PROCEDURE
HEPA filter
HEPA filter
Figure 1
- During the measurement in case of found particle which size is over 0.3 micro meters, stop
measurement and confirm the counting of particle.
- In case of no increase counting, it is understood as stuck particle and continues sampling.
Device
Manufacturer
Model
Origin
Serial
number
Anemometer
PROVA
Instrument
AVM-03
Taiwan
9300447
Particle
counter
KANOMAX
3887A
Japan
23713
5 x 10-4
5 x 10-5
5 x 10-6
5 x 10-7
5 x 10-8
K factor
10
10
30
100
300
Upper limit
Observed
Upper limit
Ca
Np
Ca
Np
3.7
13.1
When N p is
larger than 19.7
5.6
14.4
C a = N p - 2N p
7.2
15.8
8.8
17.1
10.2
10
18.4
11.7
11
19.7
Filter
S/N
Dimension
Location
Challenging
particles
concentration
(particles/cm3)
Resisdence time, s
Testing criteria
Scanning Scanning Stationary
rate, cm/s limit,
limit,
counts
counts
AHU No.
Room
Note:
TEST RESULTS
Filter material scanning
No.