Wet Venting
Incorporating Stack Venting and
NPC Harmonization
Presented by:
Rainier Bratsch-Blundel, CPSI
Plumbing Professor George Brown College
OPIA Education and Training
(d)
2
1
(b)
1
1
3
(c)
2 C/O
(e)
1
1
2 1
1
3
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
Wet Venting
Any fixture can be wet vented.
Any fixture other than a Water Closet (W.C.) can
do the wet venting
Symphonic fixtures can do the Wet Venting
Only fixtures with 2-inch trap arms and fixture
drains can connect into the wet vent above a
W.C. (there is a 3-inch floor drain exception).
The lowest connecting fixture is NOT included in
the sizing of the wet vent.
Rainier Blundel / Bryan Heyl
George Brown College
Wet Venting
Wet Venting
7.5.2.1 Wet Venting
(1) A soil or waste pipe may serve as a wet vent provided
that,
(a) the hydraulic load is in accordance with Table 7.5.8.1.
7.5.8.1. Hydraulic Loads Draining to Wet Vents
(1) The hydraulic load that drains to a wet vent shall
conform to Table 7.5.8.1.
(2) When determining the size of a wet vent, the hydraulic
load from the most downstream fixture or symmetrically
connected fixtures shall not be included.
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
No Water Closets
2 F.U.
2
2
4 F.U.
3 F.U.
F.U.
3
3
3
12 F.U.
8 F.U.
F.U.
8
4
4
36 F.U.
14 F.U.
F.U.
14
5
5
18 F.U.
F.U.
18
6
6
23 F.U.
F.U.
23
Column 1
Column 2
Column 3
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
No Water Closets
2 F.U.
4 F.U.
3 F.U.
3
3
12 F.U.
F.U.
88 F.U.
36 F.U.
14 F.U.
18 F.U.
23 F.U.
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
Continuous Vent
7 metres
11 F.U.
1 pipe
Basin
Tank
W.C.
1 F.U.
Kitchen
Sink
1.5 F.U.
Bath
tub
1.5 F.U.
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
9 (i)
7.5.8.3.
(5) For the purposes of Table 7.5.8.3., the length of a
continuous vent shall be its developed length from the
vertical soil or waste pipe connection to a vent stack, stack
vent, header or open air.
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
9 (ii)
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
9 (iii)
Continuous Vent
3 metres
Fixture Units = 12
Size = 1 Pipe
basin
basin
Wet vent
5 F.U. (8 max.)
Size = 3 pipe
Branch
Fixture Units = 12
Size = 3
Bath
Tub
Bath
Tub
Tank
W.C.
Tank
W.C.
Rainier Blundel
George Brown College
10 (i)
Rainier Blundel
George Brown College
10 (ii)
Rainier Blundel
George Brown College
10 (iii)
Continuous vent
6 F.U. (BG)
10 metres
1 Pipe
Basin
1 F.U.
2 Pipe
Bath
tub
1.5 F.U.
Tank
W.C.
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
11 (i)
Continuous vent
6 F.U. (BG)
10 metres
1 Pipe
Basin
1 F.U.
2 Pipe
Bath
tub
1.5 F.U.
Tank
W.C.
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
11 (ii)
Continuous Vent
5 metres
5 F.U.
1 pipe
Note:
A-Table 7.4.9.3. Hydraulic Loads.
Hydraulic Loads for Floor Drains.
No hydraulic load is
required from a floor
drain in a washroom
since it is for
emergency use only.
Basin
1 F.U.
3
Floor Drain
3 F.U.
No load
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
12
No Water Closets
2 F.U.
4 F.U.
3 F.U.
12 F.U.
8 F.U.
36 F.U.
14 F.U.
18 F.U.
23 F.U.
Column 1
Column 2
Column 3
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
13
No Water Closets
11
22 F.U.
F.U.
4 F.U.
3 F.U.
12 F.U.
8 F.U.
36 F.U.
14 F.U.
18 F.U.
23 F.U.
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
14
1
(1.5 F.U)
1
Continuous
Vent
1
Wet Vent
2 F.U. max.
F.D.
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
4
15 (i)
1
(1.5 F.U)
1 Hydraulic Loads.
A-Table 7.4.9.3.
Continuous
Hydraulic Loads
Vent for Laundry Traps.
When determining the hydraulic load
on a pipe, no allowance need be made
for a load from a domestic clothes
washer when discharged
into a
1
laundry tray, since
the hydraulic
Wet Vent
F.D. load
from the laundry
is sufficient.
2 F.U.tray
max.
2
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
4
15 (ii)
2 wet vent
No water closet installed
No Water Closets
2 F.U.
2
2
44 F.U.
F.U.
3 F.U.
12 F.U.
8 F.U.
36 F.U.
14 F.U.
18 F.U.
23 F.U.
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
16
1 1 4"
1 1/2"
SANITARY
TEE (TY)
2" Wet
Vent
(4 F.U. max.)
2"
757R06B5
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
17
branch
bathroom group
7.5 fixture units
3 inch pipe
Bath
tub
Continuous vent
Continuous
waste
and vent
Lav
Wet Vent
4 fixture units
3 inch pipe
fixture drain
1.5 fixture units
1 1/2 inch pipe
kitchen
sink
Tank
W.C.
Wet Vented
Branch
separately vented
fixture drain
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
18
Continuous
vent
Lav
Wet Vent
6.5 F.U.
3 inch pipe
Bath
tub
Continuous
waste and
vent
fixture drain
1.5 F.U.
1 pipe
Kitchen
Sink
Wet Vent
branch
10.5 F.U.
3 inch pipe
Tank
W.C.
separately vented
fixture drain
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
19
Bath
tub
Continuous Vent
7.6 metres
6 fixture units
1 1/2 inch pipe
Lav
Wet Vent
(fixture drain)
4 fixture units
3 inch pipe
branch
bathroom group
7.5 fixture units
3 inch pipe
Continuous
waste
and vent
fixture drain
1.5 fixture units
1 1/2 inch pipe
kitchen
sink
Wet Vent
(branch)
Tank
W.C.
separately vented
fixture drain
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
20
kitchen
sink
kitchen
sink
kitchen
sink
Stack Vent
Fixture Units = 15.5
Length = 8 metres
Stack Base = 3 Pipe
Size = 1 Pipe
Lav
Lav
Wet Vent
(Waste Stack)
Fixture Units = 7.5
Tank
W.C.
Lav
Size = 3 pipe
Tank
W.C.
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
21 (i)
kitchen
sink
Stack Vent
Fixture Units = 15.5
Length = 8 metres
Stack Base = 3 Pipe
Size = 1 Pipe
Lav
Lav
Wet Vent
(Waste Stack)
Fixture Units = 7.5
Tank
W.C.
Lav
Size = 3 pipe
Tank
W.C.
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
21 (ii)
drinking
fountain
Stack Vent
Wet Vent
(waste stack)
Tank
W.C.
Lav
kitchen
sink
bathtub
Note:
the definition of Offset means the
piping that connects the ends of
two pipes that are parallel
nominally
horizontal
offset
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
22
Stack Vent
Lav
nominally
horizontal
offset
(maximum length
1.2 metres for 2 inch
or less pipe)
branch
2.5 fixture units
1 1/2 inch pipe
kitchen
sink
Wet Vent
(waste stack)
1 Fixture Units
1 Pipe
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
23
Lav
Lav
Wet Vent
(waste stack)
6 fixture units
3 inch pipe
Lav
Lav
Lav
kitchen
sink
Branch
9 fixture units
3 inch pipe
Lav
kitchen
sink
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
24
Tank
W.C.
Continuous
vent
Bath
tub
Not
Restricted
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
Lav
25
Stack
Vent
Stack
Vent
Wet
Vent
Same size
as
Wet Vent
over 4
storeys
high
Note:
To size the Stack Vent
use Table 7.5.8.4.
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
26
(d)
2
1
(b)
1
1
3
(c)
2 C/O
(e)
1
1
2 1
1
3
Rainier Bratsch-Blundel / Bryan Heyl George Brown College Ontario Plumbing Inspectors Association
27
Wet Venting
QUESTIONS?
www.opia.info/members/
rblundel@georgebrown.ca
Code and Guide for Plumbing
2006 Professional Edition
available at www.orderline.com
28
ONTARIO PLUMBING
INSPECTORS ASSOCIATION INC.
In the public service since 1920
Wet Venting
Incorporating Stack Venting and
NPC Harmonization
Presented by:
Rainier Bratsch-Blundel, CPSI
Plumbing Professor George Brown College
OPIA Education and Training