Honeywell Genetron 407C

Properties, Uses, Storage, and Handling

Honeywell Genetron 407C


Properties, Uses, Storage, and Handling
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Skin and Eye Contact . . . . . . . . . . . . . . . . . . . . . . . . .6

Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Unitary Air Conditioning . . . . . . . . . . . . . . . . . . . . . . .3

Flammability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Chillers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Combustibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Commercial Refrigeration . . . . . . . . . . . . . . . . . . . . . .3

Thermal Stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Physical Properties . . . . . . . . . . . . . . . . . . . . . . . . . .3

Packaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

Storage and Handling . . . . . . . . . . . . . . . . . . . . . . . .6

Servicing Considerations . . . . . . . . . . . . . . . . . . . . .4

Bulk and Cylinder . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Pressure vs. Temperature


(English Units & SI Units) . . . . . . . . . . . . . . . . . . . . .4

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Leak Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

Materials Compatibility . . . . . . . . . . . . . . . . . . . . . . .4
Types of Leak Detectors . . . . . . . . . . . . . . . . . . . . . . .8
Compatibility with Metals . . . . . . . . . . . . . . . . . . . . . . .4
Retrofitting Existing Systems . . . . . . . . . . . . . . . . . .8
Chlorinated Materials and Refrigerants . . . . . . . . . . . .5
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Desiccants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Retrofit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Compatibility with Plastics and Elastomers . . . . . . . . .5
Retrofitting Procedures . . . . . . . . . . . . . . . . . . . 810
Lubricants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Retrofit Checklist For Genetron 407C . . . . . . . . .10
Miscibility of Genetron 407C with two
commercially available lubricants . . . . . . . . . . . . . .5

Summary of Materials Compatibility: Plastics and


Elastomers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Recycling and Reclamation . . . . . . . . . . . . . . . . . .11


Environmental Considerations . . . . . . . . . . . . . . . .11
Available Literature/Technical Assistance. . . . . . .11

Safety & Toxicity . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6


Thermodynamic Tables
Toxicity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
(English Units & SI Units) . . . . . . . . . . . . . . . . .1215
Inhalation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Genetron 407C

Introduction
Honeywells Genetron 407C (a ternary blend of HFC-32/HFC125/HFC-134a, assigned R-407C by ASHRAE) serves as a nonozone-depleting replacement for HCFC-22 in various air-conditioning applications, as well as in most refrigeration systems.

Physical Properties
Chemical Name
Molecular Formula
Appearance
Molecular Weight
Bubble Point Temperature

Since Genetron 407C is a close match to HCFC-22, it also


serves as a retrofit fluid in applications where HCFC-22 is gener-

Dew Point Temperature

ally used.
Bubble Point Pressure

Applications
Dew Point Pressure

Unitary Air Conditioning


Genetron 407C can serve as a non-ozone-depleting replace-

Critical Temperature**

ment for HCFC-22 in residential and light commercial air-conditioning systems. It has a capacity comparable to HCFC-22 making it easier to use in existing equipment designs. Some equip-

Critical Pressure**
Critical Volume**

Difluoromethane/Pentafluoroethane/
Tetrafluoroethane
CH2F2/CHF2CF3/CH2FCF3
Colorless
86.2
@ 1 ATM
-46.5F
@ 101.3 kPa
-43.6C
@ 1 ATM
-33.9F
@ 101.3 kPa
-36.6C
172.6 (Psia)
1190 (kPa)
147.9 (Psia)
1020 (kPa)
186.86F
86.034C
671.49 (Psia)
4629.8 (kPa)
0.0331 (ft3/lb)

ment modifications will be required when retrofitting these systems to Genetron 407C.

Critical Density**

Chillers

Vapor Density

Genetron 407C can serve as a replacement for HCFC-22 in positive displacement chillers without flooded heat-exchangers.

@ 1 ATM
@101.3 kPa

Liquid Density

Because Genetron 407C is a blend with a temperature glide, it


is not recommended for use in chillers with a flooded evaporator.
Commercial Refrigeration
Genetron 407C may be used to replace HCFC-22 in existing

Liquid Heat Capacity at constant pressure


Vapor Heat Capacity at constant pressure

medium-temperature commercial refrigeration systems, including


supermarket display cases and reach-in coolers.

Heat of Vaporization
@ 1 ATM
at boiling point
@101.3 kPa
Liquid Thermal Conductivity
Vapor Thermal Conductivity
Liquid Viscosity
Vapor Viscosity
Flammability Limits in Air (vol%)
Ozone Depletion Potential (ODP)
ASHRAE Safety Group Classification
* Based on ASHRAE Standard 34 with match ignition.
** Based on NIST Refprop 7.
All data are at 77F (25C) unless otherwise noted.

Genetron 407C

0.0021 (m3/kg)
30.23 (lb/ft3)
484.23 (kg/m3)
0.289 (lb/ft3)
4.630 (kg/m3)
71.01 (lb/ft3)
1137 (kg/m3)
0.37 (Btu/lb F)
1.54 (KJ/kg K)
0.20 (Btu/lb F)
0.837 (KJ/kg K)
107.16 (Btu/lb)
249.08 (KJ/kg)
0.0472 (Btu/hr ft F)
81.7 (mW/mK)
0.0083 (Btu/hr ft F)
14.3 (mW/m K)
0.3281 (lbm/ft hr)
135.58 (Pa sec)
0.0310 (lbm/ft hr)
12.82 a (Pa sec)
None *
0.00
A1

Specifications
Assay (Min. Wt. % of HFC-32/125/134a):
Moisture (Max. Wt. %):
High-boiling Residue (Max. Vol. %):
Chloride (Max. Wt. %):
Total Acidity (Max. Wt. %):
Non-condensibles in vapor phase (Max. Vol. %):

Pressure vs. Temperature


99.7%
0.0010
0.01
0.0001
0.0001
1.5

Servicing Considerations
Genetron 407C is a ternary blend of HFC-32/HFC-125/HFC134a. This product can generally be used to successfully retrofit
existing HCFC-22 systems.
Unlike pure fluids and azeotropes, blends boil and condense at
varying temperatures for a given pressure. The range over which
the temperature varies is referred to as temperature glide.
Genetron 407C has moderately high temperature glides
between about 9F and 13F, depending upon pressure.
When dealing with blends, pressure-temperature tables are presented in an unconventional manner. Two pressures are listed for
each temperature: the dew pressure and the bubble pressure.
The dew pressure is used for determining the system pressure
when the refrigerant is in a saturated vapor or superheated condition (i.e., on the suction and discharge sides of the compressor). The bubble pressure is used for determining the system
pressure when the refrigerant is in a saturated liquid or subcooled
condition (i.e., at the inlet to the expansion valve or capillary
tube).
Genetron 407C must be the only liquid charged into a system to
ensure proper refrigerant composition and system performance.
(See Retrofit Procedures for more information.)
If a significant leak develops in a system containing Genetron
407C and a noticeable change in system performance occurs,
recover the remaining charge and re-charge the system to
ensure that the proper composition is in the system.

Materials Compatibility
Compatibility with Metals
Genetron 407C is compatible with copper, steel and aluminum
as determined using the ASHRAE 97 sealed tube method. The
method comprised sealing the refrigerant and metals into glass
tubes, which were put in an oven at 200C for one week. After one
week, there were no visual changes in the contents of the tubes.
The amount of fluoride generated in the tubes was barely above
the background level. The conclusion of the study is that
Genetron 407C is stable in the presence of metals over the normal operating temperature range.

Temp.
(F )
-40
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
140
145
150

Temp.
(C )
-40.0
-37.2
-34.4
-31.7
-28.9
-26.1
-23.3
-20.6
-17.8
-15.0
-12.2
-9.4
-6.7
-3.9
-1.1
1.7
4.4
7.2
10.0
12.8
15.6
18.3
21.1
23.9
26.7
29.4
32.2
35.0
37.8
40.6
43.3
46.1
48.9
51.7
54.4
57.2
60.0
62.8

Bubble
Pressure
( psig )
2.7
5.1
7.7
10.6
13.7
17.2
20.9
25
29.5
34.3
39.5
45.2
51.2
57.7
64.7
72.2
80.2
88.8
97.9
107.6
117.9
128.9
140.5
152.8
165.8
179.6
194.1
209.4
225.5
242.4
260.3
279
298.6
319.2
340.7
363.3
387
411.7

65.6

437.5

Dew
Pressure
( psig )
4.6 *
0.9 *
1.6
3.9
6.5
9.3
12.3
15.7
19.4
23.5
27.9
32.7
37.9
43.5
49.6
56.1
63.2
70.7
78.8
87.5
96.8
106.7
117.3
128.5
140.5
153.2
166.7
181
196.1
212.1
229
246.9
265.8
285.7
306.6
328.8
352.1
376.6
402.5

Bubble
Temp. Pressure
(C ) bar-gauge
-40
0.2
-38
0.3
-36
0.4
-34
0.6
-32
0.7
-30
0.9
-28
1.0
-26
1.2
-24
1.4
-22
1.6
-20
1.8
-18
2.0
-16
2.2
-14
2.5
-12
2.8
-10
3.0
-8
3.3
-6
3.6
-4
4.0
-2
4.3
0
4.7
2
5.0
4
5.4
6
5.9
8
6.3
10
6.7
12
7.2
14
7.7
16
8.2
18
8.8
20
9.4
22
10.0
24
10.6
26
11.2
28
11.9
30
12.6
32
13.3
34
14.0
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68

Dew
Pressure
bar-gauge
-0.2
-0.1
0.0
0.1
0.2
0.4
0.5
0.6
0.8
1.0
1.1
1.3
1.5
1.7
1.9
2.2
2.4
2.7
3.0
3.3
3.6
3.9
4.3
4.6
5.0
5.4
5.9
6.3
6.8
7.3
7.8
8.3
8.9
9.5
10.1
10.7
11.4
12.1

14.8
15.6
16.5
17.3
18.2
19.2
20.1
21.1
22.2
23.2
24.4
25.5
26.7
27.9
29.2
30.5
31.8

Genetron 407C

12.8
13.6
14.4
15.2
16.1
17.0
17.9
18.9
19.9
20.9
22.0
23.1
24.3
25.5
26.7
28.0
29.4

Chlorinated Materials and Refrigerants


Honeywell does not recommend the use of chlorinated solvents

Miscibility of Genetron 407C with two


commercially available lubricants

to clean refrigeration systems or components.

90%
50%
10%
Genetron 407C Genetron 407C Genetron 407C

The following are three situations in which Genetron 407C and its
associated lubricant might come into contact with chlorinated

Lubricant

materials and refrigerants:

Mobil
EAL 22

A chlorinated solvent is used to clean or flush the system


An HCFC-22 system is retrofitted with Genetron 407C
HCFC-22 or another chlorinated refrigerant is accidentally
charged into a system that contains Genetron 407C

Miscibility
Limit

10%
Polyol Ester

50%
Polyol Ester

90%
Polyol Ester

Upper

>140F
> 60C
<-14F
<-10C
>140F
> 60C
<-33F
<-36C

>140F
> 60C
<-33F
<-36C
>140F
> 60C
<-33F
<-36C

>140F
> 60C
<-33F
<-36C
>140F
> 60C
<-33F
<-36C

Lower
Castrol
SW 32

Upper
Lower

Desiccants

Castrol SW 32 exhibits miscibility over the temperature range

Several desiccant driers compatible with Genetron 407C are

studied -33F to 140F (-36C to 60C). Mobil EAL 22 exhibits

commercially available. Individual drier manufacturers should be

miscibility from 14F to 140F (-10C to 60C).

contacted for specific recommendations.


Compatibility with Plastics and Elastomers
The table to the right is a summary of materials compatibility data
resulting from tests performed by Honeywell and several worldwide industry organizations. This data should be used only as a
guide to the compatibility of materials with Genetron 407C.
When retrofitting existing systems to Genetron 407C, Honeywell
recommends that service technicians consult with original equipment manufacturers for their approved replacement parts. Since
there are many different grades and formulations of these materials, we recommend that compatibility testing be performed on
the specific grade of materials under consideration when designing new systems.
The rankings in the table to the right should be used with caution
since they are judgments based on limited samplings. Customers
should consult with the manufacturer or conduct further independent testing.
Lubricants
Honeywell recommends the use of lubricants having appropriate
miscibility with Genetron 407C, such as polyol ester lubricants.
Many are commercially available and have been approved for
use with Genetron 407C by leading compressor manufacturers.
Contact the lubricant manufacturers for their specific recommendations.
The miscibility of Genetron 407C with two different polyol ester
lubricants is shown in the table.

Summary of Materials Compatibility


For Genetron 407C Compatibility:
Plastics and Elastomers
Material
Ethylene-Propylene Diene Terpolymer
Ethylene-Propylene Copolymer
Chlorosulfonated Polyethylene
Chlorinated Polyethylene
Neoprene (Chloroprene)
Epichlorohydrin
Fluorinated Rubbers
Silicone
Polyurethane
Nitriles
H-NBR
Butyl Rubber
Polysulfide
Nylon
Polytetrafluoroethylene
PEEK
ABS
Polypropylene
Polyphenyl Sulfide
Polyethylene Terephthalate
Polysulfone
Polyimide
Polyetherimide
Polyphthalamide
Polyamideimide
Acetal
Phenolic

Genetron 407C
S
S
S
D
S
D
U
D
D
D
D
D
S
S
S
S
U
D
U
D
D
S
S
D
S
D
S

S: Suitable D: Suitability dependent on formulation U: Unsuitable

Genetron 407C

Safety & Toxicity

should never be done with a mixture of Genetron 407C and air,


oxygen or other oxidizing materials. Leak-checking can be per-

Honeywell recommends reading the MSDS before using

formed safely using a mixture of Genetron 407C and nitrogen.

Genetron 407C.

Flammability
Toxicity

According to ASHRAE Standard 34, Genetron 407C is classified

Genetron 407C can be safely used in all of its intended applica-

in safety group A1, i.e., it is non-flammable at 1 atmosphere pres-

tions when handled in accordance with the Material Safety Data

sure (101.3 kPa) and 64F (18C). As defined by the U.S.

Sheet (MSDS). This is based on data developed by the Program

Department of Transportation (DOT) regulations, flash-point

for Alternative Fluorocarbon Toxicity Testing (PAFTs I, III, and V),

determinations do not apply to Genetron 407C. It has no flame

an international consortium of which Honeywell is a charter mem-

limits, and DOT considers it non-flammable (Green Label).

ber. This conclusion was reached after review of all toxicity


results, which confirmed the intrinsically low toxicity of the sub-

Since Genetron 407C does not have a flash point and is non-

stance. Honeywell recommends reading the MSDS before using

flammable, Honeywell believes that standard industrial-type elec-

Genetron 407C.

trical installations may be used. It is essential to review and com-

ply with all local building codes and other applicable regulations
Inhalation

and laws when using Genetron 407C or any other similar prod-

Honeywell has established a PEL (permissible exposure limit) for

uct.

an eight-hour day, 40-hour work-week of 1000 ppm for Genetron


407C. Inhalation of the products vapor may cause irritation.

Combustibility

Vapor inhalation at high concentrations may result in asphyxiation

There is the potential for combustibility when Genetron 407C is

or the heart may become sensitized, causing cardiac arrhythmia.

mixed with air. Because of this combustibility potential at pres-

Because of possible disturbances of cardiac rhythm, cate-

sures above atmospheric, Genetron 407C and air should never

cholamine drugs, such as epinephrine, should be used with spe-

be mixed in tanks or supply lines, or allowed to accumulate in

cial caution and only in situations of emergency life support.

storage tanks. Leak-checking should never be done with a mix-

Treatment of overexposure to Genetron 407C should be directed

ture of Genetron 407C and air. Leak-checking can be performed

at the control of symptoms.

safely with a mixture of Genetron 407C and nitrogen.

When concentrations of Genetron 407C reach levels which

Thermal Stability

reduce oxygen to 1416% by displacement, symptoms of

It is important to avoid exposing Genetron 407C to very high

asphyxiation will occur. An individual exposed to high concentra-

temperatures. When exposed to high temperatures, such as

tions of Genetron 407C must be given medical attention immedi-

those found in flames, Genetron 407C vapors will decompose.

ately. Adequate ventilation must be provided at all times.

This may produce toxic and irritating compounds. Pungent odors

released will irritate the nose and throat and generally force evacSkin and Eye Contact

uation of the area.

Genetron 407C vapors can irritate the skin and eyes. In liquid
form, it can freeze skin or eyes on contact. If skin contact should

Genetron 407C is stable under normal operating conditions.

occur, flush the exposed area with lukewarm water until all of the

Contact with certain red-hot metals may result in exothermic or

chemical is removed. If there is evidence of frostbite, soak in luke-

explosive reactions and yield toxic and/or corrosive decomposi-

warm water. Should eye contact occur, immediately flush with

tion products. Specific materials to avoid include abraded alu-

large amounts of lukewarm water for at least 15 minutes, lifting

minum surfaces and active metals such as sodium, potassium,

eyelids occasionally to facilitate irrigation. Seek medical attention

calcium, powdered aluminum, magnesium and zinc.

as soon as possible.
Leaks
If a large release of Genetron 407C vapor occurs, the area
should be evacuated immediately. Protected personnel should
de-energize or remove any ignition sources and address the leak,
if without risk. Vapors may concentrate near the floor, displacing
available oxygen. Once the area is evacuated, it must be ventilat-

Packaging
Genetron 407C is available in a variety of containers. They
include 25-lb disposable Jugs, 115-lb returnable cylinders and
one ton (1,600 lbs.) returnable tanks. In addition, bulk shipments
can be made in tank trailers and isotanks.

Storage and Handling

ed using blowers or fans to circulate the air at floor-level.


Unprotected personnel should not return to the area until the air

Bulk and Cylinder

has been tested and determined to be safe. Leak-checking

Some special handling and storage procedures are required for

Genetron 407C

Genetron 407C to minimize or prevent liquid compositional

Maintenance

changes, particularly those occurring during liquid level deple-

A thorough pre-job review must be done to determine respiratory

tion or vapor leaks from the storage container. Because these

protection requirements, as well as any other safety equipment

procedures and/or systems are sometimes site specific, contact

needed. Maintenance in areas where Genetron 407C has accu-

a Honeywell Technical Service Representative to discuss each

mulated should be performed only after confirming that work area

application.

concentrations are below the permissible exposure level (PEL).


This may be determined using a vapor-in-air analyzer capable of

Among the most important handling practices that must be followed for Genetron 407C is to ensure that all transfers be executed by using liquid flow instead of vapor flow. This practice will
help minimize compositional changes in the liquid phase and, as
a result, provide a more consistent product.

measuring the amount of airborne Genetron 407C. These vapors


are heavier than air and can accumulate at floor level. When
vapor concentrations are above the PEL, the area should be ventilated to reduce the vapor concentration to below the PEL before
entry. Ventilate the area using fans and other air movers as nec-

Genetron 407C cylinders must be clearly marked and kept in a

essary. If entry must be made to areas where vapor concentra-

cool, dry and properly ventilated storage area away from heat,

tions are above the PEL, appropriate respiratory protection

flames, corrosive chemicals, fumes, explosives -- and be other-

should be used.

wise protected from damage. Under no circumstances should


anything be put into an empty cylinder. Once empty, properly
close the cylinder valve and replace the valve cap. Return empty
cylinders to your Genetron Wholesaler.

Federal occupational health and safety agencies often have legal


requirements and guidelines for proper selection and use of respiratory protection. It is often the responsibility of the employer to
ensure the safety of the employees performing the maintenance.

Disposable Jugs should be discarded in an environmentally

Be sure to comply with applicable laws and guidelines for prop-

safe manner in accordance with all laws and regulations.

er selection and use of respiratory protection. If the airborne concentration of refrigerant is unknown or at a particular threshold,

Cylinders of Genetron 407C should be kept out of direct sun-

the law may require the use of supplied air respirators. Particular

407C

work team and work zone entry procedures may also apply.

expands significantly when heated, reducing the amount of vapor

Vessels, containers, transfer lines, pumps and other equipment

space left in the cylinder. Once the cylinder becomes liquid-full,

should not be exposed to high-temperature sources (such as

any further rise in temperature can cause it to burst, potentially

welding, brazing and open flames) until they have been thor-

resulting in severe personal injury. NEVER ALLOW A CYLINDER

oughly cleaned and found free of vapors. Exposure to these cir-

TO GET WARMER THAN 125F (52C).

cumstances can cause fire, explosion and decomposition of

light, especially in warm weather. Liquid Genetron

Always store cylinders above dirt or damp floors to prevent rusting, using a platform or parallel rails. SECURE CYLINDERS IN
PLACE BY MEANS OF A RACK, CHAIN OR ROPE TO PREVENT

refrigerant. This may result in the formation of toxic or corrosive


compounds. Potential sources for further vapor releases should
also be eliminated if possible.

THEM FROM TIPPING, FALLING, ROLLING OR ACCIDENTALLY

When possible, maintenance or cleaning of equipment should be

STRIKING EACH OTHER OR ANY OTHER OBJECT.

performed without entering the vessel. A tank or storage vessel

If the cylinder valve is broken off, rapid escape of the high pressure contents will propel the cylinder, which could potentially
result in serious injury. Keep cylinder caps in place until the cylinder is in use.

may be a confined space. These spaces may have a configuration that can hinder activities and/or expose personnel to the risk
of physical injury from entrapment, engulfment, or hazardous
atmospheres. Depending on conditions and applicable regulations, a permit may be required to enter such vessels. If a tank

The storage area should be away from corrosive chemicals or

must be entered, personnel should be required to use a formal

fumes to avoid damaging effects on the cylinder and threaded

tank entry procedure based on recognized safety principles and

areas of the valve.

comply with all applicable regulations. The procedure would provide guidance for critical items such as but not limited to respira-

Follow similar precautions for bulk storage and transport systems,

tory protection, safety equipment, work practice, and communi-

ensuring that proper design and operation satisfies the required

cation. Among the possible requirements of these procedures is

pressure rating and also avoids external corrosive conditions,

the use of a fully qualified work team and placement of a confined

overheating or overfilling.

space entry permit at the job site.

If a cylinder leak is detected contact Honeywell for guidance.

Genetron 407C

Leak Detection

Generation of bubbles will indicate a pinhole leak. Several minutes may be required to generate a bubble in the case of a very

Use leak detectors for pinpointing specific leaks or for monitoring

small leak. When it is suspected that essentially no refrigerant

an entire room on a continual basis. Leak detectors are important

remains in the system, the above method can be used to detect

for refrigerant conservation, equipment protection and perform-

leaking nitrogen gas. However, the most convenient and effec-

ance, reduction of emissions and protection of those coming in

tive means to detect a leak when Genetron 407C is in the system

contact with the system. Leak testing should not be performed

is to use an electronic leak detector designed for HFC refriger-

with mixtures of air and Genetron 407C. Make sure the leak

ants. When a leak is found, the refrigerant must be recovered

detector is capable of detecting Genetron 407C before using.

and the leak repaired prior to final charging and operation. For
commercial refrigeration applications, if the refrigerant charge is

Types of Leak Detectors


There are two types of leak detectors leak pinpointers and area
monitors. Before selecting either type, several equipment factors
should be considered, including detection limits, sensitivity and
selectivity.

50 pounds or more, the system is subject to leak repair requirements under the Refrigerant Recycling Regulations of Section
608 of the Clean Air Act Amendments of 1990. In this case, the
equipment owner must keep a record of the date and type of
service performed and the amount of refrigerant added.

With selectivity, there are three categories of leak detectors: nonselective, halogen selective or compound selective. In general,

Retrofitting Existing Systems

the complexity and cost of a leak detector increases as its speci-

As the industry moves away from the use of CFCs and HCFCs,

ficity increases.

refrigerant service personnel will play a key role in the transition

Fluorescent dyes approved for use by the equipment manufacturer can be added to systems to help pinpoint leaks.

to HFC alternatives through retrofitting. Honeywell has prepared


the following guidelines to help service technicians better understand the various technical and operational aspects of perform-

New installations should be checked for leaks prior to complete

ing retrofits on air conditioning or refrigeration systems using

charging. Whenever a leak inspection is performed, check all

Honeywells Genetron 407C.

factory and field joints throughout the system. For a system that
has been in operation for some time, check for oil at joints and
connections, as this may serve as an indication of a refrigerant
leak at that location. This approach would not commonly be considered when leak checking a new system installation since it is
much less likely that oil would have found its way to the leak. If a
system has lost all or most of its refrigerant charge, the system
must be pressurized to about 150 psig in order to perform a leak

Although the information can be helpful as a general guide, it


should not be used as a substitute for the equipment manufacturers specific recommendations. For this reason, Honeywell recommends contacting the equipment manufacturer for detailed
information on retrofitting the specific equipment under consideration. Always refer to the Material Safety Data Sheet (MSDS) for
safety information on the use of Genetron 407C.

check. Pressure can be restored for leak checking by adding

Applications

Genetron 407C using normal charging procedures or by using

Since Genetron 407C is a close match to HCFC-22, it also

dry nitrogen. DO NOT USE AIR TO LEAK CHECK THE SYSTEM.

serves as a retrofit fluid in many applications where HCFC-22 is

At pressures above atmospheric, mixtures of air and any HCFC

generally used, including unitary air conditioning, positive dis-

or HFC refrigerant will become combustible. For a system con-

placement chillers and commercial refrigeration.

taining a mixture of refrigerant and nitrogen, an electronic leak


detector can be used. The leak detector must be capable of

Retrofit

detecting a hydrofluorocarbon (HFC) refrigerant.

Older leak

Genetron 407C can be used successfully as a retrofit fluid but

detectors designed for R-22 (or other HCFCs) will not be sensi-

may require some system modifications such as changing the

tive enough to effectively detect HFC refrigerants. Halide torch-

lubricant. Mineral oils and alkylbenzene lubricants that have been

es cannot effectively detect HFC refrigerant leaks.

used traditionally with HCFC-22 are immiscible with Genetron


407C and must therefore be replaced with new lubricants.

NITROGEN IS A HIGH PRESSURE GAS. REMEMBER TO USE A

Consult the original equipment manufacturer for recommended

PRESSURE REGULATOR COMING OFF THE NITROGEN TANK

lubricants.

TO AVOID ANY RISK OF SEVERE PERSONAL INJURY.

Retrofit Procedures
A simple way to test for leaks is to use a solution of soap and
water. Commercial soap solutions for leak detection tend to be

1. Record Baseline Data

more effective. Apply the solution to the joints and connections.

Prior to retrofitting, it is desirable to record system performance


data to establish the normal operating conditions for the equipGenetron 407C

ment. Data should include temperature and pressure measure-

example, polyol ester, as the volume of the mineral oil drained in

ments throughout the system, including the evaporator, compres-

step 5.

sor suction and discharge, condenser and expansion device.


These measurements will be useful when adjusting the system to
Genetron 407C during the retrofit.

7. Reinstall the Compressor


Reinstall the compressor following the standard service practices
recommended by the manufacturer.

2. Isolate HCFC-22 Charge


The HCFC-22 charge should be isolated from the rest of the system by pumping it down into the condensing unit or receiver. If no
receiver is present, the refrigerant must be removed from the system using a certified recovery machine capable of meeting or
exceeding the required levels of evacuation as specified by the
U.S. EPA. The charge must be collected in a recovery cylinder.

8. Recharge the HCFC-22


If the system charge was pumped into the receiver, the balance
of the system should be evacuated and then the receiver valves
opened. If the original charge was collected in a recovery cylinder, the system should be evacuated and then recharged with the
original HCFC-22. It may be necessary to top off the refrigerant
charge to compensate for the small amount lost in draining the

3. Choose Compressor Lubricant

lubricant.

Mineral oil or alkylbenzenes are typically used as the lubricants


for HCFC-22 compressors. A miscible lubricant such as a polyol
ester is commonly used.

9. Run the Compressor


Run the compressor with the new lubricant and the HCFC-22 for
at least 5 hours for smaller systems and 24 hours for larger ones.

Honeywell recommends using a lubricant approved by the com-

Next, drain the lubricant and recharge with a new charge of lubri-

pressor manufacturer. Differences among the various lubricants

cant. Check the lubricant that was drained to see if the residual

make it difficult to assume that they are interchangeable. Check

mineral oil content is below 5%. Test kits are available from sev-

with the compressor manufacturer for the approved viscosity

eral lubricant suppliers that check for residual mineral oil content.

grade and brand of lubricant for the compressor in the system

Generally, it will require about one to three charges to get the min-

being retrofitted.

eral oil content down to the acceptable level.

4. Drain the Lubricant

10. Continue to Flush the System

Since many small hermetic compressors do not have oil drains, it

Repeat steps 8 and 9 until the residual mineral oil content is

may be necessary to remove the compressor from the system to

below 5%. The lubricant that was removed from the compressors

drain the lubricant. The suction line of the compressor is the best

in the flushing procedure must be disposed of properly.

point to drain the lubricant. Using this procedure, it is possible to


drain nearly 95 percent of the lubricant. Small hand-operated
pumps are available which permit insertion of a tube into the
compressor access port for removal of the mineral oil without
removing the compressor from the system. Remember that most
of the oil must be removed from the system before adding the
replacement lubricant.
For larger systems, the oil should be drained from multiple points
in the system. Particular attention should be paid to low spots
around the evaporator where lubricant often collects. The oil also
should be drained from oil separators and/or suction accumulators.

11. Evaluate the Expansion Device


Honeywell recommends consulting with the equipment manufacturer before retrofitting. Most HCFC-22 systems with either expansion valves or capillary tubes will operate satisfactorily with
Genetron 407C.
12. Replace the Filter Drier
Following system maintenance, a recommended service practice
is to replace the filter drier. There are two types of filter driers
commonly used in refrigeration equipment -- loose-fill and solidcore.
Contact your wholesaler to obtain a replacement filter drier com-

5. Measuring Existing Lubricant

patible with Genetron 407C.

Measure and record the volume of lubricant removed from the

13. Reconnect the System and Evacuate

system. Compare this amount with the amount recommended by

Use normal service practices to reconnect and evacuate the sys-

the manufacturer to ensure that the majority of lubricant has been

tem. To remove air and other non-condensibles, Honeywell rec-

removed. This volume also will be used as a guide to determine

ommends evacuating the system to a full vacuum of 1000

the amount of lubricant to add in the next step.

microns or less from both sides of the system. Attempting to

6. Recharge Compressor with a Miscible Lubricant


Add to the compressor the same volume of miscible lubricant, for

evacuate a system with the pump connected to only the low side
of the system will not adequately remove moisture and non-condensibles such as air. Use a good electronic gauge to measure

Genetron 407C

the vacuum. An accurate reading cannot be made with a refrig-

It may be necessary to reset the high pressure cutout to compen-

eration gauge.

sate for the higher discharge pressures of the Genetron 407C


system. This procedure should be done carefully to avoid

14. Check for System Leaks

exceeding the recommended operating limits of the compressor

Check the system for leaks using normal service practices.


15. Charge System with Genetron 407C

and other system components.


To avoid overcharging, it is best to charge the system by first

When charging the system with Genetron 407C, it is important to


remember that this product is a blend and not an azeotrope. For
this reason, special charging procedures are required to ensure

measuring the operating conditions (including discharge and


suction pressures, suction line temperature, compressor amps,
super heat) before using the liquid-level sight glass as a guide.

optimal system performance.


17. Label Components and System
It is essential when using Genetron 407C that the system be liquid-charged by removing only liquid from the cylinder. Never
charge the system with vapor from a Genetron 407C cylinder.
Vapor-charging Genetron 407C may result in the wrong refrigerant composition and could damage the system.

After retrofitting the system with Genetron 407C, label the system
components to identify the type of refrigerant (Genetron 407C)
and specify type of lubricant (by brand name) and viscosity
grade in the system. This will help ensure that the proper refrigerant and lubricant will be used to service the equipment in the

A throttling valve should be used to control the flow of refrigerant

future.

to the suction side to prevent slugs from entering the compressor.


NOTE: To prevent compressor damage, do not charge liquid into
the suction line of the unit.
Systems being charged with Genetron 407C require a smaller
charge size than those using HCFC-22. The charge typically will
be about 95 percent by weight of the original HCFC-22 charge.
Honeywell recommends initially charging the system with 85 percent by weight of the original HCFC-22 charge. For an air conditioning application, if the original HCFC-22 charge was 10
pounds, initially charge 8.5 pounds of Genetron 407C. If the
original HCFC-22 charge was 1000 grams, initially charge 850
grams of Genetron 407C.
16. Check System Operation
Start the system and let conditions stabilize. If the system is
undercharged, add additional Genetron 407C in increments of 5
percent by weight of the original HCFC-22 charge. For example,
if the original charge was 10 pounds, charge in increments of 0.5
pounds. If the original charge was 1000 grams, charge in increments of 50 grams. Continue until desired operating conditions
are achieved.
Use dew-point pressure as a reference in determining the appropriate saturated temperature for a superheat setting. To determine the saturated temperature for a subcooling calculation, use
bubble-point pressure.
Compressor suction pressures for the Genetron 407C after sta

bilization should be similar to that of normal system operating


pressure with HCFC-22 for most applications. Compressor discharge pressures typically will be higher (510%) than normal
system operation with HCFC-22.

Retrofit Checklist for Genetron 407C


1. Record baseline data on original system performance
2. Recover HCFC-22 refrigerant charge using appropriate
recovery equipment or pump down into receiver.
*Record the amount of HCFC-22 removed.
3. Choose compressor lubricant.
4. Drain at least 90 percent of the lubricant from
the compressor.
5. Measure amount of lubricant removed.
6. Recharge compressor with polyol ester lubricant.
*Use the same amount that was removed from
the existing system.
7. Reinstall compressor.
8. Recharge the original HCFC-22.
9. Run the System.
10. Repeat Flushing Procedure (steps 4-9).
11. Evaluate expansion device.
Consult equipment manufacturers first. No change is
necessary in most cases.
12. Replace filter drier with new drier approved for use
with Genetron 407C.
13. Reconnect system and evacuate.
14. Check system for leaks.
(Re-evaluate system following leak check).
15. Charge system with Genetron 407C.
ALWAYS REMOVE LIQUID ONLY FROM CYLINDER
Use correct charge size.
*Initial charge 85 percent by weight of original
HCFC-22 charge.
*Record amount of refrigerant charged.
16. Check system operation.
*Adjust charge to achieve desired operating conditions.
*If low, remove liquid only from cylinder in increments
of 5 percent of original HCFC-22 charge
17. Label components and system for type of refrigerant,
i.e. Genetron 407C and lubricant.

Genetron 407C

______
______
______
______
______
______
______
______
______
______
______
______
______

______
______
______
______
______
______
______
______
______
______
______

10

Recycling and Reclamation


The Clean Air Act Amendments of 1990 require mandatory recycling and reclamation of Genetron 407C during maintenance,
service or repair of air-conditioning and refrigeration equipment.
Your Genetron Wholesaler offers a refrigeration reclamation program for Genetron 407C.
For the name of your nearest Genetron Wholesaler, call 1-800631-8138.

Environmental Considerations
Genetron 407C is a halogenated hydrocarbon. Treatment or disposal of wastes generated by use of this product may require
special consideration, depending on the nature of the wastes and
the means of discharge, treatment or disposal. For more information, refer to the Material Safety Data Sheet (MSDS).
If discarded unused, Genetron 407C is not considered a hazardous waste by the Resource Conservation Recovery Act
(RCRA). Because Genetron 407C is considered to have minimum biodegradability, care should be taken to avoid releases to
the environment.
The disposal of Genetron 407C may be subject to federal, state
and local regulations. Users should conduct disposal operations
in compliance with applicable federal, state and local laws and
regulations. Appropriate regulatory agencies also should be consulted before discharging or disposing of waste materials.

Available Literature/Technical Assistance


Honeywell has a wide range of literature available for all of its
environmentally safer Genetron products, covering such topics
as reclamation, retrofitting guidelines, product specifications and
technical properties. Much of this information is available online
at www.genetron.com. In addition, Honeywell technical specialists are available to assist you in all phases of using Genetron
407C especially retrofitting, handling and storage and applications assistance. For further information, please write us at:
Honeywell
Genetron Refrigerants
P.O. Box 1053
Morristown, NJ 07962-1053
Or call us at 1-800-631-8138

11

Genetron 407C

407C Thermodynamic Table - English Units


Bubble
Dew
Pressure Pressure
Temp. (Liquid) (Vapor)
(F )
( psia )
( psia )
-40
-38
-36
-34
-32
-30
-28
-26
-24
-22
-20
-18
-16
-14
-12
-10
-8
-6
-4
-2
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60

17.4
18.4
19.3
20.3
21.3
22.4
23.5
24.7
25.9
27.1
28.4
29.8
31.2
32.6
34.1
35.6
37.2
38.9
40.6
42.4
44.2
46.1
48.0
50.0
52.1
54.2
56.4
58.7
61.0
63.4
65.9
68.5
71.1
73.8
76.6
79.4
82.4
85.4
88.5
91.7
94.9
98.3
101.7
105.3
108.9
112.6
116.4
120.3
124.3
128.4
132.6

12.4
13.1
13.9
14.7
15.5
16.3
17.2
18.1
19.1
20.1
21.2
22.2
23.4
24.6
25.8
27.0
28.4
29.7
31.1
32.6
34.1
35.7
37.3
39.0
40.8
42.6
44.4
46.4
48.4
50.4
52.6
54.8
57.0
59.4
61.8
64.3
66.8
69.5
72.2
75.0
77.9
80.8
83.9
87.0
90.2
93.5
96.9
100.4
104.0
107.7
111.5

Vapor
Volume
( ft3/lb )

Liquid
Density
( lb/ft3 )

4.0515
3.8437
3.6486
3.4653
3.2931
3.1311
2.9786
2.835
2.6997
2.5722
2.4519
2.3383
2.231
2.1296
2.0338
1.9431
1.8572
1.7759
1.6989
1.6259
1.5566
1.4909
1.4284
1.3691
1.3128
1.2592
1.2082
1.1597
1.1135
1.0695
1.0276
0.9876
0.9495
0.9131
0.8784
0.8453
0.8136
0.7833
0.7544
0.7267
0.7002
0.6748
0.6505
0.6273
0.605
0.5836
0.5631
0.5435
0.5246
0.5065
0.4891

85.50
85.28
85.06
84.85
84.63
84.41
84.19
83.97
83.75
83.53
83.31
83.09
82.86
82.64
82.41
82.19
81.96
81.73
81.50
81.27
81.04
80.81
80.57
80.34
80.10
79.87
79.63
79.39
79.15
78.91
78.66
78.42
78.17
77.93
77.68
77.43
77.17
76.92
76.67
76.41
76.15
75.89
75.63
75.37
75.10
74.83
74.57
74.29
74.02
73.75
73.47

Liquid
Enthalpy
( Btu/lb )
0.00
0.63
1.26
1.90
2.53
3.17
3.80
4.44
5.08
5.72
6.36
7.00
7.64
8.29
8.93
9.58
10.22
10.87
11.52
12.17
12.83
13.48
14.14
14.79
15.45
16.11
16.77
17.43
18.10
18.76
19.43
20.10
20.77
21.44
22.11
22.79
23.47
24.15
24.83
25.51
26.20
26.88
27.57
28.26
28.96
29.65
30.35
31.05
31.75
32.45
33.16

Enthalpy
H
(Btu/lb)

Vapor
Enthalpy
( Btu/lb )

104.25
103.90
103.55
103.19
102.84
102.47
102.12
101.76
101.39
101.02
100.65
100.28
99.91
99.53
99.16
98.77
98.40
98.01
97.62
97.24
96.83
96.44
96.04
95.64
95.24
94.83
94.42
94.01
93.59
93.17
92.75
92.32
91.89
91.46
91.02
90.58
90.13
89.68
89.23
88.77
88.31
87.85
87.38
86.91
86.42
85.94
85.45
84.96
84.46
83.96
83.45

104.25
104.53
104.81
105.09
105.37
105.64
105.92
106.20
106.47
106.74
107.01
107.28
107.55
107.82
108.09
108.35
108.62
108.88
109.14
109.41
109.66
109.92
110.18
110.43
110.69
110.94
111.19
111.44
111.69
111.93
112.18
112.42
112.66
112.90
113.13
113.37
113.60
113.83
114.06
114.28
114.51
114.73
114.95
115.17
115.38
115.59
115.80
116.01
116.21
116.41
116.61

Liquid
Vapor
Entropy
Entropy
( Btu/lb-F ) ( Btu/lb-F )
0.0000
0.0015
0.0030
0.0045
0.0060
0.0074
0.0089
0.0104
0.0118
0.0133
0.0147
0.0162
0.0176
0.0191
0.0205
0.0219
0.0234
0.0248
0.0262
0.0276
0.0291
0.0305
0.0319
0.0333
0.0347
0.0361
0.0375
0.0389
0.0402
0.0416
0.0430
0.0444
0.0458
0.0471
0.0485
0.0499
0.0512
0.0526
0.0540
0.0553
0.0567
0.0580
0.0594
0.0607
0.0621
0.0634
0.0648
0.0661
0.0675
0.0688
0.0702

0.2524
0.2518
0.2512
0.2507
0.2501
0.2496
0.2491
0.2485
0.2480
0.2475
0.2471
0.2466
0.2461
0.2456
0.2452
0.2447
0.2443
0.2439
0.2434
0.2430
0.2426
0.2422
0.2418
0.2414
0.2410
0.2406
0.2403
0.2399
0.2395
0.2392
0.2388
0.2385
0.2381
0.2378
0.2375
0.2371
0.2368
0.2365
0.2362
0.2358
0.2355
0.2352
0.2349
0.2346
0.2343
0.2340
0.2337
0.2334
0.2331
0.2328
0.2325

Genetron 407C

12

407C Thermodynamic Table - English Units


Bubble
Dew
Pressure Pressure
Temp. (Liquid) (Vapor)
(F )
( psia )
( psia )
62
136.9
115.4
64
141.4
119.4
66
145.9
123.5
68
150.5
127.7
70
155.2
132.0
72
160.1
136.4
74
165.0
140.9
76
170.1
145.6
78
175.2
150.3
80
180.5
155.2
82
185.9
160.2
84
191.5
165.3
86
197.1
170.6
88
202.9
175.9
90
208.8
181.4
92
214.8
187.0
94
221.0
192.8
96
227.2
198.6
98
233.6
204.7
100
240.2
210.8
102
246.9
217.1
104
253.7
223.6
106
260.6
230.1
108
267.7
236.9
110
274.9
243.7
112
282.3
250.8
114
289.8
258.0
116
297.5
265.3
118
305.3
272.8
120
313.3
280.5
122
321.4
288.3
124
329.7
296.3
126
338.1
304.5
128
346.7
312.8
130
355.4
321.3
132
364.3
330.1
134
373.4
338.9
136
382.7
348.0
138
392.1
357.3
140
401.6
366.8
142
411.4
376.4
144
421.3
386.3
146
431.4
396.4
148
441.7
406.7

13

Genetron 407C

Vapor
Volume
( ft3/lb )
0.4724
0.4564
0.4409
0.4261
0.4118
0.3981
0.3849
0.3722
0.3599
0.3481
0.3367
0.3257
0.3152
0.305
0.2951
0.2856
0.2765
0.2676
0.259
0.2508
0.2428
0.2351
0.2276
0.2203
0.2133
0.2066
0.2
0.1936
0.1875
0.1815
0.1757
0.1701
0.1646
0.1593
0.1542
0.1492
0.1443
0.1396
0.135
0.1305
0.1262
0.1219
0.1178
0.1137

Liquid
Density
( lb/ft3 )
73.19
72.91
72.62
72.33
72.05
71.75
71.46
71.16
70.86
70.56
70.25
69.94
69.63
69.31
68.99
68.67
68.35
68.01
67.68
67.34
67.00
66.65
66.30
65.94
65.58
65.22
64.84
64.47
64.08
63.69
63.30
62.89
62.48
62.07
61.64
61.21
60.76
60.31
59.85
59.37
58.89
58.39
57.88
57.35

Liquid
Enthalpy
( Btu/lb )
33.87
34.58
35.30
36.01
36.73
37.46
38.18
38.91
39.64
40.37
41.11
41.85
42.60
43.34
44.09
44.85
45.60
46.37
47.13
47.90
48.68
49.45
50.24
51.02
51.81
52.61
53.41
54.22
55.03
55.85
56.67
57.50
58.34
59.18
60.03
60.89
61.76
62.63
63.52
64.41
65.31
66.22
67.15
68.08

Enthalpy
H
(Btu/lb)
82.94
82.42
81.89
81.37
80.83
80.28
79.73
79.18
78.61
78.05
77.47
76.89
76.29
75.70
75.09
74.47
73.85
73.21
72.58
71.93
71.26
70.60
69.91
69.23
68.53
67.81
67.09
66.35
65.60
64.83
64.06
63.26
62.45
61.63
60.79
59.93
59.05
58.15
57.23
56.29
55.32
54.34
53.31
52.27

Vapor
Enthalpy
( Btu/lb )
116.81
117.00
117.19
117.38
117.56
117.74
117.91
118.09
118.25
118.42
118.58
118.74
118.89
119.04
119.18
119.32
119.45
119.58
119.71
119.83
119.94
120.05
120.15
120.25
120.34
120.42
120.50
120.57
120.63
120.68
120.73
120.76
120.79
120.81
120.82
120.82
120.81
120.78
120.75
120.70
120.63
120.56
120.46
120.35

Liquid
Entropy
( Btu/lb-F ) (
0.0715
0.0728
0.0742
0.0755
0.0769
0.0782
0.0795
0.0809
0.0822
0.0835
0.0849
0.0862
0.0876
0.0889
0.0902
0.0916
0.0929
0.0943
0.0956
0.0970
0.0983
0.0996
0.1010
0.1024
0.1037
0.1051
0.1064
0.1078
0.1092
0.1105
0.1119
0.1133
0.1147
0.1161
0.1175
0.1189
0.1203
0.1217
0.1232
0.1246
0.1261
0.1275
0.1290
0.1305

Vapor
Entropy
Btu/lb-F )
0.2322
0.2320
0.2317
0.2314
0.2311
0.2308
0.2305
0.2302
0.2299
0.2297
0.2294
0.2291
0.2288
0.2285
0.2282
0.2279
0.2276
0.2273
0.2270
0.2267
0.2264
0.2261
0.2258
0.2254
0.2251
0.2248
0.2244
0.2241
0.2237
0.2234
0.2230
0.2226
0.2223
0.2219
0.2215
0.2210
0.2206
0.2202
0.2197
0.2192
0.2188
0.2182
0.2177
0.2172

407C Thermodynamic Table - SI Units


Bubble
Dew
Pressure Pressure
Temp. (Liquid) (Vapor)
(C ) ( kPa )
( kPa )
-40
120
86
-39
126
90
-38
132
95
-37
138
99
-36
144
104
-35
151
110
-34
158
115
-33
165
121
-32
172
126
-31
179
132
-30
187
139
-29
195
145
-28
203
152
-27
212
159
-26
221
166
-25
230
173
-24
239
181
-23
249
189
-22
259
197
-21
269
206
-20
280
215
-19
291
224
-18
302
233
-17
314
243
-16
326
253
-15
338
263
-14
351
274
-13
364
285
-12
377
296
-11
391
308
-10
405
320
-9
419
332
-8
434
345
-7
449
358
-6
465
371
-5
481
385
-4
498
400
-3
514
414
-2
532
429
-1
550
445
0
568
461
1
587
477
2
606
494
3
625
511
4
645
529
5
666
547
6
687
566
7
709
585
8
731
604
9
753
624
10
776
645
11
800
666
12
824
688

Vapor
Volume
( m3/kg )
0.2529
0.2412
0.2302
0.2197
0.2098
0.2004
0.1916
0.1832
0.1753
0.1677
0.1606
0.1538
0.1474
0.1413
0.1354
0.1299
0.1247
0.1197
0.1149
0.1104
0.1061
0.1019
0.0980
0.0943
0.0907
0.0873
0.0840
0.0809
0.0780
0.0751
0.0724
0.0698
0.0673
0.0649
0.0626
0.0605
0.0584
0.0563
0.0544
0.0526
0.0508
0.0491
0.0475
0.0459
0.0444
0.0429
0.0415
0.0402
0.0389
0.0376
0.0364
0.0353
0.0342

Liquid
Density
( kg/m3 )
1370
1366
1363
1360
1357
1354
1351
1348
1344
1341
1338
1335
1332
1328
1325
1322
1319
1315
1312
1309
1306
1302
1299
1296
1292
1289
1285
1282
1279
1275
1272
1268
1265
1261
1258
1254
1251
1247
1243
1240
1236
1233
1229
1225
1221
1218
1214
1210
1206
1203
1199
1195
1191

Liquid
Enthalpy
( kJ/kg )
145.45
146.77
148.09
149.42
150.74
152.07
153.40
154.73
156.07
157.40
158.74
160.08
161.42
162.77
164.11
165.46
166.81
168.16
169.52
170.88
172.24
173.60
174.96
176.33
177.70
179.07
180.45
181.82
183.20
184.59
185.97
187.36
188.75
190.15
191.55
192.95
194.35
195.76
197.17
198.58
200.00
201.42
202.84
204.27
205.70
207.14
208.58
210.02
211.47
212.92
214.37
215.83
217.29

Enthalpy
H
( kJ/kg )
242.33
241.60
240.86
240.11
239.38
238.62
237.87
237.12
236.35
235.60
234.83
234.05
233.28
232.49
231.72
230.93
230.13
229.34
228.53
227.72
226.91
226.10
225.28
224.45
223.62
222.78
221.94
221.10
220.24
219.37
218.52
217.64
216.77
215.88
214.98
214.09
213.19
212.28
211.36
210.44
209.51
208.57
207.63
206.67
205.71
204.74
203.76
202.77
201.78
200.77
199.77
198.75
197.72

Vapor
Enthalpy
( kJ/kg )
387.78
388.37
388.95
389.53
390.12
390.69
391.27
391.85
392.42
393.00
393.57
394.13
394.70
395.26
395.83
396.39
396.94
397.50
398.05
398.60
399.15
399.70
400.24
400.78
401.32
401.85
402.39
402.92
403.44
403.96
404.49
405.00
405.52
406.03
406.53
407.04
407.54
408.04
408.53
409.02
409.51
409.99
410.47
410.94
411.41
411.88
412.34
412.79
413.25
413.69
414.14
414.58
415.01

Liquid
Vapor
Entropy
Entropy
( kJ/kg-C ) ( kJ/kg-C )
0.7856
1.8415
0.7913
1.8393
0.7969
1.8372
0.8025
1.8351
0.8081
1.8330
0.8136
1.8310
0.8192
1.8290
0.8247
1.8270
0.8302
1.8251
0.8357
1.8232
0.8412
1.8213
0.8467
1.8195
0.8522
1.8177
0.8576
1.8159
0.8630
1.8142
0.8684
1.8124
0.8739
1.8107
0.8792
1.8091
0.8846
1.8074
0.8900
1.8058
0.8953
1.8042
0.9007
1.8026
0.9060
1.8011
0.9113
1.7995
0.9166
1.7980
0.9219
1.7965
0.9272
1.7951
0.9324
1.7936
0.9377
1.7922
0.9429
1.7908
0.9482
1.7894
0.9534
1.7880
0.9586
1.7867
0.9638
1.7853
0.9690
1.7840
0.9742
1.7827
0.9794
1.7814
0.9845
1.7801
0.9897
1.7789
0.9949
1.7776
1.0000
1.7764
1.0051
1.7752
1.0103
1.7740
1.0154
1.7728
1.0205
1.7716
1.0256
1.7704
1.0307
1.7692
1.0358
1.7681
1.0409
1.7669
1.0460
1.7658
1.0511
1.7647
1.0561
1.7636
1.0612
1.7624

Genetron 407C

14

407C Thermodynamic Table - SI Units


Bubble
Dew
Pressure Pressure
Temp. (Liquid) (Vapor)
(C ) ( kPa )
( kPa )
13
849
710
14
874
732
15
900
756
16
926
779
17
953
804
18
981
829
19
1009
854
20
1038
880
21
1067
907
22
1097
934
23
1127
962
24
1159
991
25
1190
1020
26
1223
1050
27
1256
1080
28
1290
1112
29
1324
1143
30
1359
1176
31
1395
1209
32
1431
1243
33
1469
1278
34
1506
1313
35
1545
1349
36
1584
1386
37
1624
1424
38
1665
1462
39
1707
1501
40
1749
1541
41
1792
1582
42
1836
1624
43
1881
1666
44
1926
1709
45
1972
1754
46
2019
1799
47
2067
1845
48
2116
1891
49
2166
1939
50
2216
1988
51
2267
2037
52
2319
2088
53
2372
2139
54
2426
2192
55
2481
2245
56
2537
2300
57
2594
2356
58
2651
2412
59
2710
2470
60
2769
2529
61
2830
2589
62
2891
2650
63
2954
2712
64
3017
2775
65
3081
2840
66
3147
2906
67
3213
2973
16

Genetron 407C

Vapor
Volume
( m3/kg )
0.0331
0.0321
0.0311
0.0301
0.0292
0.0283
0.0274
0.0266
0.0258
0.0250
0.0243
0.0236
0.0229
0.0222
0.0215
0.0209
0.0203
0.0197
0.0191
0.0186
0.0180
0.0175
0.0170
0.0165
0.0160
0.0156
0.0151
0.0147
0.0143
0.0138
0.0135
0.0131
0.0127
0.0123
0.0120
0.0116
0.0113
0.0110
0.0107
0.0103
0.0100
0.0098
0.0095
0.0092
0.0089
0.0087
0.0084
0.0082
0.0079
0.0077
0.0074
0.0072
0.0070
0.0068
0.0065

Liquid
Density
( kg/m3 )
1187
1183
1179
1175
1171
1167
1163
1159
1155
1150
1146
1142
1137
1133
1129
1124
1120
1115
1111
1106
1102
1097
1092
1087
1083
1078
1073
1068
1063
1057
1052
1047
1042
1036
1031
1025
1020
1014
1008
1002
996
990
984
978
971
965
958
951
944
937
930
922
914
906
898

Liquid
Enthalpy
( kJ/kg )
218.76
220.23
221.71
223.19
224.68
226.17
227.66
229.16
230.67
232.18
233.69
235.21
236.74
238.27
239.81
241.35
242.90
244.46
246.02
247.59
249.17
250.75
252.34
253.94
255.54
257.15
258.77
260.40
262.04
263.68
265.34
267.00
268.67
270.35
272.04
273.75
275.46
277.18
278.92
280.67
282.43
284.20
285.99
287.79
289.61
291.44
293.29
295.16
297.05
298.96
300.88
302.83
304.81
306.81
308.84

Enthalpy
H
( kJ/kg )
196.68
195.63
194.57
193.50
192.42
191.33
190.23
189.12
187.99
186.86
185.72
184.56
183.39
182.21
181.01
179.81
178.58
177.34
176.09
174.82
173.54
172.24
170.93
169.59
168.25
166.89
165.50
164.10
162.67
161.24
159.77
158.29
156.78
155.25
153.70
152.12
150.52
148.89
147.23
145.55
143.83
142.09
140.30
138.49
136.64
134.75
132.82
130.85
128.82
126.76
124.65
122.48
120.24
117.95
115.59

Vapor
Enthalpy
( kJ/kg )
415.44
415.86
416.28
416.69
417.10
417.50
417.89
418.28
418.66
419.04
419.41
419.77
420.13
420.48
420.82
421.16
421.48
421.80
422.11
422.41
422.71
422.99
423.27
423.53
423.79
424.04
424.27
424.50
424.71
424.92
425.11
425.29
425.45
425.60
425.74
425.87
425.98
426.07
426.15
426.22
426.26
426.29
426.29
426.28
426.25
426.19
426.11
426.01
425.87
425.72
425.53
425.31
425.05
424.76
424.43

Liquid
Vapor
Entropy
Entropy
( kJ/kg-C ) ( kJ/kg-C )
1.0663
1.7613
1.0713
1.7602
1.0764
1.7591
1.0814
1.7580
1.0865
1.7570
1.0915
1.7559
1.0966
1.7548
1.1016
1.7537
1.1067
1.7526
1.1117
1.7516
1.1167
1.7505
1.1218
1.7494
1.1268
1.7483
1.1318
1.7472
1.1369
1.7462
1.1419
1.7451
1.1469
1.7440
1.1520
1.7429
1.1570
1.7418
1.1621
1.7407
1.1671
1.7396
1.1722
1.7385
1.1772
1.7373
1.1823
1.7362
1.1873
1.7350
1.1924
1.7339
1.1975
1.7327
1.2025
1.7315
1.2076
1.7303
1.2127
1.7291
1.2178
1.7279
1.2230
1.7266
1.2281
1.7254
1.2332
1.7241
1.2384
1.7228
1.2435
1.7215
1.2487
1.7201
1.2539
1.7187
1.2591
1.7173
1.2643
1.7159
1.2696
1.7144
1.2748
1.7129
1.2801
1.7113
1.2854
1.7097
1.2908
1.7081
1.2961
1.7064
1.3015
1.7047
1.3069
1.7029
1.3124
1.7011
1.3179
1.6992
1.3235
1.6972
1.3290
1.6952
1.3347
1.6931
1.3404
1.6909
1.3461
1.6886

Worldwide Sales Offices


For more information contact your
Honeywell Refrigerants representative
United States
Honeywell Chemicals
101 Columbia Road
Morristown, NJ 07962-1053
Phone: 800-631-8138
Fax:
973-455-6395
Latin America-Caribbean
Honeywell Chemicals Mexico
Constituyentes 900
Col. Lomas Altas
C.P. 11950, Mexico DF
Mexico
Phone: 52-55-5549-0313
Fax:
52-55-5544-9803

Northern and Central Europe


Honeywell Belgium NV
Haasrode Research Park
Grauwmeer 1
3001 Heverlee
Belgium
Phone: 32-16-39-1278
Fax:
32-16-39-1277
Southern Europe, Middle East and Africa
Honeywell Fluorine Products Italia S.r.l.
Viale De Gasperi 19
20020 Lainate MI
Italia
Phone: +39-02-9379.6777 (ext 24 / 25 or 26)

Canada
Honeywell Asca. Inc.
3333 Unity Drive
Mississauga, Ontario
L5L 3S6
Phone: 905-608-6325
Fax:
905-608-6327

www.honeywell.com/genetron

Asia-Pacific
Honeywell (China) Co., ltd.
No 430, Li Bing Road
Zhang Jiang Hi-Tech Park
Pudong New Area, Shanghai 201203
China
Phone: 86-21-2894-2000
Fax:
86-21-5855-2719

Phone: 800-522-8001
Fax:
800-458-9073

Honeywell Chemicals Inc., Japan


New Pier Takeshiba
South Tower Building, 20th Floor
1-16-1 Kaigan, Minato-ku,
Tokyo, Japan
Phone: 81-3-6730-7083
Fax:
81-3-6730-7221
Honeywell Chemicals, Korea
6F Janghakjaedan, B/D 44-1
Bangpo-Dong, Seocho-Ku
Seoul 137040, Korea
Phone: 8-22-595-0204
Fax:
8-22-595-4964

Customer Service
To place an order from anywhere in the
Continental United States, Hawaii and
the Caribbean:

In Canada:
Phone: 800-553-9749
Fax:
800-553-9750
Outside these areas:
Phone: 973-455-6300
Fax:
973-455-2763
Northern and Central Europe
Phone: +32-16-391.209
Phone: +32-16-391.265
Fax:
+32-16-391.235
Southern Europe, Middle East and Africa
Phone: +39-02-9379.6777 ext. 24 / 25 and 26
Fax:
+39-02-9379.6761

Honeywell Specialty Chemicals (Singapore) Pte. Ltd.


17 Changi Business Park Central 1
Honeywell Building
Singapore 486073
Phone: 65-6355-2828
Fax:
65-6783-2947
Honeywell International
71 Queens Road, Ground Floor
Melbourne, Victoria 3004
Australia
Phone: 61-3-9529-1411
Fax:
61-3-9510-9837
G 525-013
Printed in U.S.A.
2005 Honeywell International Inc.

Vous aimerez peut-être aussi