Académique Documents
Professionnel Documents
Culture Documents
19.5
36.0
52.0
65.0
83.0
98.0
7
8
118.0
recirculate inside the building during start-up so the chillers can come on line with
out low condensing pressure and low oil pressure problems. The system diagram
developed
for
the project depicts all of this information schematically.
Because of all of the common piping, there will be significant flow variation in the
system
depending on the pump combination selected. The fact that the two pumps that are
in
parallel are different with different pump curves complicates this a little bit. The
system will spend a significant number of hours running with only one pump.
Originally the system was to be provided flow control valves on each chiller to ensure
that the flow rates were constant regardless of operating conditions. Balance valves
were
inadvertantly installed instead. The purpose of this test is to determin if the flow
variations that occur in the system with out the flow control valves are a problem,
anda advantage,
or
non-issue. They will be a problem if:
1.
The pumps run out their curves far enough that they trip overloads
2.
3.
The tube velocities in the chiller tubes are driven high enough to make
errosion a concern.
4.
The pump energy used when the pump runs out its curve exceeds the chiller
energy saved via lower condensing pressures.
The test will also provide data on the capabilities of individual pumps serving both
condensers
condensers and
and the
the condenser
condenser of
of the
the chiller
chiller they
they are
are not
not normally
normally associated
associated with.
with.
Instructions:
Initial each step if the item is completed satisfactorily or the test item associated
with
the step met the test requirements and passed. If the item is not satisfactory or
the test
step
fails, record an "F" in the appropriate box instead of your initials. Document
the
reason for failing in the comments section as a numbered note and include the note
number
next to the F on the test form. If the test step has data associated with it,
document
it on the test form in addition to your initials and the date and time.
File name = 302339817.xls, Page 2 of 12 of Sheet Condenser Flow Test Printed on 01/29/2016 at 15:22:28
2
An Amprobe (desirable but not manditory)
Acceptance Criteria:
See the problems listed in 1-4 above. The test is passed if none of these problems
are
noted and the chiller/pump combination uses no more energy in all of the possible
operating modes, relative to the design condition. It make take some discussion with
the
chiller manufacturer subsequent to the test to determine if tube velocities are
satisfactory and what the chiller kW per ton will be at the different flow rates.
Precations:
1.
2.
Verify that all components between the pump discharge and the discharge
service
valve
are
rated
for the peak pressure on the pump curve with the largest impeller
size
installed prior to performing a shut off test.
3.
Avoid sudden flow changes to minimize the potential for water hammer.
4.
Exercise proper precaution while working around live wiring and terminals to
take
amp readings.
5.
Exercise proper precaution while working around the rotating parts of the
pump.
References:
1.
2.
The system diagram developed by CH2MHill and PECI
Requirement
Data
Completed
Include units
Initials, Date
and Time
Prerequisites:
1.
2.
3.
File name = 302339817.xls, Page 3 of 12 of Sheet Condenser Flow Test Printed on 01/29/2016 at 15:22:28
2.
3.
4.
5.
CWP-2
Make
Model
Serial Number
Flow
Head
Impeller Size
Motor Make
Motor Model
Motor HP
Motor Speed
Volts
Amps
Hz
Phase
Efficiency
Serial Number
Service Factor
Other
Other
Procedure:
File name = 302339817.xls, Page 4 of 12 of Sheet Condenser Flow Test Printed on 01/29/2016 at 15:22:28
2.
3.
4.
5.
File name = 302339817.xls, Page 5 of 12 of Sheet Condenser Flow Test Printed on 01/29/2016 at 15:22:28
7.
8.
lot)
Estimated flow over CT-4 (none, some, a
lot)bypass valve
Close the
9.
File name = 302339817.xls, Page 6 of 12 of Sheet Condenser Flow Test Printed on 01/29/2016 at 15:22:28
11.
12.
13.
lot)
Estimated flow over CT-4 (none, some, a
lot)bypass valve
Close the
Valve in the CH-1 condenser and valve out the CH2
condenser. Document the following.
CWP-2 suction pressure
CWP-2 discharge pressure
CWP-2 amps (all phases)
CH-1 condenser entering pressure
CH-1 condenser leaving pressure
14.
File name = 302339817.xls, Page 7 of 12 of Sheet Condenser Flow Test Printed on 01/29/2016 at 15:22:28
16.
17.
2.
3.
4.
File name = 302339817.xls, Page 8 of 12 of Sheet Condenser Flow Test Printed on 01/29/2016 at 15:22:28
6.
7.
8.
9.
File name = 302339817.xls, Page 9 of 12 of Sheet Condenser Flow Test Printed on 01/29/2016 at 15:22:28
11.
Test Coordinator(s)
Name
Affiliation
Affiliation
File name = 302339817.xls, Page 10 of 12 of Sheet Condenser Flow Test Printed on 01/29/2016 at 15:22:28
File name = 302339817.xls, Page 11 of 12 of Sheet Condenser Flow Test Printed on 01/29/2016 at 15:22:28
File name = 302339817.xls, Page 12 of 12 of Sheet Condenser Flow Test Printed on 01/29/2016 at 15:22:28