
kA
kA
2.3
2.3
2.4
3.6
3.8
2.2
5.0
5.1
2.1
7.2
7.3
2.0
10.0
10.1
1.9
13.6
13.1
1.9
17.2
13.1
1.8
21.5
13.1
1.8
26.5
13.1
1.7
34.3
13.1
1.7
42.9
13.1
1.6
57.2
13.1
1.6
71.5
13.1
1.6
90.1
13.1
1.6

Nominal Area

Nominal
Diameter

mm2
16
25
35
50
70
95
120
150
185
240
300
400
500
630

mm
4.9
6.1
7.0
8.1
9.8
11.4
12.9
14.3
16.0
18.4
20.8
23.5
26.6
32.7

CONDUCTOR
Min.Average
Insulation
Thickness
mm
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

ohm/km
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.02833

1.47
0.927
0.668
0.494
0.342
0.247
0.196
0.159
0.128
0.0981
0.0791
0.0633
0.0510
0.0417

ohm/km
0.151
0.141
0.132
0.126
0.119
0.112
0.108
0.106
0.103
0.0987
0.0959
0.0928
0.0897
0.0867

F/km
0.18
0.20
0.22
0.26
0.30
0.33
0.36
0.39
0.43
0.48
0.52
0.58
0.65
0.73

(a)- Based on 40C ambient air temperature and where applicable,


burial depth of 0.8m, soil temperature of 25C and thermal resistivity
of 1.2Cm/W.
(b)- For fault durations other than one second, divide the appropriate
given value by the square root of the required time (in seconds).
(c)- Based on a duct size of 100mm internal diameter.
(d)- Trefoil groups are bonded at both ends.
Screen fault ratings are based on an initial temperature of 80C
and a final temperature of 250C.
Conductor fault ratings are based on an initial temperature
of 90C and a final temperature of 250C.

Diameter over
Insulation Screen
Minimum
Maximum
mm
mm
14.2
17.1
15.5
18.4
16.3
19.2
17.4
20.3
19.1
22.0
20.7
23.6
22.3
25.2
23.7
26.6
25.3
28.2
27.7
30.6
30.2
33.1
32.9
35.8
35.9
38.8
41.8
45.1

SCREEN
Number &
Nominal
Diameter
Area
of Wires
per Core
mm2
27 x 0.85
16.0
43 x 0.85
25.0
34 x 1.13
35.0
48 x 1.13
50.0
37 x 1.53
68.0
32 x 1.89
89.8
32 x 1.89
89.8
48 x 1.53
88.2
48 x 1.53
88.2
48 x 1.53
88.2
48 x 1.53
88.2
48 x 1.53
88.2
48 x 1.53
88.2
48 x 1.53
88.2

4.2.11.6.1.3.3

General Cable Australia Pty Ltd


Sales:
1300 363 282
Fax:
1300 363 382
www.generalcable.com.au

mV/A.m
2.56
1.62
1.18
0.88
0.63
0.47
0.39
0.33
0.29
0.24
0.22
0.20
0.18
0.17

Diagrams of cables are illustrative only and are not necessarily to scale.
General Cable New Zealand Limited and General Cable Australia Pty Ltd reserves the
right to change or vary the construction of any of their products without notice. Whilst
every care has been taken in the preparation of this publication, General Cable New
Zealand Limited and General Cable Australia Pty Ltd accept no liability of any kind and
are not responsible for the results of any actions taken on the basis of this information or
resulting from errors or omissions. This technical data sheet is intended as a guide only;
any person using it must make reference to the appropriate local standards or authorities.
All rights reserved. No part of this work covered by copyright may be reproduced or
copied in any form or by any means without the written permission of General Cable
New Zealand Limited. or General Cable Australia Pty Ltd.
2001.