STUDY
SERVER
INCOMPATIBILITY
BY MIKE PUCKETT,, PE
ONE-LINE DIAGRAM
LOADS
Initial Load on UPS Systems
S stems was
as abo
aboutt
13% each
Initial
I iti l M
Maximum
i
Heat
H t Gain
G i in
i the
th UPS
Room about 90% of the A/C rating based
on each UPS being 25% loaded
A/C PERFORMANCE
A/C unit
nit set-point
set point was
as 68 and space
temperature was running about 77
When
Wh compressor cycled,
l d space
temperature climbed to low 80s during the
compressors
compressor
s 3 minute time delay
INVESTIGATION
A/C manufacturer
man fact rer checked
checked-out
o t the A/C
units performance
A/C was performing
f
i att or above
b
spec
Rechecked Heat Gain Calculations. They
looked good.
Largest Source of Heat Gain was from
UPS Systems
INVESTIGATION
Researched UPS Heat Loss
Efficiency = Pin/Pout
Heat Loss = Pin Pout = Pout/Eff - Pout
UPS Heat Losses Include:
o oad Losses:
osses Transformer
a s o e & Inductor
ducto
No-Load
core loss, capacitors, fans, controls
Load Proportional Losses: Switching
Load IR Losses: Transformer & Inductor
coil loss, Conductors, Conduction
INVESTIGATION
Measured
Meas red Inp
Inputt and O
Output
tp t kW of one UPS
System to check Heat Loss (Efficiency)
UPS was rejecting
j ti about
b t same heat
h t as if it
was 50% loaded.
Measured Heat Loss = 8.1kW.
Published Heat Loss at 25% Load = 6.4kW
Published Heat Loss at 50% Load = 8.2kW
INVESTIGATION
UPS Manufacturer
Man fact rer decided to perform
their own testing
Measured
M
d Input
I
t and
d Output
O t t kWh and
d DC
Link simultaneously for ~15 minutes.
Difference
ff
off above divided by Time =
Heat Loss
Did this for normal 13% load and with all
load on one UPS (22%)
7 4kW
7.4kW
13%
8.4kW
74%
0.923
22%
8.7
82%
0.963
MEASUREMENTS VS.
PUBLISHED SPECS
Load HeatLoss Efficiencyy LoadPF
Measured:
0
7.4kW
13%
8.4kW
22%
8.7kW
P bli h d S
PublishedSpecs:
25%
6.4kW
50%
8 2kW
8.2kW
75%
11.4kW
100% 15.7kW
74%
82%
0.923
0.963
87.60%
91 65%
91.65%
92.20%
92%
0.8 0.9
0 8 0.9
0.8
09
0.8 0.9
0.8 0.9
Power Supply
Wa eform Prior to
Waveform
Mid 80s
Power Supply
Wa eform beginning
Waveform
around Mid 80s
Power Supply
Wa eform for Data
Waveform
Center I.T
beginning around
2002
In 2001, the European Union put into effect IEC/EN61000-32, setting Limits on Harmonics for Equipment Above 75W
SWITCH-MODE POWER
SUPPLY (SMPS)
Total PF~0.7
SWITCH-MODE POWER
SUPPLY (SMPS)
PF~-0.80 to -0.97
P
Power Factor
F t Corrected
C
t d (PFC) SMPS after
ft the
th 2001
European mandate.
Includes leading PF at low loads.
LEGACY
G C UPS
U S SYSTEMS
S S
S
IINV = IF+IL. IF net will be capacitive (-jX) and for a leading PF load, IL will
also be capacitive
p
(-jX).
( j ) Therefore,, the net inverter and transformer
current could exceed its designed rating and will also increase losses.
CONCLUSIONS
Know what you are specifying and getting.
getting
Know
K
what
h t the
th loads
l d are.
Get the most accurate heat loss data you can
from the manufacturer
LIGHTNING
CASE
STUDY
PRESENTED
S
AT IEEE / MCPQG
C QG MEETING
G
NOVEMBER 28, 2012
BY MIKE PUCKETT, PE
LARGE CHURCH
Five Modular
Buildings with Steel
Floor Joists &
Metal Roof
Steel
Structure & Metal Roof
2008
Steel Roof
Structure & Rubber Roof
2001
Five Modular
Buildings with
Steel Floor
Joists & Metal
Roof
Steel Roof
St t
Structure
&
Rubber Roof
2001
Steel
Structure &
Metal Roof
2008
Wood &
Concrete
St t
Structures
1956 & 1992
Service
#1
Service
#2
Service
#3
20
21
GROUNDING BEFORE
GROUNDING AFTER
EFFECVTIVE LIGHTNING
PROTECTION
Look
L k att THE BIG PICTURE.
PICTURE
Consider all Systems and Equipment
Involved.
For Personal Safety, Respect Lightning