Users Guide
72A-1968-01
Rev. E 3/2011
Warranty
Equipment Limited
Warranty
Software Limited
Warranty
Some states do not allow the exclusion of implied warranties, so the above
exclusion may not apply. This warranty gives the purchaser specific legal
rights and the purchaser may also have other rights which vary from state to
state.
DOBLE warrants the disks on which the software product is furnished to be
free from defects in materials and workmanship under normal use for a period
of one hundred and twenty (120) days from the date of shipment from
DOBLE.
Limitations of
Remedies
Contents
1. Getting Started ..................................................................................... 1-1
Safety ............................................................................................................................................ 1-1
Installing F6TesT.......................................................................................................................... 1-1
Instruments Supported............................................................................................................ 1-1
System Requirements ............................................................................................................. 1-1
Software Installation .............................................................................................................. 1-2
Removing Previous F6TesT Versions ............................................................................. 1-2
Installing the F6TesT Software........................................................................................ 1-3
Start-up and Login ........................................................................................................................ 1-5
F6TesT Architecture and Data Views .......................................................................................... 1-8
Location................................................................................................................................ 1-12
Relay..................................................................................................................................... 1-12
Test Plan ............................................................................................................................... 1-12
Menus and Toolbars ................................................................................................................... 1-12
Context Menu ....................................................................................................................... 1-13
Copy, Cut, and Paste in the Location Tree and List View............................................. 1-13
Delete, Insert, Append, Find in the Location Tree and List View................................. 1-14
Toolbars................................................................................................................................ 1-14
File Menu ............................................................................................................................. 1-17
New ................................................................................................................................ 1-17
Open ............................................................................................................................... 1-18
Close............................................................................................................................... 1-18
Save As .......................................................................................................................... 1-18
Delete Saved Graphs...................................................................................................... 1-19
Recently Opened Databases........................................................................................... 1-19
Print Setup...................................................................................................................... 1-19
Exit ................................................................................................................................. 1-20
Edit Menu ............................................................................................................................. 1-20
Copy ............................................................................................................................... 1-22
Multiple Cut, Copy, and Delete ..................................................................................... 1-23
72A-1968-01
Rev. E 3/2011
72A-1968-01
Rev. E 3/2011
Contents
72A-1968-01
Rev. E 3/2011
vii
viii
72A-1968-01
Rev. E 3/2011
Contents
72A-1968-01
Rev. E 3/2011
ix
72A-1968-01
Rev. E 3/2011
Contents
Help ......................................................................................................................................E-11
Contents .........................................................................................................................E-11
About Vector Calculator ................................................................................................E-12
Toolbar .......................................................................................................................................E-12
Performing Calculations.............................................................................................................E-12
Source Name Column ..........................................................................................................E-13
Formula Column ..................................................................................................................E-13
Performing Formula Box Calculations.......................................................................................E-13
Formula Operators ...............................................................................................................E-13
Standard Operators.........................................................................................................E-14
a, a2 ................................................................................................................................E-14
SQRT .............................................................................................................................E-14
Parentheses.....................................................................................................................E-14
Evaluate..........................................................................................................................E-14
Save the Answer in the Vector Table...................................................................................E-15
72A-1968-01
Rev. E 3/2011
xi
xii
72A-1968-01
Rev. E 3/2011
List of Figures
Figure 1-1
Figure 1-2
Figure 1-3
Figure 1-4
Figure 1-5
Figure 1-6
Figure 1-7
Figure 1-8
Figure 1-9
Figure 1-10
Figure 1-11
Figure 1-12
Figure 1-13
Figure 1-14
Figure 1-15
Figure 1-16
Figure 1-17
Figure 1-18
Figure 1-19
Figure 1-20
Figure 1-21
Figure 1-22
Figure 1-23
Figure 1-24
Figure 1-25
Figure 1-26
Figure 1-27
Figure 1-28
Figure 1-29
Figure 1-30
Figure 1-31
Figure 1-32
72A-1968-01
Rev. E 3/2011
xiii
Figure 1-33
Figure 1-34
Figure 1-35
Figure 1-36
Figure 1-37
Figure 1-38
Figure 1-39
Figure 1-40
Figure 1-41
Figure 1-42
Figure 1-43
Figure 1-44
Figure 1-45
Figure 1-46
Figure 1-47
Figure 1-48
Figure 1-49
Figure 1-50
Figure 1-51
Figure 1-52
Figure 1-53
Figure 1-54
Figure 1-55
Figure 1-56
Figure 1-57
Figure 1-58
Figure 1-59
Figure 2-1
Figure 2-2
Figure 2-3
Figure 2-4
Figure 2-5
Figure 2-6
Figure 2-7
Figure 2-8
Figure 2-9
Figure 2-10
Figure 2-11
xiv
72A-1968-01
Rev. E 3/2011
List of Figures
Figure 2-12
Figure 3-1
Figure 3-2
Figure 3-3
Figure 3-4
Figure 3-5
Figure 3-6
Figure 3-7
Figure 3-8
Figure 3-9
Figure 3-10
Figure 3-11
Figure 3-12
Figure 3-13
Figure 3-14
Figure 3-15
Figure 3-16
Figure 3-17
Figure 3-18
Figure 3-19
Figure 3-20
Figure 3-21
Figure 3-22
Figure 3-23
Figure 3-24
Figure 3-25
Figure 3-26
Figure 3-27
Figure 3-28
Figure 3-29
Figure 3-30
Figure 3-31
Figure 3-32
Figure 4-1
Figure 4-2
Figure 4-3
Figure 4-4
Figure 4-5
72A-1968-01
Rev. E 3/2011
xv
Figure 4-6
Figure 4-7
Figure 4-8
Figure 4-9
Figure 4-10
Figure 4-11
Figure 4-12
Figure 4-13
Figure 4-14
Figure 4-15
Figure 4-16
Figure 4-17
Figure 4-18
Figure 4-19
Figure 4-20
Figure 4-21
Figure 4-22
Figure 4-23
Figure 4-24
Figure 4-25
Figure 4-26
Figure 4-27
Figure 4-28
Figure 4-29
Figure 4-30
Figure 4-31
Figure 4-32
Figure 4-33
Figure 4-34
Figure 4-35
Figure 4-36
Figure 4-37
Figure 4-38
Figure 4-39
Figure 4-40
Figure 4-41
Figure 4-42
xvi
72A-1968-01
Rev. E 3/2011
List of Figures
Figure 4-43
Figure 4-44
Figure 4-45
Figure 4-46
Figure 4-47
Figure 4-48
Figure 4-49
Figure 4-50
Figure 4-51
Figure 4-52
Figure 4-53
Figure 4-54
Figure 4-55
Figure 4-56
Figure 4-57
Figure 4-58
Figure 4-59
Figure 4-60
Figure 4-61
Figure 4-62
Figure 4-63
Figure 4-64
Figure 4-65
Figure 4-66
Figure 4-67
Figure 4-68
Figure 4-69
Figure 4-70
Figure 4-71
Figure 4-72
Figure 4-73
Figure 4-74
Figure 4-75
Figure 4-76
Figure 4-77
Figure 5-1
Figure 5-2
Figure 5-3
72A-1968-01
Rev. E 3/2011
xvii
Figure 5-4
Figure 5-5
Figure 5-6
Figure 5-7
Figure 5-8
Figure 6-1
Figure 6-2
Figure 6-3
Figure 6-4
Figure 6-5
Figure B-1
Figure B-2
Figure B-3
Figure B-4
Figure D-1
Figure D-2
Figure D-3
Figure D-4
Figure D-5
Figure D-6
Figure D-7
Figure D-8
Figure D-9
Figure D-10
Figure D-11
Figure D-12
Figure D-13
Figure D-14
Figure E-1
Figure E-2
Figure E-3
Figure E-4
Figure E-5
Figure E-6
Figure E-7
Figure E-8
Figure E-9
Figure E-10
xviii
72A-1968-01
Rev. E 3/2011
List of Figures
Figure E-11
Figure E-12
Figure E-13
Figure E-14
72A-1968-01
Rev. E 3/2011
E-11
E-11
E-12
E-14
xix
xx
72A-1968-01
Rev. E 3/2011
List of Tables
Table 1-1
Table 1-2
Table 1-3
Table 1-4
Table 2-1
Table 4-1
Table 4-2
Table A-1
Table A-2
Table A-3
Table D-1
Table E-1
Table E-2
72A-1968-01
Rev. E 3/2011
xxi
xxii
72A-1968-01
Rev. E 3/2011
1. Getting Started
Safety
WARNING! Before turning on or using any F6150, verify that the
instrument is safely grounded to eliminate the potential of a dangerous
electric shock. Always turn the source output off and disable the unit
before connecting, removing, or touching any output terminal or cable.
Installing F6TesT
Instruments Supported
F6TesT version 2.21 supports F6150, F6150A, and the F6150+F6300 external
high-power current amplifier.
System Requirements
Table 1-1 outlines the system requirements for the F6TesT software.
Table 1-1 F6TesT System Requirements
Operating System
72A-1968-01
Rev. E 3/2011
Windows 2000
Windows XP
Windows 7
Vista
1-1
Hard-Drive Space
Software Installation
Software installation consists of:
If you are using Windows 7 or Vista and are unfamiliar with the User Account
Control (UAC) and data redirection, also known as UAC virtualization, you
may want to consult with your IT support staff before uninstalling or installing
F6TesT.
1-2
1. Getting Started
Windows 7 and Vista may have used data redirection on some of the
F6TesT application folder, consult with your IT support staff if necessary
to save any desired files and to ensure complete removal of earlier
versions of F6TesT.
2. Delete the F6TesT 2.20 application folder. The default location of the
folder is:
If you have any questions about removing earlier versions of F6TesT, contact
Doble at fserieshelp@doble.com.
1-3
1-4
1. Getting Started
If you uninstall version 2.19 after installing version 2.21, you will need to
re-register cwui.ocx using the preceding steps before using version 2.21.
Windows 7 and Vista may use data redirection on some of the F6TesT
installation folders and your data; consult with your IT support staff if
necessary.
or
2. Select Start Programs F6TesT from the task bar. A Login dialog
box appears (Figure 1-4).
1-5
1-6
1. Getting Started
To log in:
1. Enter a name (up to 20 characters) in the User Name field or select a
previously entered name from the drop-down menu.
2. Select the preferred language from the Language drop-down menu.
3. Click OK. The Select Database dialog box appears (Figure 1-5).
1-7
The menu bar at the top of the window provides access to F6TesT
functions. For more information, refer to Menus and Toolbars
on page 1-12.
Three toolbars are located just below the menu bar:
Standard
Run
Battery
The icons on the toolbars provide quick access to principal F6TesT functions.
The location tree on the left shows the organization of the database
into Locations, Relays, and Test Plans. The tree view is similar to the
Windows Explorer view of folders and files.
Click the plus icon to the left of an item to display the contents of
the Location, Relay, or Test Plan.
Click the minus icon to hide the contents of the Location, Relay, or
Test Plan.
In Figure 1-6, only the locations are shown, while in Figure 1-7, the tree is
fully expanded to show individual tests.
1-8
1. Getting Started
The Table View on the right provides details on the item selected in
the location tree. There are four tables linked in a parent-child
relationship:
1. Location, when the database name at the top of the location tree is
selected
2. Relay, when a location is selected
3. Test Plan, when a relay is selected
4. Test, when a test plan is selected.
1-9
F6TEST
Database
Location
Level 1
Relay
Manufacturers
Characteristics
Z Mho
Characteristics
Location Level 2
(Up to 3 Levels)
Elements /
Setting
Relay
Functions
RELAY
Input/Output
Mapping
Z General
Characteristics
Differential
Characteristics
Test Plans
Test Module
More Locations/Sub-locations
More
Relays
More Test
Plans
1-10
1. Getting Started
Characteristics Library
Overcurrent, Under/Over Voltage,
Under/Over Frequency, Differential
Characteristic Equations
Look-up Tables
Z General
Characteristics
Z Standard
Mho/Offset Mho
Characteristic
Model
Building Blocks
Arcs/Lines
RELAY
Function 1
Function 3
Element 1
Element 2
Element 1
Element 2
Function 2
Element 1
Test 1
Element 2
Element n
Test 3
Test 1
Test 2
Test 2
TEST PLAN 1
Test 3
TEST PLAN 2
Test 1
Test 2
Test 4
TEST PLAN N
1-11
Location
The first level of a data tree is always a location, which can correspond to a
substation or to a protection panel in a substation. A location contains either
sublocations or relays, but not both. Up to three levels of locations are
allowed. The user can add an asset tracking number if necessary.
Relay
A relay record has a user assigned Relay ID, which can identify the line or
equipment being protected and an optional serial number. These are arbitrary
and can be edited by clicking the table entry and entering changes. A
timestamp records the original creation date of the record, and the login name
of the user that created the record. The timestamp and originator cannot be
changed.
The Manufacturer field enables you to enter a relay manufacturer. You can
select the manufacturer from a drop-down menu or you can type the name in
the field. Each manufacturer has a corresponding list of relay models. If the
name entered is not in the list, a prompt appears, asking whether to add the
name to the list. Care should be taken to avoid entering duplicate names or
synonyms for the same manufacturer. For consistency of the relay naming
conventions, it is advisable to enter all relay model names under the Relay
Mfrs and Models menu.
Once a test plan has been defined for a relay, the Mfr cannot be changed.
Test Plan
Each test plan has a user-assigned name to describe the purpose of the plan. A
creation date and login name are recorded when the test plan is first created.
These fields cannot be changed.
1. Getting Started
File
Edit
Module
Setup
Tools
Help
Context Menu
The Edit menu is also available as a context menu in the Location Tree and the
Table View (Figure 1-11).
To access the context menu, right-click the item in either the Location Tree or
Table View. The function of the selected menu item is applied. This menu
enables you to perform many of the functions on the Edit menu.
Copy, Cut, and Paste in the Location Tree and List View
You can copy and paste one or more records (locations, relays, test plans,
tests) from the location tree or table view, according to the following rules:
72A-1968-01 Rev. E 3/2011
1-13
See Appendix C, Cut, Copy, and Paste Operations, for more details.
A copy/cut/paste operation in F6TesT cannot be undone. A cut operation is
executed only after a paste operation is successful.
Delete, Insert, Append, Find in the Location Tree and List View
These options enable you to delete, insert, append, and find records (locations,
relays, test plans, and tests) in the location tree or table view. To perform any
of these actions, highlight a record and select one of the options from the
context menu. If you are adding, inserting, or appending, the new record will
appear before the selected record.
Toolbars
The following four toolbars provide quick access to various program
functions:
1. The Standard toolbar (Figure 1-12) presents basic file and edit functions,
using icons that are common to many Windows applications.
Open a
Database
Clipboard functions:
Cut, Copy, and Paste
1-14
1. Getting Started
4. The Formula and Functions toolbar (Figure 1-15) enables you to manage
formulae, functions, and keywords when a test definition is open.
Formula
Bar
Highlight
Formula
Find Note in
Notebook
Keyword &
Functions
1-15
1-16
Find Note alerts you to the fact that there are notes on the
Notebook tab. This icon appears only when there are notes for the test
definition.
1. Getting Started
File Menu
Use the File menu (Figure 1-18) to open, save, and close databases; print; and
exit the program.
New
To create a new database file:
1. Choose File Close to close the current database.
2. Select File New to open the New dialog box (Figure 1-19).
1-17
Open
To open an F6TesT database:
1. Close the open database.
2. Select File Open or click the folder icon in the toolbar. The F6TesT
program displays the Select Database dialog box (Figure 1-5).
3. Navigate to the desired database.
4. Click Open.
Close
To close the currently open database:
1. Select File Close from the menu bar or click the small gray X ( ) in
the upper right corner of the screen. A dialog box appears asking if you
want to close the database. There is no prompt to save or discard changes.
2. Click Yes.
Save As
To make a copy of the open database:
1. Select File Save As.
2. Enter a new name for the database.
3. Click Save. The original database remains open.
4. Select File Close. The current database closes.
5. Select File Open.
6. Select the newly created copy.
7. Click Open.
1-18
1. Getting Started
Print Setup
Print Setup opens a standard Print dialog box for selecting and configuring a
printer for F6TesT reports (refer to Reports Tab on page 4-83).
1-19
Exit
To close F6TesT:
1. Select File Exit. A dialog box appears, asking if you want to exit
F6TesT (Figure 1-19).
Edit Menu
The Edit menu (Figure 1-22) provides basic functions for adding or modifying
items selected in the location tree or in table view.
There are two ways to access the menu:
1. Select Edit from the menu bar.
2. Right-click an item in the location tree or table view to access the pop-up
context menu.
Menu bar options are disabled or grayed out if they are not applicable to the
current context window.
1-20
1. Getting Started
Short-Cut Key
Insert
Ctrl + I
Append
Ctrl + A
Delete
Delete key
Copy
Ctrl+ C
Cut
Ctrl + X
Paste
Ctrl + V
Description
1-21
Short-Cut Key
Description
Multiple Copy
Multiple Cut
Multiple Delete
Move Down
Move Up
Find
Ctrl + F
Import from SS
File
Rename
Copy
Use Copy to copy one record (location, relay, test plan, or test), including all
related records under it, to the clipboard so that it can be pasted to a
compatible place elsewhere in the open database. For example, a relay can be
copied to another location, but a test plan or test can be copied only within the
same relay because it is linked to specific relay functions and parameters.
Copying blocks of data is enabled in some test definition dialog boxes.
To copy a record from one database to another:
1. Right-click the record.
2. Select Copy from the pop-up menu or press Ctrl + C.
3. Close the database.
4. Open the destination database.
1-22
1. Getting Started
1-23
3. Select the type of record that you want to cut, copy, or delete.
4. From the Evaluation drop-down menu, select an operating range for the
records to further refine the data. Choices are:
All
Pass
Fail
Op
No Op
5. Check or uncheck the Default for auto run check box to set the parameters
as the default parameters for autorun.
6. In the Date section, select the date(s) that you want included in the dialog
box for selection. Choices include:
All
Last Tested
Last Edit
Tested Date Range
Edited Date Range
7. Once you have established all parameters, click Find. F6TesT finds and
displays all records that match your query.
8. When finished, click Cut, Copy, or Delete. The dialog box disappears and
the location you selected in step 1 is displayed.
The button that is available at the botton of the dialog box
depends on the operation you selected from the Tools
menu. All other buttons, with the exception of Close, are
greyed out.
Find
Use Find (Figure 1-24) to specify a search of the database for records that
contain a specific string.
To find a record that contains a specific string:
1. Right-click the record.
2. Select Find from the pop-up menu or press Ctrl + F. The following dialog
box appears.
1-24
1. Getting Started
Module Menu
Module menu options (Figure 1-25) are described in Table 1-3. These options
are active only when a test record is selected.
1-25
Close
Save
Setup Menu
Setup menu (Figure 1-26) options are:
1-26
1. Getting Started
Communication Setup
To configure communications between the computer and the F6000
instrument:
1. Select Setup Communication Setup from the menu bar to open the
Communication Setup dialog box (Figure 1-27).
3. Click OK.
If necessary, click Refresh to refresh the communications. Click Verify
Connection to make sure that the connection to the F6000 is up and running.
1-27
Graphics Setup
Use the Graphics Setup dialog box (Figure 1-28) to set default color and
display properties for tests:
1. Choose Setup Graphics Setup. The Graphics Setup dialog box
appears.
1-28
1. Getting Started
1-29
Oscillograph Setup
The Oscillograph Setup dialog box enables you to set color and display
properties for X (voltage) and Y (current) sources for all test types.
Oscillographs can be displayed for each test by double-clicking the test,
clicking the Test tab, and then clicking the Oscillograph button. Figure 1-31
shows a sample oscillograph.
1-30
1. Getting Started
Setup
Description
1-31
Description
Zoom In
Un Zoom
Maximize
Graph
Restore Graph
Left Cursor
Right Cursor
1-32
1. Getting Started
1-33
Analog Tab
The Analog tab enables you to set the color for a maximum of 12 sources with
power system simulators. You can also select the width of the line (in
millimeters), as well as the style of the line.
1-34
1. Getting Started
1. To configure the Analog display, select the color as you did on the General
Properties tab.
2. From the Width drop-down menu, select the width of the line (1 5
millimeters).
3. From the Style drop-down menu, select the style of the line (solid, dash,
dot, dashdot, dashdotdot).
4. Click Apply.
5. Click OK to close the Oscillograph Setup window.
1-35
Test Defaults
To review test specification defaults before configuring new tests, select
Setup Test Defaults. The Test Defaults dialog box appears, with the
following three tabs:
System Parameters
Run/Auto Run
Miscellaneous
System Parameters
Enables you to select phase rotation and names and nominal or rated values of
relay frequencies, voltages, and currents.
1-36
1. Getting Started
Run/Auto Run
Controls the way in which testing proceeds when test failures are encountered.
1-37
Miscellaneous
Enables you to set display time formats for the program and for reports. It also
enables you to perform alarm maintenance, maintain log settings, and set the
transient duration.
1-38
1. Getting Started
Format Click the drop-down menus to set date and clock formats.
Relay parameter modifications Relay parameters can be changed,
modified, or deleted only when this box is checked. This applies to
existing relays, as well as copied and pasted relays.
1-39
The value in the Next Test Due field is calculated from the Last Tested and
Test Interval values. If a test is due, a blinking button (Figure 1-43) appears in
the field. Click the button to stop the blinking.
1-40
1. Getting Started
2. Select a definition name using the drop-down menu at the top of the dialog
box.
3. Check items in the data tree to be included in the test report and uncheck
items to be excluded.
4. Enter text for the report header and footer. If desired, click the button to
the right of the Logo field to browse to a bitmap file to be included as a
logo in the report.
5. If you do not want to use a default header, enter text in the Custom Page
Header field.
6. Click Close to modify an existing template or New to create a new
template.
7. If you click New to add a new template, enter a name in the Report
definition field.
8. Click Save.
Directories
This menu option is available only when no database is open. It displays the
path for the default database directory and enables you to change the path.
To change the default database directory path:
1. Select Setup Directories. The Default Database Directory dialog box
appears (Figure 1-45).
1-41
Change Language
This menu option enables you to change the language used in F6TesT.
Currently, the following languages are supported:
English
Spanish
Portuguese
Simplified Chinese
Traditional Chinese
Korean
French
1-42
1. Getting Started
Tools Menu
The Tools menu (Figure 1-47) includes the following options:
The options that appear on this menu depend on the tab that youre
currently on.
DB Compacting Preferences
Database compacting recovers disk space allocated to deleted records and
optimizes the location of the remaining database records. Database
compacting can be run automatically or on demand.
Repacking or compacting a large database can take a long time, so it is done
infrequently.
1-43
3. Click OK.
1-44
F6000 Flash Loader Calls the Flash Loader utility (Figure 1-49) to
install revised firmware in the F6000 instrument.
1. Getting Started
F6000 IP Set Opens a dialog box (Figure 1-51) that enables you to
enter the IP address the instrument uses for Ethernet communications.
1-45
Characteristics
Select Characteristics to open a submenu with the following options:
1-46
1. Getting Started
1-47
From here, you can add or delete manufacturers and model numbers.
New model numbers and manufacturers can be added when a relay is
added to the database. It is advisable to use the global dialog for this
purpose, however, to ensure consistent names and numbers and to avoid
duplicate entries (such as SEL and Schweitzer or SEL321 and
SEL-321).
To add a manufacturer:
1. In the drop-down menu, make sure that the desired manufacturer is not
already listed.
2. Click Add Mfr to add a new manufacturer. (Once a manufacturer name is
added, it can be deleted, but not edited.)
3. Add optional contact information in the Contact Information field.
4. Add a model number, if desired.
5. Click Save.
To add or change a model number:
1. Click a model number cell (either an empty cell or an existing Model
Number cell).
2. Enter an alphanumeric name. If a model number is modified, the new
model number applies to all associated relays.
3. Click Save.
1-48
1. Getting Started
Reports
This option enables you to generate global reports for relays.
To generate a report:
1. Select Tools Reports from the menu bar. The Reports dialog box
appears (Figure 1-54).
1-49
List of relays
Test plan summary
Test result details
3. From the Report Format drop-down menu, select either the long or short
definition, or select a customized format if one exists (see Global Report
Definitions on page 1-40 for more information).
4. To filter the report further, select any or all of the following options:
a. To display only the default test definitions for each test, click the
Default for auto run check box.
Default test definitions are set in the Test Definitions dialog
box that appears when you open a test definition. For more
information, refer to Chapter 5, Running Tests for more
information on test definition defaults.
1-50
1. Getting Started
To select a date, click on the date in the calendar. Click the forward or
backward buttons to scroll through the months.
5. Select the tests for which you want reports. To do this:
Click the grey box next to the relay(s) for which you want to generate
a report and then deselect the test(s) or test plan(s) you dont want. A
red check mark appears in the grey box next to the relay and all
children (see Figure 1-56).
or
Start at a lower level and select only the test(s) or test plan(s) that you
want.
1-51
Convert Database
Software upgrades sometimes involve a change in the database schema. As a
result, a new version of F6TesT may be unable to open a previous database. In
such cases, an Invalid F6 Database error is reported.
Once a database is converted to the new schema, it may not be possible to
convert it back to the old schema. It is prudent to make a backup copy of
the database before converting it.
Browse
Buttons
1-52
1. Getting Started
Template Library
This option enables you to view templates that are associated with each
F6TesT test. Select Tools Template Library. A dialog box similar to the
following appears.
Vector Calculator
See Appendix E, Vector Calculator, for instructions on how to use the
Vector Calculator.
Help Menu
There are two selections in the Help menu:
1. F6TesT Help, which opens the online F6TesT Users Guide.
2. About F6TesT, which displays the version number of F6TesT.
1-53
1-54
2. Relay Characteristics
Expected operating points are determined by either a formula or a look-up
table based on manufacturer or user-entered specifications. As Figure 1-9 on
page 1-11 shows, there are different types of characteristics. The
Characteristic library, contained in the sample database, is used to define time
characteristics (common to overcurrent, over/under voltage, and over/under
frequency functions) and differential characteristics. This includes
characteristics defined by standard or manufacturer-supplied equations or by
user-entered lookup tables (for example, values transcribed from published
curves that have no equation). When a relay record is created, a characteristic
is selected from the library to determine expected operating values.
Because standard mho and offset mho impedance characteristics are common
to all distance relays, they are selected and customized at the relay level.
General impedance characteristics, such as quadrilateral and other arc-line
combinations, are also defined only at the relay level. Simple differential
characteristics that are not found in the library may also be customized at the
relay level.
The F6TesT sample database includes a library of time and differential
characteristics.
Characteristics Library
To examine a characteristic or add a new one:
1. Select Tools Characteristics Edit Characteristics.
The Characteristics screen appears (Figure 2-1). Characteristics are
arranged by relay function and manufacturer.
72A-1968-01
Rev. E 3/2011
2-1
Characteristic Equations
A characteristic equation is a general formula or template for equations
specific to a manufacturer and relay function. Parameterized formulas for a
function, such as overcurrent, can apply to all manufacturers and relays.
2-2
2. Relay Characteristics
To select an equation:
1. Select the relay function type (except Differential) from the drop-down
menu.
2. Click Characteristic Equations. The Characteristic Equations screen
appears (Figure 2-2).
3. Select an equation name from the drop-down menu. The related equation
appears in the Trip time window.
If the desired equation does not exist:
1. Click New.
2. Enter the equation name in the Equation Name field.
3. Enter the equation in the equation field. Two reserved variables must be
present:
4. Click Parse Equation & Show Constants. If the syntax is correct, the
variables or constants, other than M and T, are displayed.
5. Click Save. The new equation is added to the database, ready to be used
for creating specific characteristics.
To copy a formula under a different name:
1. Select the equation.
2. Select Edit Copy.
3. Select Edit Paste.
4. In the Equation Name field, enter a new name.
5. Click Save.
6. Click Close.
2-3
Characteristic Constants
The next step is to define a specific relay characteristic by selecting one of the
previously defined general equations and supplying the constants:
1. Select the relay function type (except Differential) from the drop-down
menu.
2. Click the Characteristic Constants button.
The Characteristic Constants screen appears (Figure 2-3).
2-4
2. Relay Characteristics
2-5
2-6
2. Relay Characteristics
2-7
2-8
2. Relay Characteristics
On the other hand, some manufacturers have overcurrent relays, each of which
uses different equations and/or constants for similar characteristics. In such
cases, it is helpful to prefix the equation name with the manufacturer and to
add a suffix using the model number or the series model family. Table 2-1
shows examples of this convention for three General Electric models.
Table 2-1 Same-Characteristic Equations and Constants
Characteristic Name
Time = T * (A / (M^P 1) + C)
A = 3.992; P = 0.02; C=0.0982
Time = T * (A / (M^P 1) + C) * D
A = 19.61; P = 2; C = 0.491; D = 0.2
Time = T * A / (M^P 1)
A = 13.5; P = 1
Look-up Table
Use a look-up table (Figure 2-8) when the relay characteristic does not have an
equation.
To create a look-up table:
1. Click Look-Up Table.
2. Select a manufacturer from the drop-down menu or enter a new
manufacturer.
3. Enter a characteristic name and description.
The lookup table characteristic is added to the list of characteristics
applied to the specified manufacturer. If a characteristic already in the list
is selected, an error is reported if the name exists in the list of
characteristics defined by a characteristic equation. Only table-defined
characteristics can be displayed and modified in the lookup table.
When you click outside the Characteristic Name field after entering a new
name, the Key In button is enabled (except when Differential is selected in
the drop-down menu at the top of the screen).
4. Click Key In to define the number of columns (minimum 12) and enter
values for Tap, Time Dial, and times in the table cells.
5. Click Save.
6. Check the Display Graph box to view a graph of the new characteristic.
2-9
2-10
2. Relay Characteristics
3. Click Open. An Import Details group (Figure 2-9) appears just below the
Key In and Import buttons in the look-up table.
Differential Characteristics
The Characteristic Library uses a look-up table for differential characteristics
(Figure 2-10).
2-11
2-12
2. Relay Characteristics
2-13
2-14
2. Relay Characteristics
After the copy process is complete, you can open another batch copy dialog
box and select the previous destination database as the source database to
compare the characteristics.
When a relay is copied from one database to another, existing
characteristics in the target database are checked. If a characteristic does
not exist, the characteristic is copied from the source database into the
target database.
2-15
2-16
3. Creating a Relay
Many of the dialog boxes and windows described in this chapter open with the
default values defined in the Test Defaults dialog box (see Test Defaults on
page 1-36).
To review these settings before adding a relay to a location, select Setup
Test Defaults from the menu bar.
72A-1968-01
Rev. E 3/2011
3-1
3. Press Enter.
The cursor jumps to the Model field.
4. Select a relay model from the drop-down menu. If the model is not
included in the list:
a. Enter the number in the Model column. A dialog box appears, asking
if you want to add the model number to the relay model list.
b. Click Yes.
5. Press Enter.
6. Double-click the Relay Id to open the relay table view.
Test Plan
Relay Parameters
Connections & Signals
Notebook
To open Relay Table View, double-click the relay record in the Location
Table View.
Analog Signals
Digital Inputs and Triggers
Digital Outputs
Wired Logic Inputs
IEC GSE Subscriptions
2. Click the Digital Inputs and Triggers tab (Figure 3-2) to define logic
inputs from the relay to the F6000:
3-2
3. Creating a Relay
Analog Signals Select this tab in Ramp and SSIMUL test modules
to predefine a source configuration. This facilitates source selection
for these test modules when using a nonstandard, predefined source
configuration. Other test modules use only automatic source
configuration, and this tab does not apply.
You can also select this tab to document a normal connection of the
relay to the power system, even if it is not used for testing.
3-3
Notebook
The test originator can use the Notebook tab (Figure 3-3) to enter general
instructions. Later, a user can enter comments.
3-4
3. Creating a Relay
To add comments:
1. Click the Notebook tab.
2. Enter instructions in the Originator Comments text box.
3. Click Attach to attach a file. For example, an attached file can be the relay
instruction manual or a connection diagram, which is opened from the
Notebook page using an application such as Microsoft Word, Adobe
Acrobat, or Visio.
Test Plan
When table view is opened, the Test Plan tab is selected (Figure 3-4). Test
plans are not relay parameters (see Chapter 4, Creating Test Modules).
Relay Parameters
Initially, the Relay Parameters tab (Figure 3-5) displays the values entered
with the Test Defaults dialog box (see Test Defaults on page 1-36). These
parameters are nominal frequency, voltage, and current, and can be modified.
The maximum test voltage and current are required to limit the test to values
that do not damage the relay and that are within the range of the F6000
sources. Note that nominal current, In, is the basis for multiples that determine
expected relay operation.
3-5
3-6
3. Creating a Relay
Function Window
Each type of relay function has its own set-up, displayed on a separate screen.
To access the setup for a function:
1. Select the function in the table on the right.
2. Click Show. F6TesT displays the window for the function. Figure 3-6 is
an example of impedance.
3-7
For example, a current function (Figure 3-7) shows a matrix of possible test
elements: rows are setting elements; columns are phase or sequence current
quantities. The graph on the right shows the test element matrix for
Impedance, where rows are zones and columns are phase elements.
3-8
3. Creating a Relay
Adding a Function
The following steps can be used to add all functions except Impedance,
for which the procedure can be slightly different. See the next section for
the procedure.
To add a function:
1. Click Add. The Add Relay Function dialog box appears (Figure 3-8).
ABB
AREVA
ENERTEC
3-9
ERLPhase
GE
ICE
PROTECTS
SCHLUMBERGER
SIEMENS
TOSHIBA
3-10
3. Creating a Relay
3-11
3-12
3. Creating a Relay
3-13
Copying a Function
To create a function based on an existing function:
1. Select the function in the table on the right side of the tab.
2. Click Copy. With a copy of the selected function on the clipboard, the
Paste button is enabled.
3. Click Paste. The copy is pasted into the first available row in the table of
functions. The copy is named Copy of....
4. Select the copy.
5. Enter a new name.
6. Press Enter.
3-14
3. Creating a Relay
4 low set levels: V<, V<<, V<<<, V<<<<, or f<, f<<, f<<<, f<<<<
4 high set levels: V>, V>>, V>>>, V>>>>, or f>, f>>, f>>>, f>>>>
To view a setting, select a cell in the Pickup Settings table. To change the
scaling, use the Scale Mode drop-down menu below the graph.
3-15
3-16
3. Creating a Relay
When displaying the composite graph, all elements are referred to the
lowest set element, as shown in Figure 3-17. Thus, if pickup settings are I>
= 2A, I>> = 15A, and I>>> = 30A, then on the graph, 3A corresponds to a
multiple of 3/2 = 1.5, 15A corresponds to a multiple of 15/2 = 7.5, and 30A
corresponds to a multiple of 30/2 = 15.
Generic Functions
The Generic function screen (Figure 3-18) enables you to define custom
variables that aid in testing relays. This screen enables you to create the label,
assign a value, select a type (voltage, current, frequency, etc.), and enter
comments. Variables can be Primary or Secondary; values can be entered as
formulas. Variables can also be used in test modules.
3-17
3-18
3. Creating a Relay
If you do not check this box, the values on this screen will
not be updated.
Impedance Functions
The Impedance Function screen (Figure 3-20) includes an Operating Time
table on the left, with up to eight distance zones and columns for zone
elements to test phase quantities.
3-19
3-20
3. Creating a Relay
3-21
a. For mho, enter the Forward Reach and Offset from Origin
(Figure 3-23).
General Characteristic
Use the General Characteristic screen to construct a variety of closed shapes
bounded by arcs and lines to represent an operating characteristic, such as a
quadrilateral or mho characteristic with blinders.
If you select General in the Characteristic Type drop-down menu of the Add
or Modify Zone dialog box, the next display is the General Characteristic
screen (Figure 3-24). Use the buttons and columns to define lines and arcs:
3-22
3. Creating a Relay
3-23
3-24
3. Creating a Relay
Directional Functions
Overcurrent relays can have directional elements, which use a polarizing
voltage or current to control operation. The function is defined in the
Directional Function screen (Figure 3-27). The screen includes a table of
values for each phase and a phasor diagram that shows the relationship
between the operating and polarizing quantity.
3-25
3-26
3. Creating a Relay
Differential Functions
To configure a differential relay function:
1. Select the function in the Relay Functions table.
2. Click Show. The Differential Relay Function screen appears
(Figure 3-28). The screen has three tabs:
Differential Function
Compensation Settings
Transformer Parameter
3-27
3-28
3. Creating a Relay
3-29
3-30
3. Creating a Relay
3-31
3-32
Test Plans
To create a test plan:
1. Expand the location tree to find the desired relay.
2. Right-click the relay and select Append from the pop-up menu.
F6TesT adds the new test plan to the first available row in the Test Plan
tab. The default plan name, New Test Plan, is highlighted, indicating that
the name can be changed (Figure 4-1). The name also appears in the
location tree under the selected relay.
72A-1968-01
Rev. E 3/2011
4-1
Tests
Adding tests to a plan is similar to adding test plans to a relay.
To create a test:
1. Expand the display of the relay in the location tree and select the test plan.
The tests already configured for the plan appear in the Test tab in Table
View.
2. Right-click the test plan (or anywhere in Table View) and select Append
from the pop-up menu. The new test is added to the first available row in
the Test tab. The default name, New Test Module, is highlighted,
indicating that the module name can be changed (Figure 4-2).
Test Types
Table 4-1 Supported Test Types
Test Type
Description
DiffChar
Directional
Manipulates polarizing and operating quantities to search for directional lead, lag,
and maximum torque angle.
Extern
Launches a user-specified program in the specified drive and path. Also connects
to a relay.
I-Char
Notebook
A two-section notepad for test instructions, comments, etc. Files can be attached
for viewing with other software; e.g., a Microsoft Word or Adobe Acrobat
document containing schematics or manufacturer instructions.
Ramp
Uses linear ramp of source value to find operate points similar to ProTesT; e.g.,
tests for relay pickup, relay drop out, synchronization, directional test, or voltage
regulator test.
SSIMUL
A state simulation test that approximates a real fault event, with stepped
steady-state values of voltage and current.
VF-Char
VpHzRamp
Tests the pickup and dropout of Volt per Hertz relays by simultaneously ramping
the voltage amplitudes and frequency.
WaveSim
Z-Char
4-3
Description
ZMTA
Z-Time
Measures operating time of a distance element for selected test points and
evaluates each test point based on expected time. It is used for testing
characteristic boundary points of a distance relay zone and for plotting the
operating time for faults along a fixed angle.
Test Definitions
After creating a test, you need to create one or more test definitions. When
there are multiple definitions, one is selected as the default to be used by
AutoRun.
To set up a test definition:
1. In table view, double-click the test record. If the test does not have any
definitions, the following dialog box appears (Figure 4-3). The test
definition that you create automatically becomes the default.
4-4
4-5
6. If you are creating a new test definition, the definition tabs appear
(Figure 4-7).
If you are opening an existing test definition, double-click the test name to
open the definition. A screen appears with the test definition. The layout
of the screen depends on the selected test type, but usually includes several
tabs for defining various aspects of the test model. Figure 4-7 shows the
tabs for a typical window.
The tabs are discussed in the following order:
Test Elements
Test Configuration
Test Points
Measurements
Test Tab
Reports
Notebook
Overcurrent
Figure 4-6 shows the Test Elements tab for overcurrent. Select the overcurrent
function from the drop-down menu and click the elements to be tested.
4-6
Impedance
Figure 4-7 shows the Test Elements tab for impedance tests. Select from the
Zone elements defined for that function under Relay Parameters.
4-7
Directional
Figure 4-8 shows the Test Elements tab for a directional test. Select a phase or
sequence element.
4-8
Differential
Figure 4-9 shows the Test Elements tab for differential tests.
Fault Calculation
Test Timing and Trigger Selection
Digital Outputs
Source Configuration
4-9
Test Method
Test Timing and Trigger Selection
Digital Outputs
Source Configuration
Figure 4-10 Fault Calculation Tab for Current, Voltage, and Frequency
Time Characteristics
4-10
Fault Calculation automatically uses the nominal voltage defined under Relay
Parameters as the default prefault voltage. The test current is normally the
user-entered test current or is calculated based on the test point multiple of
setting. A prefault current can also be entered, and the actual test current takes
this into consideration.
The maximum test current or voltage is automatically calculated, based on the
relay parameter values previously entered, but may be changed to a lower
value. The maximum also depends on the instrument limits.
For an overcurrent element, if directional control is selected in Relay
Parameters and checked in the Relay Elements tab, the fault voltage amplitude
and angle are entered, as shown below. Ph-N voltage values are used for
testing AN, AB, and CN elements, while Ph-Ph, 3Ph values are used for
testing AB, BC, CA, ABC and 3I2 elements.
For 3I0 elements, a Ph-N fault is applied, but the polarizing values are based
on the entries for 3I0 element, not on the general fault values above. The value
of the operating current is the residual current (3I0 and not I0).
F6TesT calculates the actual test values output by the test instrument. The
polarizing voltage or current applied here is used only for testing time
overcurrent response and to do a quick directional test, by applying a forward
or reversed fault; more accurate directional response is tested in a separate
module.
4-11
4-12
Differential Characteristics
Figure 4-12 shows the Fault Calculation screen for Differential characteristics.
4-13
Is vs. Ip
The test applies fixed levels of one source and varies the other, starting in the
middle of the restraint region where high side and low side currents are
balanced. Ip is set at 0 and Is at 180. This can be done in the following two
ways, or a combination of both:
Fix Ip and search for Is. On a graph of Is vs. Ip (Figure 4-13), this
detects the lower boundary of the restraint region.
Fix Is and search for Ip. This detects the upper boundary of the operate
region, using lower Is current than would be required if Ip were held
constant. If the combination is selected, two tests are performed, first
fixing Ip, then fixing Is, to map out both upper and lower boundaries
of the restraint region, as shown.
The restraint region is bounded between the upper and lower curves
(Figure 4-13).
4-14
Constant Current
Constant Voltage
Constant Source Z
Use this tab to select a method and specify prefault values and methods for
relay polarization or initializing.
4-15
Constant Current
A fixed test current is applied and voltage is calculated, corresponding to the
impedance. Set the maximum test voltage (Max. Acceptable Voltage). For a
remote fault (high impedance), the required test voltage may be too high, so
F6TesT automatically limits the voltage to the maximum specified value and
recalculates the test current corresponding to the impedance of the test point.
If this occurs, the background for the Actual test value field in the Test tab
becomes white (Figure 4-15).
Constant Voltage
A fixed test voltage is applied, for phase-neutral or phase-phase tests, and
current is calculated corresponding to the test point impedance. Set the
maximum test current (Max. Acceptable Current), which must be within the
limits of the F6000 sources. For close-in faults (low impedance), the required
test current may be too high, so F6TesT automatically sets the test current to
this limit and recalculates the test voltage. If this occurs, the background for
the Actual test value field in the Test tab becomes white (Figure 4-15).
4-16
Constant Source Z
Fill in the source impedance values (Figure 4-14) in the power system model,
which calculates voltage and current quantities for each impedance test point.
A maximum current is specified, which limits the test for close-in faults. If the
test point requires a current that exceeds this limit, the backgrounds for the
Actual Voltage and Actual Current fields in the Test tab become white
(Figure 4-15). These points are not tested and have a result of ITH, meaning
the current is too high. This test method tests the dynamic or expanded mho
characteristics.
A fixed test voltage is applied, for phase-neutral or phase-phase tests, and
current is calculated corresponding to the test point impedance. Set the
maximum test current (Max. Acceptable Current), which must be within the
limits of the F6000 sources. For close-in faults (low impedance), the required
test current may be too high, so F6TesT automatically sets the test current to
this limit and recalculates the test voltage. If this occurs, the background for
the Actual test value field in the Test tab becomes white (Figure 4-15).
Constant Source Z
Fill in the source impedance values (Figure 4-16) in the power system model,
which calculates voltage and current quantities for each impedance test point.
A maximum current is specified, which limits the test for close-in faults. If the
test point requires a current that exceeds this limit, the backgrounds for the
Actual Voltage and Actual Current fields in the Test tab become white
(Figure 4-15). These points are not tested and have a result of ITH, meaning
the current is too high. This test method tests the dynamic or expanded mho
characteristics.
4-17
4-18
4-19
WaveSim Characteristics
Figure 4-19 shows the WaveSim Test Configuration tab.
Test Method
1. Click the Test Method button
2. From the Type of Simulation drop-down menu, select the type of
simulation you want to use in the test. Choices include:
3. In the Time Unit section, select the time unit to be used for the test.
Choices include:
4-20
Seconds
Milliseconds
Cycles
4. From the CT Direction drop-down menu, select the starting point. Choices
include:
Towards Bus
Towards Line
4-21
Time Between Shots is the wait between test points, with the fault no
longer applied, to allow the relay to reset.
4-22
Instrument Model
Value of the Required Test Injection
Test Module Type
4-23
Instrument Model
Figure 4-23 shows the source configuration for the F6150 and the F6150A for
three voltages and a current on the left bank and three currents on the right
bank.
F6150
F6150A
Figure 4-23 Sample Source Configuration for the F6150 and the F6150A
The F6150A model has one less amplifier on both the left and right banks. For
more information on F6000 sources, refer to the F6000 User Guide.
Z-Time, Z-Char, ZMTA. Three voltages on the left bank and three
currents on the right bank.
F6150
4-24
F6150A
F6150A
I-Char and Directional. At least three voltages and three currents for
fault types AN, BN, CN, AB, BC, CA, ABC and Negative Sequence,
as shown below, plus the operating and polarizing quantity for
zero-sequence and negative-sequence directional relays, if required.
The polarizing quantity may be an internally derived voltage from the
three-phase voltages, in which case a fourth source on the left-hand
bank is not required, or it may be a separate voltage (VP) or current
(IP) source. The operating current may be internally derived from the
three-phase currents or may be a separate source (IN).
The figure below shows the configuration for a separate polarizing
current (a separate polarizing voltage is shown as VP) and a separate
operating current.
4-25
F6150
F6150A
4-26
DiffChar. Six currents for three-phase relay testing and two currents
for single-phase relay testing, all on the right-hand bank. A single
voltage is used if the Use Voltage option is checked in the Test
Configuration tab.
Three-Phase Differential Testing
F6150
F6150A
4-27
F6150A
4-28
On the graph. Double-click on the graph or click once and then click
Add Point to List.
One at a time. Enter either multiple or amplitude in the edit area and
click Add Point to List.
Multiple points in an arithmetic sequence.
1. Click Add Multiple Points. The Add Multiple Test Points dialog
box appears (Figure 4-25).
4-29
4-30
4-31
4-32
Select the zone and enter test points at a fixed line angle at different
values of %Zone (Figure 4-29).
4-33
4-34
4-35
4-36
4-37
4-38
4-39
Opens the Graph Scale dialog box for manually setting the scale. If
performed in the Test Points or Test Lines tab, the scale changes can be
saved together with the rest of the test.
The scale changes affect a general fault type. For example, changes made
in the scale for fault type Ph-N affect fault types AN, BN, and CN but
not other fault types, such as AB, BC, CA, and ABC.
Scale changes made in the Test tab are generally not saved. However, for
test modules (as ZMTA) that have no Test Points or Test Lines tab, but
have only a Test Tab to show the graph, changes to scale made in the
Test tab can be saved.
Polar Grid
R X Grid
Setup
Opens the Graphics Setup dialog box to set properties for the individual
test graph. This dialog box is selected from the Setup menu to define
default properties for all test graphs, as described in Graphics Setup on
page -25.
When used at the test level, the new settings remain only while the test is
open. The graphic properties revert to the default settings.
4-40
Tolerance
Maximize Graph
Zoom In
ZoomOut/Unzoom
Show Reference
Characteristic
The characteristic of relay under test. The relay will be tested with
respect to this characteristic. By default, this option is checked.
Show Actual
Characteristic
The options that appear in the graph pop-up menu depend on whether
youre on the Test tab or the Test Points tab.
4-41
The Z-Char test module does not have a Test Points tab, but it does have a
Test Lines tab.
To delete duplicate test points on the Test tab:
1. Select a test point.
2. Click Delete Selected Point.
To override a value, double-click and mark the value with the cursor
and type a new value. If the original value is NoOp, use the backspace
key to delete it before entering a new value.
The entries are validated in such a way that Tmin should not be more
than Texp and Tmax should not be less than Texp.
To increase all the values, enter Tmax first, then Texp and Tmin. To
decrease the values, modify Tmin first, then Texp and Tmax.
To e nter a value of NoOp (no operation), double-click the cell and
type the letter N (either uppercase or lowercase).
4-42
Depending on the test module type the columns may be sorted as follows:
Test Type
Z-Time
Z-Char
I-Char
V-Char
F-Char
DiffChar
Measurements Tab
Figure 4-36 shows the WaveSim Measurements tab.
4-43
Test Tab
The Test tab (Figure 4-37) shows test points, expected values, and the record
of actual test results with pass/fail evaluation, depending on the test type.
Once Test Elements, Test Configuration, and Test Points have been defined,
the Test tab is the only tab that you need to use when running or rerunning a
test.
4-44
Phasor Diagrams
The phasor diagram (Figure 4-38) is a separate window opened from the Test
tab that shows the voltage and current phasors and their values for each test
point, before, during, or after testing.
If separate external sources are selected from the I0 tab, the source
column can include Vpol, Ipol or Iop.
If internally derived quantities are selected, the derived quantities are
shown below the source table (Figure 4-39).
4-45
The fault voltages may be shown in wye or delta. The prefault voltages and the
symmetrical components of voltages and currents may be displayed by
checking their associated boxes.
This applies to the Z, I-Char, VF-Char and Directional test modules. The
Differential and SSIMUL test modules have different phasor diagrams. Ramp
does not have one.
4-46
Directional Test
The objective of the directional test (Figure 4-41) is to find the boundary of
operation and no operation of the relay, which should be near the specified
lead and lag angles from the MTA. Defaults are Lead = MTA + 90, Lag =
MTA 90. A binary search is performed using a series of test shots to find
the lead and lag operating points. A test shot consists of a prefault state and a
fault state. The MTA is calculated by getting the arithmetical average of the
actual lead and lag values.
4-47
The graph on the right displays the expected directional characteristics and the
voltage phasors for a selected fault type. The fault voltage and polarizing
voltages are highlighted. When the test runs, performing a binary search, the
operating current phasor is assumed to be at the same angle as the moving test
line. At the end of the search the actual lead, lag, and MTA lines are drawn.
While the test is running, the graph displays the currently running fault type.
When the test is not running:
Click an element tab (A, B, C, Zero Seq, or Neg Seq) to show the first
fault type that is checked. Otherwise, it shows the first fault type in the
list.
Right-click the graph to select from the pop-up menu other fault types
for viewing (Figure 4-41).
Use the controls below the graph to reorient the graph by selecting the
reference quantity and its angle with respect to the horizontal.
All other lines and phasors are drawn relative to this reference. The actual
angles of the F6000 test currents and voltages may be different from those
shown on the graph. They can be viewed by checking the Show Phasors box to
display the phasor diagram, as well as on the F6000 display.
Differential Test
The Test tab for a Differential test shows test points plus actual test results,
%Error, and pass/fail evaluations. Test points appear as follows:
4-48
4-49
4-50
4-51
Figure 4-45 shows two different phasor diagrams for three-phase testing:
4-52
Z-Time Test
Figure 4-47 shows the Test tab for a Z-Time test. Test points are plotted on the
graph together with the reference characteristics. The table on the left shows
the details for each point, copied from the Test Points tab, along with the
operate time and Pass/Fail evaluation, if test has been performed.
To see additional results, drag the table scroll bar to the right:
%Error, the actual zone which operated (based on the operate time)
Test voltage and current that were applied
4-53
4-54
To perform a Spiral test, click the Spiral option button in the Run Tests
group in the bottom left corner of the tab.
Use a Spiral test to show a large number of test points, starting from the center
and proceeding outward in a spiral manner until the graph area is filled. If no
testing has yet been performed, no test points are shown.
The number of horizontal and vertical divisions of the graph can be selected
before running the test (Figure 4-49).
4-55
Z-Char Test
The Test tab for Z-Char (Figure 4-50) graphs results as dots (circles, squares,
diamonds, etc.) for each of the zones. The table shows the details for each
point:
4-56
ZMTA Test
The Z Maximum Torque Angle (ZMTA) test applies only to mho
characteristics. The test is a special form of Z-Char test module, applying a
fault arc sweep (instead of straight test lines) over a range of angles, from
outside to inside the static zone of protection. Like all Z tests, the prefault and
fault conditions are specified with the Test Method button in the Test
Configuration tab.
The Test tab graph (Figure 4-51) displays the calculated expected MTA and
the lead and lag angles on the zone boundary.
4-57
WaveSim Test
The WaveSim test measures the power swing between dz and dt.
The WaveSim test is configured in the Test tab (Figure 4-52).
4-58
4-59
4-60
Voltage amplitudes
Current amplitudes
Voltage phase angles
Current phase angles
Frequency of voltage and/or current
To set up a Ramp:
1. On the Test Configuration tab, select Auto Ramp or Manual Ramp.
2. Select Voltage, Current, or Frequency.
4-61
The test allows for three kinds of ramp: a single ramp from an offset toward a
limit (stepped); a double ramp, which ramps toward a limit, stops on relay
pickup, waits a bit, and ramps back in the opposite direction to dropout
(pulsed); and frequency ramp of voltage and/or current sources (smooth).
A stepped ramp is a simple linear ramp that proceeds in staircase fashion
(Figure 4-55).
4-62
4-63
4-64
Offset and offset duration (length of time to remain at the offset before
the ramp begins) values can be zero or some prefault value for current;
for voltage, normal prefault voltage would normally be used, but zero
may be used also; for frequency, enter normal base frequency.
Delta value and Delta Time specify the ramp increments; each step is
held for Delta Time before the next step. This allows the relay to
detect the change.
The Limit value determines when the ramp stops, if the relay has not
already output a trip signal. For current, the limit value (or the offset,
whichever is higher) also determines the source range required for the
Action source. Normally an offset somewhat below the expected
pickup and a limit not too much higher is used. If the relay does not
operate, a NoOp result is recorded.
An action multiplier is available in the Amplitude column of the
source table in the Test tab. The form is A*n, where n is a constant
from 0.001 to 1000, in increments of 0.001.
9. Click the Digital Output button. The following dialog box appears.
Pulsed Ramp
For a Pulsed ramp there are two additional Action details: Pulse Duration and
Wait (Figure 4-60).
4-65
Enter the offset and offset duration as you would for a simple ramp; this
should be a normal, non-operating value. The initial current would be close to
the pickup setting. The ramp proceeds from there to the limit. After each ramp
step, however, the test value returns to the offset for a Wait time, which should
be long enough for the relay windings to cool down and for the relay to return
to a quiescent state before the next incremental pulse.
Double Ramp
Enter parameters for double ramp Action (Figure 4-61) in the same manner as
for a single ramp. After the Ramp 1 Limit, enter a Wait time to allow relay
output to stabilize before starting Ramp 2 in the opposite direction. The wait
time begins when the trip signal occurs. Ramp amplitude can either start low,
go higher, then go back down, or it can start high, go lower, then go back up.
4-66
1. On the Test Configuration tab, select a trigger name from the drop-down
menu (defined on the Connections & Signals tab; see Connections &
Signals on page 3-2) to identify which F6000 input is used and the
transition, such as Open to Close.
2. Specify the Delay and Duration.
These values enable the trigger signal to be conditioned to ensure a solid
pickup by the relay. When each ramp step occurs, the F6000 can disable
the trigger input for the sense Delay time, to allow relay output to
stabilize. Once the signal input is armed, if a trip signal occurs, a sense
Duration timer is started; if the trip signal drops out before the timer
expires, no trip is recorded. This allows debouncing of contact chatter.
These values are sometimes useful for older electromechanical relays to
allow the ramp to yield a good test result. Numerical relays do not require
this, so Delay and Duration can normally be set to zero.
3. Select time units in cycles, milliseconds, or seconds. Changing the time
units converts all time values to the selected unit.
4. In the Measurements area at the bottom left, enter a descriptive name for
Test Objective, the expected value (setpoint), and tolerance percentages.
The expected values are named variables, Exp1 and, in a double ramp,
Exp2, which can be used in formulas in other cells of the test definition.
For example, in a double ramp, the third row of the measurement table
uses a default formula of Exp1/Exp2 to compare the expected values.
(You can change this default formula.) The formula used to compare the
expected values is also used to compare the actual values.
4-67
4-68
The Delay and Duration triggers are similar to those of the standard ramp.
6. In the Measurements area, enter the Volts/Hertz at which the relay is
expected to pick up or drop out.
The tolerances can be entered in percent or in absolute values of V/Hz.
The equivalent voltage and frequency levels are calculated. After running
the test:
The graph of the V/Hz ramp (Figure 4-63) can be shown any time after the
Action conditions are entered. The graph shows the expected and actual
results using vertical lines that intersect the voltage, frequency, and Volts/Hz
curves.
4-69
4-70
2. In the table for the first state, enter amplitude, phase, and frequency.
State No. 1 is normally the prefault state, representing normal secondary
injection to the relay or relay panel being tested.
a. If the same frequency applies for all states, leave the box checked. The
frequency appears only in State 1. It is possible to have different frequencies for each of the sources.
b. If the frequency is to change during the test, uncheck the box. A
frequency column appears for each state. When the box is unchecked,
the frequency becomes the same for all sources. Changing the
frequency of one source changes the frequency of all sources.
Instead of entering a number in the emplitude, phase, and
frequency fields, you can enter INH (inherits) to indicate
that a parameter in the current state is the same as that of
the preceding state.
3. Enter the Maximum Duration for the state. The time unit can be selected
as cycles (referred to the relays nominal frequency), milliseconds, or
seconds. The minimum duration for each state is 1 cycle.
When moving from one state to the next, after expiration of the time
duration and if the instantaneous amplitude value of a preceding state
current source differs from the new state, a DC component is produced in
the currents to smooth the transition, such as when moving from a prefault
to a fault condition. The DC component decays at a rate dictated by the
specified L/R Time constant. Normal values are 10 ms for high-voltage
systems. The time constant increases for locations close to generating
stations.
When no trigger transition is specified, the state runs for the specified
maximum duration. When a Trig Transition is specified and the trigger
condition is met during execution of a state, the state ends immediately
and transitions to the next state.
A trigger can be selected from digital inputs, LN1 through LN8 or one of
the triggers previously defined at the relay level. The trigger sense
condition can be selected for triggers LN1 through LN8 but not for
predefined triggers.
4. Click Append State to add a state to the right end of the table or click
Insert State to insert a state to the left of a selected state.
4-71
5. In each new state table, enter an amplitude and phase for each source, the
state duration, and a descriptive state name in place of the default name. If
most of the values are the same as another state, use copy and paste of
contiguous cells.
The Test tab in Figure 4-64 shows four states for the sources named in the
source table. Normally, three states can represent simple Prefault, Fault,
and Postfault (breaker operate) conditions. Here, the fourth state
represents a reclose into restored normal conditions (transitory fault). A
different scenario could be reclosure into a fault condition, with a fifth
state for breaker operation. Multiple reclosures can be used to test lockout
after a number of failed reclosures.
To bring a state in view in the table, either:
Use the horizontal scroll bar to move the display right and left.
Use the arrows to the right of the State No/State Name field to select
the state.
To delete a state, select any cell in the state and click Delete State.
Fault Rotate
The Fault Rotate button applies to three-phase voltages and/or currents only.
For an ABC phase rotation, the previous values of phase A go to phase B, the
previous values of phase B go to phase C, and the previous values of phase C
go to phase A.
Display Phasors
The Display Phasors button opens a dialog box with a phasor diagram for each
state (Figure 4-65).
4-72
4-73
5. Click OK.
Time Units
Select or change the time units displayed for state duration: seconds,
milliseconds, or cycles. Any previously entered values are converted to the
display units.
Run Mode
Select the Run Mode from the drop-down menu.
4-74
Oscillograph
The Oscillograph window displays the analog voltage and current waveforms
as well as the digital outputs and timers. It also enables you to visualize and
more closely analyze the test results.
To display an oscillograph for the SSIMUL test:
4-75
Measurement Tab
The Measurement tab (Figure 4-69) enables you to set up timers to record
operation of trigger inputs and relays. At least one timer is created as a default.
To add another timer:
1. Click Append. Another line appears in the table.
2. Enter a descriptive name in the Timer Name field.
4-76
3. Click in the Start field and select from the drop-down menu a state in
which to start the timer.
4. Click in the Stop field and select from the drop-down menu a trigger name
to stop the timer.
4-77
1. Double-click the EXTERN module listed on the Test tab for the
appropriate test plan. The Save Test Definition to dialog box appears. See
Test Definitions on page 4-4 for information on test definitions.
2. Once the test definition has been selected, click OK. The following tabs
appear.
To run a test:
4-78
1. In the Working Directory field, enter the start-up path for the external
program. This can be any directory on your computer. The default is the
current database path.
2. In the Program name field, enter the command line name to execute the
program. The program must have an .exe extension.
3. In the Arguments field, enter the name of a file that the application will
open during the test. The file name must be enclosed in double quotes (for
example, TestFile.txt).
4. In the File to External Program field, enter the name of an ASCII input file
for the test. Data will be written to that file from the Originator side of the
Notebook tab.
5. In the File from External Program field, enter the name of the output file
that will be generated from the external application. If the application
writes text output to a file, it will be imported into the User side of the
Notebook tab.
6. If data is to be appended to an existing output file, check the Append
Data from External Program check box. This appends data from the
external program to the User Comments panel of the Notebook tab.
7. Click the Run button in the toolbar (see Figure 1-13). For more
information on the Run toolbar, see Running the Test on page 5-4.
For information on using the Autorun feature, see Using Autorun on
page 4-83.
4-79
4-80
4-81
4-82
Using Autorun
The Autorun feature on the Test tab (Test Tab on page 4-44) enables you to
specify test to run automatically. The following options are available:
Reports Tab
You can prepare a formatted report for each test definition on the Reports tab
(Figure 4-74).
4-83
4-84
4-85
MS Word
Rich Text Format (.rtf)
Tab-separated text
Text
4-86
Notebook Tab
The Notebook tab provides a two-column notepad for originator test
instructions and user comments. Notebooks are available at the relay level and
for each test module. You can document relay identification and settings or
provide online instructions for relay setup, manual calibration, and visual
inspection.
You can attach a file, create a link pointing to a file, or copy the file to the
Notebook folder.
See Notebook on page 3-4 for information on configuring the Notebook tab.
4-87
4-88
5. Running Tests
Selecting a Test
To select a test:
1. Expand the Location and Relay in the location tree and select the test plan.
The tests are listed in Table View (Figure 5-1).
72A-1968-01
Rev. E 3/2011
5-1
5-2
5. Running Tests
Simulation Mode
If no F6000 instrument or relay is available, it is possible to verify the
operation of a test by using Simulation Mode.
To enable this mode, select Tools Simulation Mode from the menu bar.
Select this option to run a test with no instrument connected. Simulated test
values are generated and posted in the Test tab and on the characteristic graph.
5-3
If too many points result in a failed evaluation, the test may also stop
automatically, as configured in the Test Defaults dialog box.
3. Click Pause (double vertical bars) in the Run toolbar to pause a running
test between test points.
4. Click the Run button to resume.
5-4
5. Running Tests
To hide a column:
1. Right-click on the table and select Hide Selected Columns during test
from the pop-up menu. The Hide Columns dialog box appears
(Figure 5-6).
5-5
AutoRun
Once a test plan has been populated with tests, it is possible to run more than
one test in a nonstop sequence.
To run multiple tests in a plan:
1. Select Setup Test Defaults Run/Auto Run to verify the Run/Auto
Run defaults.
2. Select the test plan in the location tree to display the individual tests in
Table View.
3. Check the box to the left of each test to be run in nonstop sequence. It is
also possible to quickly check or uncheck all tests by right clicking
anywhere on the test name column and selecting either Check All or
Uncheck All from the pop-up menu.
Six of the eight tests in Figure 5-7 have been selected for Auto Run.
5-6
5. Running Tests
5-7
5-8
Example
This example, for Z-Time, Z-Char, ZMTA, I-Char, VF-Char, DiffChar, and
directional test modules, clarifies how recalculation works.
72A-1968-01
Rev. E 3/2011
6-1
Test points are stored in the database in relative terms. For example, a multiple
of 2.0 of Iset remains as a multiple of 2.0 of Iset, but the current value in
Amperes and the operating time may change. Figure 6-2 shows the test points
and the reference graph after testing.
6-2
The reference characteristic curve and the current values (in Amperes) in the
table are automatically calculated from the new settings and the test point
current multiples. The time values remain unchanged, however, because they
are stored in the database and are directly retrieved without being immediately
recalculated when opening the test.
6-3
6-4
A. Reference Tables
Test Preparation
Table A-1 Checklist Test Preparation for a New Relay
Step
Reference
Add a Test Plan and to that add a Test module and select
test type; e.g., I-Char, Z-Time DiffChar.
72A-1968-01
Rev. E 3/2011
A-1
Reference
Abbreviations
Table A-2 Abbreviations Used in F6TesT 2.21
Abbreviation
A-2
Description
NoOp
Op
Src
ITH
VTH
A. Reference Tables
Description
TTD
FDS
NF
Shortcut Keys
Table A-3 Keyboard Shortcuts Used in F6TesT
Shortcut
Description
Ctrl + N
Ctrl + O
Ctrl + S
Del
Ctrl + X
Ctrl + C
Copy to clipboard
of selected records.
Ctrl + I
Ctrl + A
Ctrl + F
Find.
Esc
Cancel.
F1
A-3
A-4
Description
F10
F12
Alt + F12
B. Importing Functions
This appendix describes the procedures for importing functions based on
.rio file types.
Importable functions include impedance and overcurrent. Impedance
functions can be directly imported. Overcurrent functions can also be directly
imported if the imported function characteristic has been mapped in a
cross-reference table to an existing F6TesT characteristic.
Importing a Function
To import a function:
1. Open the target relay for the functions.
2. Click the Relay Parameters tab.
3. Click Import. A Select RIO Files dialog box appears.
4. Select the file with a .rio extension.
5. Click Open.
An RIO dialog box appears (Figure B-1), listing the available functions in the
.rio file. The list may contain one or more overcurrent or impedance functions.
The name of the function is taken directly from the Device Name field in the
RIO file. A sequential number is then added if more than one element is
present. The function names can be edited now or after importing.
72A-1968-01
Rev. E 3/2011
B-1
Only active elements that belong to the functions are imported. If the
characteristic being imported is not listed in the Characteristics
Cross-Reference table (see Characteristics Cross-Reference below),
another dialog box appears, listing the function elements with no direct
equivalent characteristic. Select the most suitable characteristic from the
drop-down menu.
B-2
B. Importing Functions
Characteristics Cross-Reference
To edit the characteristics cross-reference table, select Tools
Characteristics Characteristics Cross-Reference. The open database is
automatically selected. The table has two tabs, Predefined and User-Defined
(Figure B-3).
B-3
B-4
72A-1968-01
Copy a location from any level with sublocations and relays and paste
to the root level of the same database or to another database.
Copy a relay from one location and paste to the same location or to
another location within the same database or to another database.
Copy a function from one relay and paste to another relay. The
following conditions apply:
If the function is pasted to a relay with the same manufacturer, all
data will be simply copied and pasted.
In case of different manufacturers, if the function depends only on
characteristic data that are defined within the function itself, such
as impedance elements, directional, and some differential characteristics, simply copy and paste the function. In the case of differential relay characteristics, they should not refer to a characteristic
in the main characteristics section.
Copying and pasting a test plan, including all tests, to the same relay.
Pasting a test to a different relay, but only if the target relay has a
function to which the test can refer. For example, an overcurrent test
I-Char can be copied and pasted if the target relay contains at least one
overcurrent function. After pasting, the following actions apply:
If there is only one function to which the test can refer, that function is selected.
If all checked test elements are available in the function, select the
same test elements and apply all previous test points. Extra elements of the function that are not in the copied test are not
checked.
If some elements in the copied test are missing from the function,
only the available elements are checked and applied to all previous
test points.
If the target relay has more than one possible function to choose
from, copying will proceed, but the function dropdown box will be
blank. Upon opening the test, select the function to which you
wish to apply the test, then proceed as above.
Rev. E 3/2011
C-1
When using Cut instead of Copy, the source record will be deleted
after the Paste operation. If the Paste operation is not done or not
finished, the source record will not be deleted.
C-2
With dynamic relay testing, you can quickly model and play back these events
with the SSIMUL macro.
To work with the Power System Model, obtain the source impedance and line
impedance for both ends of the line. Enter only the primary values for
impedance. F6TesT calculates secondary impedance values from the PT and
CT ratios.
72A-1968-01
Rev. E 3/2011
D-1
To access the Power System Model, select Tools Power System Model. A
window similar to the following appears.
D-2
Single line
Parallel lines
Single line with tap
Parallel lines with tap
A fault location sign ( ) indicates where the fault is. Users can use the Fault
tab (Figure D-3) to select the fault location or they can drag-and-drop the fault
location sign in the top section.
Each source has a drop-down menu that enables the user to select source
impedance. Options include:
If you select Enter source Z, the following dialog box appears, enabling you
to enter the impedance for each source.
Impedance Tab
The Impedance tab contains two tabs: Primary Ohms and Secondary Ohms.
The Primary and Secondary Ohms tabs enables users to enter impedance
(accurate to within three digits after the decimal points) for lines AB, CD, ET,
and mutual impedance between lines AB and CD.
D-3
Positive Sequence
Zero Sequence
Magnitude ()
Angle ()
Magnitude ()
Angle ()
Line AB
0.06
90
0.10
90
Line CD
0.08
90
0.12
90
AB||CD mutual
n/a
n/a
0.05
90
Line ET
0.01
90
0.02
90
Once the values have been entered on the Primary tab, F6TesT calculates the
secondary values and automatically updates the Secondary tab. Likewise, if
values are entered on the Secondary tab, F6TesT calculates the primary values
and automatically updates the Primary tab.
In addition, users can enter PT and CT ratios. Default values for each of these
is 1:1.
Fault Tab
The Fault tab (Figure D-3) enables you to specify the fault element, type, and
location.
D-4
Fault Element
Select from drop-down menu:
Bus C
Bus D
Bus T
Bus E
Line AB
Line CD
Line CT
Line ET
Line TD
The items that appear in the menu depend on the type of model selected.
Location
If Bus C or Bus D is selected from the Fault Element drop-down
menu, this field should be disabled. By default, the location for all
faults is at 50% from A if the fault is on AB; 50% from C if the fault is
on CD. Numeric values only are allowed.
D-5
Fault Type
Enables you to move the fault on the line. The percentage is the
distance from the near end to the fault. For example, entering 60
places the fault 60 percent of the line length from the near-end or 40
percent from the far end. The Power System Model also allows you to
enter percentages up to 999% to test different zones of protection. To
create a fault at more than 100% of the line, set the far-end source
equal to 0 for realistic values. The following options are available
from the drop-down menu.
Ph-G
Ph-Ph
Ph-Ph-G
3-Ph
Relay Tab
The Relay tab (Figure D-4) enables you to configure relays. The number of
relays that appear on the tab depends upon the system configuration. Relays
are listed as:
D-6
Relay A
Relay B
Relay C
Relay D
Relay E
Polarizing
Fault Data
The Polarizing tab enables you to set the polarizing quantity on the selected
Polarizing sources. If you select VN as the polarizing source, the quantity is in
VA+VB+VC; if you select IN as the polarizing source, the quantity is in
IA+IB+IC. When
The Fault Data tab (Figure D-5) shows voltages and currents for the selected
relay. These figures can be in either Cartesian or polar coordinates. Click the
SS1 File button to save the data to an SS1 file.
D-7
For a load flow of two parallel lines, users must enter any two of the following
values:
D-8
Voltage at Bus C
Voltage at Bus D
Current on Line AB
Current on Line CD
The Power tab on the Load Flow tab (Figure D-7) enables users to enter the
power of the line.
D-9
Model Menu
The Model menu (Figure D-9) enables users to model different power
systems. The Model menu options are:
D-10
Setup Menu
The Setup menu (Figure D-14) enables you to navigate to the F6 Control
Panel. When you click Setup, the following dialog box appears.
D-11
D-12
E. Vector Calculator
The Vector Calculator consists of a vector table and keypad. Vectors are
displayed graphically in the vector (or phasor) view area. A vector formula
you enter with the keypad is displayed in the Formula Box. If the formula is
evaluated, the result is shown in the Answer Box.
Vector Table
The vector table contains five columns:
72A-1968-01
The Vector column contains data entry fields for vectors V1 through
V9.
Rev. E 3/2011
E-1
The second and third columns define the vector values. The headings
for these columns depend on whether you select Polar or Rectangular
form on the keypad. For Polar form, the columns are labeled
Magnitude and Angle; for Rectangular form, the columns are labeled
Real and Imaginary.
The Graph column contains buttons that enable you to choose whether
each vector appears in Normal View. If a vector entry has been saved
from a formula created in the Formula Box, the formula appears in the
Formula column of the vector table.
The Source Name column allows you to add a source name to relate
the vector to a power system source (VA, I1, and so on).
Keypad
The Keypad consists of the following key groups, each of which is described
below:
Function keys
Vector keys
Operator keys
Number keys
Recalculate Formulae
Function Keys
The function keys appear in the first two rows of the keypad:
E-2
Polar and Rect These keys switch between Polar and Rectangular
form for all vector values, including the Answer Box. This enables
values to be entered in one form and redisplayed in the other form.
Back (Backspace) Deletes the preceding value in the cell being
edited. Same as Backspace on a keyboard.
CFB (Clear Formula Box) Clears the formula in the Formula Box
and the result in the Answer Box.
SV (Save Vector) The next vector selected by a vector key (see
below) will be overwritten by the value in the Answer Box, and the
corresponding formula will also be saved in the table.
CV (Clear Vector) The next vector selected by a vector key will be
cleared.
CAV (Clear All Vectors) Clears all values in the vector table.
E. Vector Calculator
Vector Keys
Click keys V1 to V9 to specify a vector table entry. These are used in two
ways:
1. When creating a formula in the Formula Box, clicking a vector key inserts
a vector name into the formula, as an alternative to typing the vector name.
2. Clicking SV and then a vector key saves the Answer Box result to that
vector. Clicking CV and then a vector key clears the contents of that
vector.
Operator Keys
Click an operator key to enter it in the Formula Box. You can enter values
from the keyboard or the keypad. Table E-1 describes the operator keys.
Table E-1 Operator Keys
Keys
Description
+-
*/
E-3
Description
SQRT
(square
root)
CONJ
(conjugate)
a2
Number Keys
Table E-2 describes the number keys.
Table E-2 Number Keys
Keys
E-4
Description
0-9
Use to enter values in the Formula Box. You can also enter
values from the keyboard. Negative values are also valid (do
not space on either side of the -).
. (decimal
point)
E. Vector Calculator
Viewing Vectors
Two graphic displays show the vector table and Formula Box as vectors:
1. Normal View. If the button in the Graph column displays a red
checkmark, the vector is graphed on a circular plot. Vector tails begin at
the origin.
2. Formula View. If a vector formula in the Formula Box has been evaluated
and a result is displayed in the Answer Box, the vector operations are
graphed, showing the resultant vector in red. Vector tails begin at the
origin.
To evaluate a formula, press the equal sign (=) on the keypad.
Menu Bar
Menu bar options are:
File
Edit
View
Formulae
Help
File
File menu (Figure E-2) items are:
E-5
Setup
Opens the Vector Setup dialog box (Figure E-3).
Print
Opens the standard Windows Print Setup dialog box.
E-6
E. Vector Calculator
Exit
Exits the program.
Edit
Edit Menu (Figure E-4) items are as follows. They apply to highlighted data,
either cells in the vector table or data in the Formula Box.
Cut
Cuts the selected data and retains it on the clipboard. Shortcut key: Ctrl + X
Copy
Copies the selected data and retains it on the clipboard. Shortcut key: Ctrl + C
Paste
Inserts data from the clipboard. You can do multiple pastes from one cut or
copy. Shortcut key: Ctrl + V
Delete
Deletes the selected data.
View
View menu (Figure E-5) items are:
E-7
Scaling
If you have voltages and currents in the Source Name column of the vector
table (e.g., VA, VB, VC, and IA, IB, IC), by default all of them are scaled to
the largest magnitude in the list. If you select Scaling, the voltage and current
with the largest magnitudes are shown to the same scale, with the others
proportional by type.
E-8
E. Vector Calculator
Zoom In
To zoom in on an area of a graph:
1. Click just outside the area. Holding down the left mouse button, drag
diagonally downward to create a dashed box outlining the area
(Figure E-8).
E-9
a. Press Shift + Down Arrow, then Shift + Right Arrow, or vice versa.
b. Move the box outlined by the four red crosses until it encloses the area
you wish to zoom.
3. Press Enter.
Zoom Out
Right-click in the graph and select Zoom Out.
Alternate method: Select View Zoom Out Normal View or Formula
View.
Formulae
Formulae menu (Figure E-10) items are:
Standard Formulae
Opens the Formulae Manager dialog box (Figure E-11), from which you can
enter and recall formulae to be saved.
To add a formula:
1. Type the formula in the Formulae column.
2. Add any desired comments in the Comment column.
3. Click OK.
You can add more than one formula and comments at a time and save them all
simultaneously by clicking OK.
E-10
E. Vector Calculator
Help
Help menu (Figure E-12) items are:
Contents
Opens the Help window.
E-11
Toolbar
A vertical toolbar appears at the upper left of the Vector Calculator screen.
Figure E-13 shows the toolbar with icon labels.
Cut
Copy
Paste
Delete
Print
Help
Exit
Performing Calculations
To enter a vector value in the vector table:
1. Select Polar on the function keypad to enter magnitude and angle or select
Rect to enter real and imaginary values.
2. Click in the desired cell of the vector table.
3. Enter the value using the Vector Calculator keypad or the keyboard.
4. Press Enter to complete the entry or use the mouse to select another cell.
5. Click the Graph button to view the vector in Normal View.
To clear a value in the vector table, place the cursor in that cell and click CV.
To clear all values, click CAV.
E-12
E. Vector Calculator
Formula Column
The Formula column contains read-only data fields, showing a vector formula
from the Formula Box that was used to evaluate the vector in the vector table.
For example, if VA-VB is entered in the Formula Box and evaluated by
clicking the equal sign, the value and the formula can be saved as a vector in
the table. To do this, click SV on the keypad, followed by a vector keyfor
example, V7.
Enter a vector from the vector table by name. For example, click V2
on the keypad or type V2 on the keyboard. If V2 has a source name,
such as VB, you can enter VB on the keyboard.
3. Press the equal sign (=) to evaluate the formula. The result appears in the
Answer Box and in the Formula View.
Click CFB to clear the Formula Box, Answer Box, and Formula View.
Formula Operators
Use formula operators as follows:
E-13
Standard Operators
Enter the addition (+), subtraction (-), multiplication (*), and division (/)
operators from either the keypad or the keyboard.
Use parentheses around vector values entered in polar or rectangular form:
a*(-33.5-j58.02)
a, a2
Click a on the keypad as a multiplier to rotate the following vector 120:
a*V1
Click a2 to rotate the following vector 240:
a2*(VA-VB)
SQRT
Click SQRT to insert the square root value into a formula. The Square Root
dialog box opens (Figure E-14), requesting a positive real number for the
square root extraction.
Parentheses
Use parentheses to create an expression as a formula operand, such as for
addition or multiplication:
(-33.5 -j58.02) + (67@-120)
3*(1 + SQRT(2))
Evaluate
Click the equal sign (=) on the keypad or keyboard. The formula is evaluated
and the result appears in the Answer Box, in either a Polar or Rectangular
format. Change the format by clicking Polar or Rect on the keypad.
E-14
E. Vector Calculator
E-15
E-16
Index
A
Abbreviations A-2
Analog tab 1-34
Architecture 1-8
AutoRun 5-6
Autorun 4-83
B
Battery simulator source
turning off 1-15
turning on 1-15
Bias equations 4-52
C
Calculations
performing E-12
Change Scale 4-40
Characteristic constants 2-4
Characteristic equations 2-2
Characteristics
cross reference 2-15
cross-reference B-3
differential 2-11
guidelines 2-8
library 2-1
WaveSim 4-20
Compensation Settings tab 3-29
Connections and Signals 3-2
Context menu 1-13
D
Data views 1-8
72A-1968-01
Rev. E 3/2011
Database files
creating 1-17
DB Compacting Preferences 1-43
Defining individual test lines 4-38
DiffChar 4-26
Single-Phase Differential Testing 4-28
Three-Phase Differential Testing 4-26
Differential
Tests 4-48
Differential characteristics 2-11, 4-13
Differential Function tab 3-27
Differential functions 3-27
Differential test points 4-35
Digital Input tab 1-35
Digital Output
dialog box 4-74
Digital Output tab 1-35
Digital Outputs 4-22
Directional 4-25
Overcurrent Characteristics 4-11
Tests 4-47
Directional functions 3-25
Double ramp test 4-66
Draw Protected Line Impedance 4-41
E
Edit menu 1-20
Copy 1-22
Find 1-24
EXTERN module
Notebook tab 4-79
Reports tab 4-80
Index-1
F
F6TesT
abbreviations A-2
installation 1-2
installing 1-1
removal 1-2
shortcut keys A-3
Fault
Rotate 4-72
FDS A-3
File menu 1-17
Close 1-18
Delete Saved Graphs 1-19
Exit 1-20
New 1-17
Open 1-18
Print Setup 1-19
Recently Opened Databases 1-19
Save As 1-18
Formula bar 1-16
Formula box calculations
performing E-13
Formula column E-13
Formula functions 1-16
Formula keywords 1-16
Formula operators E-13
Function window 3-7
Functions
adding 3-9
copying 3-14
importing B-1
G
General Characteristic screen 3-22
General Properties tab 1-33
Generating global reports 1-49
Index-2
H
Help menu 1-53
Highlight formula 1-16
I
I-Char 4-25
time characteristics 4-46
Idiff vs. Ibias 4-13
Impedance function
adding 3-9
Impedance functions 3-19
Importing from spreadsheet 2-10
Installation 1-2
Instruments supported 1-1
Is vs. Ip 4-14
ITH A-2
K
Keys
function E-2
number E-4
operator E-3
vector E-3
L
L/R time constant 4-19
Location 1-12
adding a relay 3-1
Locations
cut, copy, and paste 1-13
delete, insert, append, and find 1-14
Login 1-5
Look-up tables 2-9
72A-1968-01
Rev. E 3/2011
Index
Phasor diagram
viewing 4-45
Polar grid 4-40
Power System Model 1-53
Fault tab D-4
Impedance tab D-3
Load Flow tab D-8
Model menu D-10
Relay tab D-6
Setup menu D-11
Pulsed ramp 4-65
N
NF A-3
NoOp A-2
entering a value of 4-42
Notebook tab 4-87
O
Offline Simulation mode 1-43
Op A-2
Oscillograph 4-75
context-sensitive menu 1-31
Oscillograph cursors 1-32
Oscillograph properties
setting 1-33
Oscillograph setup 1-30
Analog tab 1-34
Digital Input tab 1-35
Digital Output tab 1-35
General Properties tab 1-33
72A-1968-01
Rev. E 3/2011
R X grid 4-40
Ramp test 4-60
Recalculate Formulae key E-5
Relay 1-12
Relay characteristics
comparing 2-13
copying between databases 2-14
displaying 2-13
Relay functions
Differential 3-7
Directional 3-7
Generic 3-6
Impedance 3-6
Time characteristics 3-6
Relay library 3-9
Relay Maintenance schedule 1-46
Relay reports 1-50
Relays
adding to a location 3-1
cut, copy, and paste 1-13
delete, insert, append, and find 1-14
individual functions 3-6
parameters and functions 3-2
Reports tab 4-83
Requirements 1-1
Restore Graph 4-41
R-X Plane 4-34
Index-3
S
Same Characteristic Equations and Constants
2-9
Selecting a test 5-1
Setup 4-40
Setup menu 1-26
change language 1-42
Communication Setup 1-27
directories 1-41
Graphics Setup 1-28
Oscillograph Setup 1-30
Test Defaults 1-36
Shortcut keys A-3
Show Actual Characteristic 4-41
Show Reference Characteristic 4-41
Show Test Lines 4-40
Simulation mode 5-3
Single-Phase Differential Testing 4-28
Source Configuration button 4-23
Source Name column E-13
Spreadsheet
importing data from 2-10
Src A-2
SSIMUL State Simulation Test 4-69
Startup 1-5
Supported instruments 1-1
System requirements 1-1
T
Table columns
hiding 5-4
Template library 1-53
Test Configuration tab 4-9
current characteristics 4-10
Fault Calculation 4-10
frequency time characteristics 4-10
Test Method 4-15
voltage characteristics 4-10
Test defaults 1-36
miscellaneous 1-38
Run/Auto Run 1-37
Index-4
72A-1968-01
Rev. E 3/2011
Index
adding 4-2
cut, copy, and paste 1-13
delete, insert, append, and find 1-14
running 5-4
selecting 5-1
Three-Phase Differential Testing 4-26
Time
Overcurrent Test Points 4-28
Time Characteristics functions 3-15
Time units 4-74
Tolerance 4-40
Toolbars 1-12, 1-14
Battery 1-15
Tools menu 1-43
Characteristics 1-46
Characteristics Cross Reference 2-15
Convert Database 1-52
DB Compacting Preferences 1-43
F6000 Software Tools 1-44
Offline Simulation Mode 1-43
Power System Model 1-53
Relay Maintenance Schedule 1-46
Relay Manufacturers & Models 1-47
Reports 1-49
template library 1-53
Vector Calculator 1-53
Transformer Parameters tab 3-31
Trigger Selection button 4-21
TTD A-3
VF-Char 4-25
time characteristics 4-46
VpHzRamp Test 4-67
VTH A-2
W
WaveSim
Test Method 4-20
WaveSim characteristics 4-20
WaveSim test 4-58
Window Function 3-7
Z
Z-Char 4-24
Z-Char test 4-56
Z-Char test lines 4-37
Z-Char Test Points tab
deleting points on 4-56
ZMTA 4-24, 4-57
Zoom In 4-41
Zoom Out/Unzoom 4-41
Z-Time 4-24
Test Points 4-30
Z-Time test 4-53
U
Unknown characteristics 4-52
V
Vector Calculator
toolbar E-12
Vector calculator
keypad E-2
Vector Table
saving answer in E-15
Vector table E-1