Industrial Inverter for Fan and Pump

STARVERT iP5A
0.75~30kW (1~40HP) 3Phase 200~230Volts
0.75~450kW (1~600HP) 3Phase 380~480Volts
5.5~110kW (7.5~150HP) 3Phase 525~600Volts

STARVERT iP5A
LS Starvert SV-iP5A has been specifically designed
and created to provide competitive solutions for fan
and pump applications

Industrial Inverter for Fan and Pump STARVERT iP5A

Specialized
Functions for
Fan and Pump

Marine Type
Certification
From DNV

Energy
Saving and High
Efficiency

User-friendly
Interface
and Easy
Maintenance

STARVERT

iP5A

Contents

4
8
9
13
17
19
22
23
24
37
39
45
50

Intelligent
Control
Mechanism

Overview
Model & Type
Standard Specifications
Wiring
Terminal Configurations (Power Circuit Terminal)
Terminal Configurations (Control Circuit Terminal)
Programming Keypad
Programming Keypad (Parameter Navigation)
Parameter Description
Trial Run
Dimensions
DB (Dynamic Braking) Unit
External DB Resistor / Peripheral Device

iP5A

Specialized Functions for Fan and Pump


The iP5A, specifically designed for HVAC application, provides stable and cost-effective system
performance.

PID Control
In the centrifugal fan and pump field, PID control is provided as a standard function in order to maintain a constant
control of pressure, flow and oil level. This function includes Pre-PID, Sleep and Wake up and output inverse subfunctions.

Dual PID
Where external or cascaded PID control is required, the built-in dual PID
algorithm of the iP5A can be utilized to satisfy various system requirements.

Multi Motor Control (0.75~450kW)


The iP5A MMC function provides cost-effective, simultaneous control of up to eight motors, without requiring external
controllers.

Marine Type Certification From DNV


The iP5A has been tested and certified by DNV to comply with International Marine
requirements

Industrial Inverter for Fan and Pump STARVERT iP5A

Energy Saving and High Efficiency


The iP5A, specifically designed for fan and pump applications, guarantees energy savings by optimizing the
system.

Sleep and Wake-up Function


Energy savings are obtained through the Sleep and Wake-Up functions of the iP5A, which enable the drive to
automatically switch off during user-programmed low-load conditions and then to start up again when process demand
increases.
Sleep mode
Adjusting output
with detecting load

Output frequency
PID reference

(Energy saving)

Wake-up mode
Returning to
normal state

PID feedback

Run command

Pre Heating Function


When using the inverter in damp conditions, this function protects both the motor and the inverter's output

Flying Start Function


When 2 or more fans, or a high inertia load are connected to the inverter, the iP5A detects the motor speed after a
momentary power failure, enabling the motors to be smoothly reaccelerated without mechanical and electrical shockloading to the system.

Automatic Energy Saving


Load change may incur energy losses but the optimized flux control of iP5A results in more outstanding energy saving
compared to previous models.
Reduction percentage
0.75

600 RPM

Damper control
Conventional
inverter control

V/F
30% manual
energy saving

0.50
0.40

Automatic
energy saving

0.25

iP5A

0.20
0.10
0

10

20

30

40

50

60

70

Load %

iP5A

Intelligent Control
Because of effectual functions and protection algorithms, the iP5A provides constant performance,
in spite of external power fluctuations.

Constant and Stable Performance


In spite of external voltage fluctuations and lightning surges, the iP5A optimizes motor performance.

Improved System Management during Power Dips and Momentary Power Outages
During Power Dips or Momentary Power Outage, the inverter output can be maintained by utilizing the residual
mechanical energy in the load as a regenerative source. The duration of the power-dip ride-through depends on the load
characteristics.

Emitted energy

Power failure for 1 second

Power failure for 3 seconds

The mechanical energy


stored during blackout can
be used for inverters power.
Mechanical
energy

Mecha
-nical
energy

Load
Consumed
energy

Safety Stop
During unexpected power failure conditions, the iP5A can bring the load to a controlled stop, by utilizing the inertial
energy. This can prevent further process problems or accidents.

Current Leakage Reduction Algorithm


Under damp conditions, leakage currents can occur when
using inverters. These currents can cause a system
failure. The iP5A low-leakage PWM algorithm reduces
these leakage currents to ensure reliability of operation.

PWM

Zero vector

Valid vector

Zero vector

Valid vector

Flux Braking Algorithm


This algorithm reduces deceleration time, thereby improving system efficiency.

Automatic Carrier Frequency Change


By taking ambient temperature into account, the iP5A can automatically adjust the Carrier (Modulation) Frequency.

Protection
The iP5A has optimized protective functions, such as safety stop and pre-excitation of the motor, amongst others.

Industrial Inverter for Fan and Pump STARVERT iP5A

User-friendly Keypad & Easy Maintenance


The iP5A construction allows for easy maintenance, with ease-of-access to all components.

Easy Start
When pushingSTOPkey for
2~3 seconds in case inverter
turns on, the inverter turns into
Easy Start Modewith FWD,
REV, and STOP command.
SHIFT/ESCcan return it to
previous mode.
Control method: V/F
Control frequency: Jog

1
4
2 6

7 9

NPN/PNP Input

iP5A has both NPN and PNP input, and you can select
one of them easily.
2

The built-In RS485 allows for communication without external option.


However, the optional communication boards enable the iP5A to talk
to BMS and most Industrial Systems

Abundant I/O Suggestion


5

iP5A serves abundant I/O.


Digital Input/Output
Analog Input (Voltage + Current)/Output
Pulse Input
NTC/PTC Input

Built-in RS485 and Optional Communication

8 points / 4 points
(1+1) points /4 points
1 point
1 point

iP5A adopts long-life condenser and enables easy maintenance in


simple framework.
6

Consumption Time Display


iP5A displays consumption time of components so that users can
replace them in time.

Various Units of I/O Display


The iP5A display can be calibrated in many different types
of process units.

Long-life Condenser and Simple Framework

Others
Removable terminal board
External fan available
Cooling fan on/off control

iP5A

Model & Type


380~480V Class
(Classification)

525~600V Class

SV055iP5A-4NE

SV055iP5A-4NE (CLASS)

SV0055iP5A-6

SV075iP5A-4NE

SV075iP5A-4NE (CLASS)

SV0075iP5A-6

SV110iP5A-2NE

SV110iP5A-4NE

SV110iP5A-4NE (CLASS)

SV0110iP5A-6

15kW (20HP)

SV150iP5A-2NO

SV150iP5A-4NO

SV150iP5A-4NOL (CLASS)

SV0150iP5A-6

18.5kW (25HP)

SV185iP5A-2NO

SV185iP5A-4NO

SV185iP5A-4NOL (CLASS)

SV0185iP5A-6

22kW (30HP)

SV220iP5A-2NO

SV220iP5A-4NO

SV220iP5A-4NOL (CLASS)

SV0220iP5A-6

30kW (40HP)

SV300iP5A-2NO

SV300iP5A-4NO

SV300iP5A-4NOL (CLASS)

SV0300iP5A-6

37kW (50HP)

SV370iP5A-4O

SV370iP5A-4OL (CLASS)

SV0370iP5A 6

45kW (60HP)

SV450iP5A-4O

SV450iP5A-4OL (CLASS)

SV0450iP5A-6

Motor Rating

200~230V Class

380~480V Class

0.75kW (1HP)

SV008iP5A-2NE

SV008iP5A-4NE

1.5kW (2HP)

SV015iP5A-2NE

SV015iP5A-4NE

2.2kW (3HP)

SV022iP5A-2NE

SV022iP5A-4NE

3.7kW (5HP)

SV037iP5A-2NE

SV037iP5A-4NE

5.5kW (7.5HP)

SV055iP5A-2NE

7.5kW (10HP)

SV075iP5A-2NE

11kW (15HP)

55kW (75HP)

SV550iP5A-4O

SV550iP5A-4OL (CLASS)

SV0550iP5A-6

75kW (100HP)

SV750iP5A-4O

SV750iP5A-4OL (CLASS)

SV0750iP5A-6

90kW (125HP)

SV900iP5A-4O

SV900iP5A-4OL (CLASS)

SV0900iP5A-6

110kW (150HP)

SV1100iP5A-4OL

SV1100iP5A-4OL (CLASS)

SV1100iP5A-6

132kW (200HP)

SV1320iP5A-4OL

SV1320iP5A-4OL (CLASS)

160kW (250HP)

SV1600iP5A-4OL

SV1800iP5A-4OL (CLASS)

220kW (300HP)

SV2200iP5A-4OL

SV2200iP5A-4OL (CLASS)

280kW (350HP)

SV2800iP5A-4OL

SV2800iP5A-4OL (CLASS)

315kW (400HP)

SV3150iP5A-4O

SV3150iP5A-4O (CLASS)

375kW (500HP)

SV3750iP5A-4O

SV3750iP5A-4O (CLASS)

450kW (600HP)

SV4500iP5A-4O

SV4500iP5A-4O (CLASS)

NE

(CLASS)

N: No Keypad
O: UL Open Type
E: UL Enclosed Type 1
L: Built-in DC Reactor

Classification

SV

055

iP5A

Motor Rating

Series Name
iP5A

055
900

5.5 kW
90 kW

--

Input Voltage
2
4
6

200-230V
380-480V
525-600V

(15~90kW : Option / 110~280kW : Standard)

SV055iP5A-2NE
INPUT

200-230 V 3 Phase
25A
50/60HZ

OUTPUT 0-Input V 3 Phase


24A
0.01-120HZ
9.1KVA, Enclosed Type 1

Model Number
Input Rating
Output Rating
Protection Degree
Bar Cord
Serial Number

Marine Approved Drives


needs additional ordering.

Industrial Inverter for Fan and Pump STARVERT iP5A

Standard Specifications
200~230V Class (0.75~30kW / 1~40HP)
iP5A-2)
Model Number (SV
Capacity [kVA]

Note1)
Note2)

Fan or
pump load
Output
ratings General
load

Motor rating

(HP)
(kW)

Current [A]
(110% over current)
(HP)
Motor rating
(kW)
Current [A]
(150% over current)

Frequency
Voltage
Input
Voltage
ratings Frequency
Protection degree
Weight [kg (lbs.)]

008

015

022

037

1.9
1
0.75
5

3.0
2
1.5
8

4.6
3
2.2
12

6.1
5
3.7
16

055

075

110

150

185

220

300

9.1
12.2
17.5
22.9
28.2
33.5
43.8
7.5
10
15
20
25
30
40
5.5
7.5
11
15
18.5
22
30
24
32
46
60
74
88
115
110% 1 Minute (Normal Duty)
0.5
1
2
3
5.5
7.5
10
15
20
25
30
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
2.5
5
8
12
17
23
33
44
54
68
84
110% 1 Minute (Normal Duty)
150% 1 Minute (Heavy Duty)
0.01~120 Hz
200~230V Note3)
3200~230V (-15%~+10%)
50/60 Hz ( 5%)
IP20 / UL Type1
IP00 / UL Open Note4)
4.1(9.0) 4.2(9.3) 4.2(9.3) 4.9(10.8) 4.9 (10.8) 6 (13.2) 6 (13.2) 13 (28.7) 13.5 (29.8) 20 (44.1) 20 (44,1)

380~480V Class (0.75~90kW / 1~125HP)


iP5A-4)
Model Number (SV
Capacity [kVA]

Note1)
Note2)

Fan or
pump load
Output
ratings General
load

Motor rating

Current [A]
(110% over current)
(HP)
Motor rating
(kW)
Current [A]
(150% over current)

Frequency
Voltage
Input
Voltage
ratings Frequency
Protection degree
Weight [kg (lbs.)]

(HP)
(kW)

Standard Type
Built-in DCL Type

008 015

022

037

055

075

2.0
1
0.75
2.5

4.8
3
2.2
6

6.4
5
3.7
8

9.6
7.5
5.5
12

12.7
10
7.5
16

3.0
2
1.5
4

110

150

185

220

300

370

450

550

750

900

19.1 23.9 31.1 35.9 48.6 59.8 72.5 87.6 121.1 145.8
15
20
25
30
40
50
60
75
100 125
11
15
18.5 22
30
37
45
55
75
90
24
30
39
45
61
75
91
110 152 183
110% 1 Minute (Normal Duty)
0.5
1
2
3
5.5
7.5
10
15
20
25
30
40
50
60
75
100
0.4 0.75
1.5
2.2
3.7
5.5
7.5
11
15 18.5
22
30
37
45
55
75
1.25 2.5
4
6
8.8
12
16 22/24 28/30 34/39 44/45
110% 1 Minute (Normal Duty)
150% 1 Minute (Heavy Duty)
0.01~120 Hz
380~480V Note3)
3380~480V (-15%~+10%)
50/60 Hz ( 5%)
IP20 / UL Type1
IP00 / UL Open Note4)
4.1(9.0) 4.2(9.3) 4.2(9.3) 4.9(10.8) 4.9 (10.8) 6 (13.2) 6 (13.2) 12.5 (27.6) 13 (28.7) 20 (44.1) 20 (44.1) 27 (59.5) 27 (59.5) 29 (64) 42 (92.6) 43 (94.8)
- 19.5 (43.9) 19.5 (42.9)26.5 (58.3) 26.5 (58.3) 39 (86) 40 (88.2) 42 (92.6) 67 (147.4) 68 (149.9)

Note 1) Rated capacity (v 3VI) is based on 220V for 200V class and 460V for 400V class.
2) Indicates the maximum applicable capacity when using a 4-Pole LS motor.
3) Maximum output voltage will not exceed the input voltage. An output voltage less than the input voltage may be programmed if necessary.
4) IP20/UL Type1 with optional conduit, it can be modified to UL Type1.

iP5A

Standard Specifications
380~480V Class (110~450kW / 50~125HP)
iP5A-4)
Model Number (SV
Capacity [kVA]

Note1)
Note2)

Fan or
pump load
Output
ratings General
load

Motor rating

(HP)
(kW)

Current [A]
(110% over current)
(HP)
Motor rating
(kW)
Current [A]
(150% over current)

Frequency
Voltage
Input
Voltage
ratings Frequency
Protection degree
DCL
Weight [kg (lbs.)]

1100

1320

1600

178
150
110
223

210
200
132
264

259
250
160
325

125
90
183

150
10
223

200
132
264

101 (222.7)

Built-in
101 (222.7) 114 (251.3)

2200

2800

3150

3750

4500

488
400
315
613

582
500
375
731

699
600
450
877

350
280
547

400
315
613

500
375
731

344
436
300
350
220
280
432
547
110% 1 Minute (Normal Duty)
250
300
160
220
325
432
150% 1 Minute (Heavy Duty)
0.01~120 Hz
380~480V Note3)
3380~480V (-15%~+10%)
50/60 Hz ( 5%)
IP00 / UL Open Note4)
200 (441.9)

200 (441.9)

External Option
243 (535.7) 380 (837.7)

380 (837.7)

525~600V Class (5.5~110kW /7.5~150HP)


iP5A-6)
Model Number (SV
Capacity [kVA]
Fan or
pump load
Output
ratings General
load

Motor rating

(HP)
(kW)

Current [A]
(110% over current)
(HP)
Motor rating
(kW)
Current [A]
(150% over current)

0055

0075

0110

0150

0185

9.6
7.5
5.5
9

12.7
10
7.5
12

19.1
15
11
17

23.9
20
15
23

31.1
25
18.5
27

5.5
3.7
6.1

7.5
5.5
9

10
7.5
12

15
11
17

6.5
(14.4)

7.0
(15.5)

7.0
(15.5)

11.7
(25.8)

Frequency
Voltage
Input
Voltage
ratings Frequency
Protection degree
Weight [kg (lbs.)]

Standard Type

0220

0300

0370

0450

Note 1) Rated capacity (v 3VI) is based on 220V for 200V class and 460V for 400V class.
2) Indicates the maximum applicable capacity when using a 4-Pole LS motor.
3) Maximum output voltage will not exceed the input voltage. An output voltage less than the input voltage may be programmed if necessary.
4) IP20/UL Type1 with optional conduit, it can be modified to UL Type1.

10

0550

0750

0900

35.9
48.6
59.8
72.5
87.6
121.1 145.8
30
40
50
60
75
100
125
22
30
37
45
55
75
90
34
43
55
64
80
104
128
110% 1Minute (Normal Duty)
20
25
30
40
50
60
75
100
15
18.5
22
43
55
64
80
104
23
27
34
150% 1 Minute (Heavy Duty)
0.01 ~ 120 Hz
525 ~ 600V Note3)
3 525 ~ 600V (-15% ~ +10 %)
50/60 Hz (5 %)
IP20 / UL Type1 IP00 / UL Open Note4)
11.7
18.9
18.9
32
32
32
46
46
(25.8) (41.7) (41.7) (70.65) (70.65) (70.65) (101.5) (101.5)

1100
178
150
110
150
125
128
-

101
(223)

Industrial Inverter for Fan and Pump STARVERT iP5A

Common Specifications
Cooling method
Control Method

Control

Frequency Setting Resolution


Frequency Accuracy
V/F Pattern
Overload Capacity
Torque Boost
Operation Method

Input Signal
Output signal

Operatio

Frequency Setting
Start Signal
Multi-Step
Multi Step Accel/Decel Time
Emergency Stop
Jog
Fault Reset
Operating Status
Fault Output
Indicator

Forced air cooling (Self-cooling for below 1.5kW-2, 2.2kW-4)


V/F, Sensorless Vector, Slip Compensation, Easy Start Selectable
Digital Reference: 0.01 Hz (Below 100 Hz), 0.1 Hz (Over 100 Hz)
Analog Reference: 0.01 Hz / 60 Hz
Digital : 0.01% of the max frequency
Analog : 0.1% of the max frequency
Linear, Squared Pattern, User V/F
110 % per 1 min, 120% per 1 min Note5)
Manual Torque Boost (0 ~ 15 %), Auto Torque Boost
Keypad / Terminal / Communication Operation
Analog: 0 ~ 12V / -12V ~ 12V / 0~20mA/ Pulse / Ext-PID
Digital: Keypad
Forward, Reverse
Up to 18 Speeds can be set including Jog (Use Programmable Digital Input Terminal,Including Jog/Dwell )
0.1~ 6,000 sec, Max 4 types can be set via Multi- Function Terminal. Accel/Decel Pattern: Linear,
U-Curve, S-Curve Selectable
Interrupts the Output of Inverter
Jog Operation
Fault Reset
Frequency Detection Level, Overload Alarm, Stalling, Over Voltage, Low Voltage, Inverter Overheating/
Running/ Stopping/ Const ant running, Inverter By-Pass, Speed Searching
Contact Output (3A, 3C, 3B) - AC 250V 1A, DC 30V 1A
Choose 2 from Output Frequency, Output Current, Output Voltage, DC Link Voltage
(Output Voltage: 0 ~ 10V)
DC Braking, Frequency Limit, Frequency Jump, 2nd Function, Slip Compensation, Reverse Rotation

Operation Function

Prevention, Auto Restart, Invert By-Pass Auto-Tuning PID Control Start Stop Braking leakage Pre-PID
Dual-PID MMC Start Prer By Pass, Auto Tuning, Control, Flying Start, Safety Stop, Flux Braking,
Over Voltage, Low Voltage, Over Current, Ground Fault, Inverter Overheat, Motor Overheat, Output Phase

Inverter Trip

Open, Overload Protection, External Fault 1, 2, Communication Error, Loss of Speed Command,
Hardware Fault, Option Fault etc

Inverter Alarm
Keypad

Display

Protection

Low leakage, Pre PID, Dual PID, MMC, Easy Start, e-heater

Operation Information

Stall Prevention, Overload Alarm, Thermal Sensor Fault


Output Frequency, Output Current, Output Voltage, Frequency Set Value, Operating Speed, DC Voltage,
Integrating Wattmeter, Fan ON time, Run-time, Last Trip Time
Trips Indication when the Protection Function activates.

Trip Information

Max. 5 Faults are saved.

Environment

Last Trip Time.

Ambient Temperature
Storage Temperature
Ambient Humidity
Altitude-Vibration
Application Site

-10 ~ 50 (14
F ~ 122
F)
Decrease 2% of rated current for every 1 increase in above 40
-20 ~ 65 (14
F~ 149
F)
Below 90 % RH Max. (Non-Condensing)
Below 1,000m (3,300ft), Below 5.9m/sec2 (0.6g)
Pollution degree 2, No Corrosive Gas, Combustible Gas, Oil Mist, or Dust

(1) Rated capacity (3VI) is based on 220V for 200V class and 460V for 400V class.
(3) IP20 or UL Enclosed Type1 can be provided by the option.
(5) Overload rating 120%, 1 min is based on ambient 25

(2) Indicates the maximum applicable capacity when using a 4-Pole standard motor.
(4) IP20 or UL Enclosed Type1 is not provided.

11

iP5A

Standard Specifications
Common Specifications (External)
32 character display

Keypad

LCD

Remote

Remote cable

All units
keypad Download and Upload available
2m, 3m and 5m long keypad cable enables users
Optional
to control the inverter from a distant area
To enhance the regenerative braking performance,

DB resistor
it makes the inverter to accelerate/decelerate rapidly

Dynamic braking

capacity
DB unit

If it need a regenerative braking, it is used with DB resistor

Conduit for

Conduit option

According to inverter

15~90kW
Install it to fit for NEMA TYPE 1 Enclosure or IP20

NEMA TYPE 1

(20~125HP)
All series

DEVICENET

DEVICENET optional communication card


(Above S/W V10)
All series

PROFIBUS

PROFIBUS optional communication card


(Above S/W V10)
All series

LS485/MODBUS_RTU

LS485/MODBUS_RTU optional communication card


(Above S/W V10)
All series

LonWorks

Lonworks optional communication card


(Above S/W V10)

Communication

All series
BACNet

BACNet optional communication card

option card

(Above S/W V10)


All series
MODBUS_TCP

MODBUS_TCP optional communication card


(Above S/W V10)
All series

Metasys_N2

Metasys_N2 optional communication card


(Above S/W V10)
All series

CCLink

CCLink optional communication card


(Above S/W V10)
All series

CANopen

CANopen optional communication card


(Above S/W V10)

12

Industrial Inverter for Fan and Pump STARVERT iP5A

Wiring
For 0.75~30kW (1~40HP)
Main Power Circuit
Dynamic
Braking Unit
(Optional)

DC Bus Choke
(Optional)

DB Unit (Optional)
DB Resistor

P N B1 B2
DC Bus Choke

DB Resistor
P1 (+)

P2 (+) N (-)

MCCB (Option)
3
AC Input
50/60 Hz

R (L1)

S (L2)

T (L3)

Motor

Control Circuit
Programmable Digital Input 1 (Speed L)
Programmable Digital Input 2 (Speed M)
Programmable Digital Input 3 (Speed H)
Fault Reset (RST)

+
-

M1
M2

+
-

M3
M4

Inverter Disable (BX)

V+

Analog Power Source (+12V)

V1

Frequency Reference (0~12V, V1S: -12~12V)

5G

Frequency Reference Common Terminal

Frequency Reference (0~20mA or 4~20mA)

V-

Analog Power Source (-12V)

S0
S1
5G

Output Frequency Meter

M5

Jog Frequency Reference (JOG)

M6

Forward Run Command (FX)

M7

Reverse Run Command (RX)

M8

Common Terminal

Max. output voltage: 12V


Source max.: 30mA
Sink max.: 20mA

Output Voltage Meter


Common for Output Meter Signal

CM

Programmable Digital Output

A1
C1
A2
C2
A3
C3
A4

3A
3C
3B

A0
B0
5G

Fault Contact Output


less than AC250V (DC30V), 1A

Frequency Reference (Pulse: 0~100kHz)


Common for Frequency Reference (Pulse)

C4

RS485 Signal
RS485 Common

CC+

NT
5G

External Motor Thermal Detection

CM

Note 1) 5G is Common Ground for Analog Input / Output.


2) Use terminal V1 for V1, V1S (0~12V, -12~12V) input.

13

iP5A

Wiring
For 37~90kW (50~125HP) / 315~450kW (400~600HP)
Main Power Circuit
Dynamic
Braking Unit
(Optional)

DC Bus Choke
(Optional )

DB Unit (Optional)
DB Resistor

P N B1 B2
DC Bus Choke

DB Resistor
P1 (+)

P2 (+) N (-)

MCCB (Option)
3
AC Input
50/60 Hz

R (L1)

S (L2)

T (L3)

Motor

Control Circuit
Programmable Digital Input 1 (Speed L)
Programmable Digital Input 2 (Speed M)
Programmable Digital Input 3 (Speed H)
Fault Reset (RST)

+
-

M1
M2

+
-

M3
M4

Inverter Disable (BX)

V+

Analog Power Source (+12V)

V1

Frequency Reference (0~12V, V1S: -12~12V)

CM

Frequency Reference Common Terminal

Frequency Reference (0~20mA or 4~20mA)

V-

Analog Power Source (-12V)

S0
S1
5G

Output Frequency Meter

M5

Jog Frequency Reference (JOG)

M6

Forward Run Command (FX)

M7

Reverse Run Command (RX)

M8

Common Terminal

Max. output voltage: 12V


Source max.: 30mA
Sink max.: 20mA

Output Voltage Meter


Common for Output Meter Signal

CM

Programmable Digital Output

A1
C1
A2

3A
3C
3B

C2
A3

A0

C3
A4

B0
CM

Fault Contact Output


less than AC250V (DC30V), 1A

Frequency Reference (Pulse: 0~100kHz)


Common for Frequency Reference (Pulse)

C4

RS485 Signal
RS485 Common

CC+
CM

Note 1) 5G is Common Ground for Analog Meter Output (SO, S1) and External motor thermal detection (ET).
2) Use terminal V1 for V1, V1S (0~12V, -12~12V) input.
3) DC Reactor is built basically in inverters for 15~280kW.

14

ET
5G

External Motor Thermal Detection

Industrial Inverter for Fan and Pump STARVERT iP5A

For 110~280kW (150~350HP)


Main Power Circuit
Dynamic
Braking Unit
(Optional)

DB Unit (Optional)
DB Resistor

P N B1 B2
DB Resistor
P2 (+)
MCCB (Option)
DC Reactor (Built-in)
3
AC Input
50/60 Hz

R (L1)

S (L2)

T (L3)

Motor

Control Circuit
Programmable Digital Input 1 (Speed L)
Programmable Digital Input 2 (Speed M)
Programmable Digital Input 3 (Speed H)
Fault Reset (RST)

+
-

M1
M2

+
-

M3
M4

Inverter Disable (BX)

V+

Analog Power Source (+12V)

V1

Frequency Reference (0~12V,V1S: -12~12V)

CM

Frequency Reference Common Terminal

Frequency Reference (0~20mA or 4~20mA)

V-

Analog Power Source (-12V)

S0
S1
5G

Output Frequency Meter

M5

Jog Frequency Reference (JOG)

M6

Forward Run Command (FX)

M7

Reverse Run Command (RX)

M8

Common Terminal

Max. output voltage: 12V


Source max.: 30mA
Sink max.: 20mA

Output Voltage Meter


Common for Output Meter Signal

CM

Programmable Digital Output

A1
C1
A2

3A
3C
3B

C2
A3

A0

C3
A4

B0
CM

Fault Contact Output


less than AC250V (DC30V), 1A

Frequency Reference (Pulse: 0~100kHz)


Common for Frequency Reference (Pulse)

C4

RS485 Signal
RS485 Common

CC+

ET
5G

External Motor Thermal Detection

CM

Note 1) 5G is Common Ground for Analog Meter Output (SO, S1) and External motor thermal detection (ET).
2) Use terminal V1 for V1, V1S (0~12V, -12~12V) input.
3) DC Reactor is built basically in inverters for 15~280kW.

15

iP5A

Wiring
For 15~30kW (20~40HP) Built-in DCL Type

P N B1 B2
DB Resistor
P (+)

N (-)

DC Reactor

3
AC Input
50/60 Hz

R (L1)

S (L2)

T (L3)

Motor

For 37~90kW (50~125HP) Built-in DCL Type

P N B1 B2
DB Resistor
P1 (+)

P2 (+)

N (-)

DC Reactor

3
AC Input
50/60 Hz

R (L1)

S (L2)

T (L3)

Note) P1 (+) is not provided for wiring.

16

Motor

Industrial Inverter for Fan and Pump STARVERT iP5A

Terminal Configurations (Power Circuit Terminal)


0.75~30kW (1~40HP) <200V/400V Class>

R(L1) S(L2) T(L3)

(+)

(+)

(--)

P1

P2

Jumper

37~90kW (50~125HP) / 315~450kW (400~600HP)400V/600V Class

R(L1) S(L2) T(L3)

(+)

(+)

(--)

P1

P2

Jumper

15~18.5kW (20~25HP)Built-in DC Reactor Type, 400V Class

R(L1) S(L2) T(L3)

(+)

(--)

22~30kW (30~40HP)Built-in DC Reactor Type, 400V Class

R(L1) S(L2) T(L3)

(+)

(-)

37~90kW (50~125HP) / 110 ~280kW (150~350HP)Built-in DC Reactor Type, 400V Class

R(L1) S(L2) T(L3)

(+)

(--)

P2

Note) P1 (+) is not provided for wiring.

Symbol

Description

R, S, T (L1, L2, L3)

AC Line Voltage Input

Earth Ground

P1 (+), P2 (+)

External DC Reactor [P1 (+)-P2 (+)] Connection Terminals (Jumper must be removed).

P2 (+), N (-) or P (+), N (-)

DB Unit [P2 (+)-N (-)] Connection Terminals

U, V, W

3 Phase Power Output Terminals to Motor

17

iP5A

Terminal Configurations (Power Circuit Terminal)


Grounding
Inverter Capacity
kW
HP
0.75 ~ 3.7 kW
1~5
5.5 ~ 7.5
7.5 ~ 10
11 ~ 15
15 ~ 20
18.5 ~ 30
25 ~ 40
37 ~ 55
50 ~ 75
75 ~ 90
100 ~ 125
110 ~ 132
150 ~ 200
160 ~ 280
250 ~ 350
315 ~ 375
400 ~ 600
450
700

Grounding wire Sizes, kcmil (mm2)


200V Class
4
6
16
25
-

400V Class
2.5
4
10
16
25
35
70
95
150
240

Wires & Terminal lugs


Refer to below for wires, terminal lugs, and screws used to connect the inverter power input and output.
Inverter capacity

Terminal
screw size

200V
Class

400V
Class

600V
Class

0.75kW(1HP)
1.5kW(2HP)
2.2kW(3HP)
3.7kW(5HP)
5.5kW(7.5HP)
7.5kW(10HP)
11kW(15HP)
15kW(20HP)
18.5kW(25HP)
22kW(30HP)
30kW(40HP)
0.75kW(1HP)
1.5kW(2HP)
2.2kW(3HP)
3.7kW(5HP)
5.5kW(7.5HP)
7.5Kw(10HP)
11 kW(15HP)
15 kW(20HP)
18.5kW(25HP)
22~30kW(30~40HP)
37~55kW(50~75HP)
75~90kW(100~125HP)
110~132kW(150~200HP)
160kW(250HP)
220kW(300HP)
280kW(350HP)
315kW(400HP)
375kW(500HP)
450kW(600HP)
5.5kW(7.5HP)
7.5Kw(10HP)
11 kW(15HP)
15 kW(20HP)
18.5kW(25HP)
22~30kW(30~40HP)
37~55kW(50~75HP)

M4
M4
M4
M4
M4
M5
M5
M6
M6
M8
M8
M4
M4
M4
M4
M4
M4
M4
M6
M6
M8
M8
M10
M12
M12
M12
M12
M12
M12
M12
M4
M4
M4
M6
M6
M8
M8

Screw torque

Wire size
R(L1), S(L2), T(L3)

cm
Kgf

in
Ib

mm

7.1 ~12.2
7.1 ~12.2
7.1 ~12.2
7.1 ~12.2
7.1 ~12.2

6.2 ~10.6
6.2 ~10.6
6.2 ~10.6
6.2 ~10.6
6.2~10.6

24.5 ~31.8

21.2~27.6

30.6 ~38.2

26.6~33.2

61.2 ~91.8

53.1~79.7

7.1 ~12.2
7.1 ~12.2
7.1 ~12.2
7.1 ~12.2

6.2 ~10.6
6.2 ~10.6
6.2 ~10.6
6.2 ~10.6

7.1 ~12.2

6.2~10.6

30.6~38.2

26.6~33.2

61.2~91.8

53.1~79.7

89.7~122.0

77.9~105.9

182.4~215.0

158.3~186.6

7.1 ~12.2

6.2~10.6

30.6~38.2

26.6~33.2

61.2~91.8

53.1~79.7

2.5
2.5
2.5
4
5.5
8
14
22
38
38
60
2.5
2.5
2.5
2.5
3.5
3.5
5.5
8
14
22
38
60
100
150
200
250
325
2200
2250
3.5
3.5
5.5
8
14
22
38

AWG or
kcmil

14
14
14
12
10
8
6
4
2
2
1/0
14
14
14
14
12
12
10
8
6
4
2
1/0
4/0
300
400
500
700
2400
2500
12
12
10
8
6
4
2

U, V, W
mm

2.5
2.5
2.5
4
5.5
8
14
22
38
38
60
2.5
2.5
2.5
2.5
3.5
3.5
5.5
8
14
22
38
60
100
150
200
250
325
2200
2250
3.5
3.5
5.5
8
14
22
38

* Apply the rated torque to terminal screws. * Loose screws can cause of short circuit or malfunction. Tightening the screw too much can damage the terminals and cause a short circuit or malfunction.
* Use copper wires only with 600V, 75 ratings. For 7.5~11kW 240V type inverters, R(L1), S(L2), T(L3) and U, V, W terminals are only for use with insulated ring type connector.

18

AWG or
kcmil

14
14
14
12
10
8
6
4
2
2
1/0
14
14
14
14
12
12
10
8
6
4
2
1/0
4/0
300
400
500
700
2400
2500
12
12
10
8
6
4
2

Industrial Inverter for Fan and Pump STARVERT iP5A

Terminal Configurations (Control Circuit Terminal)


0.75~30kW / 1~40HP (200V/400V Class)

C+ CM C-

3A 3C 3B A1 C1

A2 C2 A3 C3 A4 C4

M6

24

M7 M8

A0

B0 5G 5G

M1 CM M2 M3

24

M4 M5

V+

V1 5G

C+ CM C-

M6

24

M7 M8

CM NC 5G 5G ET

S0

M1 CM M2 M3

24

M4 M5

V+

A0 B0

V-

S0

S1

NT

37~450 kW/50~600HP (400V Class)

3A 3C 3B A1 C1

A2 C2 A3 C3 A4 C4

V1 CM

V-

S1

19

iP5A

Terminal Configurations (Control Circuit Terminal)

Type

Symbol
M1, M2, M3
FX [M7]
RX [M8]

Starting

JOG [M6]

Name
Defines programmable digital inputs

Digital Input 1, 2, 3

(Factory setting : Multi-step frequency 1,2,3)

Forward Run
Command
Reverse Run
Command

Select

Forward run when closed and stopped when open


Reverse run when closed and stopped when open

Jog Frequency

Runs at jog frequency when the jog signal is on.

Reference

The direction is set by the FX (or RX) signal

Contact
Function

Description

Programmable

When the BX signal is ON, the output of the inverter is turned off.
BX [M5]

Emergency Stop

RST [M4]

Fault Reset

When motor uses an electrical brake to stop, BX is used to turned off the output signal.
Take caution when BX signal is off (Not turned off by latching) and FX signal (or RX signal) is on.

Input Signal

Under these conditions, the motor will run!

CM
24

V+, VV1
Analog
Frequency

Setting
A0, B0

External
Motor Thermal
Detection

Output Signal

Sequence Common

Common 24V terminal for PNP contact input.

(PNP)

Maximum output : +24V, 100mA

Analog Power Source

Power supply for analog frequency setting.

(+12V,-12V)

Maximum output : +12V, 100mA, -12V, 100mA

Frequency Reference

Used by a DC 0~12V or -12~12V input to set the frequency reference.

(Voltage)

(Input impedance is 20k)

Frequency Reference

Used by a 0-20mA input to set the frequency reference.

(Current)

(Input impedance is 249)

Frequency Reference
(Pulse)

Used by a pulse input to set the frequency reference.

Frequency Reference
Common Terminal

NT (~30kW)

External Motor

Motor thermal sensor input. Used to prevent motor from overheating by using a NTC or

ET (37kW~)

Thermal Detection

PTC thermal sensor.

5G

CM
S0, S1,
5G
3A, 3C, 3B
Contact
A1~4, C1~4

20

Common terminal for NPN contact

CM (37kW~)

Built-in RS485 Terminal

Note) NC terminal is unavailable

(NPN)

5G (~30kW)

C+, C-

Analog Output

Sequence Common

Used for fault reset.

Common for
NT (or ET)
RS485 signal
High, Low
RS485 common
Programmable
Voltage Output
Analog Common Terminal
Fault Contact
Output

Common terminal for analog frequency reference signal

Common terminal for external motor thermal detection


RS485 signal (See RS485 communication in manual for more details.)
Common ground. Terminal for RS485 interface.
Voltage output for one of the following : Output frequency, output current, output voltage, DC link voltage.
Default is set to output frequency.
(Maximum output voltage and output current are 0-12V and 1mA)
Common terminal for analog output (S0, S1)
Energizes when a fault is present. (AC250V, 1A; DC30V, 1A)
Fault : 3A-3C closed (3B-3C open)
Normal : 3B-3C Closed (3A-3C open)

Programmable

Defined by programmable digital output terminal settings

Digital Output

(AC250V, 1A or less; DC30V, 1A or less)

Industrial Inverter for Fan and Pump STARVERT iP5A

iP5A provides Sink/Source (NPN/PNP) modes for sequence input terminal on the control circuit. The logic of the
input terminal is settable to Sink mode (NPN mode)/Source mode (NPN mode) by using the J1 switch.
Connection method is shown below.
Sink mode (NPN mode)
Put J1 switch down to set to Sink mode
(NPN mode). CM terminal (24V GND) is
common terminal for contact signal
input.
The factory default is Sink mode
(NPN mode).

Source mode (PNP mode)


Internal Power Supply Used
Put J1 switch up to set to Source mode
(PNP mode). Terminal 24 (24V Power
Supply) is common terminal for contact
input signal.

Source mode (PNP mode)


External Power Supply Used
Put J1 switch up to set to Source mode
(PNP mode).
To use external 24V Power Supply,
make a sequence between external
Power Supply (-) terminal and CM
(24V GND) terminal.

21

iP5A

Programming Keypad
LCD Loader

Data set up start

32 character, background
light, LCD display.
Background tone is
adjustable.

Shift between function


groups
Shifting from group code to
the upper code

Shift to function code


Shift to next function code
Data is increased in set up
mode

Reverse run command key


Only available with loader operation
LED is turned ON with reverse run
Blinks during Acc/Deceleration of reverse run

22

Decimal point shift


Only available in case of
data setup

Forward run command key


Only available with loader operation
LED is turned ON with forward run
Blinks during Acc/Deceleration of forward run

Shift to function code


Shift to previous code
Data is decreased in set up mode

Data set up completion

Stop command
Available with the loader operation
LED is turned on when inverter stops its operation
Blinks when fault occurs
Reset
Fault reset

Industrial Inverter for Fan and Pump STARVERT iP5A

Programming Keypad (Parameter Navigation)


Parameter group moves directly to DRV group by pressing [SHIFT] key in any parameter code.

Drive Group

FU1 Group

FU2 Group

I/O Group

Note) This figure shows group and code navigation through LCD display keypad. It can be different from actual display due to the group addition or code change.

23

iP5A

Parameter Description
DRV Group
CODE

Comm.
Addr

DRV-00 Note1)

9100

DRV-01

9101

DRV-02

9102

Description
Command Frequency
(Output Frequency during
motor run, Reference
Frequency during motor
stop), Output Current (LCD)
Acceleration 0.75~90kW (1~125HP)
Time
110~450kW (150~600HP)
Deceleration 0.75~90kW (1~125HP)
Time
110~450kW (150~600HP)

LCD Keypad
Display

Setting Range

Factory
Default

Adj.
During Run

Cmd. freq

0 to FU1-30[Hz]

0 [Hz]

Acc. Time

0 to 6000 [sec]

Dec. time

DRV-03

9103

Drive Mode
(Run/Stop Method)

Drive mode

DRV-04

9104

Frequency Mode (Frequency


setting method)

Freq mode

DRV-05
DRV-06
DRV-07
DRV-08
DRV-09
DRV-10

9105
9106
9107
9108
9109
910A

Step Frequency 1
Step Frequency 2
Step Frequency 3
Output Current
Motor Speed
DC link Voltage

Step freq-1
Step freq-2
Step freq-3
Current
Speed
DC link Vtg

DRV-11

910B

User Display Selection

User disp

DRV-12
DRV-14 Note2)
DRV-15 Note2)
DRV-16
DRV-18 Note2)
DRV-19
DRV-20 Note3)

910C
910E
910F
9110
9112
9113
9114

Current Trip Display


Target/Output Frequency Display
Reference/Feedback Frequency Display
Speed Unit Selection
PID Parameter
AD Parameter
EXT-PID Parameter

Fault
Tar. Out. Freq.
Ref. Fbk. Freq.
Hz/Rpm Disp
RTFO
V1 V2 V1S I
RTFO

DRV-22

9116

Local/Remote Key

LocalRemKey

DRV-23

9117

Keypad Mode Key

Ref Mode

DRV-91 Note4)

915B

Drive mode 2

Drive mode2

DRV-92

915C

Frequency mode 2

Freq mode2

0 to 6000 [sec]
0
1
2
3
0
1
2
3
4
5
6
7
8

(Keypad)
(Fx/Rx-1)
(Fx/Rx-2)
(Int. 485)
(Keypad-1)
(Keypad-2)
(V1)
(V1S)
(I)
(V1+I)
(Pulse)
(Int. 485)
(Ext. PID)
0 to FU1-30[Hz]
* [A]
* [rpm]
* [V]

1
2
3
4
5
6
1
2
3
4
5
6
0
1
2
0
1
2
3
4
5
6

*
* [Hz]
* [Hz]
Hz or Rpm
* [Hz]
*
%
(Cntl&RefStop)
(Control Stop)
(Ref Only)
(Cntl&Ref Run)
(Control Run)
(Disable)
(Minimum Spd)
(Last Spd)
(Preset Spd 1)
(Stop)
(Fault)
(Disable)
(Keypad)
(Fx/Rx-1)
(Fx//Rx-2)
(Keypad-1)
(Keypad-2)
(V1)
(V1S)
(I)
V1+I)
(Pulse)

20 [sec]
60 [sec]
30 [sec]
90 [sec]

1
(Fx/Rx-1)

0
(Keypad-1)

10 [Hz]
20 [Hz]
30 [Hz]
* [A]
* [rpm]
* [V]
Output
voltage [V]
*
* [Hz]
* [Hz]
Hz
* [Hz]
*
%

*
*
*

Cntl&RefStop

Disable

1
(Fx/Rx-1)

0
(Keypad-1)

*
*
*
*

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set.
Note 1) The speed unit is changed from [Hz] to [%] when DRV-16 is set to [Rpm]. Only User Unit will be displayed when APP-02 is set to [Yes] and when APP-06 is set to either I, V1 or Pulse and when one of I/O-86~ I/O-88 is set to
either [Speed] (Hz or Rpm), [Percent], [Bar], [mBar], [kPa] or [Pa]. Output Frequency (Hz or Rpm; Unit of outupt speed) is displayed in DRV-00 during the Inverter is running. User Unit reference (Unit of PID controller selected) is
displayed in DRV-00 during the Inverter is not running. 2) DRV-15, DRV-18 will appear when APP-02 [Process PI Mode] is set to Yes. Also User Unit is displayed when one of I/O-86~ I/O-88 is set to either [Speed](Hz or
Rpm), [Percent], [Bar], [mBar], [kPa] or [Pa]. 3)DRV-20 will appear when APP-80 [ExtProcess PI Mode] is set to Yes. 4) DRV-91/92 will appear only when DRV-22 is set to [2nd Source].

24

Industrial Inverter for Fan and Pump STARVERT iP5A

FU1 GROUP
CODE

Comm.
Addr

FU1-00

9200

Jump to Desired Code #

Jump code

FU1-01

9201

Run Prevention

Run prevent

FU1-02

9202

Acceleration Pattern

Acc. Pattern

FU1-03

9203

Deceleration Pattern

Dec. Pattern

FU1-04 Note5)

9204

FU1-05

9205

FU1-10

920A

Pre-Heat

Pre-Heat mode

FU1-11
FU1-12

920B
920C

Pre-Heat Value
Pre-Heat Duty

Pre Heat level


Pre Heat Perc

FU1-20

9214

Start Mode

Start mode

FU1-21 Note6)
FU1-22

9215
9216

Starting DC Injection Braking Time


Starting DC Injection Braking Value

DcSt time
DcSt value

Description

Start Curve for S-Curve


Accel/Decel Pattern
End Curve for S-Curve
Accel/Decel Pattern

LCD Keypad
Display

Setting Range

0
1
2
0
1
2
0
1
2

1 to 74
(Use Only LCD Keypad)
(None)
(Fwd prev)
(Rev prev)
(Linear)
(S-curve)
(U-curve)
(Linear)
(S-curve)
(U-curve)

Factory
Default

Adj.
During Run

0 (None)

0 (Linear)

0 (Linear)

Start Curve

0 to 100[%]

50 [%]

End Curve

0 to 100[%]

50 [%]

0 (No)

30 (%)
50 (%)

0 (Accel)

0.1 [sec]
50 [%]

0 (Decel)

0.1 [sec]
5 [Hz]
1 [sec]
50 [%]

0 (No)

60.00 [Hz]
60.00 [Hz]
60.00 [Hz]
0.50 [Hz]

0 (No)

0.50 [Hz]
60.00 [Hz]

0 (Linear)

FU1-23

9217

Stop Mode

Stop mode

FU1-24 Note7)
FU1-25
FU1-26
FU1-27

9218
9219
921A
921B

DC Injection Braking On-delay Time


DC Injection Braking Frequency
DC Injection Braking Time
DC Injection Braking Value

DcBlk Time
DcBrk freq
DcBr time
DcBr value

FU1-28

921C

Safety Stop

Safety Stop

FU1-29
FU1-30
FU1-31
FU1-32

921D
921F
9220
9220

Power Source Freq


Maximum Frequency
Base Frequency
Starting Frequency

Line Freq
Max Freq
Base Freq
Start Freq

FU1-33

9221

Frequency Limit selection

Freq limit

FU1-34 Note8)
FU1-35

9222
9223

Freq Lower Limit


Freq Upper Limit

Lim Lo Freq
Lim Hi Freq FU

FU1-40

9228

Volts/Hz Pattern

V/F Pattern

0
1

0
1
2

0
1
2
3

0
1

0
1

0
1
2

(No)
(Yes)
1 to 50[%]
1 to 100 [%]
(Accel)
(Dc-start)
(Flying-start)
0 to 60 [sec]
0 to 150 [%]
(Decel)
(Dc-brake)
(Free-run)
(Flux-brake)
0.1 to 60 [sec]
0.1 to 60 [Hz]
0 to 60 [sec]
0 to 200 [%]
(No)
(Yes)
40 to 120 [Hz]
40 to 120 [Hz]
30 to 120 [Hz]
0.01 to 10 [Hz]
(No)
(Yes)
0 - FU1-35
1-34 - FU1-30
(Linear)
(Square)
(User V/F)

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set.
Note 5) Only displayed when FU1-02, FU1-03 is set to [S-Curve].
6) Only displayed when FU1-20 is set to [DC-start].
7) Only displayed when FU1-23 is set to [DC-break].
8) Only displayed when FU1-33 is set to [Yes].

25

iP5A

Parameter Description
FU1 GROUP
Comm.
Addr

CODE
FU1-41
FU1-42
FU1-43
FU1-44
FU1-45
FU1-46
FU1-47
FU1-48
FU1-49
FU1-50

Note9)

Description

9229
922A
922B
922C
922D
922E
922F
9230
9231
9232

User V/FFrequency 1
User V/FVoltage 1
User V/FFrequency 2
User V/FVoltage 2
User V/FFrequency 3
User V/FVoltage 3
User V/F Frequency 4
User V/FVoltage 4
Input voltage adjustment
Motor Rated Voltage

User freq 1
User volt 1
User freq 2
User volt 2
User freq 3
User volt 3
User freq 4
User volt 4
VAC 380.0V
Motor Volt

FU1-51

9233

Energy Save

Energy save

FU1-52 Note10)
FU1-54
FU1-55
FU1-56

9234
9236
9237
9238

Energy Save %
Integrating Wattmeter
Inverter Temperature
Motor Temperature

Manual save%
KiloWattHour
Inv. Temp.
Motor Temp.

FU1-57

9239

No Motor Selection

No Motor Sel

FU1-58
FU1-59

923A
923B

Trip Current Level


Trip Time Setting

No Motor Level
No Motor Time

FU1-60

923C

Electronic Thermal Selection

ETH select

FU1-61
FU1-62

923D
923E

ETH 1min
ETH Cont

FU1-63

923F

Motor type

FU1-64
FU1-65

9240
9241

Electronic Thermal Level for 1 Minute


Electronic Thermal Level for Continuous
Characteristic Selection
(Motor Type)
Overload Warning Level
Overload Warning Time

FU1-66

9242

Overload Trip Selection

OLT select

FU1-67 Note11)
FU1-68
FU1-69
FU1-70
FU1-71
FU1-72

9243
9244
9245
9246
9247
9248

OLT level
OLT time
Trip select
Stall Mode.
Stall level
Acc/Dec ch F

FU1-73

9249

Overload Trip Level


Overload Trip Delay Time
Input/Output Phase Loss Protection
Stall Prevention Selection
Stall Prevention Level
Accel/Decel Change Frequency
Reference Frequency for
Accel and Decel

FU1-74

924A

Accel/Decel Time Scale

Time scale

FU1-75

924B

Up Down Save Mode

UpDnSaveMode

FU1-76 Note31)

924C

Up Down Save Freq

UpDnSaveFreq

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set.
Note 9) FU1-41~48 only displayed when FU1-40 is set toUser V/F.
10) Only displayed when FU1-51 is set toManual.
11) Only displayed when FU1-66 is set toYes.
31) Only displayed when FU1-75 is set toYes.

26

LCD Keypad
Display

OL level
OL time

Acc/Dec freq

Setting Range
0 to FU1-30
0 to 100 [%]
0 to FU1-30
0 to 100 [%]
0 to FU1-30
0 to 100 [%]
0 to FU1-30
0 to 100 [%] 1
73 to 115.0 [%]
0 to 600 [V]
0
(None)
1
(Manual)
2
(Auto)
0 to 30 [%]
M kWh
0 to 160 [degree]
0 to 160 [degree]
0
(No)
1
(Yes)
5 to 100 [%]
0.5 to 10.0 [sec]
0
(No)
1
(Yes)
FU1-62 to 200 [%]
50 to FU1-61(Maximum 150%)
0
(Self-cool)
1
(Forced-cool)
30 to 110 [%]
0 to 30 [sec]
0
(No)
1
(Yes)
30 to 150 [%]
0 to 60 [sec]
000 to 111 (Bit Set)
No/Yes
30 to 200 [%]
0 to FU1-30
0
(Max freq)
1
(Delta freq)
0
(0.01 sec)
1
(0.1 sec)
2
(1 sec)
0
(No)
1
(Yes)
0 to 120[Hz]

Factory
Default

Adj.
During Run

15.00 [Hz]
25 [%]
30.00 [Hz]
50 [%]
45.00 [Hz]
75 [%]
60.00 [Hz]
00[%]
86.4 [%]
380 [V]

0 (None)

0 [%]
*
*
*

0 (No)
5 [%]
3.0 [sec]
1 (Yes)
150 [%]
120 [%]
0 (Self-cool)
110 [%]
10 [sec]
0 (No)
120[%]
60 [sec]
100
No
120[%]
0 [Hz]
0 (Max freq)

1 (0.1 sec)

0 (No)

0.00Hz

Industrial Inverter for Fan and Pump STARVERT iP5A

FU2 GROUP
CODE

Comm.
Addr

FU2-00

9300

FU2-01
FU2-02
FU2-03
FU2-04
FU2-05

9301
9302
9303
9304
9305

FU2-06

9306

FU2-07
FU2-08 Note12)

9307
9308

FU2-10

930A

FU2-11 Note13)
FU2-12
FU2-13
FU2-14
FU2-15
FU2-16

930B
930C
930D
930E
930F
9310

FU2-20

9314

FU2-21

9315

FU2-22

9316

FU2-23

9317

FU2-24

9318

FU2-25
FU2-26 Note15)
FU2-27

9319
931A
931B

FU2-40

9328

FU2-41
FU2-42

9329
932A

FU2-43

932B

Description

LCD Keypad
Display

Setting Range

1 to 95
(Use Only LCD Keypad)
Last trip 1
Last trip-1
By pressing [ENTER]
Last trip 2
Last trip-2
and [SEL] key, the
Last trip 3
Last trip-3
frequency, current,
Last trip 4
Last trip-4
and operational status
Last trip 5
Last trip-5
at the time of fault can be seen.
0
(No)
Erase trips
Erase trips
1
(Yes)
Dwell Frequency
Dwell time
0 to 10 [sec]
Dwell Frequency
Dwell freq
FU1-32 to FU1-30
0
(No)
Frequency Jump Selection
Jump Freq
1
(Yes)
Jump Frequency 1 Low
jump lo 1
0 to FU2-12
Jump Frequency 1 High
jump Hi 1
FU2-11 to FU1-30
Jump Frequency 2 Low
jump lo 2
0 to FU2-14
Jump Frequency 2 High
jump Hi 2
FU2-13 to FU1-30
Jump Frequency 3 Low
jump lo 3
0 to FU2-16
Jump Frequency 3 High
jump Hi 3
FU2-15 to FU1-30
Power-on run
0
(No)
Power ON Start Selection
RST restart
1
(Yes)
0
(No)
Restart after Fault Reset
RST restart
1
(Yes)
IPF Mode
0
(No)
Start After Interrupt Power
Fault Selection
1
(Yes)
Estimated SS
Speed Search Type Selection
Search Type
Real SS
No
Selection of Auto Retry
Retry Mode
Yes
Number of Auto Retry
Retry number
0 to 10
Delay Time Before Auto Retry
Retry delay
0 to 60 [sec]
Speed Search Current Limit
Flying Perc
30 to 160
0
(0.75kW)
1
(1.5kW)
2
(2.2kW)
3
(3.7kW)
4
(5.5kW/)
5
(7.5kW/)
6
(11.0kW)
7
(15.0kW)
8
(18.5kW)
9
(22.0kW)
10
(30.0kW)
Rated Motor Selection for
Motor select
11
(37.0kW)
inverter (0.75~450kW)
12
(45.0kW)
13
(55.0kW)
14
(75.0kW)
15
(90.0kW)
16
(110.0kW)
17
(132.0 kW)
18
(160.0 kW)
18
(220.0 kW)
20
(280.0 kW)
21
(315.0 kW)
22
(375.0 kW)
23
(450.0 kW)
* A motor rating same as inverter capacity is automatically set. If different, set the correct value.
Number of Motor Poles
Pole number
2 to 12
Rated Motor Slip
Rate-Slip
0 to 10 [Hz]
Jump to desired code #

Rated Motor Current (RMS)

Jump code

Rated-Curr

1.0 to 999.9 [A]

Factory
Default

Adj.
During Run

40

0 (None)
0 (None)
0 (None)
0 (None)
0 (None)

0 (No)

0 [sec]
5.00[Hz]

0 (No)

10.00[Hz]
15.00[Hz]
20.00[Hz]
25.00[Hz]
30.00[Hz]
35.00[Hz]

0 (No)

0 (No)

0(No)

estmated SS

No

0
1 [sec]
70%

* Depending
on the
inverter
capacity

4
Depending
on the motor
capacity

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set.
Note 12) Only displayed when FU2-07 is set to [1~10 sec].
13) FU2-11 is displayed when FU2-10 is set to [Yes]..
14) FU2-26 is displayed when FU2-25 [Retry number] is set to [1~10].
15) FU2-64 is displayed when FU2-60 is set to [Sensorless].

27

iP5A

Parameter Description
FU2 GROUP
CODE

Comm.
Addr

Description

Setting Range

Factory
Default

FU2-44

932C

No Load Motor Current(rms)

Noload-Curr

0.1 to 999.9 [A]

FU2-46
FU2-47

932E
932F

Load Inertia
Gain for Motor Speed Display

Inertia rate
RPM DisplayGn

FU2-48

9330

Carrier Frequency

Carrier freq

FU2-49

9331

PWM Type Selection

PWM Select

FU2-52
FU2-53

9334
9335

Safety Stop Dec. Rate


Safety Stop Output Dec. Rate

Dec Rate
safety_perc

FU2-60

933C

Control Mode Selection

Control Mode

FU2-61

933D

Auto Tuning Selection

Auto Tuning

FU2-62
FU2-63
FU2-64 Note16)

933E
933F
9340

%Rs
%Lsigma
PreEx time

FU2-67

9343

Stator Resistance of Motor


Leakage Inductance of Motor
Pre-excitation Time
Manual/Auto Torque Boost
Selection

FU2-68

9344

Torque Boost in Forward Direction

Fwd boost

FU2-69

9345

Torque Boost in Reverse Direction

Rev boost

FU2-80
FU2-81
FU2-82
FU2-83
FU2-84
FU2-85
FU2-87

9350
9351
9352
9353
9354
9355
9357

Power On display
User Select
Software Version
Last Trip Time
Power On Time
Run-time
Power Set

PowerOn Disp
User Disp
iP5A S/W Ver
LastTripTime
On-time
Run-time
Power Set

FU2-90

935A

Parameter Display

Para. disp

FU2-91

935B

Read Parameter

Para. Read

FU2-92

935C

Write Parameter

Para. Write

FU2-93

935D

Initialize Parameters

Para. Init

FU2-94

935E

Parameter Write Protection

Para. Lock

FU2-95

935F

Parameter Save

Para. Save

0 to 40
1 to 1000 [%]
0.75~22kW
0.7~15[kHz]
30kW
0.7~10[kHz]
37~75kW
0.7~4[kHz]
90~280kW
0.7~3[kHz]
315~450kW
0.7~2[kHz]
0
(Normal)
1
(Low leakage)
1.0 to 100.0 [sec]
2 to 500
0
(V/F)
1
(Slip compen)
2
(Sensorless)
0
(No)
1
(Static)
0.01 to 20 [%]
0.01 to 100 [%]
0 to 60 [sec]
0
(Manual)
1
(Auto)
0.75~90kW
0 to 15 [%]
110~450kW
0.75~90kW
0 to 15 [%]
110~450kW
0 to 12
Voltage Watt
Ver X.X Ver
X:XX:XX:XX:XX:X
X:XX:XX:XX:XX:X
X:XX:XX:XX:XX:X
0.01 to 400 [%]
0
Default
1
(All Para)
2
(Diff Para)
0
(No)
1
(Yes)
0
(No)
1
(Yes)
0
(No)
1
(All Groups)
2
(BAS)
3
(DRV)
4
(FU1)
5
(FU2)
6
(I/O)
7
(EXT)
8
(COM)
9
(APP)
0 to 9999
0
(No)
1
(Yes)

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set.
Note 16) FU2-64 is displayed when FU2-60 is set to [Sensorless].
Table 1) Switching frequency and fatory default value for each inverter capacity

28

LCD Keypad
Display

Torque boost

Inverter Capacity
0.75 ~ 22 kW
30 kW
37 ~ 75 kW
90 ~ 280 kW
315 ~ 450 kW

Adj.
During Run

Depending
on the motor
capacity
10
100 [%]

5.0 [kHz]
4.0 [kHz]
3.0 [kHz]
2.0 [kHz]

0 (Normal )

100.0 [sec]
21
0 (V/F)

0 (No)

4[%]
12[%]
1 [sec]

0 (Manual)

2.0 [%]
1.0 [%]
2.0 [%]
1.0 [%]
0
Voltage
X.X
*
*
*
100

0 (Default)

0 (No)

0 (No)

0 (No)

0 (No)

Setting Range
0.7 ~ 15 [kHz]
0.7 ~ 10 [kHz]
0.7 ~ 4 [kHz]
0.7 ~ 3 [kHz]
0.7 ~ 2 [kHz]

Factory Default
5.0 [kHz]
4.0 [kHz]
3.0 [kHz]
2.0 [kHz]

Industrial Inverter for Fan and Pump STARVERT iP5A

I/O GROUP
CODE
I/O-00

Comm.
Addr
9400

Description

LCD Keypad
Display

Setting Range

Factory
Default

Adj.
During Run

Jump to Desired Code #

Jump code

1 to 98

V1 Filter

0 to 9999 [msec]

10 [msec]

0.00 [V]

0.00 [Hz]

10 [V]

60.00 [Hz]

10 [msec]
4 [mA]

0.00 [Hz]

20 [mA]

60.00 [Hz]

1 (A)

10 [msec]
0 [kHz]

0 [Hz]

10 [kHz]

60.00 [Hz]

0 (None)

0 (None)

1.0 [sec]

0 (Speed-L)

I/O-01 Note17)

9401

I/O-02

9402

I/O-03

9403

I/O-04

9404

Filtering Time Constant for


V1 Signal Input
V1 Input Minimum Voltage
Frequency Corresponding to
V1 Input Minimum Voltage
V1 Input Minimum Voltage

I/O-05

9405

V1 Input Maximum Voltage

V1 Freq y2

I/O-06
I/O-07

9406
9407

I Filter
I curr x1

I/O-08

9408

I/O-09

9409

I/O-10

940A

Filtering Time Constant for I Signal Input


I Input Minimum Current
Frequency Corresponding to
I Input Minimum Current
Filtering Time Constant for I Signal Input
Frequency Corresponding to
I Input Maximum Current

I/O-11

940B

Pulse Input Method

P Pulse set

I/O-12
I/O-13

940C
940D

P filter
P pulse x1

I/O-14

940E

I/O-15

940F

I/O-16

9410

Pulse Input Filter


Pulse Input Minimum Frequency
Frequency Corresponding to
I/O-13 Pulse Input Minimum Frequency
Pulse Input Maximum Frequency
Frequency Corresponding to
I/O-15 Pulse Input Maximum Frequency

I/O-17

9411

Criteria for Analog Input Signal Loss

Wire broken

I/O-18

9412

Operating selection at Loss


of Freq. Reference

Lost command

I/O-19

9413

Waiting Time after Loss of Freq. Reference

Time out

V1 volt x1
V1 Freq y1
V1 volt x2

I Freq y1
I curr x2
I Freq y2

P freq y1
P pulse x2
P freq y2

Programmable Digital Input Terminal


I/O-20

9414

M1 Define

0
1

M1 Define

0
1
2
0
1
2
3
0
1
2
3
4
5
6
7
8
9
10
11
13

0 to 12[V]
0 to FU1-30 [Hz]
0 to 100.00 [**] Note18)
0 to 12[V]
0 to FU1-30 [Hz]
0 to 100.00 [**] Note18)
0 to 9999 [msec]
0 to 20 [mA]
0 to FU1-30 [Hz]
0 to 100.00 [**] Note18)
0 to 20 [mA]
0 to FU1-30 [Hz]
0 to 100.00 [**] Note18)
(A+B)
(A)
0 to 9999 [msec]
0 to 10 [kHz]
0 to FU1-30 [Hz]
0 to 100.00 [**] Note18)
0 to 100 [kHz]
0 to FU1-30 [Hz]
0 to 100.00 [**] Note18)
(None)
(half of x1)
(below x1)
(None)
(FreeRun)
(Stop)
(Protection)
0.1 to 120 [sec]
(Speed-L)
(Speed-M)
(Speed-H)
(XCEL-L)
(XCEL-M)
(XCEL-H)
(Dc-brake)
(2nd Func)
(Exchange)
(- Reserved -)
( Up)
(Down)
(Ext Trip)

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set.
Note 17) When DRV-04 is set to either V1, V1S, I or V1+I or Pulse, only selected item codes are displayed in I/O-1~I/O-19.
18) I/O-3,5,8,10,14,16 is displayed 0~100.00 [**] when App-02 is set to [proc PI mode] or APP-80 is set to [Ext PImode] and APP-06 PID Feedback Signal Selection is set to one of I, VI, Pulse, after then, one of I/O-86 ~I/O-88
is set to percentage, Bar, mBar, kPa, Pa except for Speed. Unit will be changed to selected unit. Only user unit displayed when APP-02 or APP-80 is set to [Yes], after APP-06 is set to one of I, V, Pulse, after then one of
I/O-86 ~I/O-88 is set to either speed, percentage, Bar, mBar, kPa, Pa..

29

iP5A

Parameter Description
I/O GROUP
CODE

Comm.
Addr

I/O-20

9414

I/O-21

9415

I/O-22

9416

I/O-23

9417

I/O-24

9418

I/O-25

9419

I/O-26

941A

I/O-27

941B

I/O-28

941C

I/O-29

941D

I/O-30
I/O-31
I/O-32
I/O-33
I/O-34
I/O-35
I/O-36
I/O-37
I/O-38

Note19)

941E
941F
9420
9421
9422
9423
9424
9425
9426

Description

Programmable Digital Input


Terminal M1 Define

Programmable Digital Input


Terminal M2 Define
Programmable Digital Input
Terminal M3 Define
Programmable Digital Input
Terminal M4 Define
Programmable Digital Input
Terminal M5 Define
Programmable Digital Input
Terminal M6 Define
Programmable Digital Input
Terminal M7 Define
Programmable Digital Input
Terminal M8 Define
Terminal Input Status
Filtering Time Constant for
Programmable Digital Input Terminals
Jog Frequency Setting
Step Frequency 4
Step Frequency 5
Step Frequency 6
Step Frequency 7
Step Frequency 8
Step Frequency 9
Step Frequency 10
Step Frequency 11

LCD Keypad
Display

M1 Define

Setting Range
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35

(Pre-Heat)
(iTerm Clear)
(Open-loop)
(LOC/REM)
(Analog hold)
(XCEL stop)
(P Gain2)
-Reserved(Interlock1)
(Interlock2)
(Interlock3)
(Interlock4)
(Speed_X)
(RST)
(BX)
(JOG)
(FX)
(RX)
(ANA_CHG)
(Pre-Excite)
(Ext PID Run)
(Up/Dn Clr)

Factory
Default

0 (Speed-L)

M2 define

Same as I/O-20

1 (Speed-M)

M3 define

Same as I/O-20

2 (Speed-H)

M4 define

Same as I/O-20

27 (RST)

M5 define

Same as I/O-20

12 (Stop/3-wire )

M6 define

Same as I/O-20

29 (JOG)

M7 define

Same as I/O-20

30 (FX)

M8 define

Same as I/O-20

31 (RX)

In status

00000000000/11111111111

00000000000

Ti Filt Num

2 to 1000 [msec]

15

10 [Hz]
40 [Hz]
50 [Hz]
40 [Hz]
30 [Hz]
20 [Hz]
10 [Hz]
20 [Hz]
30 [Hz]

Jog Freq
Step Freq-4
Step Freq-5
Step Freq -6
Step Freq-7
Step Freq -8
Step Freq -9
Step Freq -10
Step Freq -11

0 to FU1-30

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set.
Note 19) I/O-30 ~ I/O-34 displayed only when one of I/O-20 ~ I/O-27 is set to either JOG, Speed_L, Speed_M, Speed_H. I/O-35 ~ I/O-42 displayed only when one of I/O-20 ~ I/O-27 is set to Speed_X.

30

Adj.
During Run

Industrial Inverter for Fan and Pump STARVERT iP5A

CODE

Comm.
Addr

I/O-39
I/O-40
I/O-41
I/O-42

9427
9428
9429
942A

I/O-50

9432

I/O-51

9433

I/O-52 Note20)

9434

I/O-53
I/O-54
I/O-55
I/O-56
I/O-57
I/O-58
I/O-59
I/O-60
I/O-61
I/O-62
I/O-63

9435
9436
9437
9438
9439
943A
943B
943C
943D
943E
943F

Description
Step Frequency 12
Step Frequency 13
Step Frequency 14
Step Frequency 15
Acceleration Time 1
(for Step speed)
Deceleration Time 1
(for Step speed)
Acceleration Time 1
(for Step speed)
Deceleration Time 2
Acceleration Time 3
Deceleration Time 3
Acceleration Time 4
Deceleration Time 4
Acceleration Time 5
Deceleration Time 5
Acceleration Time 6
Deceleration Time 6
Acceleration Time 7
Deceleration Time 7

LCD Keypad
Display

Setting Range

Factory
Default

Adj.
During Run

Step Freq-12
Step Freq-13
Step Freq-14
Step Freq-15

0 to FU1-30

40 [Hz]
50 [Hz]
40 [Hz]
30 [Hz]

Acc time-1

0 to 6000 [sec]

20 [sec]

Dec time-1

0 to 6000 [sec]

20 [sec]

Acc time-2

0 to 6000 [sec]

30 [sec]

Dec time-2
Acc time-3
Dec time-3
Acc time-4
Dec time-4
Acc time-5
Dec time-5
Acc time-6
Dec time-6
Acc time-7
Dec time-7

30 [sec]
40 [sec]
40 [sec]
50 [sec]
50 [sec]
40 [sec]
40 [sec]
30 [sec]
30 [sec]
20 [sec]
20 [sec]

0
(Frequency)

100 [%]
2 (Voltage)
100 [%]
30.00 [Hz]

10.00 [Hz]

0 (NONE)

I/O-70

9446

S0 Output Selection

S0 mode

I/O-71
I/O-72
I/O-73
I/O-74 Note21)

9447
9448
9449
944A

S0 adjust
S1 mode
S1 adjust
FDT freq

I/O-75

944B

S0 Output Adjustment
S1 Output Selection
S1 Output Adjustment
Frequency Detection Level
Frequency Detection
Bandwidth

0 to 6000 [sec]
0 to 6000 [sec]
0 to 6000 [sec]
0 to 6000 [sec]
0 to 6000 [sec]
0 to 6000 [sec]
0 to 6000 [sec]
0 to 6000 [sec]
0 to 6000 [sec]
0 to 6000 [sec]
0 to 6000 [sec]
(Frequency)
(Current)
(Voltage)
(DC link Vtg)
(Ext PID Out)
10 to 200 [%]
Same as I/O-70
10 to 200 [%]
0 to FU1-30 [Hz]

FDT band

0 to FU1-30 [Hz]

I/O-76

944C

Programmable Digital
Output Terminal Define
(Aux terminal)

Aux Mode1

0
1
2
3
4

0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

(NONE)
(FDT-1)
(FDT-2)
(FDT-3)
(FDT-4)
(FDT-5)
(OL)
(IOL)
(Stall)
(OV)
(LV)
(OH)
(Lost Command)
(Run)
(Stop)
(Steady)

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set.
Note 20) I/O-52 ~ I/O-63 displayed only when one of I/O-20 ~ I/O-27 is set to either XCEL_L, XCEL_M, XCEL_H.
21) I/O-74 ~ I/O-75 displayed only when one of I/O-76 ~ I/O-79 is set to either FDT-1~FDT5

31

iP5A

Parameter Description
I/O GROUP
CODE

Comm.
Addr

Description

Output Terminal Define

Setting Range

Factory
Default

Adj.
During Run

(INV line)
(COMM line)
(SpeedSearch)
(Ready)
(MMC)
(CriticalTrip)

0 (NONE)

Aux mode2

Same as I/O-76

0 (NONE)

Aux mode3

Same as I/O-76

0 (NONE)

Aux mode4

Same as I/O-76

0 (NONE)

Relay mode

000 to 111 [bit]

010 [bit]

Out status

00000000/11111111

00000000

Relay On

0 to 9999

Relay Off

0 to 9999

0
(Power On Fan)

70 []

0 (Percent)

100[%]
1

3 (9600 bps)

0 (None)

1.0 [sec]

I/O-76

944C

I/O-77

944D

I/O-78

944E

I/O-79

944F

I/O-80

9450

I/O-81

9451

I/O-82

9452

I/O-83

9453

I/O-84

9454

Fan Con Sel (37 ~ 90kW)

Fan Con. Sel

I/O-85

9455

Fan Temp (37 ~ 90kW)

Fan Temp

Programmable Digital
Output Terminal Define
Programmable Digital
Output Terminal Define
Programmable Digital
Output Terminal Define
Fault Output Relay Setting
(3A, 3B, 3C)
Terminal Output Status
Waiting Time after Fault
Output Relay On
Waiting Time after Fault
Output Relay Off

Aux Mode1

COM Time Out


Delay Time

2 to 1000 [msec]

5 [msec]

In No/Nc Set
In CheckTime
OH Trip Sel
MO Trip Temp

00000000000/11111111111
1 to 1000
000 to 111 [bit]
0 to 255 []

00000000000
1 [msec]
010 [bit]
110 []

9456

Input User Unit Selection

Unit Sel

I/O-87
I/O-90

9457
945A

Unit Maximum Selection


Inverter Number

Unit Max Val


Inv No.

I/O-91 Note22)

945B

Baud Rate Selection

Baud rate

I/O-92 Note23)

945C

Operating Method
at Loss of Freq. Reference

COM Lost Cmd

I/O-93

945D

I/O-94

945E

I/O-95
I/O-96
I/O-97
I/O-98

945F
9460
9461
9462

Waiting Time after Loss of Freq. Reference


Communication Response
Delay time
A or B contact
Input time
Overheat Trip Selection
Motor Overheat Trip Temperature

16
17
18
19
20
21

(Power On Fan)
(Run Fan)
(Temper-Fan)
0 to 70 []
(Percent)
(Bar)
(mBar)
(kPa)
(PSI)
(Pa)
1.0 to 999.9[%]
1 to 250
(1200 bps)
(2400 bps)
(4800 bps)
(9600 bps)
(19200 bps)
(38400 bps)
(None)
(FreeRun)
(Stop)
0.1 to 120 [sec]

I/O-86

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set.
Note 22) 38400 bps can be set only when the external communication option card is installed.
23) Only I/O-92 ~ I/O-93 displayed when DRV-03/04 is set to [int485].

32

LCD Keypad
Display

0
1
2
0
1
2
3
4
5

0
1
2
3
4
5
0
1
2

Industrial Inverter for Fan and Pump STARVERT iP5A

APP GROUP
CODE
APP-00
APP-01
APP-02
APP-03
APP-04

Note25)
Note26)

Comm.
Addr

Description

LCD Keypad
Display

9700

Jump to Desired Code #

Jump code

9701

Application Mode Selection

App mode

9702

PID Operation Selection

Proc PI mode

9703

PID F Gain Selection


PID Auxiliary Reference
Mode Selection

PID F-Gain

9704

Aux Ref Enbl

APP-05 Note27)

9705

PID Auxiliary Reference


Signal Selection

Aux Ref Sel

APP-06

9706

PID Feedback Signal Selection

PID F/B

APP-07
APP-08
APP-09
APP-11
APP-12
APP-13
APP-14
APP-15
APP-16
APP-17
APP-18

9707
9708
9709
970B
970C
970D
970E
970F
9710
9711
9712

Meter I Maximum Value


Meter V Maximum Value
Meter P Maximum Value
P Gain for PID Control
I Time for PID Control
D Time for PID Control
High Limit Frequency for PID Control
Low Limit Frequency for PID Control
PID Output Gain
PID P2 Gain
P Gain Scale

Meter I Max
Meter V Max
Meter P Max
PID P Gain
PID I Time
PID D Time
PID Hi Limit
PID LowLimit
PID OutScale
PID P2 Gain
P Gain Scale

APP-19

9713

PID Output Inverse

PID OutInv.

APP-20

9714

PID U Curve Feedback Select

PID U Fbk

APP-23
APP-24
APP-25

9717
9718
9719

PrePID Reference Frequency


PrePID Exit Level
PrePID Stop delay

PrePID Freq
PrePID Exit
PrePID Dly

APP-26

971A

Pipe Broken

Pipe Broken

APP-27
APP-28
APP-29
APP-30 Note28)
APP-31
APP-32

971B
971C
971D
971E
971F
9720

Sleep Delay Time


Sleep Frequency
Wake-Up Level
2nd Acceleration Time
2nd Deceleration Time
2nd Base Frequency

Sleep Delay
Sleep Freq
WakeUp level
2nd Acc Time
2nd Dec Time
2nd BaseFreq

APP-33

9721

2nd V/F Pattern

2nd V/F

APP-34
APP-35
APP-36
APP-37

9722
9723
9724
9725

2nd Forward Torque Boost


2nd Reverse Torque Boost
2nd Stall Prevention Level
2nd Electronic Thermal Level for 1 Minute

2nd F-Boost
2nd R-Boost
2nd Stall
2nd ETH 1min

Setting Range
0
1
0
1
0
1
0
1
2
3
4
5
6
7
8
0
1
2

0
1
0
1

0
1

0
1
2

1 to 80
(None)
(MMC)
(No)
(Yes)
0 to 999.9[%]
(No)
(Yes)
(Keypad-1)
(Keypad-2)
(V1)
(V1S)
(I)
(V1+I)
(Pulse)
(Int. 485)
(Ext. PID)
(I)
(V1)
(Pulse)
0 to 20.00 mA
0 to 12.00 V
0 to100.0kHz
0 to 999.9 [%]
0 to 32.0 [sec]
0 to100 [msec]
0.00 to FN1-30
FN1-32 to APP-10
0.0 to 999.9 [%]
0.0 to 999.9 [%]
0.0 to 100.0 [%]
(No)
(Yes)
(No)
(Yes)
0 to FU1-30
0 to 100.0%
0 to 9999
(No)
(Yes)
0.0 to 9999 [sec]
0 to FU1-30 [Hz]
0.0 to 100.0 [%]
0 to 6000 [sec]
0 to 6000 [sec]
30 to FN1-30 [Hz]
(Linear)
(Square)
(User V/F)
0.0 to 15.0 [%]
0.0 to 15.0 [%]
30 to 150 [%]
FU2-28 to 200 [%]

Factory
Default

Adj.
During Run

0 (None)

0 (No)

0.0 [%]

0 (No)

2 (V1)

0 (I)

20.00 mA
10.00V
100.0kHz
1.0 [%]
10.0 [sec]
0.0 [msec]
60 .00[Hz]
0.5 [Hz]
100.0 [%]
100.0 [%]
100.0 [%]

0 (No)

0 (No)

0
0
600

0 (No)

60.0 [sec]
0.00 [Hz]
2 .0[%]
5 [sec]
10 [sec]
60 [Hz]

0 (Linear)

2.0 [%]
2.0 [%]
100 [%]
130[%]

The gray highlighted codes are hidden parameters and will appear when the related functions are to be set.
Note 25) Only APP-03 ~ APP-17 displayed when APP-02 is set to [Yes]. Only APP-03 ~ APP-17 and APP-63 ~ APP-65 displayed when APP-2 is set to [Yes].
26) If APP-04 Aux Ref Mode is no set, DRV-04 setting will be reference of process PID. And APP -05 setting will be ignored
27) If APP-04 is set, APP-04 will appear. And APP -05 setting value will be reference of process PID, DRV-04 setting will be ignored.
28) Only APP-20 ~ APP-29 displayed only when one of I/O-20 ~ I/O-27 is set to either2nd Func.

33

iP5A

Parameter Description
APP GROUP
Comm.
Addr

Description

LCD Keypad
Display

APP-38
APP-39
APP-40 Note29)
APP-41
APP-42
APP-43

9726
9727
9728
9729
972A
972B

2nd Electronic Thermal Level for Continuous


2nd Rated Motor Current
Number of Auxiliary Motor Run Display
Aux. Motor Start Selection
Operation Time Display on Auto Change
The Number of Aux Motor

2nd ETH Cont


2nd R-Curr
Aux Mot Run
Starting Aux
Auto Op Time
Nbr Aux`s

APP-44

972C

Aux. Motor Stop Sequence

F-in L-Out

APP-45

972D

How to stop Aux. Motor

ALL Stop

APP-47
APP-48
APP-49
APP-50
APP-51
APP-52
APP-53
APP-54
APP-58
APP-59

972F
9730
9731
9732
9733
9734
9735
9736
973A
973B

Start freq 1
Start freq 2
Start freq 3
Start freq 4
Stop freq 1
Stop freq 2
Stop freq 3
Stop freq 4
Aux start DT
Aux stop DT

APP-60

973C

APP-61

973D

Start Frequency of Aux. Motor 1


Start Frequency of Aux. Motor 2
Start Frequency of Aux. Motor 3
Start Frequency of Aux. Motor 4
Stop Frequency of Aux. Motor 1
Stop Frequency of Aux. Motor 2
Stop Frequency of Aux. Motor 3
Stop Frequency of Aux. Motor 4
Delay Time before Operating Aux Motor
Delay Time before Stopping Aux Motor
Accel Time when the Number of
Pump Decreases
Decel Time when the Number of Pump Increases

CODE

Adj.
During Run

120[%]
3.6[A]
*
1
*
4

1 (Yes)

1 (Yes)

49.99 [Hz]
49.99 [Hz]
49.99 [Hz]
49.99 [Hz]
20.00 [Hz]
20.00 [Hz]
20.00 [Hz]
20.00 [Hz]
5.0 [sec]
5.0 [sec]

Pid AccTime

0 to 600.0 [sec]

2.0 [sec]

0 to 600.0 [sec]
(No)
(Yes)
(EXCH_NONE),
(AUX_EXCH),
(MAIN_ EXCH)
00:00 to 99:00
FN1-32 to FN1-30[Hz]
0 (No)
0 to100%
0 to100%
(No)
(Yes)
(I)
(V1)
(Pulse)
(Keypad)
0 to 100.00 [%]
(I)
(V1)
(Pulse)
0 to 999.9 [%]
0 to 32.0 [sec]
0 to 2000 [msec]
0 to 100.00 [%]
0 to 30.00 [%]
0 to 999.9
0 to 999.9
0 to 100.0
0 to 999.9 [%]
(No)
(Yes)
50 to 200 [msec]

2.0 [sec]

0 (No)

0(EXCH_NONE)

72:00
20.0 [Hz]
0 (No)
2[%]
2[%]

0 (No)

3(Keypad)

50.00 [%]

0 (I)

1.0 [%]
10.0 [sec]
0 [msec]
100.00 [%]
0 [%]
100.0 [%]
100.0 [%]
100.0 [%]
0.0 [%]

0 (No)

100 [msec]

973E

PID Bypass Selection

Regul Bypass

APP-66

9742

Auto Change Mode Selection

AutoCh_Mode

APP-67
APP-68
APP-69
APP-71
APP-72

9743
9744
9745
9747
9748

Auto Change Time


Auto Change Freq
Inter-Lock Selection
Pressure difference for Aux motor Start
Pressure difference for Aux motor Stop

AutoEx-intv
AutoEx-Freq
Inter-lock
Aux Stt Diff
Aux Stp Diff

APP-80

9750

Ext PID Operation Selection

Ext PI Mode

APP-81 Note30)

9751

Ext PID Reference Signal Selection

ExtPI RefSel

APP-82

9752

Ext PID Reference Level

Ext PI Ref %

APP-83

9753

Ext PID Feedback Signal Selection

ExtPI FbkSel

APP-85
APP-86
APP-87
APP-88
APP-89
APP-90
APP-91
APP-92
APP-93

9755
9756
9757
9758
9759
975A
975B
975C
975D

P Gain for ExtPID


I Time for ExtPID
D Time for ExtPID
High Limit Frequency for ExtPID Control
Low Limit Frequency for ExtPID Control
ExtPID Output Scale
ExtPID P2 Gain
ExtPID P Gain Scale
ExtPID F Gain

ExtPID Pgain
ExtPID Itime
ExtPID Dtime
ExtPID Lmt-H
ExtPID Lmt-L
ExtPID Scale
ExtPI P2Gain
ExtPI PScale
ExtPID F-gain

APP-95

975F

ExtPID Output Inverse

ExtPI OutInv

APP-97

9761

ExtPID Loop Time

ExtPI LoopTm

34

0
1
0
1

50 to FU2-27 (Max 150%)


1 to 200 [A]
*
1 to 4
*
0 to 7
(No)
(Yes)
(No)
(Yes)
0 to FU1-30
0 to FU1-30
0 to FU1-30
0 to FU1-30
0 to FU1-30
0 to FU1-30
0 to FU1-30
0 to FU1-30
0.0 to 999.9 [sec]
0.0 to 999.9 [sec]

Factory
Default

Pid DecTime

APP-62

The gray-highlighted codes are hidden parameters and will appear when the related functions are to be set.
Note 29) Only APP-40 ~ APP-71 displayed when APP-01 is set to [MMC].
30) Only APP-81 ~ APP-97 displayed when APP-80 Ext PI mode is set to [Yes].

Setting Range

0
1
0
1
2

0
1
0
1
2
3
0
1
2

0
1

Industrial Inverter for Fan and Pump STARVERT iP5A

EXT GROUP
CODE

Comm.
Addr

Description

LCD Keypad
Display

Setting Range

Factory
Default

Adj.
During Run

Frequency

100 [%]

0 [%]

DC link Vtg

EXT-00

9500

Jump to Desired Code #

Jump code

1 to 45

EXT-01

9501

Type of SUB Board

Sub B/D

Frequency

Sub-E
Current
Voltage
EXT-40

9528

Current Output Terminal 1(CO1) Selection

AM1 mode

DC link Vtg
Ext PID Out

EXT-41

9529

Adjust Gain of Current Output Terminal 1(CO1)

AM1 adjust

10-200 [%]
0-100 [%]

EXT-42

952A

Adjust Offset of Current Output Terminal 1(CO1)

AM1 Offset

Frequency
Current
Voltage

EXT-43

952B

Current Output Terminal 2(CO2) Selection

AM2 mode

EXT-44

952C

Adjust Gain of Current Output Terminal 2(CO2)

AM2 adjust

10-200 [%]

100 [%]

EXT-45

952D

Adjust Offset of Current Output Terminal 2(CO2)

AM2 Offset

0-100 [%]

0 [%]

LCD Keypad
Display

Setting Range

Factory
Default

Adj.
During Run

1 to 60

None

Ver X.X

70

DC link Vtg
Ext PID Out

* Only the above EXT group displayed when the corresponding option board is installed.
* Refer to the SUB board option manual for details.

COM GROUP
CODE

Comm.
Addr

Description

COM-00

9600

Jump to Desired Code #

Jump code

COM-01

9601

Type of SUB Board

Opt B/D

RS485
DeviceNet
Profibus
BACnet
LonWork

COM-02

9602

Option Mode

Opt mode

None
Command
Freq
Cmd + Freq

COM-03

9603

Option Version

Opt Version

Ver X.X

COM-13

960D

Device Net Input Instance

In Instance

70
71
110
111

COM-17

9611

PLC Station ID

Station ID

0 to 63

COM-20

9614

Profi MAC ID

Profi MAC ID

1 to 127

COM-30

961E

Output Num

Output Num

0 to 8

COM-31

961F

Output 1

Output 1

0000-FFFF (HEX)

000A(HEX)

35

iP5A

Parameter Description
COM GROUP
CODE

Comm.
Addr

Description

LCD Keypad
Display

Setting Range

Factory
Default

Adj.
During Run

COM-32

9620

Output 2

Output 2

0000-FFFF (HEX)

000E(HEX)

COM-33

9621

Output 3

Output 3

0000-FFFF (HEX)

000F(HEX)

COM-34

9622

Output 4

Output 4

0000-FFFF (HEX)

0000(HEX)

COM-35

9623

Output 5

Output 5

0000-FFFF (HEX)

0000(HEX)

COM-36

9624

Output 6

Output 6

0000-FFFF (HEX)

0000(HEX)

COM-37

9625

Output 7

Output 7

0000-FFFF (HEX)

0000(HEX)

COM-38

9626

Output 8

Output 8

0000-FFFF (HEX)

0000(HEX)

COM-40

9628

Input Num

Input Num

0-8

COM-41

9629

Input 1

Input 1

0000-FFFF (HEX)

0005(HEX)

COM-42

962A

Input 2

Input 2

0000-FFFF (HEX)

0006(HEX)

COM-43

962B

Input 3

Input 3

0000-FFFF (HEX)

0000(HEX)

COM-44

962C

Input 4

Input 4

0000-FFFF (HEX)

0000(HEX)

COM-45

962D

Input 5

Input 5

0000-FFFF (HEX)

0000(HEX)

COM-46

962E

Input 6

Input 6

0000-FFFF (HEX)

0000(HEX)

COM-47

962F

Input 7

Input 7

0000-FFFF (HEX)

0000(HEX)

COM-48

9630

Input 8

Input 8

0000-FFFF (HEX)

0000(HEX)

8None/1Stop

None/1Stop
8None/2Stop

COM-60

963C

Parity/Stop

Parity/Stop 8

COM-61

963D

Opt Para-1

Opt Para-1

0 to FFFF

COM-62

963E

Opt Para-2

Opt Para-2

0 to FFFF

COM-63

963F

Opt Para-3

Opt Para-3

0 to FFFF

COM-64

9640

Opt Para-4

Opt Para-4

0 to FFFF

COM-65

9641

Opt Para-5

Opt Para-5

0 to FFFF

COM-66

9742

Opt Para-6

Opt Para-6

0 to FFFF

0 (No)

8Even/1Stop
8Odd/1Stop

COM-67

9743

Comm UpDate

* Only the above COM group displayed when the corresponding option board is installed.
* COM-61~66 parameter is used to LonWorks and BACnet communication.

36

Comm UpDate

(No)

(Yes)

Industrial Inverter for Fan and Pump STARVERT iP5A

Trial Run
Operation Example (1)

Wiring

V/F Control + Analog Voltage Input (V1)


+ Operation via Terminal (FX/RX)
3P AC INPUT

Operation condition
Control mode: V/F control
Frequency command:
50 [Hz] analog input via V1 terminal
Accel/Decel time: Accel15 [sec],
Decel25 [sec]
Drive mode: Run/Stop via FX/RX terminal,
Control terminal: NPN mode

R (L1)

S (L2)

T (L3)

IM

G
S0

S/W
M8 (RX)

S1

M7 (FX)
5G

M6
M5
M4

3A

M3

3C

M2

3B

M1
CM
Potentiometer
2 [kohm], 1/2W
V+
V1
5G

Step

Parameter setting

Description

Code

Control Mode Selection

Drive Mode

DRV-3

Set it to Fx/Rx-1.

Frequency Mode

DRV-4

Set V1 Analog input value in frequency mode.

4
5

50 [Hz] Freq
Command Setting
Accel/Decel Time

FU2-60

DRV-0
DRV-1
DRV-2

Set it to 0 (V/F).

Set freq command 50 [Hz] via V1


(Potentiometer).
Set Accel time to 15 [sec] in DRV-2.
Set Decel time to 25 [sec] in DRV-3.
Motor starts to rotate in forward direction
at 50Hz with Accel time 15 [sec] when

Terminal FX

I/O-26

FX terminal is turned ON.


Motor decelerates to stop with Decel time
25 [sec] when FX terminal is turned OFF.
When RX terminal is turned ON motor
starts to rotate in Reverse direction

Terminal RX

I/O-27

at 50 [Hz] with Accel time 15 [sec].


When it is OFF, motor decelerates to stop
with Decel time 25 [sec].

37

iP5A

Trial Run
Operation Example (2)

Wiring

V/F control + Analog input (V1S)


+ Operation via terminal FX/RX
Operation condition
Control mode: V/F control
Frequency command:
Setting 50 [Hz] via Analog input (V1S)
Accel/Decel time: Accel time 15 [sec],
Decel time 25 [sec]
Drive mode: Run/Stop via FX/RX,
Control terminal: NPN mode

3P AC INPUT
R (L1)

S (L2)

T (L3)

IM

G
S0

S/W
M8 (RX)

S1

M7 (FX)
5G

M6
M5
M4

3A

M3

3C

M2

3B

M1
CM
Potentiometer
2 [kohm], 1/2W
V+
V1
V-

Step

Parameter setting

Description

Code

Control Mode Selection

FU2-60

Set it to 0 (V/F).

Drive Mode

DRV-3

Set it to 1 (Fx/Rx-1).

Frequency Mode

DRV-4

Set it to 3 (V1S).

DRV-0

Set 50 [Hz] via potentiometer (V1S).

DRV-1

Set accel time to 15 [sec] in DRV-1

DRV-2

with decal time to 25 [sec] in DRV-2.

4
5

Operating Frequency
Command 50 [Hz] Setting
Accel/Decel Time Setting

When FX terminal is turned ON,


motor rotating in forward direction starts
6

FX Terminal (M7)

IO-26

running at 50 [Hz] for 15 [sec].


When FX terminal is turned OFF,
motor decelerates to stop for 25 [sec].
When RX terminal is turned ON,
motor rotating in reverse direction starts

RX Terminal (M8)

IO-27

running at 50 [Hz] for 15 [sec].


When RX terminal is turned OFF,
motor decelerates to stop for 25 [sec].

38

Industrial Inverter for Fan and Pump STARVERT iP5A

Dimensions
SV008~055iP5A (200/400V Class) & SV0055~0110iP5A (600V Class)

DRV

FU1

FU2

I/O

EXT

LE-200
LC-200
MODE

PROG

RUN
SHIFT
ENTER

ESC
SHIFT

REV

FWD

C2

RUN

STOP

C3

RESET

W2
W1

7.5

H2
H1

RESET

C1

PROG
ENT

STOP

D1

mm (inches)

Model
SV008iP5A-2/4
SV015iP5A-2/4
SV022iP5A-2/4
SV037iP5A-2/4
SV055iP5A-2/4
SV0055iP5A-6
SV0075iP5A-6
SV0110iP5A-6

W1

W2

H1

H2

D1

C1

C2

C3

Enclosure
Type

150 (5.91)
150 (5.91)
150 (5.91)
150 (5.91)
150 (5.91)
7.87(200)
7.87(200)
7.87(200)

130 (5.12)
130 (5.12)
130 (5.12)
130 (5.12)
130 (5.12)
7.09(180)
7.09(180)
7.09(180)

284 (11.18)
284 (11.18)
284 (11.18)
284 (11.18)
284 (11.18)
13.98(355)
13.98(355)
13.98(355)

269 (10.69)
269 (10.69)
269 (10.69)
269 (10.69)
269 (10.69)
13.39(340)
13.39(340)
13.39(340)

156.5 (6.16)
156.5 (6.16)
156.5 (6.16)
156.5 (6.16)
156.5 (6.16)
7.19(182.5)
7.19(182.5)
7.19(182.5)

24 (0.98)
24 (0.98)
24 (0.98)
24 (0.98)
24 (0.98)
1.12(28.5)
1.12(28.5)
1.12(28.5)

24 (0.98)
24 (0.98)
24 (0.98)
24 (0.98)
24 (0.98)
0.94(24)
0.94(24)
0.94(24)

24 (0.98)
24 (0.98)
24 (0.98)
24 (0.98)
24 (0.98)
1.12(28.5)
1.12(28.5)
1.12(28.5)

IP20 UL Type 1
IP20 UL Type 1
IP20 UL Type 1
IP20 UL Type 1
IP20 UL Type 1
IP 20 UL Type 1
IP 20 UL Type 1
IP 20 UL Type 1

SV075~300iP5A (200/400V Class) & SV0150~0300iP5A (600V Class)

DRV

FU1

FU2

I/O

EXT

LE-200
LC-200
MODE

PROG

RUN
SHIFT
ENTER

SV150~300
iP5A-2/4

ESC
SHIFT

PROG
ENT

STOP
REV

RESET

FWD

STOP

RUN

RESET

C2

H1
H2

C1

C3

7.5

SV075~110
iP5A-2/4
W3

W3

D1

W2
W1

mm (inches)

Model
SV075iP5A-2/4
SV110iP5A-2/4
SV150iP5A-2/4/6
SV185iP5A-2/4/6
SV220iP5A-2/4/6
SV300iP5A-2/4/6

W1

W2

200 (7.87) 180 (7.09)


200 (7.87) 180 (7.09)
250 (9.84) 230 (9.06)
250 (9.84) 230 (9.06)
304 (11.97)284 (11.18)
304 (11.97)284 (11.18)

W3
6 (0.23)
6 (0.23)
9 (0.35)
9 (0.35)
9 (0.35)
9 (0.35)

H1

H2

D1

C1

C2

C3

284 (11.18)269 (10.69) 182 (7.16) 35 (1.37) 24 (0.98) 35 (1.37)


284 (11.18)269 (10.69) 182 (7.16) 35 (1.37) 24 (0.98) 35 (1.37)
385 (15.16)370 (14.57) 201 (7.91)
385 (15.16)370 (14.57) 201 (7.91)
460 (18.11)445 (17.52) 234 (9.21)
460 (18.11)445 (17.52) 234 (9.21)
-

Enclosure
Type
IP20 UL Type 1
IP20 UL Type 1
IP00 UL Open
IP00 UL Open
IP00 UL Open
IP00 UL Open

39

iP5A

Dimensions
SV150~300iP5A (UL Type 1 or UL Open Type with Conduit Option used, 200V/400V Class)
W1
W2

Note) Mounting NEMA 1 conduit option to the


15~90kW (20~125HP) Open Type meets
NEMA 1 but does not comply with UL
Enclosed Type 1. To that end, please
purchase UL Type 1 product.

LC-200
MODE

PROG

ENTER

ESC
SHIFT

STOP
FWD

RESET

D2

D1

H3

H2
H1

REV

9
7.5

W3

mm (inches)

Model
SV150iP5A-2/4
SV185iP5A-2/4
SV220iP5A-2/4
SV300iP5A-2/4

W1

W2

H1

H2

H3

D1

D2

C3

Enclosure
Type

250 (9.84)
250 (9.84)
304 (11.97)
304 (11.97)

230 (9.06)
230 (9.06)
284 (11.18)
284 (11.18)

200.8 (7.9)
200.8 (7.9)
236 (9.29)
236 (9.29)

385 (15.16)
385 (15.16)
460 (18.11)
460 (18.11)

370 (14.57)
370 (14.57)
445 (17.52)
445 (17.52)

454.2 (17.88)
454.2 (17.88)
599.2 (23.59)
599.2 (23.59)

201 (7.91)
201 (7.91)
234 (9.21)
234 (9.21)

146 (5.74)
146 (5.74)
177.5 (6.98)
177.5 (6.98)

IP20 UL Type 1
IP20 UL Type 1
IP20 UL Type 1
IP20 UL Type 1

-Built-in DCL Type


SV150~SV300 iP5A (400V Class)D1

W1
W2

LC-200
MODE

PROG

ENTER

ESC
SHIFT

STOP
RESET

FWD

H1
H2

REV

W3

mm (inches)

Model
SV150, 185iP5A-4L
SV220, 300iP5A-4L

40

W1

W2

W3

H1

H2

D1

Enclosure
Type

250 (9.84)
260 (10.23)

186 (7.32)
220 (8.66)

7 (0.28)
7 (0.28)

403.5 (15.88)
480 (18.89)

392 (15.43)
468.5 (18.44)

261.2 (10.28)
268.6 (10.57)

IP00 UL Type 1
IP20 UL Type 1

Industrial Inverter for Fan and Pump STARVERT iP5A

SV150~SV300 iP5A (Built-in DCL Type, UL Type 1 or UL Open Type with Conduit Option used, 400V Class)
W1
W2

LC-200
MODE

PROG

ENTER

ESC
SHIFT

STOP
RESET

FWD

D2

D1

H1

H2

REV

W3

mm (inches)

Model
SV150, 185iP5A-4L
SV220, 300iP5A-4L

W1

W2

W3

250 (9.84)
260 (10.23)

186 (7.32)
220 (8.66)

7 (0.28)
7 (0.28)

H1

H2

D1

475.5 (18.72) 392 (15.43) 261.2 (10.28)


552 (21.73) 468.5 (18.44) 268.6 (10.57)

D2

Enclosure
Type

188.4 (7.42)
188.8 (7.43)

IP20 UL Type 1
IP20 UL Type 1

SV370~SV550iP5A (400V Class) & SV0370~0550iP5A (600V Class)

LC-200
MODE

PROG

ENTER

ESC
SHIFT

STOP
RESET

FWD

H1
H2

REV

D1
W3

W3

mm (inches)

W2
W1

Model

W1

300 (11.81)
SV370, 450iP5A-4
SV550iP5A-4, SV0370 300 (11.81)
0450, 0550iP5A-6
SV370, 450iP5A-4L 300 (11.81)
(Built-in DCLType)

SV550iP5A-4L
(Built-in DCL Type)

300 (11.81)

H2

D1

Enclosure
Type

W2

W3

H1

190 (7.48)

9 (0.35)

534 (21.02)

515 (20.28) 265.6 (10.46)

IP00 UL Open

190 (7.48)

9 (0.35)

534 (21.02)

515 (20.28) 292.6 (11.52)

IP00 UL Open

190 (7.48)

9 (0.35)

684 (26.92)

665 (26.18) 265.6 (10.46)

IP00 UL Open

190 (7.48)

9 (0.35)

684 (26.92)

665 (26.18) 292.6 (11.52)

IP00 UL Open

41

iP5A

Dimensions
SV370~550iP5A (UL Type 1 or UL Open Type with Conduit Option Used, 400V Class)
W1
W2
Note) Mounting NEMA 1 conduit option to the
15~90kW (20~125HP) Open Type meets
NEMA 1 but does not comply with UL
Enclosed Type 1. To that end, please
purchase UL Type 1 product.

LC-200
MODE

PROG

ENTER

ESC
SHIFT

STOP
RESET

FWD

D2

D1

H1

H2

REV

W3

mm (inches)

Model
SV370, 450iP5A-4
SV550iP5A-4
SV370, 450iP5A-4L
SV550iP5A-4L

W1

W2

W3

H1

H2

D1

300 (11.81)
300 (11.81)
300 (11.81)
300 (11.81)

190 (7.48)
190 (7.48)
190 (7.48)
190 (7.48)

9 (0.35)
9 (0.35)
9 (0.35)
9 (0.35)

642 (25.28)
642 (25.28)
792 (31.18)
792 (31.18)

515 (20.28)
515 (20.28)
665 (26.18)
665 (26.18)

D2

265.6 (10.46) 163.4 (6.43)


292.6 (11.52) 190.4 (7.5)
265.6 (10.46) 163.4 (6.43)
292.6 (11.52) 190.4 (7.5)

Enclosure
Type
IP20 UL Type 1
IP20 UL Type 1
IP20 UL Type 1
IP20 UL Type 1

SV750, 900iP5A (400V Class) & SV0750~0900iP5A (600V Class)

LC-200
MODE

PROG

ENTER

ESC
SHIFT

STOP
RESET

FWD

H1
H2

REV

W3

D1

W3
W2
W1

mm (inches)

Model
SV750, 900iP5A-4
SV0750, 0900iP5A-6
SV750, 900iP5A-4L
(Built-in DCL Type)

42

W1

W2

W3

H1

H2

D1

Enclosure
Type

370 (14.57)

220 (8.66)

9 (0.35)

610 (24.02)

586.5 (23.09)

337.6 (13.29)

IP00 UL Open

370 (14.57)

220 (8.66)

9 (0.35)

760 (29.92)

736.6 (28.99)

337.6 (13.29)

IP00 UL Open

Industrial Inverter for Fan and Pump STARVERT iP5A

SV750, 900iP5A (UL Type 1 or UL Open Type with Conduit Option used, 400V Class)
W1
W2

Note) Mounting NEMA 1 conduit option to the


15~90kW (20~125HP) Open Type
meets NEMA 1 but does not comply
with UL Enclosed Type 1. To that end,
please purchase UL Type 1 product.

LC-200
MODE

PROG

ENTER

ESC
SHIFT

STOP
RESET

FWD

D2

D1

H1

H2

REV

W3

mm (inches)

Model
SV750, 900iP5A-4
SV750, 900iP5A-4L
(Built-in DCL Type)

W1

W2

W3

H1

H2

D1

D2

Enclosure
Type

370 (14.57)

220 (8.66)

9 (0.35)

767.5 (30.22)

586.5 (23.09)

337.6 (13.29)

223.4 (8.8)

IP20 UL Type 1

370 (14.57)

220 (8.66)

9 (0.35)

917.5 (36.12)

736.5 (28.99)

337.6 (13.29)

223.4 (8.8)

IP20 UL Type 1

SV1100, 1600iP5A (400V Class) & SV1100iP5A (600V Class)


W1
W2

H1
H2

D1

W3

W3

mm (inches)

Model
SV1100, 1320iP5A-4L
SV1100iP5A-6L
SV1600iP5A-4L

W1

W2

W3

H1

H2

D1

Enclosure
Type

510 (20.08)

381 (15.00)

11 (0.43)

783.5(30.85)

759(29.88)

422.6 (16.64)

IP00 UL Open

510 (20.08)

381 (15.00)

11 (0.43)

861(33.90)

836.5(32.93)

422.6 (16.64)

IP00 UL Open

43

iP5A

SV2200, 2800iP5A (400V Class)

D1

H1
H2

W1
W2

W3

W3

W3

mm (inches)

Model
SV2200,
2800iP5A-4L

W1

W2

W3

H1

H2

D1

Enclosure
Type

690 (27.17)

581 (22.87)

14 (0.55)

1063 (41.85)

1043.5 (41.08)

449.6 (17.70)

IP00 UL Open

SV3150, 4500iP5A (400V Class)


D1

H1
H2

15

W1
W2

W3

W3

W3

W4

mm (inches)

Model
SV3150, iP5A-4L
SV3750,
4500iP5A-4L

44

W1

W2

W3

H1

H2

D1

Enclosure
Type

772 (30.39)

500 (19.69)

13 (0.51)

1140.5 (44.90)

1110 (43.70)

442 (17.40)

IP00 UL Open

922 (36.30)

580 (22.83)

14 (0.55)

1302.5 (51.28) 1271.5 (50.06)

495 (19.49)

IP00 UL Open

Industrial Inverter for Fan and Pump STARVERT iP5A

DB (Dynamic Braking) Unit


DBU Models
UL

Inverter

Applicable motor rating

200V class

Non UL type
400V class

DB Unit

11~15 kW (15~20 HP)

SV150DBU-2

18.5~22 KW (25~30 HP)

SV220DBU-2

Dimension
Group 1.

30~37 kW (40~50 HP)

SV037DBH-2

45~55 kW (60~75 HP)

SV037DBH-2, 2set

11~15 kW (15~20 HP)

SV150DBU-4

18.5~22 kW (25~30 HP)

SV220DBU-4

30~37 kW (40~50 HP)

SV037DBH-4

Group 1.

45~55 kW (60~75 HP)

Group 2.
SV075DBH-4

75 kW (100 HP)
11~15 kW (15~20 HP)
200V class

UL type

SV150DBU-2U

18.5~22 kW (25~30 HP)

SV220DBU-2U

30~37 kW (40~50 HP)

SV370DBU-2U

45~55 kW (60~75 HP)

SV550DBU-2U

11~15 kW (15~20 HP)

SV150DBU-4U

18.5~22 kW (25~30 HP)

SV220DBU-4U

30~37 kW (40~50 HP)

SV370DBU-4U

45~55 kW (60~75 HP)

SV550DBU-4U

75 kW (100 HP)

400V class

Group 2.

Group 3.

SV750DBU-4U

90~110 kW (125~150 HP)

SV550DBU-4, 2set

132~160 kW (200~250 HP)

SV750DBU-4, 2set

220 kW (300 HP)

SV750DBU-4, 3set

280~315 kW (350~400 HP)

375~450 kW (500~600 HP)

Terminal Configuration
Group 1 -

CM

OH

Group 2 -

B2

P/B1

Group 3 -

B1

B2

B1

B2

Terminals

Description

Terminals

Ground terminal

Connect to inverter terminal N

B2

Connect to DB Resistors B2

Connect to inverter terminal P1

B1

Connect to DB Resistors B1

CM

OH common

Connect to inverter terminal N

Connect to inverter terminal P1

OH*

Description

Over Heat Trip output terminal


(Open Collector output: 20mA, 27V DC)

45

iP5A

Wiring for DB unit and DB resistor (For 5.5~90kW/7.5~125HP inverters)

DB Resistor

DB Unit

TH2

B2

B2

TH1

B1

B1

Max distance between


P & P2: 5m

P
Short

P1 (+)

P2 (+)

N (-)

MCCB (Option)
3
AC Input
50/60 Hz

R (L1)

S (L2)

T (L3)

Motor

Programmable Digital Input: Ext Trip

M1
M2

Max. output voltage: 12V


Source max.: 30mA
Sink max.: 20mA

S0
S1
5G

Output Frequency Meter


Output Voltage Meter
Common for output meter signal

M3
M4
M5

3A

M6

3C

M7

3B

Fault Contact Output


less than AC250V (DC30V), 1A

M8

Common Terminal

CM

DB resistor terminal
B1, B2

TH1, TH2

46

Description
Wire terminal properly based on wiring block diagram.
Connect a DB resistor to the DB Unit
s B1, B2 terminals.
Thermal sensor terminal of DB resistor.
Normal temperature (Ambient): Contact ON (TH1-TH2 closed)
DB resistor overheated: Contact OFF (TH1-TH2 Open).
Wire it to the inverter terminal defined as External Trip.

Industrial Inverter for Fan and Pump STARVERT iP5A

DB (Dynamic Braking) Unit


Group 1
(Unit: mm)

4-M5 Mounting

Dynamic Braking Unit


WIRING
U
R
V
S
(P2)
T
W
P N

B1
B2

IM

G
B2
B1

12.5

POWER

125

172

RUN

12.5

3.5

OHT

192

185

N
P

68.5

150

47

iP5A

Group 2
(Unit: mm)

80

Dynamic Braking Unit

RESET
231.5

OHT

258

RUN

245

POWER

12

OCT

5.5

15

80
123

27

75

130

48

Industrial Inverter for Fan and Pump STARVERT iP5A

DB (Dynamic Braking) Unit


Group 3
(Unit: mm)

49

iP5A

External DB Resistor
iP5A do not have built-in DB resistor on power stack as factory installation. External DB Unit and Resistor (Optional)
should be installed. See the following table for more details (ED: 5%, Continuous Braking Time: 15 sec). If Enable duty
(%ED) is increased to 10%, use external DB resistor having twice Wattage rating.
Applied motor
capacity (kW/HP)

200V

400V

0.75/1
1.5/2
2.2/3
3.7/5
5.5/7.5
7.5/10
11/15
15/20
18.5/25
22/30
30/40
0.75/1
1.5/2
2.2/3
3.7/5
5.5/7.5
7.5/10
11/15
15/20
18.5/25
22/30
30/40
37/50
45/60
55/75
75/100
90/125

Operating rate
(ED/Continuous
Braking Time)

[ohm]

[W]

Type

[ohm]

[W]

Type

5%/15 sec
5%/15 sec
5%/15 sec
5%/15 sec
5%/15 sec
5%/15 sec
5%/15 sec
5%/15 sec
5%/15 sec
5%/15 sec
10%/6 sec
5%/15 sec
5%/15 sec
5%/15 sec
5%/15 sec
5%/15 sec
5%/15 sec
5%/15 sec
5%/15 sec
5%/15 sec
5%/15 sec
10%/6 sec
10%/6 sec
10%/6 sec
10%/6 sec
10%/6 sec
10%/6 sec

200
100
60
40
30
20
15
11
9
8
4.2
900
450
300
200
120
90
60
45
35
30
16.9
16.9
11.4
11.4
8.4
8.4

100
200
300
500
700
1000
1400
2000
2400
2800
6400
100
200
300
500
700
1000
1400
2000
2400
2800
6400
6400
9600
9600
12800
12800

TYPE 1
TYPE 1
TYPE 1
TYPE 2
Type3
Type 3
Type 3
Type 3
Type 3
Type 3
TYPE 1
TYPE 1
TYPE 1
TYPE 2
Type 3
Type 3
Type 3
Type 3
Type 3
Type 3
-

150
60
50
33
20
15
10
8
5
5
600
300
200
130
85
60
40
30
20
20
-

150
300
400
600
800
1200
2400
2400
3600
3600
150
300
400
600
1000
1200
2000
2400
3600
3600
-

TYPE 1
TYPE 1
TYPE 1
TYPE 2
Type 3
Type 3
Type 3
Type 3
Type 3
Type 3
TYPE 1
TYPE 1
TYPE 1
TYPE 2
Type 3
Type 3
Type 3
Type 3
Type 3
Type 3
-

100 % Braking Torque

150% Braking Torque

Peripheral Device
MCCB (Molded Case Circuit Breaker) and MC (Magnetic Contactor)
Voltage

200V
Class

50

Motor [kW]
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30

Inverter Model
SV008iP5A-2
SV015iP5A-2
SV022iP5A-2
SV037iP5A-2
SV055iP5A-2
SV075iP5A-2
SV110iP5A-2
SV150iP5A-2
SV185iP5A-2
SV220iP5A-2
SV300iP5A-2

MCCB
(LS Industrial Systems)

MC
(LS Industrial Systems)

ABS53b/50A
ABS63b/60A
ABS103b/100A
ABS103b/100A
ABS203b/125A
ABS203b/150A
ABS203b/175A

GMC-40
GMC-40
GMC-50
GMC-85
GMC-100
GMC-100
GMC-150

Industrial Inverter for Fan and Pump STARVERT iP5A

Peripheral Device
MCCB (Molded Case Circuit Breaker) and MC (Magnetic Contactor)
Voltage

400V
Class

600V
Class

Motor [kW]

Inverter Model

MCCB
(LS Industrial Systems)
-

MC
(LS Industrial Systems)

0.75

SV008iP5A-4

1.5

SV015iP5A-4

2.2

SV022iP5A-4

3.7

SV037iP5A-4

5.5

SV055iP5A-4

ABS33b/30A

GMC-22

7.5

SV075iP5A-4

ABS33b/30A

GMC-22

11

SV110iP5A-4

ABS53b/50A

GMC-40

15

SV150iP5A-4

ABS63b/60A

GMC-50

18.5

SV185iP5A-4

ABS63b/60A

GMC-50

22

SV220iP5A-4

ABS103b/100A

GMC-65

30

SV300IP5A-4

ABS103b/100A

GMC-75

37

SV370iP5A-4

ABS203b/125A

GMC-100

45

SV450iP5A-4

ABS203b/150A

GMC-125

55

SV550iP5A-4

ABS203b/175A

GMC-150

75

SV750iP5A-4

ABS203b/225A

GMC-180

90

SV900iP5A-4

ABS403b/300A

GMC-220

110

SV1100iP5A-4

ABS403b/400A

GMC-300

132

SV1300iP5A-4

ABS603b/500A

GMC-300

160

SV1600iP5A-4

ABS603b/600A

GMC-400

220

SV2200iP5A-4

ABS803b/700A

GMC-600

280

SV2800iP5A-4

ABS803b/800A

GMC-600

315

SV3150iP5A-4

ABS1003/1000A

GMC-800

375

SV3750iP5A-4

ABS1203/1200A

900A

450

SV4500iP5A-4

ABS1203/1200A

1000A

5.5

SV055iP5A-4

ABS33b/30A

GMC-22

7.5

SV075iP5A-4

ABS33b/30A

GMC-22

11

SV110iP5A-4

ABS53b/50A

GMC-40

15

SV150iP5A-4

ABS63b/60A

GMC-50

18.5

SV185iP5A-4

ABS63b/60A

GMC-50

22

SV220iP5A-4

ABS103b/100A

GMC-65

30

SV300IP5A 4

ABS103b/100A

GMC 75

37

SV370iP5A-4

ABS203b/125A

GMC-100

45

SV450iP5A-4

ABS203b/150A

GMC-125

55

SV550iP5A-4

ABS203b/175A

GMC-150

75

SV750iP5A-4

ABS203b/225A

GMC-180

90

SV900iP5A-4

ABS403b/300A

GMC-220

51

iP5A

AC Input Fuse
Voltage

200V
Class

400V
Class

52

AC Reactor

Motor [kW]

Inverter Model

AC Input Fuse
[A]

[mH]

0.75

SV008iP5A-2

10

2.13

1.5

SV015iP5A-2

15

1.2

2.2

SV022iP5A-2

20

3.7

SV037iP5A-2

5.5
7.5

DC Reactor
[A]

[mH]

[A]

5.7

10

0.88

14

30

0.56

20

SV055iP5A-2

40

0.39

30

1.37

29

SV075iP5A-2

60

0.28

40

1.05

38

11

SV110iP5A-2

80

0.20

59

0.74

56

15

SV150iP5A-2

100

0.15

75

0.57

71

18.5

SV185iP5A-2

125

0.12

96

0.49

91

22

SV220iP5A-2

150

0.10

112

0.42

107

30

SV300iP5A-2

200

0.07

160

0.34

152

0.75

SV008iP5A-4

10

8.63

2.8

1.5

SV015iP5A-4

10

4.81

4.8

2.2

SV022iP5A-4

10

3.23

7.5

3.7

SV037iP5A-4

15

2.34

10

5.5

SV055iP5A-4

20

1.22

15

5.34

14

7.5

SV075iP5A-4

30

1.14

20

4.04

19

11

SV110iP5A-4

40

0.81

30

2.76

29

15

SV150iP5A-4

60

0.61

38

2.18

36

18.5

SV185iP5A-4

70

0.45

50

1.79

48
55

22

SV220iP5A-4

80

0.39

58

1.54

30

SV300IP5A-4

100

0.287

80

1.191

76

37

SV370iP5A-4

125

0.232

98

0.975

93

45

SV450iP5A-4

150

0.195

118

0.886

112

55

SV550iP5A-4

175

0.157

142

0.753

135

75

SV750iP5A-4

250

0.122

196

0.436

187

90

SV900iP5A-4

300

0.096

237

0.352

110

SV1100iP5A-4

350

0.081

289

Built-in

132

SV1300iP5A-4

400

0.069

341

Built-in

160

SV1600iP5A-4

450

0.057

420

Built-in

220

SV2200iP5A-4

700

0.042

558

Built-in

280

SV2800iP5A-4

800

0.029

799

Built-in

315

SV3150iP5A-4

900

0.029

799

0.090

375

SV3750iP5A-4

1000

0.024

952

0.076

996

450

SV4500iP5A-4

1200

0.024

952

0.064

1195

225

836

Industrial Inverter for Fan and Pump STARVERT iP5A

iP5A

MEMO

53

iP5A

MEMO

54

Industrial Inverter for Fan and Pump STARVERT iP5A

53


2006.8 LSIS Co.,Ltd. All rights reserved.

Dalian LSIS Co., Ltd.

LS Tower, 127, LS-ro, Hogye-dong, Dongan-gu, Anyang-si,


Gyeonggi-do 431-848, Korea

Global Network

LSIS (Middle East) FZE

HEAD OFFICE

www.lsis.biz
Dubai, U.A.E.

LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab
Add
Emirates
re ss :
Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: jungyongl@lsis.biz

Dalian, China

Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China
Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn

+82-2-2034-4901
/ bonseongk@lsis.biz
EMEA

LSIS (Wuxi) Co., Ltd.

Wuxi, China

Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China
Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn

/ mswoo@lsis.biz
Asia+82-2-2034-4620
Pacific

LSIS-VINA Co., Ltd.

Hanoi, Vietnam

Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam


Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com

Hochiminh , Vietnam
LSIS-VINA Co., Ltd.

Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam
Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: sbpark@lsisvina.com

LSIS Shanghai Office

Shanghai, China

Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China
Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn

LSIS Beijing Office

Beijing, China

ddress: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
A
Beijing 100013, P.R. China
Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn

LSIS Guangzhou Office

Guangzhou, China

Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China
Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.biz

LSIS Chengdu Office

Chengdu, China

Address: Room 1701 17Floor, huanminhanjun internationnal Building, No1 Fuxing Road Chengdu, 610041, P.R. China
Tel: 86-28-8670-3101 Fax: 86-28-8670-3203 e-mail: yangcf@lsis.com.cn

LSIS Qingdao Office

Qingdao, China

Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China
Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn

LSIS NETHERLANDS Co.Ltd

Specifications in this catalog are subject to change without notice due to


continuous product development and improvement.

Netherlands

Address: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The Netherlands


Tel: 31-20-654-1420 Fax: 31-20-654-1429 e-mail: junshickp@lsis.biz

LSIS Gurgaon Office

Gurgaon ,India

Address: 109 First Floor, Park Central, Sector-30, Gurgaon- 122 002, Haryana, India

2012. 01
Safety Instructions

Starvert iP5A(E) 2006. 08/(11) 2012. 01 Printed in Korea Pacomkorea


Any maintenance and inspection shall be performed by the personnel having expertise concerned.
Please contact a qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Contact the nearest authorized service facility for examination, repair, or adjustment.
For your safety, please read user's manual thoroughly before operating.