Vous êtes sur la page 1sur 9

VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.

6
Licenced to: Sevo Systems, Inc.
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results

Project:
Project-No:
Building:
Object:
Contractor:
Owner:
Project engineer:
Date:
Regulation rule for calculation of FK-5-1-12 quantities:
Altitude above sealevel:
Atmospheric correction factor:

Quipus
9044_1_1
Kallutaca
Data Room
ISTC
Telis S.R.L.
mrg
6/16/2015
NFPA 2001, Edition 2012
3650 m
0.660

Project description:
1 x 1.5" 180 Sidewall Nozzle 10108
1 x 1.0" 180 Sidewall Nozzle 10110

Pipe catalogue:
Component catalogue:
Nozzle catalogue:

schedule40.rkl
SEVOcomp_1_2.arm
SEVO.noz

Page: 1
Serial no: [dongle]
6/16/2015

VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6


Licenced to: Sevo Systems, Inc.
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results

Page: 2
Serial no: [dongle]
6/16/2015

VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6


Licenced to: Sevo Systems, Inc.
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results

Page: 3
Serial no: [dongle]
6/16/2015

Pipesystem data:
SectionNo:

Startingnode

Endnode

1
2
3
4
5
6
7
8

0
3
4
5
6
7
6
9

3
4
5
6
7
10108
9
10110

Length
[m]

Height
[m]

Pipetype

0.953
0.164
2.347
2.560
0.200
0.500
0.150
0.100

0.953
0.000
2.347
0.000
0.000
-0.500
0.000
-0.100

10
13
13
13
13
13
13
13

Diameter
[mm] **

Fitting
*

code

Component
coefficient

Nb of containers
FK-5-1-12 quantity

5/4
5/4
3/2
3/2
3/2
3/2
1
1

C
E
E
E
T-0
E
T-90
E

165
-

1.600
-

1.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

* C=Component, B=Bend, T=T-Piece, E=Elbow


** If a pipe diameter is equal zero see the extra table of the calculated diameters

Legend of pipetypes
Type Pipeclass

Pipe roughness

10
13

smooth
black pipe

schedule 40
schedule 40

Legend of components
Code
Type

Resistance coefficient

165

1.600

SEVO 164 LB/1 1/4" (CV14817) W/ 1 1/4" Flex Hose

Nozzle data:
No.

Calculation zone

Diameter [mm]

10108
10110

Main
False Ceiling

15.3
6.0

Legend of nozzles:
Type
1 Nozzle 1

Number of
orifices

C1

C2

C3

C4

C5

C6

0.10652

0.26900

0.23203

-0.20251

0.00000

0.00000

VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6


Licenced to: Sevo Systems, Inc.
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results

Page: 4
Serial no: [dongle]
6/16/2015

Calculation zone data:


Calculation of design quantity:
Zone

Total
volume
[m3]

Volume of
building
parts [m3]

Calculated
volume
[m3]

Total
surface

Max. Overpressure
[mbar]

Design
temp.
[C]

Extinguishconc.
[% Vol]

Design
factor

Design
conc.
[% Vol]

Design
quantity
[kg]

1 Main

93.3

0.0

93.3

130.2

1.000

20.0

3.5

1.35

4.7

42.48

2 False Ceiling

12.9

0.0

12.9

73.4

1.000

20.0

3.5

1.35

4.7

5.86

Regulation rule for calculation of FK-5-1-12 quantities:


Calczone no. 1:
Calczone no. 2:
Altitude above sealevel:
Atmospheric correction factor:

NFPA 2001, Edition 2012


Class C Fire, NFPA 2001 (Edition 2012)
Class C Fire, NFPA 2001 (Edition 2012)
3650.0 m
0.660

FK-5-1-12 storage input data:


Container volume:

62.0 l

Maximum filling ratio of a container:

1.200 kg/l

Filling pressure:

25.0 bar abs

Storage temperature:

20.0 C

Supplement factor:

1.01

Minimum storage quantity:

48.39 kg

Number of containers:

Discharge time (input value):

10.0 s

Further information:
Design with included gas discharge time
Design with predeterminated orifice diameters

VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6


Licenced to: Sevo Systems, Inc.
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results

Calculation results:
FK-5-1-12 storage data:
Design quantity:
Supplement factor:
Minimum storage quantitiy:

48.3 kg
1.01
48.8 kg

Container volume:
Filling ratio:
Filling pressure:
FK-5-1-12 -mass per container:
Number of containers:
Actual storage quantity:

62.0 l
0.79 kg/l
25.0 bar abs
48.8 kg
1
48.8 kg

Storage temperature:
Starting container pressure:

20.0 C
25.0 bar abs

Discharge time:
Discharge time air:
Total gas discharge time:
Two-phase discharge time:
Total discharge time:

0.2 s
0.4 s
8.7 s
9.1 s

System information:
Container working pressure:
Container working temperature:
Total network volume:
Medium pipe content:
Filling portion in pipe system:

14.4 bar abs


20.0 C
8.6 l
13.1 kg FK-5-1-12
0.27 kg FK-5-1-12 /kg FK-5-1-12 -storage

Page: 5
Serial no: [dongle]
6/16/2015

VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6


Licenced to: Sevo Systems, Inc.
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results

Page: 6
Serial no: [dongle]
6/16/2015

Pipe system:
SectionNo:

Startingnode

Endnode

Pressure
[bar abs]

Flowrate
[kg/s]

Pipedimension
Di [mm]
DN

1
2
3
4
5
6
7
8

0
3
4
5
6
7
6
9

3
4
5
6
7
10108
9
10110

14.02
13.80
13.30
13.14
13.11
13.11
13.05
13.04

5.24
5.26
5.26
5.26
4.62
4.62
0.65
0.65

35.1
35.1
40.9
40.9
40.9
40.9
26.6
26.6

---------

Tee split table


T-Type

Side Tee

Flow in
Section
No.

Flow
kg/s

1th Flow out


Section
Flow
No.
kg/s

Split
%

2nd Flow out


Section
Flow
No.
kg/s

Split
%

5.26

87.833

12.357

4.62

0.65

Regulation
conform

Yes

VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6


Licenced to: Sevo Systems, Inc.
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results

Page: 7
Serial no: [dongle]
6/16/2015

Nozzle data:
Calculationzone no:

Nozzle
no.

Nozzle
type

Number of
orifices

Pipeconnection
Di [mm]
DN

Orifice
[mm]

FK-5-1-12 output [kg]

1
2

10108
10110

1
1

1
1

40.9
26.6

15.3
6.0

42.6
6.0

Two-phase discharge time:

---

8.7 s

MAXIMUM TRANSPORT TIME DIFF. BETWEEN NOZZLES: 10110./ 10108. IS 0.14 S

Calculationzone no:

Nozzle
no.

Outlet velocity
[m/s]

Transport
time [s]

Jetdistance
[m]

Evaporation
distance [m]

1
2

10108
10110

15.5
24.9

2.49
2.35

5.6
3.1

4.9
1.7

VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6


Licenced to: Sevo Systems, Inc.
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results

Page: 8
Serial no: [dongle]
6/16/2015

Concentrations:
Calculationzone no:

O2

1
2

19.9
19.9

Gascomposition after discharge [%]


FK-5-1-12
N2
4.7
4.8

74.4
74.4

Pressure relief opening:


Calculationzone no:

Recommended area against overpressure


Area [m]
Overpressure [mbar]

Max. flow [kg/s]

1
2

0.055
0.008

4.6
0.6

1.0
1.0

VdS SCHADENVERHTUNG FK-5-1-12 -Calculationprogram Version 7.6


Licenced to: Sevo Systems, Inc.
File: C:\Program Files (x86)\VdS\FK-5-1-12\Projects\9044_1_1 Quipus - Telis S.R.L. - ISTC.prj - Results

Page: 9
Serial no: [dongle]
6/16/2015

Component list:
Component

Number

Code

Coefficient

SEVO 164 LB/1 1/4" (

165

1.600

Nozzle-type

Number

C1

C2

C3

C4

C5

C6

0.10650

0.26900

0.23200

-0.20250

0.00000

0.00000

Pipe-type

Di [mm]

DN

Length [m]

10
13
13
13

35.10
35.10
40.90
26.60

5/4
5/4
3/2
1

1.000
0.200
5.600
0.200

Number of bends (+) and elbows (-)


Bend-type

Di [mm]

DN

Number

-90
-90
-90

35.10
40.90
26.60

5/4
3/2
1

1
3
1

Number of T-distributors (in- and outdiameter)


Number

Input

90-out

90-out

0-out

40.9

26.6

0.0

40.9