Timing Belt
Screw
Springs
Electrical connections
Remove the cover of the valve to access to the
control board.
In the bottom of the board there are two
connectors with two different cables.
Externals cables connectors
J1
J3
Other connectors
J4
J5
J2
Simonazzi
Calibration procedure
The calibration procedure is necessary to give the Maximum Stroke and Zero to the positioner.
The Zero point corresponds to a reference signal of 4 mA, the Maximum Stroke signal corresponds to a reference
signal of 20 mA.
Work direction
Dip Switch 4
OFF
ON
CO2 valve
Water and Syrup valves
Simonazzi
Calibration of close position
1.
2.
3.
4.
5.
6.
7.
8.
9.
Put the valve in the maximum opening position, 40 mm from the full close position, (corresponding to an input
signal of 20 mA) with the pushbuttons UP and DOWN.
10. If the physical maximum opening position is overcomed is possible that the motor looses the step; in this case bring
again the Switch 1 in OFF position and repeat the procedure from point n. 4.
11. Store in the EEprom memory the zero position setting ON and then OFF the switch 3 in the control board.
12. Set OFF the switch 1 to leave the learning mode and set ON the switch 6 to enter in automatic mode.
Check of calibration.
At the end of calibration procedure we recommend to check the calibration of the valve and the compression1 of the
spring opening and closing the valve from the PC maintenance screen; if its no good repeat the calibration.
Working Modes
Automatic Mode
Switch 6
Switch 7
Switch 8
ON
OFF
OFF
Automatic Mode active: the valve follows the analog input reference 4..20 mA
Manual Mode
Switch 6
Switch 7
Switch 8
OFF
ON
OFF
Manual Mode active: is possible to move manually the valve using the pushbuttons UP and DOWN
Test Mode
Switch 6
OFF
1 The valve is close correctly when, in the zero position, the spring is compressed about 0.5mm. Is very important to pay attention to
the spring compression during the zero position calibration, because overcoming the maximum torque is possible to damage the
transmission system and the belt of the valve; in the other hand a spring compression too low may not ensure the correct closure of
the valve.
Simonazzi
Switch 7
Switch 8
OFF
ON
Test Mode active: the valve does full strokes between 0% and 100% position
RESET Mode
Switch 1
Switch 2
Switch 6
Switch 7
Switch 8
OFF
ON ( 1 Sec )
OFF
OFF
OFF
RESET Mode: deletes any calibration of the valve restoring the factory conditions.
Control Board
Connectors
Connector J1
Power supply connector (motor + control board)
Pin1
Pin2
Pin3
Pin4
Connector J2
Step Motor connection
Pin1
Pin2
Pin3
Pin4
Pin5
Pin6
Pin7
Pin8
COMMON (Signal)
PULSE
CW_CCW
BOOST
+24V (Motor)
+24V (Motor)
0V (Motor)
0V (Motor)
Connector J3
PLC Signals connector
Pin1
Pin2
Pin3
+ in 4..20 mA
- in 4..20 mA
Shield
Simonazzi
Pin4
Pin5
Pin6
0V digital
Out Valve close
In Aux
LED
DL1
DL2
DL3
DL4
DL5
DL6
DL7
DL8
DL9
VCC ( +5V )
PULSE
BOOST
CW_CCW
Sensor valve close in Reverse mode (Off = sensor engaged)
Out Valve closed
Sensor valve close in Direct mode (Off = sensor engaged)
Auxiliary Input
Power (+ 24V )
DIP SWITCH
DW1
DW2
DW3
DW4
DW5
DW6
DW7
DW8
NB.
Learning Mode
Save Zero Position
Save Full Open Position
Reverse Mode
Low Speed Mode
Automatic Mode
Manual Mode
Test Mode
With switches 1 , 6 , 7 , 8 OFF and setting the switch 2 ON for 1 Sec the EEProm of the control board is
erased and all the calibrations of the valve are deleted.
DISPLAY
The display shows the state of the valve as follows:
Automatic Mode
Test Mode
Manual Mode
EEPROM Erased
Learning Mode
Position stored
Motor Connector
Simonazzi
Front View
CONNECTOR
1
2
3
4
5
6
7
8
COMMON
PULSE
CW-CCW
BOOST
+24V
+24V
GND
GND